USER`S GUIDE MOTOR DIGITAL MULTI

Anuncio
USER’S GUIDE
MOTOR
DIGITAL MULTI-FUNCTION RELAY
NPM 800
ICE - 11, rue Marcel Sembat - 94146 ALFORTVILLE CEDEX - France
TEL. : (33) 01 41 79 76 00 - FAX : (33) 01 41 79 76 01 – E-MAIL : contact@icelec.com
SITE WEB : www.groupeice.com
User’s Guide
NPM 800
Issue : b
File : A0343E1E
Date : 02/2004
This document is the sole property of ICE. No duplication nor release to third party is allowed without prior authorization
PREFACE
This aim of this handbook is to provide to the User information useful for the operation of
NPM800 relays with the local MMI.
We advise you to read it attentively, in order to take note of the available functionalities and
to proceed to connection and power of the product in accordance with the provided
recommendations.
Locally, setting, commissioning and real time or event readings are accessible from keyboard
and displayed on the protection display.
To be fully exploited, the available functions must be parameterized and consulted with the
setting software PC – Protection, provided with the product.
Before any use, we recommend you to read the safety instructions of this User’s guide.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 1
Issue : b
CONTENTS
1.
SAFETY INSTRUCTIONS ____________________________________________________________ 3
DOCUMENTATION .................................................................................................................................... 3
CONNECTION OF NP800 RELAYS.............................................................................................................. 3
ON LOAD WITHDRAWAL ........................................................................................................................... 3
REMOVAL AND DESTRUCTION .................................................................................................................. 3
2.
PROTECTION AND OPERATION FUNCTIONS ________________________________________ 4
2.1
PROTECTION FUNCTIONS NPM800 .......................................................................................................... 4
2.2
OPERATION FUNCTIONS NPM 800 ........................................................................................................... 4
2.3
LOCALLY AVAILABLE USER’S FUNCTIONS ............................................................................................... 4
2.4
REMOTELY AVAILABLE USER’S FUNCTIONS............................................................................................. 4
3.
FIRST USE__________________________________________________________________________ 5
3.1
DEFAULT SCREEN..................................................................................................................................... 5
3.2
PRESENCE OF A FAULT OR AN ALARM ...................................................................................................... 5
4.
GENERAL INFORMATION ON MENUS _______________________________________________ 6
4.1
SETTING MODE (IN / OUT) ........................................................................................................................ 6
4.2
MODIFICATION OF A PARAMETER............................................................................................................. 6
4.3
ACCESS CODE........................................................................................................................................... 7
4.4
ASSIGNMENT OF OUTPUT UNITS ............................................................................................................... 7
5.
MENU LIST_________________________________________________________________________ 8
5.1
ACCESS TO MAIN MENUS .......................................................................................................................... 8
5.2
MEASUREMENT MENU.............................................................................................................................. 9
5.3
AFTER START PHASE/EARTH FAULT MENU ..............................................................................................10
5.4
GENERIC FUNCTIONS MENU ....................................................................................................................11
5.5
THERMAL OVERLOAD MENU ...................................................................................................................11
5.6
START MENU ...........................................................................................................................................12
5.7
LOSS OF LOAD MENU (OR PUMP UNPRIMING)...........................................................................................13
5.8
UNBALANCE MENU .................................................................................................................................14
5.9
LOAD SHEDDING MENU ...........................................................................................................................14
5.10 REMOTE CONTROL MENU ........................................................................................................................15
5.11 DISTURBANCE RECORDING MENU ...........................................................................................................15
5.12 COUNTERS MENU ....................................................................................................................................16
5.13 OPERATION MENU ...................................................................................................................................16
5.14 MODBUS® COMMUNICATION MENU (OPTIONAL) ....................................................................................17
5.15 CHANGE OF CODE MENU .........................................................................................................................18
5.16 INFORMATION MENU ...............................................................................................................................18
6.
CONTENT OF AN EVENT___________________________________________________________ 19
6.1
EVENTS GENERATED ON 50/51N/37/46 THRESHOLDS .............................................................................19
6.2
THERMAL OVERLOAD EVENT ..................................................................................................................20
6.3
CUSTOMIZED INPUTS EVENTS ..................................................................................................................21
6.4
OTHER EVENTS .......................................................................................................................................21
6.5
ACKNOWLEDGEMENT OF EVENTS ...........................................................................................................21
6.6
READING OF THE LAST 250 MEMORIZED EVENTS ....................................................................................21
7.
LIST OF FAULTS OR OPERATION MESSAGES_______________________________________ 22
1.1
1.2
1.3
1.4
8.
8.1
8.2
8.3
8.4
8.5
CONNECTION OF NPM800 PROTECTIONS __________________________________________ 23
DESCRIPTION OF THE TERMINAL BLOCKS ................................................................................................23
CONNECTIONS.........................................................................................................................................24
DIAGRAM ................................................................................................................................................24
CONNECTION OF THE CURRENT INPUTS ...................................................................................................24
CONNECTION OF THE MODBUS RS485 COMMUNICATION .......................................................................25
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 2
Issue : b
1.
