Memòria i Annexes - perfil de contractant

Anuncio
PROJECTE D’EXECUCIÓ DEL CENTRE CÍVIC I DEPENDÈNCIES SOCIALS
A BELL-LLOC D’URGELL
SETEMBRE 2009
DOCUMENT 1:
MEMÒRIA
I
ANNEXES
PROMOTOR: AJUNTAMENT DE BELL·LLOC D’URGELL
AUTOR: COSTA · PORTOLÉS ARQUITECTES, SLP
CONTINGUT DEL PROJECTE
DOCUMENT 1: MEMÒRIA I ANNEXES
1.
MEMÒRIA DESCRIPTIVA
1.1
Dades Bàsiques
1.2
Contingut del Projecte
1.3
Fitxa Urbanística
1.4
Estat actual i disponibilitat de terrenys
1.5
Quadre de superficies
2.
MEMÒRIA CONSTRUCTIVA
2.1
Introducció
2.2
Demolicions
2.3
Excavacions i encofrats
2.4
Fonaments
2.5
Solera
2.6
Estructura
2.7
Acabats exteriors
2.8
Impermeabilitzants i aïllants
2.9
Divisions interiors
2.10
Paviments i revestiments
2.11
Fusteries
2.12
Pintura
2.13
Instal·lacions i eficiència energética
3.
MEMÒRIA DE L’ESTRUCTURA
4.
ANNEX. PROJECTE DE CLIMATITZACIÓ
5.
ANNEX. INSTAL·LACIÓ BAIXA TENSIÓ
DOCUMENT 2: PLEC DE CONDICIONS
DOCUMENT 3: PRESSUPOST
DOCUMENT 4: ESTUDI DE SEGURETAT I SALUT
DOCUMENT 5: JUSTIFICACIÓ COMPLIMENT DEL CODI TÈCNIC
6.
PLÀNOLS
- PLÀNOL I01
SITUACIÓ I EMPLAÇAMENT
- PLÀNOL E01
ESTRUCTURA EDIFICI ANNEX
- PLÀNOL A01
PLANTA BAIXA - DISTRIBUCIÓ
- PLÀNOL A02
PLANTA PRIMERA - DISTRIBUCIÓ
- PLÀNOL A03
PLANTA COBERTA – DISTRIBUCIÓ
- PLÀNOL A04
PLANTA BAIXA – COTES I SUPERFÍCIES
- PLÀNOL A05
PLANTA PRIMERA – COTES I SUPERFÍCIES
- PLÀNOL A06
PLANTA COBERTA – COTES
- PLÀNOL A07
FAÇANES NORD I SUD
- PLÀNOL A08
FAÇANA EST I OEST
- PLÀNOL A09
SECCIÓ SUD, DETALLS
- PLÀNOL A10
SECCIÓ OEST
- PLÀNOL A11
FUSTERIES
- PLÀNOL INS01
PLANTA BAIXA AIGUA FREDA I CALENTA
- PLÀNOL INS02
PLANTA PRIMERA AIGUA FREDA I CALENTA
- PLÀNOL INS03
ESQUEMA UNIFILAR
- PLÀNOL INS04
PLANTA BAIXA INSTAL·LACIÓ ELÈCTRICA
- PLÀNOL INS05
PLANTA PRIMERA INSTAL·LACIÓ ELÈCTRICA
- PLÀNOL INS06
PLANTA BAIXA CLIMATITZACIÓ
- PLÀNOL INS07
PLANTA PRIMERA CLIMATITZACIÓ
- PLÀNOL INS08
PLANTA BAIXA VENTILACIÓ
- PLÀNOL INS09
PLANTA PRIMERA VENTILACIÓ
- PLÀNOL INS10
PLANTA BAIXA PROTECCIÓ CONTRA INCENDIS
- PLÀNOL INS11
PLANTA PRIMERA PROTECCIÓ CONTRA INCENDIS
- PLÀNOL INS12
PLANTA BAIXA CEL RAS
- PLÀNOL INS13
PLANTA PRIMERA CEL RAS
1 MEMÒRIA DESCRIPTIVA
1.1 DADES BÀSIQUES
FINALITAT :
La finalitat d’aquesta memòria és la remodelació de l’edifici de les antigues escoles per a ubicar un
equipament socio-cultural a la població de Bell-lloc
DADES CADASTRALS :
Referència cadastral: 4914611CG1141S0001JU
Localització: c/ Joan Oró, 3
BELL·LLOC D'URGELL 25220 LLEIDA
Classe: Urbana
Superfície(*): 807 m2
Ús: Cultural
Any construcció local principal: 1965
PROMOTOR :
Ajuntament de Bell-lloc d’Urgell
EQUIP REDACTOR :
Costa · Portolés , arquitectes sl
Passeig de Ronda, 162 6è E
25008 Lleida
Tel. 973 239 439
David Portolés Martínez, arquitecte urbanista
Anna Costa Isern, arquitecta
Jael Soro Astals, arquitecte tècnic
Joan Capdevila Cebollero, delineant
1.2 FITXA URBANÍSTICA
NORMATIVA VIGENT :
POUM BELL·LLOC
CLASSIFICACIÓ DEL SÒL :
SÒL URBÀ
QUALIFICACIÓ DEL SOLAR :
EQUIPAMENT
1.3 ESTAT ACTUAL I DISPONIBILITAT DE TERRENYS
En l’actualitat l’edifici de les escoles es de titularitat municipal. Tot i que no te un ús específic, es
utilitzat esporàdicament per realitzar activitats de caràcter educatiu.
Es una edificació construïda a l’any 65 amb una configuració característica de les realitzades a les
hores per l’estat central amb destí escolar. Es tracta d’un edifici composat de diferents cossos
paralepipèdics
de planta i pis, articulats al voltant d’un cos específic que alberga l’escala. La
estructura portant es mixta, amb pilars d’obra en façana i parets de carrega conformant les
distribucions interiors. Els forjats son de ceràmica armada i aquest element es el que es troba més
degradat, degut fonamentalment a la seva incorrecta execució, ja que es pot observar el fet que el
formigó abocat ‘in situ’ no va acabar de recobrir les armadures metàl·liques, amb la qual cosa
aquestes van quedar exposades a un procés de corrosió especialment intens. La coberta es
inclinada de teula àrab. En la composició de façana els trets
més característics són les
fenestracions continues que configuren franges horitzontals on la separació entre finestres es a
l’hora l’element portant. La superfície construïda actual es de uns 800 m2 de sostre.
1.4 PROGRAMA I QUADRE DE SUPERFÍCIES
Les noves instal·lacions s’han de composar de :
-
Un centre de dia per a avis, amb les següents dependències: Sala d’estar i d’activitats,
menjador, cuina, gimnàs, oficines pels assistents socials, oficina pel podòleg, vestuaris i
bugaderia, tot amb les corresponents parts proporcional d’espais de circulació i de serveis
adaptats.
-
Un dispensari mèdic que ha de substituir i fer les funcions del que actualment funciona a la
població.
-
Una sèrie d’aules destinades a ensenyança de noves tecnologies i l’ús de les associacions
cíviques i veïnals .
-
Una biblioteca
El projecte es desenvolupa segons el programa i el quadre de superfícies següent :
QUADRE DE SUPERFÍCIES CONSTRUIDES
PLANTA BAIXA-
723.02 m2
PLANTA PRIMERA-
543.08 m2
PLANTA TERCERA-
87.73 m2
TOTAL- 1353.83 m2
QUADRE DE SUPERFÍCIES ÚTILS
Planta baixa
Estància
Consultori
Centre de dia
Consulta metge 1
Cures
Infermeria
Consulta metge 2
Bany personal
Arxiu
Sala d'espera 2
Passadís 3
Passadís 2
Bany homes
Bany dones
Rebost
Cuina
Vestíbul
Minibar
Menjador
Sala d'activitats
Passadís 1
Despatx de gestió
Podòleg
Vestidors personal
Vestidors usuaris
Gimnàs
Fisioteràpia
Magatzem
Bugaderia
Distribuïdor banys
Escales
Banys geriàtrics
Dutxa geriàtrica 1
Dutxa geriàtrica 2
Neteja
TOTAL
Superfíces
21,23
14,08
15,17
18,94
4,87
12,24
29,06
10,99
14,58
13,21
14,68
8,38
20,67
37,3
8,28
43,69
36,44
60
25,82
21,15
14,15
23,14
22,61
8,49
12,46
17,92
4,86
9,35
13,6
4,14
4,14
2,46
568,1
Planta primera
Estància
Zona d'acollida i
promoció
Zona de treball intern
Biblioteca
Zona general
Zona infantil
Local 1
Local 2
Sales actes Local 3
Local 4
Local 5
Banys
Zones comuns Escales
Passadís
TOTAL
SUPERFÍCIE ÚTIL TOTAL = 1052,96 M2
Superfícies
49,98
23,31
155,55
46,68
23,53
23,53
24,11
24,34
33,56
17,01
13,27
49,99
484,86
2 MEMÒRIA CONSTRUCTIVA
2.1 INTRODUCCIÓ
Sota cap concepte es permetrà l’ inici de les obres sense l'autorització de la Direcció Facultativa i
signatura del Llibre d’Ordres per part del contractista. Durant tot el procés s'exigirà la presència
continua a l'obra d'una persona concreta responsable de la mateixa i interlocutora de la Direcció
Facultativa.
La zona d'actuació estarà efectivament delimitada, senyalada i tancada a l’accés de persones
alienes a l'obra. Aquesta actuació restarà des de l' inici dels treballs fins al final de l'obra.
2.2 MOVIMENT DE TERRES
Desprès de netejar el solar, s’hauran de replantejar els fonaments, es farà l’excavació de rases i
pous, d’acord amb les especificacions dels plànols.
Es preveu una tensió de treball admissible del terreny de 0.07 N /mm2.
El moviment de terres es realitzarà per mitjans mecànics fins a la fondària especificada en els
plànols, excepte on faci falta realitzar-ho manualment.
2.3 EXCAVACIONS I ENCOFRATS
S’excavaran les rases i els pous corresponents als fonaments i a les instal·lacions soterrades, que
es col·locaran segons les especificacions dels plànols.
Els encofrats tindran en les seves unions i apuntalaments la resistència i rigidesa necessàries per a
complir aquesta condició i estaran disposats de la forma que puguin desencofrar-se sense que
calgui donar cops que perjudiquin al formigó.
Els apuntalaments es disposaran de manera que no es produeixin sobre els elements inferiors de
l’estructura, càrregues de treball superiors a 1/3 de la seva resistència.
Els motlles s’humitejaran i netejaran immediatament abans del formigonat.
La fusta dels encofrats tindrà les fibres rectes sense esquerdes ni nusos.
Es permetran encofrats metàl·lics o de melamina homologats.
2.4 FONAMENTS
Per les característiques de l’edificació i de l’estudi geotècnic, els fonaments es realitzaran mitjançant
una cimentació superficial, de sabates aïllades centrades i arriostrades, sobre pous de cimentació.
2.5 SOLERA
Després de netejar i anivellar el terreny interior, es col·locarà una subbase de grava, una làmina de
polietilè i una base de 15cm. de formigó armat.
2.6 ESTRUCTURA
L’estructura, que en aquesta fase solament es la corresponent al cos d’ampliació destinat a
bugaderia serà de murs de carrega amb forjat unidireccional de biguetes autor resistents
2.7 ACABATS EXTERIORS
Els acabats exteriors seran de xapa minionda galvanitzada en el cas dels tancaments existents i del
volum de la sala d’actes, o de morter monocapa en el cas de les plantes baixes per als tancaments
de termoarcilla.
2.8 IMPERMEABILITZANTS I AÏLLANTS
Es farà un drenatge horitzontal circunvoltant de tot l’edifici existent. A la coberta invertida la làmina
impermeabilitzant serà de betum plastomèric amb doble armadura: feltre de poliester i film de
polietilè; col·locada no adherida a la base i doblegada en els punts singulars. En les ampliacions la
coberta es realitzarà amb xapa minionda similar a la de façana. Els aïllaments tèrmics es realitzaran
amb polieuretà projectat de cela tancada.
2.9 DIVISIONS INTERIORS
Els envans no coincidents amb parets de càrrega cerán ceramics de 6 cmts
2.10 PAVIMENTS I REVESTIMENTS
El paviment de l’edifici serà de gres ceràmic anti-lliscamentper en les arees humides i paviment
continuo vinilic a la resta de locals, amb mides i disposició especificats en els plànols i en els
amidaments.
2.11 FUSTERIES
La fusteria interior serán de fusta eventualment vidriada El vidre serà laminar de dues capes de
3mm+3mm.
2.12 PINTURA
La pintura serà plàstica llisa per l’interior, amb una capa d’imprimació i dues mans d’acabat.
A tota la fusta se li farà un tractament insecticida-fungicida, una capa de segellat i dues mans de
pintura.
2.13 INSTAL·LACIONS I EFICIÈNCIA ENERGÈTICA
El sistema de calefacció es farà a partir d’una caldera de bio-massa. La composició de les façanes
es dissenya de tal manera que la inèrcia tèrmica es situa a l’interior de l’edifici. Es preveu la
instal·lació de captadors solars d’aigua calenta i de plaques fotovoltaiques.
Lleida, setembre de 2009
Anna Costa Isern i David Portolés Martínez, arquitectes.
ANNEX. CÀLCUL ESTRUCTURAL
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
ÍNDEX
DOCUMENT 1
MEMÒRIA DE CÀLCUL
1.- CARACTERÍSTIQUES DE L'ESTRUCTURA I SOLICITACIONS
0
1.1.- SITUACIÓ. EXPEDIENT. DATA. PROMOTOR
0
1.2.- DEFINICIÓ i JUSTIFICACIÓ DE LA TIPOLOGIA ESTRUCTURAL
0
1.3.- CARACTERÍSTIQUES GEOMÈTRIQUES
0
1.3.1.- CARACTERÍSTIQUES DEL FORJAT
0
GRUIX DEL FORJAT
0
1.4.- JUSTIFICACIÓ D’ACCIONS A L’EDIFICACIÓ (CTE-DB-SE-AE)
0
1.4.1.- CÀRREGUES SUPERFICIALMENT REPARTIDES
0
1.4.1.1.- PLANTA AMB NERVAT SEMIBIGUETA 25+5
0
1.4.1.2.- PLANTA AMB FORJAT COL·LABORANT
0
1.4.2.- CÀRREGUES LINEALMENT REPARTIDES
0
1.4.3.- PES DEL FORJAT
0
1.5.- SOL·LICITACIONS HORITZONTALS: EÒLIQUES i SÍSMIQUES (CTE-DB-SE-AE i
NCSE-02)
0
1.5.1.- ACCIÓ EÒLICA (CTE-DB-SE-AE)
0
1.5.2.- JUSTIFICACIÓ DE LA NORMA NCSE-02
0
1.6.- SOL·LICITACIONS ESPECIALS, TÈRMIQUES O REOLÒGIQUES
0
1.7.- CARACTERÍSTIQUES DELS MATERIALS ESTRUCTURALS
0
2.- ELEMENTS ESTRUCTURALS
0
2.1.- DEFINICIÓ DEL PROCÉS DE CÀLCUL (SEGONS CTE-DB-SE; EHE; EFHE; CTEDB-SE-F i CTE-DB-SE-A)
0
2.1.1.- FORMIGÓ ARMAT
0
2.1.2.- MURS DE FÀBRICA DE MAÓ
0
2.1.3.- ESTRUCTURA METÀL.LICA
0
2.1.4.- TIPUS DE CONTROL, COEFICIENTS DE SEGURETAT ADOPTATS(γ) I
COEFICIENTS DE COMBINACIÓ(ψ)
0
2.1.5.- PROGRAMES DE CÀLCUL EMPRATS PER LA RESOLUCIÓ
D’ESTRUCTURES PER EDIFICACIÓ.
