4X-LCD and 4X-LCD-LC User Interface Installation Sheet EN ES FR PT Installation EN: Installation Sheet WARNING: Electrocution hazard. To avoid personal injury or death from electrocution, remove all sources of power and allow stored energy to discharge before installing or removing equipment. Description The 4X-LCD and 4X-LCD-LC provide the user interface for the fire alarm control panel. Only one user interface is required to provide a point of control for the entire network. However, additional user interfaces can be added to any panel in the network to provide additional points of control. Caution: Circuit boards are sensitive to electrostatic discharge (ESD). To avoid damage, follow ESD handling procedures. To install the 4X-LCD(-LC) user interface: The 4X-LCD-LC allows you to install separately ordered language inserts into pockets on the interface for the control and indicator labels. See the 4X-LK Language Kit Installation Sheet (P/N 3101995-ML) for a list of available kits and installation instructions. 1. Connect the data ribbon cable from J1 on the 4X-LCD(-LC) to J9 on the front of the SFS1-CPU main board. See Figure 2. 2. Hold the 4X-LCD(-LC) in the open position at an angle of approximately 45 to 50 degrees and then insert its hinge pins into the hinges on the SFS1-CPU. 3. Power up the panel and check the display screen brightness. Turn the potentiometer on the back of the 4X-LCD(-LC) clockwise to darken the screen, or counterclockwise to brighten it. See Figure 2. 4. Close the 4X-LCD(-LC). Make sure it snaps into place. Controls and indicators Figure 1: Controls and indicators XXXXX XXXXXXX XXX XXX XXXXX XXX XXXX XXXXXXX XXXXX (1) (2) (3) (4) XXXXXXXXXXX (1) (2) (3) (4) XXXXX XXXXXX XXXXX XXXXXXX XXXXX System status indicators LCD screen Rotary controller Common controls with indicators © 2012 UTC Fire & Security. All rights reserved. 1/8 P/N 3101767-ML • REV 2.0 • ISS 27FEB12 Figure 2: Installing the 4X-LCD(-LC) (1) (2) P/N 250194-02 4X-LCD(-LC) SFS1-CPU J1 (3) (1) (2) Hinge pins Hinges (1) (3) Regulatory information Voltage 24 VDC Current Standby Alarm 55 mA 66 mA Indicators Alarm Disable Sup Gnd Fault CPU Fail Trouble Power Acknowledge Alarm Silence Panel Silence Reset Controls Operating environment Temperature Relative humidity 2/8 (2) Display brightness potentiometer Specifications Display J9 Monochrome QVGA backlit liquid crystal display (LCD) 240 × 320 pixels 24 lines of 40 characters Red LED Yellow LED Yellow LED Yellow LED Yellow LED Yellow LED Green LED Yellow LED integrated with Acknowledge button Yellow LED integrated with Alarm Silence button Yellow LED integrated with Panel Silence button Yellow LED integrated with Reset button Rotary controller Acknowledge button Alarm Silence button Panel Silence button Reset button 32 to 120°F (0 to 49°C) 0 to 93% noncondensing Manufacturer Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Year of manufacture The first two digits of the date of manufacture (located on the product identification label) are the year of manufacture. Environmental class UL: Indoor dry Contact information For contact information, see www.utcfireandsecurity.com. ES: Hoja de instalación Descripción El 4X-LCD(-LC) proporciona la interfaz de usuario para el panel de control de alarmas contra incendio. Sólo se requiere un interfaz de usuario para proporcionar un punto de control para toda la red. Sin embargo, se pueden agregar interfaces de usuario adicionales a cualquier panel de en la red, a fin de obtener