Safety instructions
For your safety, we recommend you to read the following information carefully. They have
the aim of specifying the precautions essential to the good installation and the correct
operation of the relays.
1.1
Documentation
Following documentations are available for the products of the range NP800:
♦ General Presentation of the NP800 range
♦ User’s Guide of Setting Software for NP800 range
♦ User’s Guide (for each kind of relay)
♦ First Handling Guide (for each kind of relay)
♦ Diagram of each relay.
We advise you to read them before any handling.
1.2
Connection of NP800 relays
The terminal blocks of the relays are studied to ensure the safety of the people during the
operation of the relays.
During installation, commissioning or maintenance, they can however present high voltages
and possibly a thermal heating. Consequently, the following precautions must be respected:
♦ Connection of the terminal blocks at installation must be carried out after having
ensured of the absence of any voltage
♦ Their access during operation must be carried out through adequate means ensuring
as well electric as thermal insulation
♦ The connection of the earth at the back of the relays must imperatively be done with
mean of a 2.5 mm² wire.
Before powering the relays, it will be necessary to check in particular:
♦ The value of the voltage rating of the auxiliary supply and its polarization
♦ The tightening of the intensity circuits and the good realization of connections
♦ The integrity of the connection to the earth.
1.3
On load withdrawal
It is formally misadvised to withdraw the connectors, in particular the current terminal blocks,
under voltage or on load.
1.4
Removal and destruction
The relays should in no case be opened by the User. During their removal, they must be
completely isolated from any external polarity and condensers must be discharged by
connecting their external terminals to the earth.
Destruction of the relays will have to be carried out in accordance with legislation in force, in
particular in compliance with the environment and safety requirements.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 3
Issue : b
2. Protection and operation functions
2.1
Protection functions NPM800
♦
♦
♦
♦
♦
ANSI 49 Thermal overload function, with inhibition of closing on load.
Short-circuit protection, with one ANSI 50 threshold
Earth fault protection, with one ANSI 51N threshold
Minimum load protection (pump unpriming) ANSI 37
Inverse over-current protection with one ANSI 46 threshold for the detection of
unbalance, loss or inversion of phase ANSI 46
♦ Too long starts and locked rotor Protection
♦ ANSI 66 number of starts authorisation Function
♦ Load-shedding and re acceleration Function by external input
2.2
Operation functions NPM 800
♦
♦
♦
♦
♦
Two setting groups
Assignment of digital inputs and relay outputs
User programmable LEDs
Storage of the last 250 events
Storage of four 52 periods disturbance recordings, according to COMTRADE
standard
♦ 8 User configurable generic functions.
2.3
Locally available User’s functions
Locally, the following functions are available:
♦ Choice of language
♦ Setting in or out of order of the functions
♦ Customized identification of protection
♦ Setting of adjustment and primary values for the two tables
♦ Assignment of the inputs / outputs
♦ Reading of fault values
♦ Reading of each memorized value: measurements and counters
♦ Reset of counters
♦ Reading of events
♦ Configuration of disturbance recording and local trigger
♦ Configuration of Modbus® communication.
2.4
Remotely available User’s functions
The following functionalities can only be accessed through the RS232 or RS485 links:
♦ Saving of configuration
♦ Commissioning tests: LCD display, adjustment of contrast, LEDs
♦ Commissioning tests: relays, wiring
♦ Reading of real time values: measurement and counters
♦ Reading of disturbance recordings.
These functions are however available with the setting software.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 4
Issue : b
3.
First use
When powering the relay, the displays below can appear. The recommended action allows
starting the parameter setting of protection.
3.1
Default screen
In absence of a fault, the protection displays the phase 1 current measurement in HV value.
CURRENT I1
0.0 A
3.2
Presence of a fault or an alarm
If a fault or alarm occurs, a message indicates the type of fault.
When threshold is exceeded or when tripping, the following messages appear:
TRIP
PHASE FAULT
This message disappears at once after acknowledgement of the fault and is replaced by the
following message.
TRIP PH FAULT
S
10/12 16:38.15
R
This message remains until the acknowledgement of the fault by the User.
The use of the
and
keys allows to visualize additional information on the fault.
note: if the mode " simplified recording of events" is not chosen, the display will be as follows:
TRIP PH FAULT E
INST PH FAULT E
TRIP PH FAULT S
INST PH FAULT S
17/06 14:22:28
17/08 14 :22 :28 R
17/08 14 :22 :27 R
17/08 14 :22 :26 R
R
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 5
Issue : b
4.
General information on menus
All parameters can be accessed for reading. On the other hand, parameters are writeprotected by an access code requested on the first modification.
4.1
Setting mode (In / Out)
Press any key except CLEAR to enter in setting mode.
If no parameter has been modified, exit the mode by pressing the CLEAR key:
CURRENT I1
MAIN MENU
CLEAR,
ENTER MEASUREMENTS
0.0 A
CURRENT I1
CLEAR
0.0 A
If a parameter has been modified, confirm the exit from setting mode:
MAIN MENU
CLEAR
PHASE EARTH FLT.