3.- MECÀNICA DEL SÒL
MEMÒRIA DE CÀLCUL
0
0
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
3.1.- DEFINICIÓ I JUSTIFICACIÓ DE LA TIPOLOGIA DE FONAMENTACIÓ
0
3.2.- ESTUDI GEOTÈCNIC
0
3.2.1.- TENSIÓ DE TREBALL DEL TERRENY
0
3.2.2.- NIVELL FREÀTIC
0
3.2.3.- AGRESSIVITATS DEL TERRENY O AIGUA RESPECTE AL FORMIGÓ
0
3.3.- CERTES SITUACIONS ATÍPIQUES
0
4.- REFERÈNCIA A LES NORMATIVES EMPRADES
0
5.- CONSIDERACIONS DEL PROCES CONSTRUCTIU
0
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
1.- CARACTERÍSTIQUES DE L'ESTRUCTURA I SOLICITACIONS
1.1.- SITUACIÓ. EXPEDIENT. DATA. PROMOTOR
Emplaçament edifici:
BELL·LLOCH
Expedient estructura: EF/1140/0108
Data: MARÇ 2008
Promotors:
Tipus d’edifici: CENTRE CIVIC
Superfícies de càlcul:
SUPERFÍCIE
FONAMENTS
341,83 m²
SOSTRE PL. BAIXA
572,17 m²
COBERTA
528,90 m²
TOTAL SUP. HABITATGE
MEMÒRIA DE CÀLCUL
SUPERFÍCIE
1442,90 m2
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
1.2.- DEFINICIÓ i JUSTIFICACIÓ DE LA TIPOLOGIA ESTRUCTURAL
S’ha escollit la tipologia de sostre unidireccional amb semibigueta que recolzen en murs o
jàsseres que recolzen sobre pilars de formigó armat i també s’ha escollit la tipologia de forjat
col·laborant recolzat sobre estructura metàl·lica de jàsseres i pilars metàl·lics i amb una capa de
formigó armat de 12cm.
1.3.- CARACTERÍSTIQUES GEOMÈTRIQUES
1.3.1.- CARACTERÍSTIQUES DEL FORJAT
FORJAT DE NERVAT DE SEMIBIGUETA 25+5
tipus......................................... unidireccional semibigueta
suport.......................................pilars de formigó armat
intereix......................................70 cm
revoltó.......................................prefabricat formigó 70*23*(25)cm
gruix del forjat...........................25+5= 30 cm
capa superior .......................... 5 cm
mallat electrosoldat...................ME 15*30 cm, BØ 5mm. B 500 S
encadenat perimetral................segons plànol de jàsseres
fletxa permesa.......................... L/500 // 1,00 cm
FORJAT COL·LABORANT
tipus.........................................forjat col·laborant amb xapa HAIRCOL59 e=0,75mm
gruix total del forjat 12cm
suport.......................................pilars de metàl·lics
intereix......................................revoltó.......................................gruix del forjat...........................12cm + gruix de jàssera metàl·lica
capa superior .......................... 12 cm
mallat electrosoldat...................ME15*20cm, Ø10mm longitudinal a xapa
i Ø6mm transversal a xapa B500S
encadenat perimetral................fletxa permesa.......................... L/500 // 1,00 cm
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
FORJAT DE NERVAT DE BIGUETA 25+5
tipus......................................... unidireccional semibigueta
suport.......................................pilars de formigó armat
intereix......................................70 cm
revoltó.......................................prefabricat formigó 70*23*(25)cm
gruix del forjat...........................25+5= 30 cm
capa superior .......................... 5 cm
mallat electrosoldat...................ME 15*30 cm, BØ 5mm. B 500 S
encadenat perimetral................segons plànol de jàsseres
fletxa permesa.......................... L/500 // 1,00 cm
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
GRUIX DEL FORJAT
L’elecció del gruix de la llosa alleugerida ve en funció de les llums entre eixos pilars. Hi ha la
banda de llums de 6,00m aproximadament. També respon a la necessitat de limitar
notablement la fletxa diferida, mantenint-la en uns valors sensiblement inferiors als habituals en
l’edificació.
La regla pràctica de no excedir el 1/24 de la llum més desfavorable s’acompleix al adoptar un
cantell de 25+5=30.
1.4.- JUSTIFICACIÓ D’ACCIONS A L’EDIFICACIÓ (CTE-DB-SE-AE)
1.4.1.- CÀRREGUES SUPERFICIALMENT REPARTIDES
1.4.1.1.- PLANTA AMB NERVAT SEMIBIGUETA 25+5
ESTAT DE CÀRREGUES
pes propi........................
311 Kg/m2
càrregues permanents.....
110 Kg/m2
sobrecàrrega d’envans...
100 Kg/m2
sobrecàrrega de servei...
300 Kg/m2
sobrecàrrega de vent.....
0 Kg/m2
sobrecàrrega de neu......
0 Kg/m2
-------------821 Kg/m2
1.4.1.2.- PLANTA AMB NERVAT BIGUETA 25+5
ESTAT DE CÀRREGUES
pes propi........................
311 Kg/m2
càrregues permanents.....
110 Kg/m2
sobrecàrrega d’envans...
000 Kg/m2
sobrecàrrega de servei...
200 Kg/m2
sobrecàrrega de vent.....
0 Kg/m2
sobrecàrrega de neu......
0 Kg/m2
-------------621 Kg/m2
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
1.4.1.3.- PLANTA AMB FORJAT COL·LABORANT
ESTAT DE CÀRREGUES
pes propi........................
200 kg/m2
càrregues permanents.....
110 Kg/m2
sobrecàrrega d’envans...
100 Kg/m2
sobrecàrrega de servei...
500 Kg/m2
sobrecàrrega de vent.....
000 Kg/m2
sobrecàrrega de neu......
000 Kg/m2
------------910 Kg/m2
1.4.2.- CÀRREGUES LINEALMENT REPARTIDES
Hi ha tres tipus de càrregues bàsiques d’aquesta modalitat:
1) Els tancaments: paret de maó perforat “totxana”, arrebossat amb cambra d’aire i envà. En
planta pis tindrà 2,50 metres: 0,75 T/m..
2) Les separacions entre veïns amb paret també de maó perforat “calat” “gero” de 15cm
revestida. En planta pis tindrà 2,50 metres: 0,56 T/m.
3) Les baranes tindran la consideració o possibilitat que siguin massisses, amb un possible pes
propi i una sobrecàrrega, amb una càrrega total màxima de 0,41 T/m.
1.4.3.- PES DEL FORJAT
Anant a favor de la seguretat, s’ha pres el valor recomanat per l´Associació de Consultors
d´Estructures sobre pesos propis dels forjats habituals a la construcció (Revista Quaderns
d’estructures, número 4, novembre de 1999). L´esmentat pes és un cop rectificat per intereix de
70cm es de 311 kg/m2 per al forjat de (25+5)cm i de 200kg/m2 per al forjat col·laborant.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
1.5.- SOL·LICITACIONS HORITZONTALS: EÒLIQUES i SÍSMIQUES (CTE-DB-SE-AE i
NCSE-02)
1.5.1.- ACCIÓ EÒLICA (CTE-DB-SE-AE)
L'acció del vent es calcula a partir de la pressió estàtica qe que actua en la direcció
perpendicular a la superfície exposada, amb l’expressió que s’exposa a continuació:
qe = qb·ce·cp
On:
qb És la pressió dinàmica.
ce És el coeficient d'exposició.
cp És el coeficient eòlic o de pressió.
Per la tipologia i característiques de l’edifici en qüestió s’agafaran els valors simplificats segons
l’article 3.3 del CTE-DB-SE-AE (sempre que es puguin aplicar, en cas contrari es farà el
càlcul complert). Aquests valors que es detallen a continuació, seran els que s’utilitzaran pel
càlcul i/o s’introduiran en el programa de càlcul de l’estructura:
- Altura de l'edifici: fins a 8 plantes
- Dimensions de l’edifici: segons plànols d’arquitectura
- Situació topogràfica: zona urbana en general
- 'edifici: fins a 8 plantes
- Pressió dinàmica: W= 52 Kg/m² (no simplificat zona C; Velocitat vent: 29 m/seg)
- Coeficient d’exposició: 2
- Coeficient d’eòlic o de pressió:
Esveltesa de l’edifici (h/b)
>0,25
0,50
0,75
1,00
1,25
≤5,00
Coeficient eòlic de pressió(Cp)
0,70
0,70
0,80
0,80
0,80
0,80
Coeficient eòlic de succió(Cp)
-0,30
-0,40
-0,40
-0,50
0,60
0,70
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
1.5.2.- JUSTIFICACIÓ DE LA NORMA NCSE-02
En compliment del RD 997/2002, de 27 de setembre, o s’aprova la norma de construcció
sismoresistent part general i edificació (NCSE-02). On aplicant els següents paràmetres:
•
MUNICIPI: BELL·LLOCH
•
CLASSIFICACIÓ DE LA CONSTRUCCIÓ (segons el l’1.2.2 de la NCSE-02): NORMAL
•
(ab) acceleració sísmica bàsica segons Annex 1 de NCSE-02: < 0,04g
Segons el Capítol 1 en el punt 1.2.3. de la Norma sismoresistent NCSE-02 la norma no es
d’aplicació en les següent situacions:
•
Les construccions de importància moderada.
•
Les edificacions de importància normal o especial quan l’acceleració sísmica bàsica (ab)
sigui inferior a 0,04g, essent g la acceleració de la gravetat.
•
En les construccions de importància normal amb pòrtics ben arriostrats entre ells en
totes les direccions quan l’acceleració sísmica bàsica (ab) sigui inferior a 0,08 g. No
obstant, la Norma serà de aplicació en els edificis de més de 7 plantes si la acceleració
sísmica de càlcul (ac) es igual o major de 0,08g
Pel que resolem que no es necessari l’aplicació de la norma en aquesta construcció.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
1.6.- SOL·LICITACIONS ESPECIALS, TÈRMIQUES O REOLÒGIQUES
Per estar l’edificació subdividida en unitats de longitud menors de 40m, no s'introdueixen en
l'estructura els efectes produïts per l'acció tèrmica, ni els reològics.
1.7.- CARACTERÍSTIQUES DELS MATERIALS ESTRUCTURALS
ESTRUCTURA DE FORMIGÓ ARMAT
-FORMIGÓ:
Resistència característica als 28 dies: 25 N/mm2
Resistència característica als 7 dies: 17.5 N/mm2
Tipus de ciment RC-03: CEM I, 32.5
Tipus d’ambient (agressivitat): fonaments IIa, resta obra I
Classe d'àrid: palet de riu
Tamany màxim de l'àrid: 16 mm.
Additius:No s'admeten sense l'autorització de la Direcció Facultativa.
Dosificació per metre cúbic:
Ciment: 275 Kg/m3.
Aigua: 180 Kg/m3.
Sorra: 635 Kg/m3.
Grava: 1275 Kg/m3.
Docilitat:Consistència tova (denominació B)
Assentament en con d'Abrams: 7+1cm.
Compactació: per vibrat normal.
Control del formigó: Normal.
Número de sèrie de provetes per assaig: 1 sèrie.
Número de provetes per sèrie: 6 unitats.
Freqüència d'assaigs: cada unitat de formigonat.
Tipus de provetes: cilíndriques,de d=15cm. h=30cm
Edat de ruptura:2 unitats a 7 dies
2 unitats a 28 dies
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
2 unitats a reserva
Assaig sistemàtic de con d'Abrams. Tolerància ±1cm
-ACER:
Tipus: B 500 SD
Límit elàstic: 500 N/mm2
Control de l'acer: Normal
Coeficient de minoració: 1,15
Resistència de càlcul de les barres: 443,5 N/mm2
-MALLES ELECTROSOLDADES
Designació B 500 SD
Límit elàstic: 500 N/mm2
AENOR certifica amb conformitat a normes i en aquest cas segons la norma UNE 36092:1996
“Mallas electrosoldadas de acero para armaduras de hormigón armado”, que no considera les
xarxes amb diàmetres inferiors a 5mm.
Des de l’1 d’abril de 1997 els fabricants de xarxes electrosoldades en possessió de marca “N”
d’AENOR empren diàmetres a partir de 5mm. Com a referència a les noves xarxes
electrosoldades amb capes de compressió en sostres normals, en substitució de les antigues es
poden considerar:
Sostres unidireccionals: 200*200*5*5mm., 150*300*5*5mm
Sostres bidireccionals: 200*200*5*5mm., 150*150*5*5mm
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
MURS DE FÀBRICA DE MAÓ
MAONS
Tipus de maons RL-88: perforat
Classe de maons RL-88: NV
Resistència a compressió: 15 N/mm2
MORTERS
Tipus de ciment RC-03: CEM I, 32.5
Tipus de calç: ----Tipus de sorra (rodat/matxucat): natural
Tamany màxim de la sorra: 2,5 mm
Additius: ----------Tipus de morter: M-40
Resistència a compressió: 4.0 N/mm2
Plasticitat: gras
Dosificació: 1:0:6
MURS
Classe de mur: aparellat
Tipus de paredat: a trencajunt
Resistència de càlcul de la fàbrica: 2.2 N/mm2
ACCIONS
Cas de càrrega:
I
Coeficients de ponderació: 1,60
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
ESTRUCTURA METÀL·LICA
Els acers emprats cumpleixen la Norma CTE-DB-SE-A.
Característiques mecàniques dels acers:
(S275-JR)
RESISTÈNCIA A LA TRACCIÓ (KG/MM2)
42-50
LÍMIT DE FLUÈNCIA MÍNIM (KG/MM2)
26
ALLARGAMENT DE RUPTURA(%)
22
Com a valors habituals de càlcul les constants elàstiques de l'acer són:
Módul d'elasticitat
E= 2.100.000 Kp/cm2
Módul de rigidesa
G = 810.000 Kp/cm2
Coeficient de Poisson V = 0,30
Coeficient de dilatació αt= 1,2 x 10-5 m/m Cº
La modificació d'aquestes dades haurà de ser aprovada de forma expressa per la
Direcció Facultativa.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
2.- ELEMENTS ESTRUCTURALS
2.1.- DEFINICIÓ DEL PROCÉS DE CÀLCUL (SEGONS CTE-DB-SE; EHE; EFHE; CTEDB-SE-F i CTE-DB-SE-A)
2.1.1.- FORMIGÓ ARMAT
La determinació de les sol·licitacions s’ha realitzat segons els principis de la Mecànica
rotacional, complementats per les teories clàssiques de la Resistència de Materials i de
l’Elasticitat.
D’acord amb la Norma CTE-DB-SE 1 i 2 amb també va la EHE (Art.49), el procés general de
càlcul emprat és el dels estats límits (E.L.U. de trencament. Formigó), en què es tracta de
reduir a un valor suficientment baix la probabilitat que s’assoleixin aquells estats límits que
posen l’estructura fora de servei.
Les comprovacions dels estats límits últims (equilibri, esgotament o trencament, inestabilitat o
guerxament, adherència, ancoratge i fatiga) es realitzen per a cada hipòtesi de càrrega, amb
accions majorades i propietats resistents dels materials minorades, mitjançant una sèrie de
coeficients de seguretat.
Les comprovacions dels estats límits d’utilització (fissuració i deformació) es realitzen per a cada
hipòtesi de càrrega, amb accions de servei (sense majorar) i propietats resistents dels materials
de servei (sense minorar).
