CAIDA DE TENSION EN LINEAS DE MEDIA TENSION - UTILICE LOS DATOS DE LA SIGUIENTE TABLA PARA CALCULAR LA CAIDA DE VOLTAJE PARA TODAS LAS TENSIONES ELECTRICAS NOMINALES DE LAS LINEAS AEREAS PRIMARIAS DE DISTRIBUCION EN TODAS LAS ESTRUCTURAS NORMALES, MENOS EN LAS ESTRUCTURAS TIPO "H". SE CONSIDERA UN SISTEMA TRIFASICO BALANCEADO. - MULTIPLIQUE LA CAIDA DE TENSION CORRESPONDIENTE AL CALIBRE Y MATERIAL DEL CONDUCTOR POR LA CORRIENTE DE FASE Y POR LA LONGITUD EN KILOMETROS. LA CAIDA DE TENSION ES ENTRE FASES. - EL CONDUCTOR AAC SE CONSIDERA SIMILAR AL ACSR EN ESTE PARAMETRO. CAIDA DE VOLTAJE POR AMPERE POR KILOMETRO CONDUCTOR FACTOR DE POTENCIA EN % CALIBRE AWG o KCM MATERIAL 75 80 85 90 95 100 6 4 2 1/0 3/0 2 1/0 3/0 266.4 336.8 COBRE " " " " ACSR " " " " 2.332 1.668 1.246 0.964 0.778 1.682 1.247 0.962 0.740 0.673 2.396 1.690 1.246 0.946 0.753 1.709 1.247 0.946 0.718 0.647 2 453 1.704 1.233 0.920 0.718 1.727 1.237 0.922 0.687 0.614 2.489 1.701 1.209 0.881 0.668 1.728 1.213 0.882 0.644 0.567 2.491 1.664 1.152 0.808 0.590 1.694 1.154 0.811 0.573 0.493 2.336 1.474 0.946 0.595 0.375 1.512 0.953 0.600 0.375 0.297 - DATOS CALCULADOS EN BASE A 25°C Y DISTANCIA MEDIA GEOMETRICA DE 1.38 m. FRECUENCIA DE 60 Hz. FORMULA: R y X SON LA RESISTENCIA Y LA REACTANCIA TOTAL DEL CONDUCTOR, EN OHMS. (θ) ES EL ANGULO DEL FACTOR DE POTENCIA DE LA CARGA. EJEMPLO: CARGA DE 500 kW, FACTOR DE POTENCIA DE 90%, TENSION 13 kV, CONDUCTOR ACSR 3/0 AWG Y DISTANCIA DE 2.5 km, TRES FASES. CORRIENTE EN AMPERES = CAIDA DE TENSION = 0,882 x 24,3 x 2,5 = 53, 58 VOLT. 971024 REV.