puntos adicionales de control. El 4X-LCD-LC le permite instalar insertos de idioma que se ordenan por separado en las cavidades de la interfaz para las etiquetas de control e indicación. Véase la 4X-LK Language Kit Installation Sheet (P/N 3101995-ML) para obtener una lista de los kits disponibles y las instrucciones de instalación. P/N 3101767-ML • REV 2.0 • ISS 27FEB12 Controles e indicadores Instalación Figura 1: Controles e indicadores ADVERTENCIA: Peligro de electrocución. Para evitar lesiones personales o la muerte por electrocución, retire todas las Fuentes de energía eléctrica y permita que la energía almacenada se descargue antes de instalar o retirar el equipo. XXXXX XXXXXXX XXX XXX XXXXX XXX XXXX XXXXXXX XXXXX (1) Precaución: Las tarjetas de circuitos son sensibles a descargas electrostáticas (ESD). Para evitar daños, siga los procedimientos de manejo de ESD. (2) Para instalar la Interfaz de usuario de 4X-LCD(-LC) 1. Conecte el cable de cinta de datos desde J1 en 4X-LCD(-LC) hasta J9 en la parte frontal de la tarjeta principal de la SFS1-CPU. Véase Figura 2. 2. Mantenga la 4X-LCD(-LC) en la posición abierta a un ángulo de aproximadamente 45 a 50 grados y, a continuación, inserte sus clavijas de bisagras en las bisagras de la SFS1-CPU. 3. Inicie el panel y verifique el brillo de la pantalla de presentación. Encienda el potenciómetro en la parte posterior de la 4X-LCD(-LC) en sentido horario para oscurecer la pantalla, o en sentido antihorario, para hacerla más brillante. Véase Figura 2. 4. Cierre la 4X-LCD(-LC). Asegúrese de que quede insertada a presión. (3) (4) XXXXXXXXXXX (1) (2) (3) (4) XXXXX XXXXXX XXXXX XXXXXXX XXXXX Indicadores de estado del sistema Pantalla LCD Controlador rotativo Controles communescon indicadores Figura 2: Instalación de la 4X-LCD(-LC) (1) (2) P/N 250194-02 4X-LCD(-LC) SFS1-CPU J1 (3) (1) (2) Clavijas de las bisagras Bisagras P/N 3101767-ML • REV 2.0 • ISS 27FEB12 (1) (3) J9 (2) Potenciómetro de brillo de la pantalla 3/8 Especificaciones Voltaje 24 VCC Corriente En espera Alarma 55 mA 66 mA Pantalla Monocromática QVGA pantalla de cristal líquido con iluminación posterior (LCD) 240 x 320 píxeles 24 líneas de 40 caracteres Indicadores Alarma Inhabilitar Sup Falla de Tierra Falla de CPU Problema Alimentación Reconocimiento Silencio de Alarma Silencio de Panel Restablecer Controles LED rojo LED amarillo LED amarillo LED amarillo LED amarillo LED amarillo LED verde LED amarillo integrado con botón de Reconocimiento LED amarillo integrado con botón de silencio de alarma LED amarillo integrado con botón de silencio de panel LED amarillo integrado con botón de Restablecimiento FR: Fiche d’installation Description Le système 4X-LCD(-LC) fournit une interface utilisateur pour le panneau de commande de l’alarme-incendie. Une seule interface utilisateur est nécessaire pour fournir un point de contrôle pour la totalité du réseau. Cependant, les interfaces utilisateurs supplémentaires peuvent être ajoutées à n’importe quel panneau du réseau pour fournir des points de contrôle supplémentaires. Le 4X-LCD-LC vous permet d’installer des encarts de langue (disponibles séparément) dans des pochettes sur l’interface pour les étiquettes des commandes et des voyants. Consultez la 4X-LK Language Kit Installation Sheet (P/N 3101995-ML) pour obtenir une liste des nécessaires disponibles ainsi que les instructions d’installation. Commandes et voyants Figure 1 : Commandes et voyants Controlador rotativo Botón de reconocimiento Botón