Per al càlcul dels forjats, s’ha adoptat el diagrama d’envolvents plàstiques de moments flectors,
d’acord amb la Norma CTE-DB-SE 1 i 2 amb també EFHE.
Les seccions de formigó es calculen considerant el període plàstic
del diagrama
tensió-deformació, amb distribució parabòlica-rectangular, seguint la teoria dels dominis de
la deformació, dins el càlcul de ruptura.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
ARMAT DE SECCIONS
Per al dimensionat de les seccions de formigó s’empra el mètode de la paràbola-rectangle. Es
respecten les quanties mínimes exigides per CTE-DB-SE 1 i 2 amb també la Instrucció EHE
(Art. 42.3.5).
El procés general d’armat es basa en l’elecció, dins la taula corresponent, d’un màxim de tres
paquets d’armat que cobreixen en cada punt la quantia necessària.
ESFORÇ TALLANT
S’acompleixen els límits del CTE-DB-SE 1 i 2 amb també la Instrucció EHE (Arts. 44 i 52.5).
ANCORATGES DE LES ARMADURES
S’empren les longituds d’ancoratge corresponents a l’Article 66.5 de la Instrucció EHE, tenint en
compte les reduccions: As necessària/ As real i calculant-se per a cada paquet d’armadures el
màxim d’envolvent de les longituds d’ancoratge necessàries per a cada moment que cobreix.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
2.1.2.- MURS DE FÀBRICA DE MAÓ
D’acord amb la Norma CTE-DB-SE-F, el càlcul de les sol·licitacions s’ha realitzat pels mètodes
generals de la Resistència de Materials.
Per a cada element s’ha comprovat que la tensió ponderada general resultant i la tensió
ponderada local en les àrees de recolzament no superen la resistència de càlcul especificada.
A més, s’han realitzat les comprovacions relatives a l’estabilitat del conjunt, tenint en compte els
esforços horitzontals, i en el càlcul de la fonamentació s’han considerat les excentricitats de les
càrregues produïdes per aquest tipus d’esforços.
2.1.3.- ESTRUCTURA METÀL.LICA
D’acord amb la Norma CTE-DB-SE 1 i 2 amb també el CTE-DB-SE-A, el procés general de
càlcul emprat és el dels estats límits (E.L.U. de trencament. Acer laminat), en què es tracta de
reduir a un valor suficientment baix la probabilitat que s’assoleixin aquells estats límits que
posen l’estructura fora de servei.
Les comprovacions dels estats límits últims (equilibri, esgotament o trencament, inestabilitat o
guerxament, adherència, ancoratge i fatiga) es realitzen per a cada hipòtesi de càrrega, amb
accions majorades i propietats resistents dels materials minorades, mitjançant una sèrie de
coeficients de seguretat.
Les comprovacions dels estats límits d’utilització (fissuració i deformació) es realitzen per a cada
hipòtesi de càrrega, amb accions de servei (sense majorar) i propietats resistents dels materials
de servei (sense minorar).
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
2.1.4.- TIPUS
DE
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
CONTROL,
COEFICIENTS
DE
Ref.: EF/1140/0108
SEGURETAT
ADOPTATS(γ)
I
COEFICIENTS DE COMBINACIÓ(ψ)
Nivell de control de l’estructura: NORMAL.
Per el càlcul de les fletxes dels elements sotmesos a flexió, s’han tingut en compte tant les
deformacions instantànies com les diferides, i s’han considerat els moments d’inèrcia
equivalents de les seccions fissurades.
Els límits de deformació vertical (fletxes) de les bigues i dels forjats, establerts per la
compatibilitat de deformacions dels diferents elements estructurals i constructius, son els que
assenyala al CTE-DB-SE 1 i 2 la norma EFHE.
Per a les diferents situacions de projecte, les combinacions d'accions es definiran d'acord amb
els següents criteris:
ƒ
Amb coeficients de combinació
∑γ
j ≥1
ƒ
Gj
Gkj + γ Q1Ψ p1Qk1 + ∑ γ Qi Ψ aiQki
i >1
Sense coeficients de combinació
∑γ
j ≥1
Gj
Gkj + ∑ γ QiQki
i≥1
On:
Gk
Qk
γG
Acció permanent
Acció variable
Coeficient parcial de seguretat de les accions permanents
γQ,1
Coeficient parcial de seguretat de l'acció variable principal
γQ,i
Coeficient
ψp,1
ψa,i
parcial
de
seguretat
de
les
accions
variables
(i > 1)
Coeficient de combinació de l'acció variable principal
Coeficient
de
combinació
de
les
accions
variables
(i > 1)
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
Per a cada situació de projecte i estat límit, els coeficients a utilitzar seran:
ƒ
E.L.U. de trencament. Formigó: EHE-CTE
Persistent o transitòria sense sisme
Coeficients parcials de seguretat
(γ)
Càrrega permanent
(G)
Coeficients de combinació (ψ)
Favorable
Desfavorable
Principal (ψp)
Acompanyament (ψa)
1.00
1.50
1.00
1.00
Sobrecàrrega (Q)
0.00
1.60
1.00
0.70
Vent (Q)
0.00
1.60
1.00
0.60
Neu (Q)
0.00
1.60
1.00
0.50
Sisme (A)
ƒ
E.L.U. de trencament. Acer laminat: CTE DB-SE A
Persistent o transitòria sense sisme
Coeficients parcials de seguretat
(γ)
Coeficients de combinació (ψ)
Favorable
Desfavorable
Principal (ψp)
Acompanyament (ψa)
Càrrega permanent
(G)
0.80
1.35
1.00
1.00
Sobrecàrrega (Q)
0.00
1.50
1.00
0.70
Vent (Q)
0.00
1.50
1.00
0.60
Neu (Q)
0.00
1.50
1.00
0.50
Sisme (A)
ƒ
Desplaçaments
Accions variables sense sisme
Coeficients parcials de seguretat
(γ)
Favorable
Desfavorable
Càrrega permanent
(G)
1.00
1.00
Sobrecàrrega (Q)
0.00
1.00
Vent (Q)
0.00
1.00
Neu (Q)
0.00
1.00
Sisme (A)
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
2.1.5.- PROGRAMES DE CÀLCUL EMPRATS PER LA RESOLUCIÓ D’ESTRUCTURES
PER EDIFICACIÓ.
El despatx d’enginyeria KUBIC CONSULTORIA TECNICA, SL associada a l’Associació de
Consultors d’Estructures amb el num. 75, i amb adreça c/Costa de Magdalena, 2, 4rt D,
25007 - LLEIDA; propietari de la llicència del programa CYPECAD i METAL3D vers. 2007.1.d,
ha utilitzat aquest per tal de realitzar els calculs dels elements estructurals (pilars, jasseres,
forjats i lloses armades) de l’obra objecte d’aquesta memoria.
3.- MECÀNICA DEL SÒL
3.1.- DEFINICIÓ I JUSTIFICACIÓ DE LA TIPOLOGIA DE FONAMENTACIÓ
S’ha projectat una fonamentació amb sabates aïllades o corregudes i riostres de formigó, sota
els pilars o pantalles o murs de contenció, dimensionats d’acord a les característiques del
terreny i a les càrregues en base dels diferents suports que ens trobem en l’obra, segons les
consideracions de càlcul (combinacions de càlcul i factors de seguretat) del CTE-DB-SE-C.
En el plànol de fonaments es defineixen totes les dimensions dels elements de fonamentació,
així com els diferents detalls de muntatge del elements de fonamentació. La resistència
característica del formigó serà HA-25
3.2.- ESTUDI GEOTÈCNIC
L’estudi geotècnic ha estat realitzat per l’empresa ICEC, S.L. amb el numero d’expedient
08.02/CUA-04/03.01 amb data de febrer de 2008.
3.2.1.- TENSIÓ DE TREBALL DEL TERRENY
A partir dels valors obtinguts en assaigs pressiomètrics, i en aplicar la formulació de Mènard pel
càlcul de la capacitat mecànica, amb un factor de seguretat F=3, es considera un tensió de
treball admissible del terreny de 0,30N/mm² per a les sabates aïllades i de 0,30N/mm2 per a la
sabata correguda.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
3.2.2.- NIVELL FREÀTIC
NUL.
3.2.3.- AGRESSIVITATS DEL TERRENY O AIGUA RESPECTE AL FORMIGÓ
AGRESSIVITAT TERRENY – FORMIGÓ: NUL.
AGRESSIVITAT AIGUA – FORMIGÓ: NUL·LA.
3.3.- CERTES SITUACIONS ATÍPIQUES
Res fa pensar la presencia de situacions atípiques segons s’observa en el estudi geotècnic.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
4.- REFERÈNCIA A LES NORMATIVES EMPRADES
ACCIONS
Per al càlcul de les sol·licitacions, s’han considerat, com accions característiques, les
establertes en les normes CTE-DB-SE-AE i NCSE-2002.
TERRENY
Per a l’estimació de les pressions admissibles sobre el terreny i les empentes produïdes per
aquest sobre la fonamentació, s’ha seguit l’especificat en els capítols CTE-DB-SE-AE i CTE-DBSE-C.
CIMENT
Els ciments que s’empraran en l’execució dels elements estructurals acompliran l’especificat en
la “Instrucción para la Recepción de Cementos RC-03”.
FORMIGÓ ARMAT
El disseny i càlcul de la fonamentació i/o l’estructura s’ajusten en tot moment a l’establert a les
normes CT-DB-SE-1 i 2 amb la EHE i EFHE, i la seva construcció es realitzarà d’acord amb
l’especificat en ambdues normes.
MURS DE FÀBRICA DE MAÓ
El disseny i el càlcul dels murs resistents d’aquesta estructura s’ajusten en tot moment a
l’especificat en la norma CT-DB-SE-1 i 2; i CTE-DB-SE-F.
Els maons emprats en els murs acompleixen l’especificat en el “Pliego General para la
Recepción de Ladrillos Cerámicos RL-88”.
MEMÒRIA DE CÀLCUL
pàg. 0
Kubic
CONSULTORIA TÈCNICA, SL
PROJECTE DE CÀLCUL D’ESTRUCTURA
DE FORMIGÓ
Ref.: EF/1140/0108
ESTRUCTURA METÀL·LICA
El disseny i càlcul dels diferents elements que formen el conjunt de l’estructura de principal del
forjat col·laborant s’ajusten en tot moment a l’establert a la CT-DB-SE-1 i 2; i CTE-DB-SE-A i la
seva construcció es realitzarà d’acord amb l’especificat en aquesta.
5.- CONSIDERACIONS DEL PROCES CONSTRUCTIU
S’insistirà que els processos constructius s’adequaran a les normes vigents i particularment pel
que fa a:
- Ancoratges.
- Recolzaments.
- Ritme d’apuntalament i desencofrat.
- Velocitat de formigonat.
- Curat de formigons.
- Control de carregaments dels tancaments en els forjats.
- Càrregues degudes al mateix procés de construcció.
- Fases construcció
Lleida, setembre de 2009
Anna Costa Isern i David Portolés Martínez, arquitectes
MEMÒRIA DE CÀLCUL
pàg. 0
ANNEX. PROJECTE DE CLIMATITZACIÓ PROJECTE DE CLIMATITZACIÓ
1.- EXPEDIENT I AUTOR DE L'ENCÀRREC
1.1.- EXPEDIENT
Referència:
Descripció:
Data:
Adreça:
Localitat:
Projectat per:
CENTRE CIVIC BELL-LLOC
05/03/08
1.2.- AUTOR DE L'ENCÀRREC
Propietari:
CIF:
Adreça:
Localitat:
Codi postal:
Pàgina 1 de 72
2.- MEMÒRIA DESCRIPTIVA
2.1.- DESCRIPCIÓ ARQUITECTÒNICA DE L'EDIFICI
L'edifici objecte d'aquest projecte s'ha dividit en les zones tèrmiques que apareixen
resumides en la taula següent:
Sistema/Zona
PLANTA BAIXA
GIMNÀS
BANY2
DESPATX GESTIÓ
SALA D'ESTAR
BAR-MENJADOR
VESTÍBUL
SALA ESPERA1
SERVEI SOCIAL
PODÒLEG
BANY HOMES
BANY DONES
SALA D'ESPERA2
CONSULTA METGE1
CURES
INFERMERIA
CONSULTA METGE2
Sistema/Zona
PLANTA PRIMERA
NOVES TECNOLOGIES
LOCAL4
LOCAL3
LOCAL2
LOCAL1
RECEPCIÓ
DESPATX SALA D’ACTES
VESTÍBUL
BANY DONES
BANY HOMES
SALA D’ACTES
Superfície
(m²)
46,0
20,5
15,4
49,7
114,4
44,6
29,1
15,8
18,9
14,5
16,4
42,5
22,5
15,0
16,6
20,0
Altura
(m)
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
Volum
(m³)
119,6
53,3
40,0
129,2
297,4
116,0
75,7
41,1
49,1
37,7
42,6
110,5
58,5
39,0
43,2
52,0
Superfície
(m²)
38,8
26,2
26,1
24,9
25,7
25,8
8,6
44,5
25,3
21,1
171,1
Altura
(m)
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
2,6
3,0
Volum
(m³)
100,9
68,1
67,9
64,7
66,8
67,1
22,4
115,7
65,8
54,9
513,3
Ús
Gimnasios
Aseos públicos (por urinario, inodoro, vertedero,...)
Oficinas
Descanso (salas de)
Comedores
Vestíbulos
Espera y recepción (salas)
Oficinas
Salas de recuperación
Aseos públicos (por urinario, inodoro, vertedero,...)
Aseos públicos (por urinario, inodoro, vertedero,...)
Espera y recepción (salas)
Salas de curas
Salas de curas
Salas de curas
Salas de curas
Ús
Aulas (sin fumadores)
Aulas (sin fumadores)
Aulas (sin fumadores)
Aulas (sin fumadores)
Aulas (sin fumadores)
Espera y recepción (salas)
Oficinas
Vestíbulos
Aseos públicos (por urinario, inodoro, vertedero,...)
Aseos públicos (por urinario, inodoro, vertedero,...)
Aulas (sin fumadores)
2.2.- HORARIS DE FUNCIONAMENT, OCUPACIÓ I NIVELLS DE VENTILACIÓ
L'ocupació s'ha estimat en funció de la superfície de cada zona, considerant els
metres quadrats per persona típics per al tipus d'activitat que en ella es desenvolupa.
Els nivells d'ocupació de cada zona són els descrits en la taula següent:
Sistema/Zona
Activitat
Ocupación TIPICA
Núm .
pers.
7
m² per
pers.
6,6
BANY2
Ocupación TIPICA
4
5,1
Cs
(w)
13
9
89
DESPATX GESTIÓ
Ocupación TIPICA
2
7,7
78
Cl
(w)
38
3
12
1
46
PLANTA BAIXA
GIMNÀS
SALA D'ESTAR
Ocupación TIPICA
16
3,1
71
31
BAR-MENJADOR
Ocupación TIPICA
50
2,3
71
91
VESTÍBUL
Ocupación TIPICA
6
7,4
89
SALA ESPERA1
Ocupación TIPICA
8
3,6
71
12
1
31
Horari de
Funcionament
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Pàgina 2 de 72
SERVEI SOCIAL
Ocupación TIPICA
3
5,3
78
46
PODÒLEG
Ocupación TIPICA
3
6,3
BANY HOMES
Ocupación TIPICA
3
4,8
10
9
89
BANY DONES
Ocupación TIPICA
3
5,5
89
SALA D'ESPERA2
Ocupación TIPICA
14
3,0
71
24
8
12
1
12
1
31
CONSULTA METGE1
Ocupación TIPICA
4
5,6
72
CURES
Ocupación TIPICA
3
5,0
72
INFERMERIA
Ocupación TIPICA
3
5,5
72
CONSULTA METGE2
Ocupación TIPICA
4
5,0
72
14
8
14
8
14
8
14
8
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Cs: Calor sensible en w aportat per persona a una temperatura ambient de 25°C.