QUIT SETTINGS
MODE ?
ENTER
CURRENT I1
0.0 A
Without any operation, return to OPERATION mode is carried out automatically after 5
minutes.
4.2
Modification of a parameter
Use the "
parameter
" and "
" keys to select a menu then press the ENTER key to access the first
MAIN MENU
MAIN MENU
MEASUREMENTS
PHASE EARTH FLT.
Use the "
" and "
SETTING
ENTER
set 1
" keys to access the various parameters in the menu::
SHORT CIRCUIT
SHORT CIRC.DELAY
SHORT CIRC.THRES
Active
0,50 s
3,0 * In
Use the
and
keys to modify the parameter.
You must confirm your change using the ENTER key after each parameter modification.
After storing the new parameter value, next parameter is displayed:
SHORT CIRC.DELAY.
SHORT CIRC.DELAY.
0.60 s
0.70
Use the CLEAR and
ENTER
SHORT CIRC.THRES
3,0 * In
to change menu :
SHORT CIRC.DELAY.
0,70 s
CLEAR
MAIN MENU
MAIN MENU
PHASE EARTH FLT.
GENERIC FUNCTION
Leaving any sub menu with the CLEAR key will lead to the above menu.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 6
Issue : b
4.3
Access code
On first modification of a parameter, the software requests the access code.
The factory-programmed code is " ICE1 ".
To enter your own personalised code, use the " CHANGE CODE " menu. The code can be
composed up to four alphanumeric characters.
The following example shows how to replace code "AA" with " 99 ":
MAIN MENU
ENTER
CHANGE CODE
NEW PASSWORD
_
OLD PASSWORD
OLD PASSWORD
OLD PASSWORD
OLD PASSWORD
_
A
A_
AA
NEW PASSWORD
9
NEW PASSWORD
NEW PASSWORD
9_
MAIN MENU
ENTER
99
ENTER
CHANGE CODE
In case of loss of the code, contact us to obtain an emergency password for your
configuration.
4.4
Assignment of output units
Relays assigned to a function are displayed with" * ".
Key " " allows modifying assignment of the relays.
Key
allows selection of next relay.
Example: assignment of relay B to TRIP Io> function. At the beginning, no function was
assigned to this relay.
EARTH TRIP RELAY
A_
B
C
D
EARTH TRIP RELAY
A
B_ C D
EARTH TRIP RELAY
A
B*
C
D
ENTER
EARTH TRIP RELAY
E
F
G
Caution: do not to forget to confirm by ENTER key
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 7
Issue : b
5.
Menu list
5.1
Access to main menus
The following menus enable setting of the available functions. Each one allows access to the
parameters of adjustment and ensures their coherence.
CURRENT I1
100.0 A
ENTER, , , , ,
CLEAR
MAIN MENU
MEASUREMENTS
MAIN MENU
PHASE EARTH FLT.
MAIN MENU
GENERIC FUNCTION
MAIN MENU
THERMAL REPLICA
MAIN MENU
STARTING FCT
MAIN MENU
LOSS OF LOAD
MAIN MENU
UNBALANCE
MAIN MENU
DELOAD
MAIN MENU
TELECONTROL
MAIN MENU
PERTURBOGRAPHY
MAIN MENU
COUNTERS
MAIN MENU
OPERATION
MAIN MENU
MODBUS COMMS
MAIN MENU
CHANGE CODE
MAIN MENU
INFORMATION
MAIN MENU
EVENTS
Press on any key other than CLEAR
to enter the parameter setting mode
Press on CLEAR key to leave
the parameter setting mode
Real time measures
Use the or
select a menu
keys to
Parameters of the functions 50 and
51N
Parameters of the customized
functions
Parameters of the thermal overload
function
Parameters of the functions 51LR
and 66 (starts)
Parameters of the minimum load
function (pump unpriming) 37
Parameters of the function 46
(unbalance)
Parameters of the load-shedding
function
Parameters of the remote control
option
Information about disturbance
recording
Information about counters
Operating parameters to be defined
at commissioning
Configuration of the Modbus RS485
communication option
(if option available)
Change of the access code
Information about protection
Reading of the event log
Leaving any sub menu with the CLEAR key will lead to the above menu.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 8
Issue : b
5.2
Measurement menu
This menu displays any real time measurement of the protection, as well as the values kept
in memory.
MAIN MENU
Available real time measures
MEASUREMENTS
ENTER / CLEAR
CURRENT I1
Measure of the phase 1 primary
0.0 to 64000 A
current
0.0 A
CURRENT I3
Measure of the phase 3 primary
0.0 to 64000 A
current
0.0 A
CURRENT Io
Measure of the earth Io primary
0.0 to 64000 A
current
0.00 A
FREQUENCY
Measure of the network frequency
45 to 55 if Fn = 50 Hz
55 to 65 if Fn = 60 Hz
50.00 Hz
THERMAL STATE
Measure of the thermal state of
0.0 to 500 %
motor
0.0 %
NEGATIVE SEQ.
Measure of the rate of negative
sequence of current
0.0 %
POSITIVE SEQ.
