Controller Ceiling-Mounted RF Receiver rta-rx-sw-1 03.17.07 RadioTouchTM RF Switchpack Controller RTA-RX-SW RTA-RX-SW-347 RadioTouch RTA-RX-SW 120/277 V 16 A Max. TM Description The RadioTouch switchpack controller is designed to work in conjunction with RadioTouch transmitters that have been addressed to the controller. The controller can be addressed to respond to signals from up to 16 RadioTouch transmitters. The controller can switch 16 amps of high inrush lighting loads, including magnetic fluorescent ballasts, electronic fluorescent ballasts, incandescent, magnetic low-voltage, electronic low-voltage, and HID loads. 60 Hz LISTED 243C Ind. Cont. E q. Coopersburg, PA 18036 USA ® Refer to the Installers Guide for more detailed instructions. 1-800-523-9466 Consulte la Guía de Instaladores para 1-888-235-2910 información más detallada. USA, Canada Mexico www.lutron.com Référer au Guide d’installation pour plus de renseignements détaillés. STAT 3 4 5 6 7 Cir Com 3 Sig 1 2 15 V 2 24 V 1 Occ. Com PELV (Class 2: USA) ON 8 PROG RESTAURAR REINITIALISE RESET P/N 500-10635 © 2006 Lutron Electronics Co., Inc. CONFIGURACIONES REGLAGES PWR SETTINGS The controller mounts to a standard 4 x 4 in. (120 x 120 mm) junction box or to the knockout of a fluorescent fixture. The controller can directly accept inputs from standard 15 and 24 V occupant sensors. The controller operates at either 120/277 V or 347 V , depending on the model number. Ratings Model Number RTA-RX-SW RTA-RX-SW-347 R Voltage 120 or 277 V 347 V Maximum Current 16 A (20 A breaker) 16 A (20 A breaker) S P E C I F I C AT I O N S U B M I T TA L Job Name: Job Number: Model Numbers: Page 1 Controller Ceiling-Mounted RF Receiver rta-rx-sw-2 03.17.07 Dimensions RadioTouch RTA-RX-SW 120/277 V 16 A Max. TM 60 Hz LISTED 243C Ind. Cont. E q. Coopersburg, PA 18036 USA ® Refer to the Installers Guide for more detailed instructions. 1-800-523-9466 Consulte la Guía de Instaladores para 1-888-235-2910 información más detallada. USA, Canada Mexico www.lutron.com Référer au Guide d’installation pour plus de renseignements détaillés. STAT PROG 3 3 4 3 4 5 6 7 8 Cir Com Sig 1 2 15 V 2 24 V 1 Occ. Com PELV (Class 2: USA) ON RESTAURAR REINITIALISER RESET P/N 500-10635 © 2006 Lutron Electronics Co., Inc. CONFIGURACIONES REGLAGES PWR SETTINGS 7.75 in. (197 mm) ON 1 2 3 1 TX 2 5 6 7 8 RX 4 in. (100 mm) 2.5 in. (17.8 mm) Features • Capable of switching 16 amps of high inrush lighting load (magnetic fluorescent ballasts, incandescent, magnetic low-voltage, electronic low-voltage, and HID loads). • RTA-RX-SW operates at 120 or 277 V line voltage. • RTA-RX-SW-347 operates at 347 V line voltage. • Each controller can be programmed to accept control information from 16 unique RadioTouch transmitters. • Accepts inputs from standard 15 and 24 V occupant sensors and provides power to them (not to exceed 30 mA). • One required per lighting zone to be controlled. • Accepts control signals from RadioTouch transmitters at 418 MHz. • Provides a burn-in function to assist in the seasoning of new fluorescent bulbs for 100 hours. • Mounts to a standard 4 x 4 in. (120 x 120 mm) junction box or to the knockout of a fluorescent fixture. Mounting Using two screws, mount the unit to a 4 x 4 in. (120 x 120 mm) junction box or directly to a wall (screws and wall anchors are provided) as shown. R S P E C I F I C AT I O N S U B M I T TA L Job Name: Job Number: Model Numbers: Page 2 Controller Ceiling-Mounted RF Receiver rta-rx-sw-3 03.17.07 Power Wiring Diagram Green White Black (120 V Black/Red Ground Neutral Switched Hot ) Blue Distribution panel RadioTouch RTA-RX-SW 120/277 V 16 A Max. TM Fixture ground Switched load 60 Hz LISTED 243C Ind. Cont. E q. Coopersburg, PA 18036 USA Green White Black ® Refer to the Installers Guide for more detailed instructions. 1-800-523-9466 Consulte la Guía de Instaladores para 1-888-235-2910 información más detallada. USA, Canada Mexico www.lutron.com STAT ON 3 Sig 15 V 3 4 24 V 1 2 5 6 7 Cir Com 2 Occ. Com 1 8 PROG RESTAURAR REINITIALISER RESET P/N 500-10635 © 2006 Lutron Electronics Co., Inc. CONFIGURACIONES REGLAGES PWR SETTINGS PELV (Class 2: USA) Ground Neutral Hot Référer au Guide d’installation pour plus de renseignements détaillés. Green White Black Red (277 or 347 V ) Cap the wire that is not being used (red or black, depending on voltage) R Job Number: Switched load To additional switched loads S P E C I F I C AT I O N S U B M I T TA L Job Name: Fixture ground Model Numbers: Page 3