Cl: Calor latent en w aportat per persona a una temperatura ambient de 25°C.
Sistema/Zona
Activitat
Ocupación TIPICA
Núm .
pers.
15
m² per
pers.
2,6
Cs
(w)
78
Cl
(w)
46
PLANTA PRIMERA
NOVES TECNOLOGIES
LOCAL4
Ocupación TIPICA
20
1,3
78
46
LOCAL3
Ocupación TIPICA
20
1,3
78
46
LOCAL2
Ocupación TIPICA
20
1,2
78
46
LOCAL1
Ocupación TIPICA
20
1,3
78
46
RECEPCIÓ
Ocupación TIPICA
12
2,2
71
31
DESPATX SALA D’ACTES
Ocupación TIPICA
2
4,3
78
46
VESTÍBUL
Ocupación TIPICA
8
5,6
89
BANY DONES
Ocupación TIPICA
4
6,3
89
BANY HOMES
Ocupación TIPICA
4
5,3
89
SALA D’ACTES
Ocupación TIPICA
80
2,1
78
12
1
12
1
12
1
46
Horari de
Funcionament
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Cs: Calor sensible en w aportat per persona a una temperatura ambient de 25°C.
Cl: Calor latent en w aportat per persona a una temperatura ambient de 25°C.
El cabal d'aire de ventilació s'obté en funció de l'ús del local, de la seva superfície i
del número d'ocupants, aplicant la Taula 2 de la norma UNE 100011.
Els nivells de ventilació assignats a cada zona són els que apareixen en el següent
taula:
Sistema/Zona
PLANTA BAIXA
GIMNÀS
Per
persona
(l/s)
12,0
Cabal d'aire exterior
Per
Per
m²
local/altres
(l/s)
(l/s)
4,0
-
Valor
escollit
(m³/h)
358,8
Renov.
(1/h)
Horari de
Funcionament
3,0
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
BANY2
25,0
-
-
360,0
6,8
DESPATX GESTIÓ
10,0
1,0
-
72,0
1,8
SALA D'ESTAR
20,0
15,0
-
1.292,2
10,0
BAR-MENJADOR
10,0
6,0
-
2.974,4
10,0
Pàgina 3 de 72
VESTÍBUL
10,0
15,0
-
1.739,4
15,0
SALA ESPERA1
8,0
4,0
-
418,0
5,5
SERVEI SOCIAL
10,0
1,0
-
82,2
2,0
PODÒLEG
10,0
1,5
-
108,0
2,2
BANY HOMES
25,0
-
-
270,0
7,2
BANY DONES
25,0
-
-
180,0
4,2
SALA D'ESPERA2
8,0
4,0
-
612,0
5,5
CONSULTA METGE1
12,0
2,0
-
180,0
3,1
CURES
12,0
2,0
-
130,0
3,3
INFERMERIA
12,0
2,0
-
130,0
3,0
CONSULTA METGE2
12,0
2,0
-
180,0
3,5
Valor
escollit
(m³/h)
432,0
Renov.
(1/h)
Horari de
Funcionament
4,3
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Sistema/Zona
PLANTA PRIMERA
NOVES TECNOLOGIES
Per
persona
(l/s)
8,0
Cabal d'aire exterior
Per
Per
m²
local/altres
(l/s)
(l/s)
-
LOCAL4
8,0
-
-
576,0
8,5
LOCAL3
8,0
-
-
576,0
8,5
LOCAL2
8,0
-
-
576,0
8,9
LOCAL1
8,0
-
-
576,0
8,6
RECEPCIÓ
8,0
4,0
-
371,5
5,5
DESPATX SALA D’ACTES
10,0
1,0
-
72,0
3,2
VESTÍBUL
10,0
15,0
-
925,6
8,0
BANY DONES
25,0
-
-
360,0
5,5
BANY HOMES
25,0
-
-
360,0
6,6
SALA D’ACTES
8,0
-
-
2.566,5
5,0
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Els nivells d'il·luminació i de potència dels equips elèctrics que es faran servir en
cada zona estan enumerats a la llista següent:
Sistema/Zona
Tipus d'il·luminació
w
Núm .
w/m²
PLANTA BAIXA
GIMNÀS
Alumbrado TIPICO
15,0
46
15,0
BANY2
Alumbrado TIPICO
15,0
20
15,0
DESPATX GESTIÓ
Alumbrado TIPICO
30,0
15
30,0
SALA D'ESTAR
Alumbrado TIPICO
15,0
49
15,0
BAR-MENJADOR
Alumbrado TIPICO
30,0
114
30,0
VESTÍBUL
Alumbrado TIPICO
15,0
44
15,0
SALA ESPERA1
Alumbrado TIPICO
15,0
29
15,0
Horari de
Funcionament
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Pàgina 4 de 72
SERVEI SOCIAL
Alumbrado TIPICO
30,0
15
30,0
PODÒLEG
Alumbrado TIPICO
20,0
18
20,0
BANY HOMES
Alumbrado TIPICO
15,0
14
15,0
BANY DONES
Alumbrado TIPICO
15,0
16
15,0
SALA D'ESPERA2
Alumbrado TIPICO
15,0
42
15,0
CONSULTA METGE1
Alumbrado TIPICO
30,0
22
30,0
CURES
Alumbrado TIPICO
40,0
15
40,0
INFERMERIA
Alumbrado TIPICO
40,0
16
40,0
CONSULTA METGE2
Alumbrado TIPICO
30,0
20
30,0
Tipus d'il·luminació
w
Núm .
w/m²
PLANTA PRIMERA
NOVES TECNOLOGIES
Alumbrado TIPICO
25,0
38
25,0
LOCAL4
Alumbrado TIPICO
25,0
26
25,0
LOCAL3
Alumbrado TIPICO
25,0
26
25,0
LOCAL2
Alumbrado TIPICO
25,0
24
25,0
LOCAL1
Alumbrado TIPICO
25,0
25
25,0
RECEPCIÓ
Alumbrado TIPICO
15,0
25
15,0
DESPATX SALA D’ACTES
Alumbrado TIPICO
30,0
8
30,0
VESTÍBUL
Alumbrado TIPICO
15,0
44
15,0
BANY DONES
Alumbrado TIPICO
15,0
25
15,0
BANY HOMES
Alumbrado TIPICO
15,0
21
15,0
SALA D’ACTES
Alumbrado TIPICO
25,0
171
25,0
Sistema/Zona
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Horari de
Funcionament
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Funcionamiento
continuo 1-24h
Evolució del percentatge de funcionament al llarg del dia per a cada un dels horaris
utilitzats:
Referència
1
2
3
4
5
6
7
8
9
10
11
Percentatge de càrrega per a cada hora solar
12 13 14 15 16 17 18 19 20 21
22
23
24
Funcionamiento continuo 1-24h
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
2.3.- DESCRIPCIÓ DELS TANCAMENTS
En un annex d'aquesta memòria es relacionen els diferents tancaments que
delimiten les zones de l'edifici.
2.4.- CONDICIONS EXTERIORS DE PROJECTE
Es té en compte la norma UNE 100001 per a la selecció de les condicions exteriors
de projecte, que queden definides de la següent manera:
Temperatura seca estiu
32,2 °C
Pàgina 5 de 72
Temperatura humida estiu
Percentil condicions d'estiu
Temperatura seca hivern
Percentil condicions d'hivern
21,3 °C
5,0 %
-1,8 °C
97,5 %
Variació diürna de temperatures
Graus acumulats en base 15 – 15°C
Orientació del vent dominant
Velocitat del vent dominant
Altura sobre el nivell del mar
Latitud
13,1 °C
1163 dies-grau
NO
7,4 m/s
202 m
41° 40' Nord
En un annex de càlcul apareix l'evolució de les temperatures seques i humides
màximes corregides per a tots els mesos de l'any i hores del dia, segons les taules
de correcció que recull la norma UNE 100014.
2.5.- CONDICIONS INTERIORS DE CÀLCUL
Les condicions climatològiques interiors han estat establertes en funció de l'activitat
metabòlica de les persones i del seu grau de vestimenta, sempre d'acord amb la ITE
02 Apartat 2.1.
Per a les hores considerades punta han estat seleccionades les següents condicions
interiors:
Sistema/Zona
PLANTA BAIXA
GIMNÀS
BANY2
DESPATX GESTIÓ
SALA D'ESTAR
BAR-MENJADOR
VESTÍBUL
SALA ESPERA1
SERVEI SOCIAL
PODÒLEG
BANY HOMES
BANY DONES
SALA D'ESPERA2
CONSULTA METGE1
CURES
INFERMERIA
CONSULTA METGE2
Sistema/Zona
PLANTA PRIMERA
NOVES TECNOLOGIES
LOCAL4
LOCAL3
LOCAL2
LOCAL1
RECEPCIÓ
DESPATX SALA D’ACTES
VESTÍBUL
BANY DONES
BANY HOMES
SALA D’ACTES
Temperatura
seca (°C)
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
Estiu
Humitat
relativa (%)
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
Temperatura
humida (°C)
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
Hivern
Temperatura
seca (°C)
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
Temperatura
seca (°C)
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
25,0
Estiu
Humitat
relativa (%)
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
56,9
Temperatura
humida (°C)
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
19,0
Hivern
Temperatura
seca (°C)
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
Pàgina 6 de 72
2.6.- MÈTODE DE CÀLCUL DE CÀRREGUES TÈRMIQUES
El mètode de càlcul utilitzat TFM (mètode de la funció de transferència) correspon al
descrit per ASHRAE en la seva publicació HVAC Fundamentals de 1988. En un
annex d'aquest projecte es realitza una breu descripció d'aquest mètode.
A continuació es mostra un resum de resultats de càrregues tèrmiques per a cada
sistema i cada una de les seves zones.
Descripció
PLANTA BAIXA
GIMNÀS
BANY2
DESPATX GESTIÓ
SALA D'ESTAR
BAR-MENJADOR
VESTÍBUL
SALA ESPERA1
SERVEI SOCIAL
PODÒLEG
BANY HOMES
BANY DONES
SALA D'ESPERA2
CONSULTA METGE1
CURES
INFERMERIA
CONSULTA METGE2
Descripció
PLANTA PRIMERA
NOVES TECNOLOGIES
LOCAL4
LOCAL3
LOCAL2
LOCAL1
RECEPCIÓ
DESPATX SALA D’ACTES
VESTÍBUL
BANY DONES
BANY HOMES
SALA D’ACTES
Càrrega
Refrigeració
Simultània
(kW)
71,6
6,9
2,3
1,4
7,6
21,0
7,7
2,7
1,3
2,1
2,6
1,6
5,7
2,5
1,7
2,0
2,4
Càrrega
Refrigeració
Màxima
(kW)
7,2
2,3
1,5
7,7
21,2
7,9
2,7
1,4
2,1
2,7
1,6
5,9
2,5
1,8
2,0
2,4
Càrrega
Refrigeració
Simultània
(kW)
71,2
5,6
5,8
5,8
5,8
5,8
3,7
0,8
6,0
3,4
2,2
26,2
Càrrega
Refrigeració
Màxima
(kW)
5,6
5,8
5,8
5,8
5,8
3,7
0,8
6,3
3,5
2,2
26,3
Data per a Màxima Càrrega
Individual
Calefacció
(kW)
Volum
Ventilació
(m³/h)
Agosto 15 horas
Septiembre 14 horas
Junio 16 horas
Septiembre 14 horas
Agosto 14 horas
Julio 15 horas
Julio 15 horas
Agosto 14 horas
Junio 16 horas
Julio 15 horas
Junio 14 horas
Julio 15 horas
Julio 16 horas
Julio 15 horas
Julio 15 horas
Junio 14 horas
Julio 15 horas
9.087
359
360
72
1.292
2.974
1.739
418
82
108
270
180
612
180
130
130
180
114,9
5,9
4,3
1,6
13,2
32,1
21,7
4,8
1,9
2,5
3,6
2,7
10,1
3,0
2,8
1,9
2,9
Data per a Màxima Càrrega
Individual
Calefacció
(kW)
Volum
Ventilació
(m³/h)
Agosto 14 horas
Agosto 14 horas
Agosto 14 horas
Agosto 14 horas
Agosto 14 horas
Agosto 14 horas
Agosto 14 horas
Julio 15 horas
Junio 15 horas
Junio 14 horas
Junio 16 horas
Agosto 15 horas
7.392
432
576
576
576
576
372
72
926
360
360
2.567
73,8
5,5
5,3
5,3
5,3
5,3
3,8
0,9
10,2
4,0
2,9
25,2
El detall del càlcul de càrregues tèrmiques es recull en un annex d'aquest projecte i
conté les taules del càlcul de càrregues tèrmiques per als diferents sistemes,
subsistemes i zones en què s'ha dividit l'edifici.
2.7.- DESCRIPCIÓ DELS SISTEMES DE CLIMATITZACIÓ SELECCIONATS
El sistema de calefacció de l’edifici estarà format per una caldera de biomassa, un
circuit de canonades d’aigua i unitats fan-coil a cada una de les sales a calefactar.
A més a més, el sistema es deixa preparat per la instal·lació d’una refredadora
d’aigua per una futura climatització de l’edifici.
Pàgina 7 de 72
ANNEX 1. MÈTODE DE CÀLCUL DE CÀRREGUES TÈRMIQUES
Es segueix el mètode desenvolupat per ASHRAE (American Society o Heating,
Refrigerating and Air-conditioning Engineers, Inc.) que basa la conversió de guanys
instantanis de calor a càrregues de refrigeració en les anomenades funcions de
transferència.
1.1.- Guanys tèrmics instantanis
El primer pas consisteix en el càlcul per a cada mes i cada hora del guany de calor
instantani degut a cada un dels següents elements:
1.1.1.- Guany solar vidre
Insolació a través d'envidraments a l'exterior.
QGAN ,t = CS × A × SHGF × n
Essent:
SHGF = GSd + Ins × GSt
que depèn del mes, de l'hora solar i de la latitud.
On:
QGAN,t =
A
=
CS
=
n
=
SHGF =
GSt =
GSd =
Ins
=
Guany instantani de calor sensible (watts)
Àrea de la superfície envidrada (m²)
Coeficient d'ombrejat
Núm. d'unitats de finestres del mateix tipus
Guany solar per al vidre tipus (DSA)
Guany solar per radiació directa (watts/m²)
Guany solar per radiació difusa (watts/m²)
Percentatge d'ombra sobre la superfície envidrada
1.1.2.- Transmissió parets i sostres
Tancaments opacs a l'exterior, tret dels que no reben els raigs solars. El guany
instantani per a cada hora es calcula usant la següent funció de transferència
(ASHRAE):
(QGAN ,t −nΔ )
⎡
⎤
QGAN ,t = A × ⎢∑ bn × (t sa ,t − nΔ ) − ∑ d n ×
− t ai × ∑ c n ⎥
A
n =1
n =0
⎣ n =0
⎦
On:
QGAN,t =
Guany de calor sensible en l'ambient a través de la superfície interior
del sostre o paret (w)
A
=
Àrea de la superfície interior (m²)
Tsa,t-nΔ =
Temperatura sol aire en l'instant t-nΔ
Pàgina 8 de 72
Δ
tai
bn
cn
dn
=
=
Increment de temps igual a 1 hora.