Measure of the rate of direct
component
of current
0.0 %
CURRENT START
Maximum current measured during
0 to 64 000 A
last start (software 2.xx)
0.0 A
STARTS ALLOWED
number of authorized remaining
Inactive if function MAX
starts
NBR STARTS inactive.
4
START TIME
Duration of the last start
1 à 200 s
3.00 s
AVER. CURRENT I1
Value of the average primary current
0 to 64 000 A
of
phase
1
100.0 A
AVER. CURRENT I3
Value of the average primary current
0 to 64 000 A
of
phase
3
100.0 A
AVER. CURRENT I0
Value of the average earth-fault
0 to 64 000 A
primary
current
0.0 A
SETTING
Display of the active setting
Set 1 or Set 2
set 1
02/07/01
Day / Month / Year
10:19:42
Hour / minute / second
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 9
Issue : b
5.3
After start phase/earth fault menu
This menu allows the setting of the phases and earth fault over current functions: setting in
and out of order, choice of the types of time delay and curves, adjustment of thresholds,
assignment of the output units.
This configuration must be carried out successively for each of the two settings groups if they
are to be used alternatively.
MAIN MENU
PHASE EARTH FLT.
ENTER / CLEAR
Parameters of the ANSI 50, 51N
functions
SETTING
set 1
SHORT CIRCUIT
Active
SHORT CIRC.DELAY.
0.06 s
SHORT CIRC.THRES
3.0 * In
SHORT C.INST.REL
A B C D
SHORT C.INST.REL
E F G
SHORT C.TRIP.REL
A B C D
SHORT C.TRIP.REL
E F G
EARTH FAULT
Active
INHIBITION Io
Active
EARTH FLT DELAY
0.06 s
EARTH FLT THRESH
0.1 * In
EARTH INST.RELAY
A B C D
EARTH INST.RELAY
E F G
EARTH TRIP RELAY
A B C D
EARTH TRIP RELAY
E F G
Choose the setting group
Set 1 or Set 2
Choose Active to use the phase to
phase short-circuit function
Active or Inactive
Set the value of time delay of the
phase to phase short-circuit function
0.04 à 3 s
Set the threshold of the phase to
phase short-circuit function
3.0 à 12.0 * In
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Relay to assign to the short-circuit
instantaneous function
Relay to assign to the short-circuit
instantaneous function
(relays D, E, F, G if option
available)
Relay to assign to the short-circuit trip
function
Relay to assign to the short-circuit trip
function
(relays D, E, F, G if option
available)
Choose Active to use the earth fault
function
Choose Active to use the earth fault
function during the start
Set the value of the time delay of
earth fault function
0.04 à 3 s
Set the value of the threshold of earth
fault function
0.03 à 0.4 * In
Relay to assign to the earth fault
instantaneous function
Relay to assign to the earth fault
instantaneous function
(relays D, E, F, G if option
available)
Relay to assign to the earth fault trip
function
Relay to assign to the earth fault trip
function
User’s Guide
NPM 800
(relays D, E, F, G if option
available)
Date : 01/2004
Print :11/03/2004
Sheet : 10
Issue : b
5.4
Generic functions menu
This menu allows the parameter setting of 8 customized functions: setting in and out of order,
adjustment of the time delays, assignment of the output units, assignment of a logical input.
MAIN MENU
GENERIC FUNCTION
ENTER / CLEAR
FCT GENERIC
1
Inactive
TEMP GENERIC 1
0,06 s
RELAY GENERIC 1
A_ B
C
D
RELAY GENERIC 1
E_ F
G
DIG.INP.GENER. 1
No input
NAME GENERIC 1
GENERIC 1
……………
5.5
Parameters of the customized
functions
Choose Active to use function 1
Active or Inactive
Set the time delay of function 1
0.04 to 300.00s
Relay to assign to function 1
Relay to assign to function 1
Display of input selected for function 1
(configurable with the
setting software)
Display of label of function 1
(configurable with the
setting software)
Thermal overload menu
This menu authorizes the parameter setting of the thermal overload function: setting in and
out of order, type of thermal overload, adjustment of the thermal time-constant, adjustment of
the thermal trip and alarm thresholds, assignment of the output units for alarm and trip.
MAIN MENU
THERMAL REPLICA
ENTER / CLEAR
Parameters of the thermal overload
option
SETTING
set 1
THERMAL OVERLOAD
Active
HEATING CONST
40 mn
COOLING CONST
4.0
START FACTOR
50 %
NEG. SEQ. FACTOR
3
THERM THR. Iref
0.40 * In
Choose the setting group
Set 1 or Set 2
Choose Active to use thermal
overload function
Active or Inactive
Set the value of the thermal overload
time-constant
4 to 64 min
Set the cooling constant
1.0 to 6.0 * heating constant
Set the coefficient calculation of the
thermal overload (starting mode)
50 to 100 %
Set the negative sequence factor K
(thermal heating)
0 to 9
Set the thermal reference current Iref
0.40 to 1.3 x In
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 11
Issue : b
TH. TRIP RELAY
A B C D
TH. TRIP RELAY
E F G
TH. ALARM THRESH.