de silencio de alarma Botón de silencio de panel Botón de restablecimiento XXXXX XXXXXXX XXX XXX XXXXX XXX XXXX XXXXXXX XXXXX (1) (2) Ambiente de operación Temperatura 32 a 120°F (0 a 49°F) Humedad relativa 0 a 93% sin condensación Información regulatoria Fabricante Año de fabricación Clase ambiental Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA (3) Los primeros dos dígitos de la fecha de fabricación (ubicada en la etiqueta de identificación del producto) representan el año de manufactura. (4) XXXXXXXXXXX XXXXX XXXXXX XXXXX XXXXXXX XXXXX UL: Ambientes interiores secos Información de contacto (1) (2) (3) (4) Voyants d’état de système Écran à cristaux liquides Contrôleur rotatif Commandes courantes avec voyants Para información de contacto, véase www.utcfireandsecurity.com. 4/8 P/N 3101767-ML • REV 2.0 • ISS 27FEB12 Pour installer l’interface utilisateur 4X-LCD(-LC) : Installation AVERTISSEMENT : Risque d’électrocution. Pour éviter tout dommage corporel ou danger de mort par électrocution, retirez toutes les sources d’alimentation et laissez l’énergie emmagasinée se décharger avant d’installer ou de retirer l’équipement. Mise en garde : Les cartes de circuits imprimés sont sensibles aux décharges électrostatiques (ESD). Observez les consignes de sécurité relatives aux ESD pour éviter tout dommage. 1. Branchez le câble plat de données de J1 situé sur l’interface 4X-LCD(-LC) à J9 situé sur la partie avant de la carte mère SFS1-CPU. Voir Figure 2. 2. Maintenez l’interface 4X-LCD(-LC) en position ouverte à un angle d’environ 45 à 50 degrés et insérez ensuite les axes d’articulation dans les articulations situées sur le système SFS1-CPU. 3. Démarrez le panneau et vérifiez la luminosité de l’écran Tournez le potentiomètre situé à l’arrière de l’interface 4X-LCD(-LC) dans le sens des aiguilles d’une montre pour assombrir l’écran ou dans le sens inverse des aiguilles d’une montre pour l’éclaircir. Voir Figure 2. 4. Fermez l’interface 4X-LCD(-LC). Assurez-vous qu’elle s’enclenche bien à sa place. Figure 2: : Installation de l’interface 4X-LCD(-LC) (1) (2) P/N 250194-02 4X-LCD(-LC) SFS1-CPU J1 (3) (1) (2) Axes d’articulation Articulations (1) (3) 24 VCC Courant En veille Alarme 55 mA 66 mA Écran Voyants Alarme Désactivation Sup. Défaut de Mise à la Terre Défaillance de L’unité Centrale Problème Alimentation Accusé de Réception (2) Potentiomètre de réglage de la luminosité de l’écran Caractéristiques techniques Tension J9 Silence Alarme Silence Panneau Réinitialisation QVGA monochrome écran à cristaux liquides rétroéclairé (LCD) 240 x 320 pixels 24 lignes de 40 caractères DEL rouge DEL jaune DEL jaune DEL jaune Commandes DEL jaune intégré avec le bouton Alarm Silence (Silence alarme) DEL jaune intégré avec le bouton Panel Silence (Silence panneau) DEL jaune intégré avec le bouton Reset (Réinitialisation) Contrôleur rotatif Bouton Acknowledge (Accusé de réception) Bouton Alarm Silence (Silence alarme) Bouton Panel Silence (Silence panneau) Bouton Reset (Réinitialisation) Environnement de fonctionnement Température 0 à 49 C (32 à 120 F) Humidité relative 0 à 93 % sans condensation DEL jaune DEL jaune DEL vert DEL jaune intégré avec le bouton Acknowledge (Accusé de réception) P/N 3101767-ML • REV 2.0 • ISS 27FEB12 5/8 Information réglementaire Controles e indicadores Fabricant Figura 1: Controles e indicadores Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Année de fabrication Les deux premiers chiffres de la date de fabrication (sur l’étiquette