Temperatura de l'espai interior suposada constant
=
Coeficients de la funció de transferència segons el tipus de tancament
La temperatura sol-aire serveix per corregir l'efecte dels raigs solars sobre la
superfície exterior del tancament:
t sa = t ec + α ×
It
ΔR
−ε ×
× cos(90° − β )
ho
ho
On:
Tsa
Tec
It
ho
α
β
=
=
=
=
=
=
Temperatura sol-aire per a un mes i una hora donades (°C)
Temperatura seca exterior corregida segons mes i hora (°C)
Radiació solar incident en la superfície (w/m²)
Coeficient de termotransferència de la superfície (w/m² °C)
Absorbència de la superfície a la radiació solar (depèn del color)
Angle d'inclinació del tancament pel que fa a la vertical (horitzontals
=
=
Emitància hemisfèrica de la superfície.
Diferència de radiació superfície/cos negre (w/m²)
90°).
ε
ΔR
1.1.3.- Transmissió excepte parets i sostres
1.1.3.1.- Tancaments a l'interior
Guanys instantanis per transmissió en tancaments opacs interiors i que no estan
exposats als raigs solars.
QGAN ,t = K × A × (t l − t ai )
On:
QGAN,t
K
A
tl
tai
=
=
=
=
=
Guany de calor sensible en l'instant t (w)
Coeficient de transmissió del tancament (w/m²·°C)
Àrea de la superfície interior (m²)
Temperatura del local contigu (°C)
Temperatura de l'espai interior suposada constant (°C)
1.1.3.2.- Envidraments a l'exterior
Guanys instantanis per transmissió en superfícies envidrades a l'exterior.
QGAN ,t = K × A × (t ec − t ai )
Pàgina 9 de 72
On:
QGAN,t
K
A
tec
tai
=
=
=
=
=
Guany de calor sensible en l'instant t (w)
Coeficient de transmissió del tancament (w/m²·°C)
Àrea de la superfície interior (m²)
Temperatura exterior corregida (°C)
Temperatura de l'espai interior suposada constant (°C)
1.1.3.3.- Portes a l'exterior
Un cas especial són les portes a l'exterior, en les que cal distingir segons la seva
orientació:
QGAN ,t = K × A × (t l − t ai )
On:
QGAN,t
K
A
tai
tl
=
=
=
=
=
Guany de calor sensible en l'instant t (w)
Coeficient de transmissió del tancament (w/m²·°C)
Àrea de la superfície interior (m²)
Temperatura de l'espai interior suposada constant (°C)
Per a orientació Nord: Temperatura exterior corregida (°C)
Excepte orientació Nord:Temperatura sol-aire per a l'instant t (°C)
1.1.4.-Calor intern
1.1.4.1.- Ocupació (persones)
Calor generat per les persones que es troben dins de cada local. Aquesta calor és
funció principalment del número de persones i del tipus d'activitat que estan
desenvolupant.
QGAN ,t = Qs × n × 0'01 × Fd t
On:
QGAN,t
Qs
n
Fdt
=
=
=
=
Guany de calor sensible en l'instant t (w)
Guany sensible per persona (w). Depèn del tipus d'activitat
Número d'ocupants
Percentatge d'ocupació per a l'instant t (%)
Es considera que 67% de la calor sensible es dissipa per radiació i la resta per
convecció.
QGANl ,t = Ql × n × 0'01 × Fd t
On:
QGANl,t =
Ql
=
Guany de calor latent en l'instant t (w)
Guany latent per persona (w). Depèn del tipus d'activitat
Pàgina 10 de 72
n
Fdt
=
=
Número d'ocupants
Percentatge d'ocupació per a l'instant t (%)
1.1.4.2.- Enllumenat
Calor generat pels aparells de llum que es troben dins de cada local. Aquesta calor
és funció principalment del número i tipus d'aparells.
QGAN ,t = Qs × n × 0'01 × Fd t
On:
QGAN,t
Qs
n
Fdt
=
=
=
=
Guany de calor sensible en l'instant t (w)
Potència per lluminària (w). Per a fluorescent es multiplica per 1'25.
Número de lluminàries.
Percentatge de funcionament per a l'instant t (%)
1.1.4.3.- Aparells elèctrics
Calor generada pels aparells exclusivament elèctrics que es troben dins de cada
local. Aquesta calor és funció principalment del número i tipus d'aparells.
QGAN ,t = Qs × n × 0'01 × Fd t
On:
QGAN,t
Qs
n
Fdt
=
=
=
=
Guany de calor sensible en l'instant t (w)
Guany sensible per aparell (w). Depèn del tipus.
Número d'aparells.
Percentatge de funcionament per a l'instant t (%)
Es considera que el 60% de la calor sensible es dissipa per radiació i la resta per
convecció.
1.1.4.4.- Aparells tèrmics
Calor generada pels aparells tèrmics que es troben dins de cada local. Aquesta calor
és funció principalment del número i tipus d'aparells.
QGAN ,t = Qs × n × 0'01 × Fd t
On:
QGAN,t
Qs
n
Fdt
=
=
=
=
Guany de calor sensible en l'instant t (w)
Guany sensible per aparell (w). Depèn del tipus.
Número d'aparells.
Percentatge de funcionament per a l'instant t (%)
Es considera que el 60% de la calor sensible es dissipa per radiació i la resta per
convecció.
Pàgina 11 de 72
QGANl ,t = Ql × n × 0'01 × Fd t
On:
QGANl,t =
Ql
=
n
=
=
Fdt
Guany de calor latent en l'instant t (w)
Guany latent per aparell (w). Depèn del tipus
Número d'aparells
Percentatge de funcionament per a l'instant t (%)
1.1.5.- Aire exterior
Guanys instantanis de calor a causa de l'aire exterior de ventilació. Aquests guanys
passen directament a ser càrregues de refrigeració.
QGAN ,t = 0'34 × f a × Vae s × 0'01 × Fd t × (t ec − t ai )
On:
QGAN,t
fa
Vae
tec
tai
Fdt
=
=
=
=
=
=
Guany de calor sensible en l'instant t (w)
Coeficient corrector per altitud geogràfica.
Cabal d'aire exterior (m³/h).
Temperatura seca exterior corregida (°C).
Temperatura de l'espai interior suposada constant (°C)
Percentatge de funcionament per a l'instant t (%)
Es considera que el 100% de la calor sensible apareix per convecció.
QGANl ,t = 0'83 × f a × Vae s × 0'01 × Fd t × ( X ec − X ai )
On:
QGANl,t =
fa
=
Vae
=
=
Xec
Xai
=
=
Fdt
Guany de calor sensible en l'instant t (w)
Coeficient corrector per altitud geogràfica.
Cabal d'aire exterior (m³/h).
Humitat específica exterior corregida (gr aigua/kg aire).
Humitat específica de l'espai interior (gr aigua/kg aire)
Percentatge de funcionament per a l'instant t (%)
1.2.- Càrregues de refrigeració
La càrrega de refrigeració depèn de la magnitud i naturalesa del guany tèrmic
instantani així com del tipus de construcció del local, del seu contingut, tipus
d'il·luminació i del seu nivell de circulació d'aire.
Els guanys instantanis de calor latent així com les parts corresponents de calor
sensible que apareixen per convecció passen directament a ser càrregues de
refrigeració. Els guanys deguts a la radiació i transmissió es transformen en
càrregues de refrigeració per mitjà de la funció de transferència següent:
Pàgina 12 de 72
QREF ,t = v0 × QGAN ,t + v1 × QGAN ,t − Δ + v 2 × QGAN ,t −Δ 2 − w1 × QREF ,t − Δ
QREF,t
QGAN,t
Δ
vo, v1 i v2
w1
=
Càrrega de refrigeració per a l'instant t (w)
=
Guany de calor en l'instant t (w)
=
Increment de temps igual a 1 hora.
=
Coeficients en funció de la naturalesa del guany tèrmic
instantani.
=
Coeficient en funció del nivell de circulació de l'aire en el local.
Pàgina 13 de 72
ANNEX 2. DETALL DEL CÀLCUL TÈRMIC
2.1.- EVOLUCIÓ ANUAL DE TEMPERATURA EXTERIOR SECA MÀXIMA (°C)
Hora
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Gen.
3,5
2,9
2,3
1,7
1,2
0,6
2,9
5,2
6,6
8,1
9,5
10,9
12,0
13,1
13,7
13,1
12,5
12,0
10,7
9,4
8,1
6,8
5,4
4,1
Feb.
12,1
11,6
11,0
10,4
9,8
9,3
11,5
13,8
15,3
16,8
18,2
19,6
20,7
21,8
22,4
21,8
21,2
20,7
19,4
18,1
16,8
15,5
14,1
12,7
Mar.
15,0
14,4
13,8
13,3
12,7
12,1
14,4
16,7
18,1
19,6
21,0
22,4
23,5
24,6
25,2
24,6
24,1
23,5
22,2
20,9
19,6
18,3
16,9
15,6
Abr.
17,2
16,6
16,1
15,5
14,9
14,3
16,6
18,9
20,4
21,8
23,2
24,6
25,7
26,8
27,4
26,8
26,3
25,7
24,4
23,2
21,8
20,5
19,2
17,8
Maig.
19,8
19,3
18,7
18,1
17,5
17,0
19,2
21,5
23,0
24,5
25,9
27,3
28,4
29,5
30,1
29,5
28,9
28,4
27,1
25,8
24,5
23,2
21,8
20,4
Jun.
21,4
20,8
20,2
19,7
19,1
18,5
20,8
23,1
24,5
26,0
27,4
28,8
29,9
31,0
31,6
31,0
30,5
29,9
28,6
27,3
26,0
24,7
23,3
22,0
Jul.
22,0
21,4
20,8
20,3
19,7
19,1
21,4
23,7
25,1
26,6
28,0
29,4
30,5
31,6
32,2
31,6
31,1
30,5
29,2
27,9
26,6
25,3
23,9
22,6
Ago.
22,0
21,4
20,8
20,3
19,7
19,1
21,4
23,7
25,1
26,6
28,0
29,4
30,5
31,6
32,2
31,6
31,1
30,5
29,2
27,9
26,6
25,3
23,9
22,6
Set.
20,7
20,2
19,6
19,0
18,4
17,9
20,1
22,4
23,9
25,4
26,8
28,2
29,3
30,4
31,0
30,4
29,8
29,3
28,0
26,7
25,4
24,1
22,7
21,3
Oct.
18,3
17,7
17,2
16,6
16,0
15,4
17,7
20,0
21,5
22,9
24,3
25,7
26,8
27,9
28,5
27,9
27,4
26,8
25,5
24,3
22,9
21,6
20,3
18,9
Nov.
14,5
13,9
13,3
12,8
12,2
11,6
13,9
16,2
17,6
19,1
20,5
21,9
23,0
24,1
24,7
24,1
23,6
23,0
21,7
20,4
19,1
17,8
16,4
15,1
Des.
9,7
9,2
8,6
8,0
7,4
6,9
9,1
11,4
12,9
14,4
15,8
17,2
18,3
19,4
20,0
19,4
18,8
18,3
17,0
15,7
14,4
13,1
11,7
10,3
2.2.- EVOLUCIÓ ANUAL DE TEMPERATURA EXTERIOR HUMIDA MÀXIMA (°C)
Hora
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Gen.
10,0
10,0
10,0
10,0
10,0
10,0
10,2
10,4
10,7
10,9
11,5
12,0
12,3
12,6
12,6
12,6
12,3
12,0
11,8
11,5
11,2
10,9
10,5
10,0
Feb.
13,9
13,9
13,9
13,9
13,9
13,9
14,1
14,3
14,6
14,8
15,4
15,9
16,2
16,5
16,5
16,5
16,2
15,9
15,7
15,4
15,1
14,8
14,4
13,9
Mar.
15,3
15,3
15,3
15,3
15,3
15,3
15,5
15,7
15,9
16,2
16,7
17,3
17,6
17,9
17,9
17,9
17,6
17,3
17,0
16,8
16,5
16,2
15,7
15,3
Abr.
16,4
16,4
16,4
16,4
16,4
16,4
16,6
16,8
17,1
17,3
17,9
18,4
18,7
19,0
19,0
19,0
18,7
18,4
18,2
17,9
17,6
17,3
16,9
16,4
Maig.
17,6
17,6
17,6
17,6
17,6
17,6
17,8
18,0
18,3
18,5
19,1
19,6
19,9
20,2
20,2
20,2
19,9
19,6
19,4
19,1
18,8
18,5
18,0
17,6
Jun.
18,7
18,7
18,7
18,7
18,7
18,7
18,9
19,1
19,4
19,6
20,2
20,7
21,0
21,3
21,3
21,3
21,0
20,7
20,5
20,2
19,9
19,6
19,1
18,7
Jul.
18,7
18,7
18,7
18,7
18,7
18,7
18,9
19,1
19,4
19,6
20,2
20,7
21,0
21,3
21,3
21,3
21,0
20,7
20,5
20,2
19,9
19,6
19,1
18,7
Ago.
18,7
18,7
18,7
18,7
18,7
18,7
18,9
19,1
19,4
19,6
20,2
20,7
21,0
21,3
21,3
21,3
21,0
20,7
20,5
20,2
19,9
19,6
19,1
18,7
Set.
17,9
17,9
17,9
17,9
17,9
17,9
18,1
18,4
18,6
18,9
19,4
20,0
20,3
20,6
20,6
20,6
20,3
20,0
19,7
19,5
19,2
18,9
18,4
17,9
Oct.
16,6
16,6
16,6
16,6
16,6
16,6
16,8
17,0
17,3
17,5
18,1
18,6
18,9
19,2
19,2
19,2
18,9
18,6
18,4
18,1
17,8
17,5
17,1
16,6
Nov.
15,1
15,1
15,1
15,1
15,1
15,1
15,3
15,5
15,7
16,0
16,5
17,1
17,4
17,7
17,7
17,7
17,4
17,1
16,8
16,6
16,3
16,0
15,5
15,1
Des.
12,9
12,9
12,9
12,9
12,9
12,9
13,1
13,4
13,6
13,9
14,4
15,0
15,3
15,6
15,6
15,6
15,3
15,0
14,7
14,5
14,2
13,9
13,4
12,9
Pàgina 14 de 72
2.3.- FULL DE CÀRREGUES PER A REFRIGERACIÓ DEL SISTEMA
PROJECTE:
SISTEMA:
CENTRE CIVIC BELL-LLOC
PLANTA BAIXA
CONDICIONS DE DISSENY: Estimat per a les 15 hora solar del mes de Agosto.
T.seca
32,2 °C
Exterior:
T.hum.
21,3 °C
H.rel.
37,8 %
H.esp.
11,4 gr/kg
GUANYS DE CALOR:
Ts
(°C)
Th
(°C)
Àrea
(m²)
Vol.
(m³)
GIMNÀS
25,0 19,0 46,0
119,6
BANY2
25,0 19,0 20,5
53,3
DESPATX GESTIÓ
25,0 19,0 15,4
40,0
SALA D'ESTAR
25,0 19,0 49,7
129,2
BAR-MENJADOR
25,0 19,0 114,4 297,4
VESTÍBUL
25,0 19,0 44,6
116,0
SALA ESPERA1
25,0 19,0 29,1
75,7
SERVEI SOCIAL
25,0 19,0 15,8
41,1
PODÒLEG
25,0 19,0 18,9
49,1
BANY HOMES
25,0 19,0 14,5
37,7
BANY DONES
25,0 19,0 16,4
42,6
SALA D'ESPERA2
25,0 19,0 42,5
110,5
CONSULTA METGE1
25,0 19,0 22,5
58,5
CURES
25,0 19,0 15,0
39,0
INFERMERIA
25,0 19,0 16,6
43,2
CONSULTA METGE2
25,0 19,0 20,0
52,0
Gsc
(W)
Tpt
(W)
Tept
(W)
Cis
(W)
Aes
(W)
Cil
(W)
Ael
(W)
RSHF C.refr.