80 %
TH. ALARM RELAY
A B C D
TH. ALARM RELAY
E F G
5.6
Select the relays of thermal overload
trip
Select the relays of thermal overload
trip
(relays D, E, F, G if option
available)
Set the thermal alarm threshold
80 to 100 %
Select the relays to be assigned to
the thermal alarm function
Select the relays to be assigned to
the thermal alarm function
(relays D, E, F, G if option
available)
Start menu
This menu authorizes the parameter setting of the too long start, locked rotor, limitation of the
number of start and inhibition of hot start functions: setting in and out of order, adjustment of
the start motor and inhibition of hot start threshold, adjustment of the time delays (start,
locked rotor, restarting), assignment of the output units for the trip (too long start, locked rotor
and inhibition of start).
MAIN MENU
STARTING FCT
ENTER / CLEAR
SETTING
set 1
LONG ST/ST.ROTOR
Active
START THRESHOLD
2.0 * Iref
START DELAY
20 s
STALLED DELAY
0.2 s
REL.LONG S/ROT S
A B C D
REL.LONG S/ROT S
E F G
MAX NBR STARTS
Active
MAX NBR STARTS
3
COUNT DELAY
15 min
RESTART DELAY
15 min
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
number of starts, too long start, rotor
stall after start period
Choose the setting group
Set 1 or Set 2
Choose Active for too long start and
locked rotor (51 LR)
Active or Inactive
Detection Threshold of the start of
the motor (Iref: thermal current of
reference)
Maximum duration of start for too
long start
1.0 to 10.0 * Iref
Time delay to detect a locked rotor
after a start
0.2 to 2.0 s
2 to 200 s
Set the too long start and locked
rotor relays (51 LR)
Set the too long start and locked
rotor relays (51 LR)
(relays D, E, F, G if option
available)
Choose Active for the maximum
number of starts function
Active or Inactive
maximum Number of starts during
time delay
1 to 4
Set the time delay for counting
15 to 60 min
Duration of the inhibition of restarting
15 to 60 min
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 12
Issue : b
HOT START
Active
HOT START THRESH
40 %
START RELAY
A B C D
START RELAY
E F G
5.7
Choose Active for the hot motor
inhibition of start function
Active or Inactive
Setting of the threshold of inhibition
of hot motor starting
40 à 100 %
Set the relays Inhibition of hot motor
starting
Set the relays Inhibition of hot motor
starting
(relays D, E, F, G if option
available)
Loss of load menu (or pump unpriming)
This menu allows parameterizing operation on loss of load.
MAIN MENU
LOSS OF LOAD
ENTER / CLEAR
SETTING
set 1
LOSS OF LOAD
Active
MIN THRESHOLD Id
0.20 * In
LOAD LOSS DELAY
2s
LOAD LOSS RELAY
A B C D
LOAD LOSS RELAY
E F G
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Choose the setting group
Set 1 or Set 2
Choose Active to use the loss of load Active or Inactive
function
Minimum direct current for loss of
load threshold
0.10 to 2.40 * In
Set the time delay of the loss of load
function
0.05 to 120 s
Select the relays to be assigned to
the loss of load function
Select the relays to be assigned to
the loss of load function
User’s Guide
NPM 800
(relays D, E, F, G if option
available)
Date : 01/2004
Print :11/03/2004
Sheet : 13
Issue : b
5.8
Unbalance menu
This menu allows parameterizing the unbalance function.
MAIN MENU
UNBALANCE
ENTER / CLEAR
SETTING
set 1
UNBALANCE
Active
NEG. SEQ. THRESH
0.20 * In
NEG. SEQ. DELAY
1s
TRIP.MIN.N.S.DEL
0.06 s
UNBAL.INST.RELAY
A B C D
UNBAL.INST.RELAY
E F G
UNBAL.TRIP RELAY
A B C D
UNBAL.TRIP RELAY
E F G
5.9
Choose the setting group
Set 1 or Set 2
Choose Active to use the unbalance
and phase reversal function
Active or Inactive
Set the negative sequence
threshold
0.20 to 0.80 * In
Set the dependent time curve
1 to 10 s
Set the minimum duration of trip
0.04 to 10 s
Select relays for the instantaneous
unbalance and phase reversal
functions
Select relays for the instantaneous
unbalance and phase reversal
functions
Select relays for the instantaneous
unbalance and phase reversal trip
(relays D, E, F, G if option
available)
Select relays for the instantaneous
unbalance and phase reversal trip
(relays D, E, F, G if option
available)
Load shedding menu
This menu allows parameterizing the load-shedding function on order external and the
restarting of the motor.