d’identification du produit) correspondent à l’année de fabrication. Classe de service UL : Milieu intérieur sec XXXXX XXXXXXX XXX XXX XXXXX XXX XXXX XXXXXXX XXXXX (1) (2) Coordonnées Pour obtenir nos coordonnées, consultez le site Web www.utcfireandsecurity.com. PT: Folheto de instalação (3) (4) Descrição O 4X-LCD(-LC) fornece a interface do usuário do painel de controle de alarme de incêndio. É necessário apenas uma interface do usuário para fornecer um ponto de controle para toda a rede. No entanto, mais interfaces do usuário podem ser adicionadas a qualquer painel do na rede para fornecer pontos de controle adicionais. O 4X-LCD-LC permite instalar etiquetas de idioma, compradas separadamente, em porta-etiquetas na interface para legenda de controles e indicadores. Consulte uma lista de kits disponíveis e instruções de instalação no 4X-LK Language Kit Installation Sheet (P/N 3101995-ML). XXXXXXXXXXX (1) (2) (3) (4) XXXXX XXXXXX XXXXX XXXXXXX XXXXX Indicadores de status de sistema Tela LCD Controlador rotativo Controles comuns com indicadores Instalação AVISO: Perigo de eletrocussão. A fim de evitar ferimentos ou morte por eletrocussão, remova todas as fontes de energia e espere que a energia armazenada descarregue antes de instalar ou remover um equipamento. Cuidado: Placas de circuito são sensíveis a descargas eletrostáticas (ESD). Para evitar danos, siga os procedimentos de manuseio de ESD. Para instalar a interface do usuário do 4X-LCD(-LC): 6/8 1. Conecte o cabo de dados do J1, no 4X-LCD(-LC), ao J9, na parte frontal da principal do SFS1-CPU. Consulte Figura 2. 2. Mantenha o 4X-LCD(-LC) na posição aberta em um ângulo de aproximadamente 45 a 50 graus e insira os pinos da dobradiça na dobradiça do SFS1-CPU. 3. Ligue o painel e verifique o brilho da tela do visor. Gire o potenciômetro, localizado na parte de trás do 4X-LCD(-LC), no sentido horário, para escurecer a tela, ou no sentido anti-horário, para aumentar o brilho da tela. Consulte Figura 2. 4. Feche o 4X-LCD(-LC). Certifique-se de que ele encaixou corretamente. P/N 3101767-ML • REV 2.0 • ISS 27FEB12 Figura 2: Instalando o 4X-LCD(-LC) (1) (2) P/N 250194-02 4X-LCD(-LC) SFS1-CPU J1 (3) (1) Pinos da dobradiça (2) Dobradiças (1) Informações regulamentares Voltagem 24 VCC Atual Standby Alarme 55 mA 66 mA Indicadores Alarme Desabilitar Sup Falha Gnd Falha de CPU Dificuldade Alimentação Reconhecer Silenciar alarme Silenciar painel Reinicializar Controles Ambiente de operação Temperatura Umidade relativa (2) (3) Potenciômetro de brilho do visor Especificações Visor J9 QVGA monocromo Visor de cristal líquido com retroiluminação (LCD) 240 x 320 pixels 24 linhas de 40 caracteres LED vermelho LED amarelo LED amarelo LED amarelo LED amarelo LED amarelo LED Verde LED amarelo integrado ao botão Acknowledge LED amarelo integrado ao botão Alarm Silence LED amarelo integrado ao botão Panel Silence LED amarelo integrado ao botão Reset Fabricante Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Ano de fabricação Os primeiros dois dígitos da data de fabricação (localizados na etiqueta de identificação do produto) representam o ano de fabricação. Classe ambiental UL: Secagem interna Informações de contato Para obter informações de contato, consulte www.utcfireandsecurity.com. Controlador rotativo Botão Acknowledge Botão Alarm Silence Botão Panel Silence Botão Reset 32 a 120°F (de 0 a 49°C) de 0 a 93%, sem condensação P/N 3101767-ML • REV 2.0 • ISS 27FEB12 7/8 8/8 P/N 3101767-ML • REV 2.0 • ISS 27FEB12