(W)
1.264
103
119
1.746
860
2.815
29
0,534
6.935
114
32
51
697
863
508
29
0,638
2.294
427
20
52
649
173
97
6
0,922
1.423
1.709
49
156
1.976
3.097
521
103
0,882
7.610
736
228
599
7.331
7.128
4.778
237
0,651
21.037
616
236
556
1.263
4.168
762
138
0,778
7.740
267
72
37
1.055
1.002
260
33
0,846
2.725
147
29
40
743
197
145
7
0,869
1.308
147
15
158
740
259
781
9
0,576
2.109
861
49
100
509
647
381
21
0,799
2.568
0
0
187
539
431
381
14
0,656
1.552
1.111
679
209
1.713
1.467
456
49
0,891
5.683
208
46
143
1.011
431
622
14
0,694
2.476
0
101
0
857
312
466
10
0,673
1.746
208
40
21
924
312
466
10
0,719
1.981
238
112
81
932
431
622
14
0,687
2.430
2.507
22.685 21.777 14.061 723
0,714
71.615
CÀRREGA DE REFRIGERACIÓ TOTAL
501,9 1.304,9 8.053 1.811
Factor de seguretat: 5%
Cabal total d'aire exterior: 9.087 m³/h
Càrrega de refrigeració per unitat de superfície: 143 w/m²
Ts: T emperatura seca interior (°C).
Th: Temperatura humida interior (°C).
Vol.: Volum de la zona.
Gsc: Guany solar vidre.
Tpt: Transmissió parets i sostre.
Tept: Transmissió excepte parets i sostre.
Cis:
Calor intern sensible.
Aes:
Aire exterior sensible.
Cil:
Calor intern latent.
Ael:
Aire exterior latent.
RSHF: Factor de calor sensible de la zona.
C.Refr.: Càrregues de refrigeració.
Pàgina 15 de 72
FULL DE CÀRREGUES PER A CALEFACCIÓ DEL SISTEMA
PROJECTE:
SISTEMA:
CENTRE CIVIC BELL-LLOC
PLANTA BAIXA
CONDICIONS DE DISSENY:
Temperatura exterior:
Dies grau acumulats:
Orientació del vent dominant:
Velocitat del vent dominant:
-1,8 °C
1163
NO
7,4 m/s
PÈRDUES DE CALOR:
ZONES
GIMNÀS
BANY2
DESPATX GESTIÓ
SALA D'ESTAR
BAR-MENJADOR
VESTÍBUL
SALA ESPERA1
SERVEI SOCIAL
PODÒLEG
BANY HOMES
BANY DONES
SALA D'ESPERA2
CONSULTA METGE1
CURES
INFERMERIA
CONSULTA METGE2
Tsi
(°C)
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
CÀRREGA DE CALEFACCIÓ TOTAL
Àrea
(m²)
46,0
20,5
15,4
49,7
114,4
44,6
29,1
15,8
18,9
14,5
16,4
42,5
22,5
15,0
16,6
20,0
Vol.
(m³)
119,6
53,3
40,0
129,2
297,4
116,0
75,7
41,1
49,1
37,7
42,6
110,5
58,5
39,0
43,2
52,0
Tae
(W)
1.142
583
299
1.096
2.331
2.400
366
563
481
763
0
1.237
271
214
255
493
Tol
(W)
1.916
900
680
2.069
5.997
3.125
1.232
642
1.166
636
1.297
2.163
1.326
610
675
1.005
Ipv
(W)
154
53
52
208
1.178
2.945
33
68
68
126
0
2.080
30
970
30
35
501,9
1.304,9 12.494 25.438 8.030
Vae
(W)
2.723
2.732
546
9.806
22.572
13.200
3.172
624
820
2.049
1.366
4.644
1.366
987
987
1.366
C.calef.
(W)
5.935
4.268
1.578
13.180
32.078
21.670
4.803
1.897
2.534
3.574
2.663
10.125
2.993
2.780
1.947
2.899
68.959 114.922
Factor de seguretat: 0,0%
Cabal total d'aire exterior: 9.087 m³/h
Càrrega de calefacció per unitat de superfície: 229 w/m²
Tsi: Temperatura seca interior (°C).
Vol.: Volum de la zona.
Tae: Transmissió ambient exterior.
Tol: Transmissió altres locals.
Ipv:
Infiltracions portes i finestres.
Vae:
Ventilació aire exterior.
C.calef.: Càrregues de calefacció.
ABREVIATURES I UNITATS:
Or.: Orientació del tancament exterior
SQ: Coeficient d'ombrejat (adimensional)
K: Coeficient de transmissió (W/m²·°C)
Tsa: Temperatura Sol-Aire (°C)
Tec: Temperatura exterior corregida (°C)
Tac: Temperatura ambient contigu (°C)
Xec: Humitat específica exterior (gr/kgr)
Ud. Número d'elements del mateix tipus
Cabal: Aire exterior (m³/h)
Sup.: Superfície de tancaments (m²)
Pressió: Pressió del vent (Pa)
Supl.: Suplement per orientació.
G.Inst.: Guanys instantanis (W)
Càrrega.Refr.: Càrregues de refrigeració (W)
Càrrega.Calef.: Càrregues de calefacció (W)
Pàgina 16 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
GIMNÀS
CONDICIONS
Ts (°C)
DESTINADA A
Gimnasios
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
46,0 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
119,6 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Fachada S
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
LADS02
S
S
S
REF.
Or.
MEXA02
MEXA02
EXCEPTE
PARETS
Ventana S
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
2,4
2,3
0,89
0,89
0,89
1
1
1
Sup. (m²)
O
S
REF.
16,6
14,4
Sup. (m²)
LADS02
LADS02
LADS02
TAB007
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
2,4
2,4
2,3
39,0
1,9
46,0
46,0
Potència
7 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
358,8 m³/h Ventilación
Tsa
60,5
47,0
K
Tac
2,73
2,73
2,73
2,49
2,13
3,03
0,69
32,2
32,2
32,2
25,0
29,4
25,0
25,0
Ud.
139,0
46,0
Cabal
K
0,61
0,61
%Ús
7
15
Tec
359
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
551
551
528
G. Inst. (w)
26
63
G. Inst. (w)
47
47
45
0
18
0
0
G. Inst. (w)
973
690
G. Inst. (w)
860
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
407
407
390
1.264
Càrrega Refr. (w)
38
60
103
Càrrega Refr. (w)
34
34
32
0
13
0
0
119
Càrrega Refr. (w)
973
690
1.746
Càrrega Refr. (w)
860
860
4.091 w
Potència
7 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
383,0
Cabal
358,8 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
7
Xec
359
100
%Ús
11,4
100
G. Inst. (w)
2.681
G. Inst. (w)
29
Càrrega Refr. (w)
2.681
2.815
Càrrega Refr. (w)
29
29
2.844 w
6.935 w
Factor de calor sensible de la zona (RSHF): 0,534
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 151 w/m²
Pàgina 17 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
GIMNÀS
Ts
DESTINADA A
Gimnasios
DIMENSIONS
46,0 m² x 2,6 m
REF.
MEXA02
MEXA02
LADS02
LADS02
LADS02
Supl.
Sup. (m²)
1,075
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
LADS02
358,8 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
16,6
14,4
2,4
2,4
2,3
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
O
S
S
S
S
Sup. (m²)
S
S
S
Pressió
Tac
0,61
0,61
4,30
4,30
4,30
K
39,0
1,9
46,0
46,0
Or.
21,0
Diferència
22,8
119,6 m³
TAB007
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Fachada S
Ventana S
Ventana S
Ventana S
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
2,49
2,13
2,44
0,66
Cabal
26,7
26,7
26,7
-1,8
-1,8
-1,8
-1,8
-1,8
21,0
9,3
4,3
21,0
Tac
6,9
6,9
6,6
Cabal
-1,8
-1,8
-1,8
Tac
359
-1,8
Càrrega Calef. (w)
247
199
235
235
225
1.142
Càrrega Calef. (w)
0
47
1.869
0
1.916
Càrrega Calef. (w)
52
52
50
154
Càrrega Calef. (w)
2.723
2.723
0,0%
0,0%
1,000
5.935 w
129 w/m²
Pàgina 18 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
BANY2
CONDICIONS
Ts (°C)
Th (°C)
DESTINADA A
Aseos públicos
vertedero,...)
32,2
21,3
DIMENSIONS
20,5 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
53,3 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
(por
urinario,
GUANY SOLAR VIDRE
Ventana N
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Fachada N
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
inodoro, Exteriors
REF.
Or.
LADS02
N
REF.
Or.
MEXA02
MEXA02
EXCEPTE
PARETS
Ventana N
Cerramiento interior 1
Puerta interior 1
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,1
0,89
1
K
Tsa
0,61
0,61
60,5
36,4
K
Tac
2,73
2,49
2,13
3,03
0,69
32,2
25,0
29,4
25,0
25,0
Sup. (m²)
O
N
REF.
5,7
15,8
Sup. (m²)
LADS02
TAB007
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
2,1
26,4
2,7
20,5
20,5
Potència
4 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
89,0
20,5
Cabal
360,0 m³/h Ventilación
%Ús
4
15
Tec
360
100
100
%Ús
32,2
100
G. Inst. (w)
159
G. Inst. (w)
9
16
G. Inst. (w)
41
0
25
0
0
G. Inst. (w)
356
308
G. Inst. (w)
863
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Xe (gr/kgr)
11,4
Càrrega Refr. (w)
109
114
Càrrega Refr. (w)
13
18
32
Càrrega Refr. (w)
29
0
19
0
0
51
Càrrega Refr. (w)
356
307
697
Càrrega Refr. (w)
863
863
1.757 w
Potència
4 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Hr (%)
37,8
Ud.
121,0
Cabal
360,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
4
Xec
360
100
%Ús
11,4
100
G. Inst. (w)
484
G. Inst. (w)
29
Càrrega Refr. (w)
484
508
Càrrega Refr. (w)
29
29
537 w
2.294 w
Factor de calor sensible de la zona (RSHF): 0,638
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 112 w/m²
Pàgina 19 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
BANY2
Ts
DESTINADA A
Aseos públicos (por urinario, inodoro,
vertedero,...)
DIMENSIONS
20,5 m² x 2,6 m
REF.
MEXA02
MEXA02
LADS02
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Solera 1
Forjado interior 1
O
N
N
REF.
LADS02
Supl.
Sup. (m²)
1,075
1,175
1,175
360,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
5,7
15,8
2,1
Sup. (m²)
N
Pressió
Tac
0,61
0,61
4,30
K
26,4
2,7
20,5
20,5
Or.
21,0
Diferència
22,8
53,3 m³
TAB007
PIMP20
SOLE01
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
Or.
Interior
-1,8
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana N
Exterior
(°C)
VOLUM
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Fachada N
Ventana N
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
2,49
2,13
2,44
0,66
Cabal
33,4
-1,8
-1,8
-1,8
21,0
9,3
4,3
21,0
Tac
7,0
Cabal
-1,8
Tac
360
-1,8
Càrrega Calef. (w)
85
257
242
583
Càrrega Calef. (w)
0
67
833
0
900
Càrrega Calef. (w)
53
53
Càrrega Calef. (w)
2.732
2.732
0,0%
0,0%
1,000
4.268 w
208 w/m²
Pàgina 20 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
DESPATX GESTIÓ
CONDICIONS
Ts (°C)
DESTINADA A
Oficinas
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
15,4 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
40,0 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
S
REF.
Or.
MEXA02
EXCEPTE
PARETS
Ventana S
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
0,89
1
K
Tsa
0,61
47,0
K
Tac
2,73
2,49
2,13
2,13
3,03
0,69
32,2
25,0
29,4
25,0
25,0
25,0
Sup. (m²)
S
REF.
4,6
Sup. (m²)
LADS02
TAB007
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
2,4
33,7
2,2
2,0
15,4
15,4
Potència
2 Ocupantes
30 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
78,0
15,4
Cabal
%Ús
2
30
Tec
72,0 m³/h Ventilación
72
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
551
G. Inst. (w)
20
G. Inst. (w)
47
0
21
0
0
0
G. Inst. (w)
156
462
G. Inst. (w)
173
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
407
427
Càrrega Refr. (w)
19
20
Càrrega Refr. (w)
34
0
15
0
0
0
52
Càrrega Refr. (w)
156
462
649
Càrrega Refr. (w)
173
173
1.320 w
Potència
2 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
46,0
Cabal
72,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
2
Xec
72
100
%Ús
11,4
100
G. Inst. (w)
92
G. Inst. (w)
6
Càrrega Refr. (w)
92
97
Càrrega Refr. (w)
6
6
102 w
1.423 w
Factor de calor sensible de la zona (RSHF): 0,922
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 92 w/m²
Pàgina 21 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
DESPATX GESTIÓ
Ts
DESTINADA A
Oficinas
DIMENSIONS
15,4 m² x 2,6 m
REF.
MEXA02
LADS02
Supl.
Sup. (m²)
1,000
1,000
REF.
LADS02
72,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
4,6
2,4
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
Sup. (m²)
S
Pressió
Tac
0,61
4,30
K
33,7
2,2
2,0
15,4
15,4
Or.
21,0
Diferència
22,8
40,0 m³
TAB007
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
2,49
2,13
2,13
2,44
0,66
Cabal
26,7
-1,8
-1,8
21,0
9,3
21,0
4,3
21,0
Tac
6,9
Cabal
-1,8
Tac
72
-1,8
Càrrega Calef. (w)
64
235
299
Càrrega Calef. (w)
0
55
0
626
0
680
Càrrega Calef. (w)
52
52
Càrrega Calef. (w)
546
546
0,0%
0,0%
1,000
1.578 w
102 w/m²
Pàgina 22 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
SALA D'ESTAR
CONDICIONS
Ts (°C)
DESTINADA A
Descanso (salas de)
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
49,7 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
129,2 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
LADS02
LADS02
S
S
S
S
REF.
Or.
MEXA02
EXCEPTE
PARETS
Ventana S
Ventana S
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Puerta interior 3
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
2,4
2,4
2,4
0,89
0,89
0,89
0,89
1
1
1
1
K
Tsa
0,61
47,0
K
Tac
2,73
2,73
2,73
2,73
2,49
2,13
2,13
2,13
3,03
0,69
32,2
32,2
32,2
32,2
25,0
29,4
25,0
25,0
25,0
25,0
Sup. (m²)
S
REF.
11,2
Sup. (m²)
LADS02
LADS02
LADS02
LADS02
TAB007
PIMP20
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
2,4
2,4
2,4
2,4
42,6
2,0
1,8
7,0
49,7
49,7
Potència
16 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
71,0
49,7
Cabal
1.292,2 m³/h Ventilación
%Ús
16
15
Tec
1.292
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
551
551
551
551
G. Inst. (w)
49
G. Inst. (w)
47
47
47
47
0
19
0
0
0
0
G. Inst. (w)
1.136
746
G. Inst. (w)
3.097
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
407
407
407
407
1.709
Càrrega Refr. (w)
47
49
Càrrega Refr. (w)
34
34
34
34
0
14
0
0
0
0
156
Càrrega Refr. (w)
1.136
745
1.976
Càrrega Refr. (w)
3.097
3.097
6.986 w
Potència
16 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
31,0
Cabal
1.292,2 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
16
Xec
1.292
100
%Ús
11,4
100
G. Inst. (w)
496
G. Inst. (w)
103
Càrrega Refr. (w)
496
521
Càrrega Refr. (w)
103
103
624 w
7.610 w
Factor de calor sensible de la zona (RSHF): 0,882
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 153 w/m²
Pàgina 23 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
SALA D'ESTAR
Ts
DESTINADA A
Descanso (salas de)
DIMENSIONS
49,7 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
LADS02
LADS02
Supl.