MAIN MENU
DELOAD
ENTER / CLEAR
Load-shedding on external order
and re acceleration parameters
SETTING
set 1
DELOAD
Active
DELOAD DELAY
0.10 s
DELOAD RELAY
A B C D
DELOAD RELAY
E F G
Choose the setting group
Set 1 or Set 2
Choose Active to use the loadshedding function
Active or Inactive
Set time delay of load-shedding
0.06 à 120 s
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Select relays for the load-shedding
function
Select relays for the load-shedding
function
User’s Guide
NPM 800
(relays D, E, F, G if option
available)
Date : 01/2004
Print :11/03/2004
Sheet : 14
Issue : b
5.10 Remote control menu
This menu authorizes the parameter setting of the remote control function: setting in and out
of order, level of load-shedding, adjustment of the time delay of reconnection, assignment of
the trip and reclosing relays, pulse of reclosing, assignment of the logical inputs.
MAIN MENU
TELECONTROL
ENTER / CLEAR
TELECONTROL
Inactive
LOAD SHED LEVEL
6
RE-LOAD DELAY
1,00 s
TRIP RELAY
A_ B
C
D
TRIP RELAY
E_ F
G
RECLOSE RELAY
A_ B
C
D
RECLOSE RELAY
E_ F
G
RECLOSE PULSE
200 ms
O/O INPUT
E1
C/O INPUT
E2
LOCAL INPUT
E3
DISTANT INPUT
E4
Information about remote control
option
Choose Active to use the remote
control function
Active or Inactive
Set the level of load-shedding. Level
6 inhibits the load-shedding function
1 to 6 (step 1)
Set the value of time delay before
reclosing
1.00 to 120.00 s
Select the relays to be assigned to
the trip
Select the relays to be assigned to
the trip
(relays D, E, F, G if option
available)
Select the relays to be assigned to
the reclosing
Select the relays to be assigned to
the reclosing
(relays D, E, F, G if option
available)
Set the reclosing pulse
100 to 500 ms
Display of the logical input assigned
to the position of the interlock
(configurable with setting
software)
Display of the logical input assigned
to the position of the interlock
(configurable with setting
software)
Display of the logical input assigned
to the mode of OPERATION
(configurable with setting
software)
Display of the logical input assigned
to the mode of OPERATION
(configurable with setting
software)
5.11 Disturbance recording menu
This menu is used to configure the parameters of the disturbance recording.
MAIN MENU
Parameters of the disturbance
recording function
PERTURBOGRAPHY
ENTER / CLEAR
PRE-TIME
Set pre time
1 to 52
35 period(s)
PERTURBO. INPUT
Display of input assigned to external (configurable with the
trip
setting software)
No input
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 15
Issue : b
5.12 Counters menu
This menu allows the parameter setting of the counters: display of cut A², number of circuit
breaker operations, current maximeters, restoring of the counters.
MAIN MENU
COUNTERS
ENTER / CLEAR
Parameters of the counters function
A2 CUTOFF I1
100000.0 kA2
A2 CUTOFF I3
0,0 kA2
RESET A2 CUTOFF
Confirm: ENTER
NBER OPERATIONS
0
RESET NB OPERAT.
Confirm: ENTER
MAX. METER I1
1049 A
MAX. METER I3
1048 A
MAX. METER I0
68 A
MAX. METER RESET
Confirm: ENTER
Display of cut A² of phase 1
Display of cut A² of phase 3
Reset of cut A² with ENTER key
Display of the number of operations
of the circuit breaker
Reset of the number of operations of
the circuit breaker
Display of the current maximeter on
phase 1
Display of the current maximeter on
phase 3
Display of the current maximeter on
earth
Reset of current maximeter with
ENTER key
5.13 Operation menu
This menu authorizes the parameter setting of the operation function: choice of the language,
adjustment of LCD contrast, parameter setting of the values of the phase and earth-fault
CTs, display of the input logical corresponding to set 2, trip pulse, maximum of cut A² and
number of operations of the circuit breaker, assignment of the relays for circuit breaker failure
and discrepancy, average current.
MAIN MENU
OPERATION
ENTER / CLEAR
LANGUAGE
English
ADJUST LCD
200
I NOMINAL PRIM.
1000 A
Io NOMINAL PRIM.
100 A
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Operating parameters to be defined
at commissioning
Choice of the language used locally
by protection
French or English
Adjustment of the angle of vision of
the LCD display
70 to 255
Set the value of the phase primary
rated current of the CTs
1 to 10000 A
Set the value of the earth primary
rated current of the CT
1 to 10 000 A
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 16
Issue : b
SET 2 INPUT
E6
CLEAR REL. INPUT
E5
TRIP PULSE
100 ms
MAX A2 CUTOFF
5000000 kA2
MAX NBER OPERAT.
9999
RELAY C.B. FAULT
A_ B
C
D
RELAY C.B. FAULT
E_ F
G
RELAY DISC. L/D
A_ B
C
D
RELAY DISC. L/D
E_ F
G
I AVERAGE
in 30 mn
Display of input assigned to setting
group 2
No input, E1 to E8
Display of input assigned to reset of
relays
No input, E1 to E8
Setting of minimum duration of trip
pulse
100 to 500 ms
Adjustment of the maximum of cut A² 1 to 64 000 000 kA²
Adjustment of the maximum number
of operations of the circuit breaker
1 to 10000
Select the relay assigned to the
circuit breaker failure function
Select the relay assigned to the
circuit breaker failure function
Select the relay assigned to the
local/distant discrepancy function
Select the relay assigned to the
local/distant discrepancy function
(if remote control option)
Adjustment of the time for calculation 5 to 60 min
of average values and maximeters
5.14 Modbus® communication menu (optional)
This menu is used to set the parameters of the Modbus® communication function: slave
number, size, speed, activity and loop tests.