Sup. (m²)
1,000
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
LADS02
LADS02
1.292,2 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
11,2
2,4
2,4
2,4
2,4
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
S
S
S
Sup. (m²)
S
S
S
S
Pressió
Tac
0,61
4,30
4,30
4,30
4,30
K
42,6
2,0
1,8
7,0
49,7
49,7
Or.
21,0
Diferència
22,8
129,2 m³
TAB007
PIMP20
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Puerta interior 3
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Ventana S
Ventana S
Ventana S
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
2,49
2,13
2,13
2,13
2,44
0,66
Cabal
26,7
26,7
26,7
26,7
-1,8
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
21,0
4,3
21,0
Tac
6,9
6,9
6,9
6,9
Cabal
1.292
-1,8
-1,8
-1,8
-1,8
Tac
-1,8
Càrrega Calef. (w)
155
235
235
235
235
1.096
Càrrega Calef. (w)
0
50
0
0
2.019
0
2.069
Càrrega Calef. (w)
52
52
52
52
208
Càrrega Calef. (w)
9.806
9.806
0,0%
0,0%
1,000
13.180 w
265 w/m²
Pàgina 24 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
BAR-MENJADOR
CONDICIONS
Ts (°C)
DESTINADA A
Comedores
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
114,4 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
297,4 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana N
Ventana N
Ventana N
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Fachada S
Puerta acceso S
Fachada N
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
LADS02
N
N
N
REF.
Or.
MEXA02
MEXA02
PEMP03
MEXA02
EXCEPTE
PARETS
Ventana N
Ventana N
Ventana N
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Puerta interior 3
Puerta interior 4
Cerramiento interior 2
Puerta interior 5
Puerta interior 6
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
4,5
4,5
4,5
0,89
0,89
0,89
1
1
1
Sup. (m²)
O
S
S
N
REF.
8,8
24,2
1,9
12,8
Sup. (m²)
LADS02
LADS02
LADS02
TAB007
PIMP20
PIMP20
PIMP20
PIMP20
TAB007
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
4,5
4,5
4,5
33,4
1,7
3,8
3,9
2,0
22,6
3,9
7,0
114,4
114,4
Potència
50 Ocupantes
30 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Cabal
Tsa
60,5
47,0
47,0
36,4
K
Tac
2,73
2,73
2,73
2,49
2,13
2,13
2,13
2,13
2,49
2,13
2,13
3,03
0,69
32,2
32,2
32,2
29,4
29,4
29,4
29,4
29,4
25,0
29,4
25,0
25,0
25,0
Ud.
71,0
114,4
2.974,4 m³/h Ventilación
K
0,61
0,61
2,38
0,61
%Ús
50
30
Tec
2.974
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
341
341
341
G. Inst. (w)
14
106
99
13
G. Inst. (w)
88
88
88
366
16
36
37
19
0
37
0
0
0
G. Inst. (w)
3.550
3.432
G. Inst. (w)
7.128
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
234
234
234
736
Càrrega Refr. (w)
20
101
82
14
228
Càrrega Refr. (w)
63
63
63
274
12
27
27
14
0
27
0
0
0
599
Càrrega Refr. (w)
3.550
3.432
7.331
Càrrega Refr. (w)
7.128
7.128
16.023 w
Potència
50 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
91,0
Cabal
2.974,4 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
50
Xec
2.974
100
%Ús
11,4
100
G. Inst. (w)
4.550
G. Inst. (w)
237
Càrrega Refr. (w)
4.550
4.778
Càrrega Refr. (w)
237
237
5.014 w
21.037 w
Factor de calor sensible de la zona (RSHF): 0,651
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 184 w/m²
Pàgina 25 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
BAR-MENJADOR
Ts
DESTINADA A
Comedores
DIMENSIONS
114,4 m² x 2,6 m
REF.
MEXA02
MEXA02
PEMP03
MEXA02
LADS02
LADS02
LADS02
Supl.
Sup. (m²)
1,075
1,000
1,000
1,175
1,175
1,175
1,175
REF.
PEMP03
LADS02
LADS02
LADS02
2.974,4 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
8,8
24,2
1,9
12,8
4,5
4,5
4,5
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
O
S
S
N
N
N
N
Sup. (m²)
S
N
N
N
Pressió
26,7
33,4
33,4
33,4
0,61
0,61
2,38
0,61
4,30
4,30
4,30
K
33,4
1,7
3,8
3,9
2,0
22,6
3,9
7,0
114,4
114,4
Or.
21,0
Diferència
22,8
297,4 m³
TAB007
PIMP20
PIMP20
PIMP20
PIMP20
TAB007
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Puerta acceso S
Ventana N
Ventana N
Ventana N
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Puerta interior 3
Puerta interior 4
Cerramiento interior 2
Puerta interior 5
Puerta interior 6
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Fachada S
Puerta acceso S
Fachada N
Ventana N
Ventana N
Ventana N
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
2,49
2,13
2,13
2,13
2,13
2,49
2,13
2,13
2,44
0,66
Cabal
110,4
14,9
14,9
14,9
Cabal
2.974
Tac
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
Tac
9,3
9,3
9,3
9,3
9,3
21,0
9,3
21,0
4,3
21,0
Tac
-1,8
-1,8
-1,8
-1,8
Tac
-1,8
Càrrega Calef. (w)
131
334
103
208
518
518
518
2.331
Càrrega Calef. (w)
969
42
94
97
50
0
97
0
4.648
0
5.997
Càrrega Calef. (w)
838
113
113
113
1.178
Càrrega Calef. (w)
22.572
22.572
0,0%
0,0%
1,000
32.078 w
280 w/m²
Pàgina 26 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
VESTÍBUL
CONDICIONS
Ts (°C)
DESTINADA A
Vestíbulos
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
44,6 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
116,0 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana N
Ventana N
Ventana N
Ventana N
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Fachada N
Fachada N
Puerta acceso N
Fachada E
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
LADS02
LADS02
N
N
N
N
REF.
Or.
MEXA02
MEXA02
MEXA02
PEAP53
MEXA02
EXCEPTE
PARETS
Ventana N
Ventana N
Ventana N
Ventana N
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Cerramiento interior 2
Puerta interior 3
Puerta interior 4
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
4,6
3,0
1,3
2,4
0,89
0,89
0,89
0,89
1
1
1
1
K
Tsa
0,61
0,61
0,61
4,80
0,61
60,5
36,4
36,4
32,2
36,4
K
Tac
2,73
2,73
2,73
2,73
2,49
2,13
2,13
2,49
2,13
2,13
3,03
0,69
32,2
32,2
32,2
32,2
29,4
29,4
25,0
25,0
25,0
25,0
25,0
25,0
Sup. (m²)
O
N
N
N
E
REF.
11,1
4,3
1,6
5,2
10,9
Sup. (m²)
LADS02
LADS02
LADS02
LADS02
TAB007
PIMP20
PIMP20
TAB007
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
4,6
3,0
1,3
2,4
41,9
3,9
1,9
13,4
2,0
1,9
44,6
44,6
Potència
6 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
89,0
44,6
Cabal
1.739,4 m³/h Ventilación
%Ús
6
15
Tec
1.739
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
348
227
98
182
G. Inst. (w)
18
4
2
180
74
G. Inst. (w)
90
59
26
47
459
37
0
0
0
0
0
0
G. Inst. (w)
534
669
G. Inst. (w)
4.168
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
239
156
67
125
616
Càrrega Refr. (w)
25
5
2
128
64
236
Càrrega Refr. (w)
65
42
18
34
343
27
0
0
0
0
0
0
556
Càrrega Refr. (w)
534
669
1.263
Càrrega Refr. (w)
4.168
4.168
6.840 w
Potència
6 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
121,0
Cabal
1.739,4 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
6
Xec
1.739
100
%Ús
11,4
100
G. Inst. (w)
726
G. Inst. (w)
138
Càrrega Refr. (w)
726
762
Càrrega Refr. (w)
138
138
901 w
7.740 w
Factor de calor sensible de la zona (RSHF): 0,778
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 174 w/m²
Pàgina 27 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
VESTÍBUL
Ts
DESTINADA A
Vestíbulos
DIMENSIONS
44,6 m² x 2,6 m
REF.
MEXA02
MEXA02
LADS02
MEXA02
PEAP53
LADS02
LADS02
LADS02
MEXA02
Supl.
Sup. (m²)
1,075
1,175
1,175
1,175
1,175
1,175
1,175
1,175
1,125
REF.
LADS02
PEAP53
LADS02
LADS02
LADS02
1.739,4 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
11,1
4,3
4,6
1,6
5,2
3,0
1,3
2,4
10,9
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
O
N
N
N
N
N
N
N
E
Sup. (m²)
N
N
N
N
N
Pressió
33,4
33,4
33,4
33,4
33,4
0,61
0,61
4,30
0,61
4,80
4,30
4,30
4,30
0,61
K
41,9
3,9
1,9
13,4
2,0
1,9
44,6
44,6
Or.
21,0
Diferència
22,8
116,0 m³
TAB007
PIMP20
PIMP20
TAB007
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana N
Puerta acceso N
Ventana N
Ventana N
Ventana N
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Cerramiento interior 2
Puerta interior 3
Puerta interior 4
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Fachada N
Ventana N
Fachada N
Puerta acceso N
Ventana N
Ventana N
Ventana N
Fachada E
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
2,49
2,13
2,13
2,49
2,13
2,13
2,44
0,66
Cabal
15,3
350,6
10,0
4,3
8,0
Cabal
1.739
Tac
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
Tac
9,3
9,3
21,0
21,0
21,0
21,0
4,3
21,0
Tac
-1,8
-1,8
-1,8
-1,8
-1,8
Tac
-1,8
Càrrega Calef. (w)
165
70
530
26
669
346
150
276
169
2.400
Càrrega Calef. (w)
1.216
97
0
0
0
0
1.812
0
3.125
Càrrega Calef. (w)
116
2.660
76
33
60
2.945
Càrrega Calef. (w)
13.200
13.200
0,0%
0,0%
1,000
21.670 w
486 w/m²
Pàgina 28 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
SALA ESPERA1
CONDICIONS
Ts (°C)
DESTINADA A
Espera y recepción (salas)
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
29,1 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
75,7 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
Fachada E
Fachada S
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
S
REF.
Or.
MEXA02
MEXA02
MEXA02
EXCEPTE
PARETS
Ventana S
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Puerta interior 3
Puerta interior 4
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
1,5
0,89
1
K
Tsa
0,61
0,61
0,61
47,0
36,4
47,0
K
Tac
2,73
2,49
2,13
2,13
2,13
2,13
3,03
0,69
32,2
25,0
25,0
29,4
25,0
25,0
25,0
25,0
Sup. (m²)
S
E
S
REF.
12,9
1,8
0,9
Sup. (m²)
LADS02
TAB007
PIMP20
PIMP20
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
1,5
32,5
1,9
2,0
2,0
1,9
29,1
29,1
Potència
8 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
71,0
29,1
Cabal
418,0 m³/h Ventilación
%Ús
8
15
Tec
418
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
344
G. Inst. (w)
57
12
4
G. Inst. (w)
29
0
0
19
0
0
0
0
G. Inst. (w)
568
437
G. Inst. (w)
1.002
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
254
267
Càrrega Refr. (w)
54
11
4
72
Càrrega Refr. (w)
21
0
0
14
0
0
0
0
37
Càrrega Refr. (w)
568
436
1.055
Càrrega Refr. (w)
1.002
1.002
2.432 w
Potència
8 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
31,0
Cabal
418,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
8
Xec
418
100
%Ús
11,4
100
G. Inst. (w)
248
G. Inst. (w)
33
Càrrega Refr. (w)
248
260
Càrrega Refr. (w)
33
33
294 w
2.725 w
Factor de calor sensible de la zona (RSHF): 0,846
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 94 w/m²
Pàgina 29 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
SALA ESPERA1
Ts
DESTINADA A
Espera y recepción (salas)
DIMENSIONS
29,1 m² x 2,6 m
REF.
MEXA02
LADS02
MEXA02
MEXA02
Supl.
Sup. (m²)
1,000
1,000
1,125
1,000
REF.
LADS02
418,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
12,9
1,5
1,8
0,9
Sup. (m²)
TAB007
PIMP20
PIMP20
PIMP20
PIMP20
SOLE01
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
E
S
S
Pressió
Tac
0,61
4,30
0,61
0,61
K
32,5
1,9
2,0
2,0
1,9
29,1
29,1
Or.
21,0
Diferència
22,8
75,7 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Puerta interior 3
Puerta interior 4
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Fachada E
Fachada S
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
2,49
2,13
2,13
2,13
2,13
2,44
0,66
Cabal
26,7
-1,8
-1,8
-1,8
-1,8
21,0
21,0
9,3
21,0
21,0
4,3
21,0
Tac
4,3
Cabal
-1,8
Tac
418
-1,8
Càrrega Calef. (w)
178
147
28
12
366
Càrrega Calef. (w)
0
0
50
0
0
1.182
0
1.232
Càrrega Calef. (w)
33
33
Càrrega Calef. (w)
3.172
3.172
0,0%
0,0%
1,000
4.803 w
165 w/m²
Pàgina 30 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
SERVEI SOCIAL
CONDICIONS
Ts (°C)
DESTINADA A
Oficinas
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
15,8 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
41,1 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana N
Ventana N
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Fachada N
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
N
N
REF.
Or.
MEXA02
MEXA02
EXCEPTE
PARETS
Ventana N
Ventana N
Cerramiento interior 1
Puerta interior 1
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
1,3
1,4
0,89
0,89
1
1
Sup. (m²)
O
N
REF.
7,9
8,3
Sup. (m²)
LADS02
LADS02
TAB007
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
1,3
1,4
21,2
1,9
15,8
15,8
Potència
3 Ocupantes
30 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
K
Tsa
0,61
0,61
60,5
36,4
K
Tac
2,73
2,73
2,49
2,13
3,03
0,69
32,2
32,2
25,0
25,0
25,0
25,0
Ud.
78,0
15,8
Cabal
%Ús
3
30
Tec
82,2 m³/h Ventilación
82
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
98
106
G. Inst. (w)
13
8
G. Inst. (w)
26
28
0
0
0
0
G. Inst. (w)
234
474
G. Inst. (w)
197
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
67
73
147
Càrrega Refr. (w)
18
9
29
Càrrega Refr. (w)
18
20
0
0
0
0
40
Càrrega Refr. (w)
234
474
743
Càrrega Refr. (w)
197
197
1.156 w
Potència
3 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
46,0
Cabal
82,2 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
3
Xec
82
100
%Ús
11,4
100
G. Inst. (w)
138
G. Inst. (w)
7
Càrrega Refr. (w)
138
145
Càrrega Refr. (w)
7
7
151 w
1.308 w
Factor de calor sensible de la zona (RSHF): 0,869
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 83 w/m²
Pàgina 31 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
SERVEI SOCIAL
Ts
DESTINADA A
Oficinas
DIMENSIONS
15,8 m² x 2,6 m
REF.