MAIN MENU
MODBUS COMMS
ENTER / CLEAR
SLAVE NUMBER
2
FORMAT
8b+0p+2s ASCII
Configuration of the Modbus
RS485 communication option
SPEED
9600 bauds
Speed transmission on RS485 link
RECEPT. TIMEOUT
0.10 s
ACTIVITY TIMEOUT
0.20 s
ACTIVITY TEST
Mess.Receiv.com1
Set the time delay of reception
timeout
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Slave number of protection
1 to 255
number of bits + parity + bits of
stop + ASCII/Binary format
Parity: 1p = pair, 1i = odd,
0p= without
p0 = forced to 0, p1 = forced
to 1,
300, 600 ,1200 ,1800, 2400,
4800, 9600, 19200 38400,
57 600,115 200 bauds
0.10 to 20 s
Set the time delay of activity
timeout
0.10 to 20 s
Test of the parameter setting and
the wiring of Modbus
message received / not
received: correct activity /
communication problem
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 17
Issue : b
5.15 Change of code menu
This menu allows change of code and is described in chapter Access Code.
5.16 Information menu
Information menu specifies the factory set characteristics of the protection, as well as the
label assigned by the User.
MAIN MENU
INFORMATION
ENTER / CLEAR
Information about protection
NP.M 800
50 Hz
PROC. VER. 1.22a
Type of protection
Rated frequency
Version of the software of
protection
PHASES RAT. 1 A
EARTH RAT. 1 A
NPM 800
ICE
Display of the phases and earth
ratings
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
32 characters zone programmable with the setting software.
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 18
Issue : b
6.
Content of an event
Events are different according to information recorded when fault occurs. There are three
different types of structures of event.
They can be read with the local MMI, the setting software (RS232 link) and the Modbus
communication network.
6.1
Events generated on 50/51N/37/46 thresholds
Events are recorded as soon as a trip or alarm threshold of the current functions is reached:
♦ INST PH FAULT
♦ TRIP PH FAULT
♦ INST Io FAULT
♦ TRIP Io FAULT
♦ INST UNBALA PH
♦ TRIP UNBALA PH
♦ TRIP START LON
♦ TRIP STALL ROT
♦ TRIP LOSS LOAD
♦ TRIP DELOAD
Detail of available information can be consulted for each event, in accordance with the list
below:
MAIN MENU
List of the last 250 events
EVENTS
ENTER / CLEAR
TRIP PH FAULT
E
17/06 14:22:00
R
17/06/03
14:22:00.990
SETTING
set 1
CURRENT I1
745 A
CURRENT I3
746 A
CURRENT Io
0.1 A
NEGATIVE SEQ.
175,6 %
THERMAL STATE
100,0 %
The use of the
and
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group
set 1 or
set 2
Current of phase 1 measured at disappearance of the trip
Current of phase 3 measured at disappearance of the trip
Earth-fault current measured at disappearance of the trip
Rate of negative sequence current
Motor thermal state measured at appearance of trip
keys
allows to visualize additional information on the fault.
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 19
Issue : b
6.2
Thermal overload event
Events are recorded as soon as a trip or alarm threshold of the voltage or frequency
functions is reached:
♦ ALRM THERM REP
♦ TRIP THERM REP
Detail of available information can be consulted for each event, in accordance with the list
below:
6.2.1 Thermal alarm
ALRM THERM REP S
17/06 13:25:55
R
17/06/03
13:25:55.240
SETTING
set 1
CURRENT I1
2484 A
CURRENT I3
0A
CURRENT Io
0,0 A
NEGATIVE SEQ.
90.0 %
THERMAL STATE
80 %
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group when tripping
set 1 or
set 2
Phase 1 current measured at appearance of alarm
Phase 3 current measured at appearance of alarm
Earth fault 1 current measured at appearance of alarm
Rate of negative sequence current
Motor thermal state measured at appearance of alarm
6.2.2 Thermal trip
TRIP THERM REP
17/06 13:25:59
17/06/03
13:26:59.920
SETTING
set 1
CURRENT I1
2490 A
CURRENT I3
0A
CURRENT Io
0,0 A
NEGATIVE SEQ.
100 %
THERMAL STATE
0%
S
R
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day: Month: Year
Hour: Minute: Second. Millisecond
Active setting group when tripping
set 1 or
set 2
Phase 2 current measured at disappearance of trip
Phase 3 current measured at disappearance of trip
Earth fault current measured at disappearance of trip
Rate of negative sequence current
Motor thermal state measured at appearance of trip
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 20
Issue : b
6.3
Customized inputs events
Events are recorded as soon as one of the customized input status changes.
♦ GENERIC 1
Detail of available information can be consulted for each event, in accordance with the list
below:
GENERIC 1
S
Type of fault
Start or End of fault
17/06 13:42:23
R Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
17/06/03
Day / Month / Year
Hour: Minute: Second. Millisecond
13:42:23.240
SETTING
Active setting group
set 1 or
set
2
set 1
6.4
Other events
The contents of the following events can be specified:
♦ ALRM NB OPERAS
♦ ALRM A2 CUTOFF
♦ CB FAIL
♦ DISC LOCA/REMO
♦ MODE REMOTE
♦ UNLISTED EVENT
♦ SETTING SET 2
♦ TRIP TELECONTR
♦ RECLOSE TELECO
Detail of available information can be consulted for each event, in accordance with the list
below:
ALRM NB OPERAS S
25:6 9:35:45 R
25/6/95
9:35:45.011
SETTING
set 1
6.5
Type of fault
Start or End of fault
Day/Month Hour/Minute/Second - Dated event Relative/Synchronous
Day / Month / Year
Hour: Minute: Second. Millisecond
Active setting group
set 1 or
set 2
Acknowledgement of events
The acknowledgement of the last event is carried out while pressing on CLEAR key:
TRIP PH FAULT E
10/12 16:38.15
6.6
R
CLEAR
ACKNOWLEDGE ALL
Confirm: ENTER
ENTER
CURRENT I1
0,0 A
Reading of the last 250 memorized events
After acknowledgement, the memorized events still may be read. It is necessary to use the
local sub-menu EVENTS of the MMI.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 21
Issue : b
7.
List of faults or operation messages
The following messages are locally displayed in real time on LCD display throughout fault.
Messages related to instantaneous type functions:
INSTANTANEOUS PHASE FAULT
INSTANTANEOUS EARTH FAULT
ALARM THERMAL REPLICA
INSTANTANEOUS UNBALANCE
Messages related to trip type functions:
TRIP PHASE FAULT
TRIP EARTH FAULT
TRIP THERMAL REPLICA
TRIP START TOO LONG
TRIP STALLED ROTOR
TRIP UNBALANCE PHASE
TRIP LOSS OF LOAD
TRIP DELOAD
TRIP BY TELECONTROL
TRIP GENERIC
Messages related to alarm type functions:
ALARM NUMBER OPERATIONS
ALARM A2 CUTOFF
CIRCUIT BREAKER FAIL
DISCORDANCE : LOCAL / REMOTE
Various messages:
RECLOSE BY TELECONTROL
REMOTE MODE
UNLISTED EVENT
Note: disappearance of cut A² and number of operations alarms is done by resetting the
COUNTERS menu.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 22
Issue : b
8.
Connection of NPM800 protections
8.1
Description of the terminal blocks
Extension board (connectors E, F, G and RS485-2) is optional on the NPM800.
+
-
RS485-1
E
1
F
7
S1
IA
A
S2
6
S1
1
IB
S2
1
5
B
G
5
1
S1
IC
C
1
S2
D
S1
I0
S2
7
-
+
-
RS485-2
AUX
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
+
Date : 01/2004
Print :11/03/2004
Sheet : 23
Issue : b
8.2
Connections
Connections
Location Characteristics
Modbus® or IEC870-5-103
Communication
RS485-1
RS485-2
Connection of the VTs
A
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Logical inputs
B
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Relays
C and D
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Auxiliary supply
AUX
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Relays
(optional board)
E and F
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Logical inputs
(optional board)
G
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Connection of the CTs
IA to IO
4 mm ring type terminal. Section of wire ≤ 6 mm²
8.3
Screw terminal block. Section of wire 0.6 to 2.5
mm²
Diagram
The diagram is available under the reference S 38024.
8.4
Connection of the current inputs
Connection is done by 6mm² ring terminals for M4 screw. It is identical for all the variants of
inputs:
♦ Phases CT 1A or 5A
♦ Earth-fault CT 1A or 5A or CT Ring.
Respect the rotating sense of phases and the direction of the connection of phases.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 24
Issue : b
8.5
Connection of the Modbus RS485 communication
8.5.1 Characteristics of the network cable
Recommended characteristics for the cable:
• Shielded twisted pairs, maximum length 1000 m.
• resistance < 100 ohms/km
• capacity between wires < 60 pF/m
• capacity between wire and shield < 100 pF/m
It is imperatively necessary to tighten the fixing clamp on the shield and not on insulator, in
order to ensure continuity of the shield of the cable and its earthing.
8.5.2 Resistance of adaptation
Connect a 120 ohms resistance of adaptation to each protection located at each end of the
network.
It is necessary to connect the Rterm +T/R according to the diagram
RS485
*
+T/R
-T/R
120
Ohms
R term
If the Master is connected at one end of the network, it is necessary to place a resistance of
adaptation on the Master and another on the protection located at the other end of line using
the switches of the communication board.
This document is the sole property of
ICE. No duplication nor release to third
party
is
allowed
without
prior
authorization
User’s Guide
NPM 800
Date : 01/2004
Print :11/03/2004
Sheet : 25
Issue : b
Descargar