MEXA02
MEXA02
LADS02
LADS02
Supl.
Sup. (m²)
1,075
1,175
1,175
1,175
REF.
LADS02
LADS02
82,2 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
7,9
8,3
1,3
1,4
Sup. (m²)
TAB007
PIMP20
SOLE01
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
O
N
N
N
N
N
Pressió
Tac
0,61
0,61
4,30
4,30
K
21,2
1,9
15,8
15,8
Or.
21,0
Diferència
22,8
41,1 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana N
Ventana N
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Fachada N
Ventana N
Ventana N
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
2,49
2,13
2,44
0,66
Cabal
33,4
33,4
-1,8
-1,8
-1,8
-1,8
21,0
21,0
4,3
21,0
Tac
4,3
4,6
Cabal
-1,8
-1,8
Tac
82
-1,8
Càrrega Calef. (w)
117
135
150
161
563
Càrrega Calef. (w)
0
0
642
0
642
Càrrega Calef. (w)
33
35
68
Càrrega Calef. (w)
624
624
0,0%
0,0%
1,000
1.897 w
120 w/m²
Pàgina 32 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
PODÒLEG
CONDICIONS
Ts (°C)
DESTINADA A
Salas de recuperación
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
18,9 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
49,1 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana N
TRANSMISSIÓ PARETS I SOSTRE
Fachada N
Fachada O
Fachada N
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
N
REF.
Or.
MEXA02
MEXA02
MEXA02
EXCEPTE
PARETS
Ventana N
Cerramiento interior 1
Cerramiento interior 2
Puerta interior 1
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,7
0,89
1
K
Tsa
0,61
0,61
0,61
36,4
60,5
36,4
K
Tac
2,73
1,98
1,98
2,13
3,03
0,69
32,2
29,4
25,0
25,0
25,0
25,0
Sup. (m²)
N
O
N
REF.
2,6
1,8
6,2
Sup. (m²)
LADS02
TAB008
TAB008
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
2,7
17,2
13,9
2,0
18,9
18,9
Potència
3 Ocupantes
20 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
109,0
18,9
Cabal
108,0 m³/h Ventilación
%Ús
3
20
Tec
108
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
205
G. Inst. (w)
3
3
6
G. Inst. (w)
53
150
0
0
0
0
G. Inst. (w)
327
378
G. Inst. (w)
259
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
140
147
Càrrega Refr. (w)
3
4
7
15
Càrrega Refr. (w)
38
112
0
0
0
0
158
Càrrega Refr. (w)
327
378
740
Càrrega Refr. (w)
259
259
1.319 w
Potència
3 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
248,0
Cabal
108,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
3
Xec
108
100
%Ús
11,4
100
G. Inst. (w)
744
G. Inst. (w)
9
Càrrega Refr. (w)
744
781
Càrrega Refr. (w)
9
9
790 w
2.109 w
Factor de calor sensible de la zona (RSHF): 0,576
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 112 w/m²
Pàgina 33 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
PODÒLEG
Ts
DESTINADA A
Salas de recuperación
DIMENSIONS
18,9 m² x 2,6 m
REF.
MEXA02
MEXA02
MEXA02
LADS02
Supl.
Sup. (m²)
1,175
1,075
1,175
1,175
REF.
LADS02
108,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
2,6
1,8
6,2
2,7
Sup. (m²)
TAB008
TAB008
PIMP20
SOLE01
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
N
O
N
N
N
Pressió
Tac
0,61
0,61
0,61
4,30
K
17,2
13,9
2,0
18,9
18,9
Or.
21,0
Diferència
22,8
49,1 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana N
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Cerramiento interior 2
Puerta interior 1
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada N
Fachada O
Fachada N
Ventana N
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
1,98
2,13
2,44
0,66
Cabal
33,4
-1,8
-1,8
-1,8
-1,8
9,3
21,0
21,0
4,3
21,0
Tac
9,0
Cabal
-1,8
Tac
108
-1,8
Càrrega Calef. (w)
42
27
101
311
481
Càrrega Calef. (w)
398
0
0
768
0
1.166
Càrrega Calef. (w)
68
68
Càrrega Calef. (w)
820
820
0,0%
0,0%
1,000
2.534 w
134 w/m²
Pàgina 34 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
BANY HOMES
CONDICIONS
Ts (°C)
Th (°C)
DESTINADA A
Aseos públicos
vertedero,...)
32,2
21,3
DIMENSIONS
14,5 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
37,7 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
(por
urinario,
GUANY SOLAR VIDRE
Ventana E
Ventana E
Ventana E
TRANSMISSIÓ PARETS I SOSTRE
Fachada E
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
inodoro, Exteriors
REF.
Or.
LADS02
LADS02
LADS02
E
E
E
REF.
Or.
MEXA02
EXCEPTE
PARETS
Ventana E
Ventana E
Ventana E
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
1,9
1,9
2,0
0,89
0,89
0,89
1
1
1
K
Tsa
0,61
36,4
K
Tac
2,73
2,73
2,73
1,98
2,13
2,13
3,03
0,69
32,2
32,2
32,2
25,0
29,4
25,0
25,0
25,0
Sup. (m²)
E
REF.
7,9
Sup. (m²)
LADS02
LADS02
LADS02
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
1,9
1,9
2,0
29,5
1,9
2,0
14,5
14,5
Potència
3 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
89,0
14,5
Cabal
270,0 m³/h Ventilación
%Ús
3
15
Tec
270
100
100
%Ús
32,2
100
G. Inst. (w)
144
144
151
G. Inst. (w)
53
G. Inst. (w)
37
37
39
0
18
0
0
0
G. Inst. (w)
267
218
G. Inst. (w)
647
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Xe (gr/kgr)
11,4
Càrrega Refr. (w)
269
269
283
861
Càrrega Refr. (w)
47
49
Càrrega Refr. (w)
27
27
28
0
13
0
0
0
100
Càrrega Refr. (w)
267
217
509
Càrrega Refr. (w)
647
647
2.166 w
Potència
3 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Hr (%)
37,8
Ud.
121,0
Cabal
270,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
3
Xec
270
100
%Ús
11,4
100
G. Inst. (w)
363
G. Inst. (w)
21
Càrrega Refr. (w)
363
381
Càrrega Refr. (w)
21
21
403 w
2.568 w
Factor de calor sensible de la zona (RSHF): 0,799
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 177 w/m²
Pàgina 35 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
BANY HOMES
Ts
DESTINADA A
Aseos públicos (por urinario, inodoro,
vertedero,...)
DIMENSIONS
14,5 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
LADS02
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
E
E
E
E
REF.
LADS02
LADS02
LADS02
Supl.
Sup. (m²)
1,125
1,125
1,125
1,125
270,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
7,9
1,9
1,9
2,0
Sup. (m²)
E
E
E
Pressió
Tac
0,61
4,30
4,30
4,30
K
29,5
1,9
2,0
14,5
14,5
Or.
21,0
Diferència
22,8
37,7 m³
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
Or.
Interior
-1,8
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana E
Ventana E
Ventana E
Exterior
(°C)
VOLUM
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Ventana E
Ventana E
Ventana E
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
2,13
2,44
0,66
Cabal
26,7
26,7
26,7
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
4,3
21,0
Tac
5,4
5,4
5,7
Cabal
-1,8
-1,8
-1,8
Tac
270
-1,8
Càrrega Calef. (w)
123
210
210
221
763
Càrrega Calef. (w)
0
47
0
589
0
636
Càrrega Calef. (w)
41
41
43
126
Càrrega Calef. (w)
2.049
2.049
0,0%
0,0%
1,000
3.574 w
246 w/m²
Pàgina 36 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
BANY DONES
CONDICIONS
Ts (°C)
Th (°C)
DESTINADA A
Aseos públicos
vertedero,...)
32,2
21,3
DIMENSIONS
16,4 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
42,6 m³
Diferències
7,2
2,3
-19,1
0,1
TRANSMISSIÓ
SOSTRE
EXCEPTE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
(Máximas por Sistema)
(por
PARETS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Cerramiento interior 2
Solera 1
Forjado interior 1
urinario,
I
inodoro, Exteriors
REF.
Sup. (m²)
TAB008
PIMP20
PIMP20
TAB008
SOLE01
FOREX1
CALOR SENSIBLE INTERN
25,2
2,0
1,9
18,4
16,4
16,4
Potència
3 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Cabal
Tac
1,98
2,13
2,13
1,98
3,03
0,69
29,4
25,0
29,4
25,0
25,0
25,0
Ud.
89,0
16,4
180,0 m³/h Ventilación
K
%Ús
3
15
Tec
180
100
100
%Ús
32,2
100
G. Inst. (w)
220
0
18
0
0
0
G. Inst. (w)
267
246
G. Inst. (w)
431
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Xe (gr/kgr)
11,4
Càrrega Refr. (w)
165
0
13
0
0
0
187
Càrrega Refr. (w)
267
246
539
Càrrega Refr. (w)
431
431
1.157 w
Potència
3 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Hr (%)
37,8
Ud.
121,0
Cabal
180,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
3
Xec
180
100
%Ús
11,4
100
G. Inst. (w)
363
G. Inst. (w)
14
Càrrega Refr. (w)
363
381
Càrrega Refr. (w)
14
14
395 w
1.552 w
Factor de calor sensible de la zona (RSHF): 0,656
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 95 w/m²
Pàgina 37 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
BANY DONES
Ts
DESTINADA A
Aseos públicos (por urinario, inodoro,
vertedero,...)
DIMENSIONS
16,4 m² x 2,6 m
REF.
TAB008
PIMP20
PIMP20
TAB008
SOLE01
FOREX1
VENTILACIÓ AIRE EXTERIOR
180,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
Càrrega de calefacció per unitat de superfície:
Exterior
(°C)
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Cerramiento interior 2
Solera 1
Forjado interior 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Interior
-1,8
21,0
Diferència
22,8
42,6 m³
Sup. (m²)
K
25,2
2,0
1,9
18,4
16,4
16,4
1,98
2,13
2,13
1,98
2,44
0,66
Cabal
Tac
9,3
21,0
9,3
21,0
4,3
21,0
Tac
180
-1,8
Càrrega Calef. (w)
583
0
47
0
666
0
1.297
Càrrega Calef. (w)
1.366
1.366
0,0%
0,0%
1,000
2.663 w
162 w/m²
Pàgina 38 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
SALA D'ESPERA2
CONDICIONS
Ts (°C)
DESTINADA A
Espera y recepción (salas)
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
42,5 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
110,5 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana O
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Puerta acceso O
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
O
REF.
Or.
MEXA02
PEAP53
EXCEPTE
PARETS
Ventana O
Cerramiento interior 1
Puerta interior 6
Puerta interior 7
Cerramiento interior 2
Puerta interior 1
Puerta interior 2
Puerta interior 3
Puerta interior 4
Puerta interior 5
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
5,4
0,89
1
K
Tsa
0,61
4,80
60,5
70,0
K
Tac
2,73
1,98
2,13
2,13
1,98
2,13
2,13
2,13
2,13
2,13
3,03
0,69
32,2
29,4
29,4
29,4
25,0
29,4
25,0
25,0
25,0
25,0
25,0
25,0
Sup. (m²)
O
O
REF.
14,9
3,8
Sup. (m²)
LADS02
TAB008
PIMP20
PIMP20
TAB008
PIMP20
PIMP20
PIMP20
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
5,4
12,4
2,0
2,0
30,4
2,0
1,9
2,0
1,9
1,9
42,5
42,5
Potència
14 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
71,0
42,5
Cabal
612,0 m³/h Ventilación
%Ús
14
15
Tec
612
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
2.869
G. Inst. (w)
24
821
G. Inst. (w)
106
108
19
19
0
19
0
0
0
0
0
0
G. Inst. (w)
994
638
G. Inst. (w)
1.467
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
1.058
1.111
Càrrega Refr. (w)
34
613
679
Càrrega Refr. (w)
76
81
14
14
0
14
0
0
0
0
0
0
209
Càrrega Refr. (w)
994
637
1.713
Càrrega Refr. (w)
1.467
1.467
5.179 w
Potència
14 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
31,0
Cabal
612,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
14
Xec
612
100
%Ús
11,4
100
G. Inst. (w)
434
G. Inst. (w)
49
Càrrega Refr. (w)
434
456
Càrrega Refr. (w)
49
49
504 w
5.683 w
Factor de calor sensible de la zona (RSHF): 0,891
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 134 w/m²
Pàgina 39 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
SALA D'ESPERA2
Ts
DESTINADA A
Espera y recepción (salas)
DIMENSIONS
42,5 m² x 2,6 m
REF.
MEXA02
PEAP53
LADS02
Supl.
Sup. (m²)
1,075
1,075
1,075
REF.
PEAP53
LADS02
612,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
14,9
3,8
5,4
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
O
O
O
Sup. (m²)
O
O
Pressió
33,4
33,4
0,61
4,80
4,30
K
12,4
2,0
2,0
30,4
2,0
1,9
2,0
1,9
1,9
42,5
42,5
Or.
21,0
Diferència
22,8
110,5 m³
TAB008
PIMP20
PIMP20
TAB008
PIMP20
PIMP20
PIMP20
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Puerta acceso O
Ventana O
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 6
Puerta interior 7
Cerramiento interior 2
Puerta interior 1
Puerta interior 2
Puerta interior 3
Puerta interior 4
Puerta interior 5
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Puerta acceso O
Ventana O
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
1,98
2,13
2,13
1,98
2,13
2,13
2,13
2,13
2,13
2,44
0,66
Cabal
Tac
-1,8
-1,8
-1,8
Tac
9,3
9,3
9,3
21,0
9,3
21,0
21,0
21,0
21,0
4,3
21,0
Tac
256,2
17,9
Cabal
-1,8
-1,8
Tac
612
-1,8
Càrrega Calef. (w)
221
447
569
1.237
Càrrega Calef. (w)
287
50
50
0
50
0
0
0
0
1.727
0
2.163
Càrrega Calef. (w)
1.944
136
2.080
Càrrega Calef. (w)
4.644
4.644
0,0%
0,0%
1,000
10.125 w
238 w/m²
Pàgina 40 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
CONSULTA METGE1
CONDICIONS
Ts (°C)
DESTINADA A
Salas de curas
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
22,5 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
58,5 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana E
TRANSMISSIÓ PARETS I SOSTRE
Fachada E
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
E
REF.
Or.
MEXA02
EXCEPTE
PARETS
Ventana E
Cerramiento interior 1
Cerramiento interior 2
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
1,4
0,89
1
K
Tsa
0,61
36,4
K
Tac
2,73
1,98
1,98
2,13
2,13
3,03
0,69
32,2
29,4
25,0
25,0
25,0
25,0
25,0
Sup. (m²)
E
REF.
7,5
Sup. (m²)
LADS02
TAB008
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
1,4
17,8
22,6
2,0
2,0
22,5
22,5
Potència
4 Ocupantes
30 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
72,0
22,5
Cabal
180,0 m³/h Ventilación
%Ús
4
30
Tec
180
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
106
G. Inst. (w)
51
G. Inst. (w)
28
155
0
0
0
0
0
G. Inst. (w)
288
675
G. Inst. (w)
431
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
198
208
Càrrega Refr. (w)
44
46
Càrrega Refr. (w)
20
116
0
0
0
0
0
143
Càrrega Refr. (w)
288
675
1.011
Càrrega Refr. (w)
431
431
1.840 w
Potència
4 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
148,0
Cabal
180,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
4
Xec
180
100
%Ús
11,4
100
G. Inst. (w)
592
G. Inst. (w)
14
Càrrega Refr. (w)
592
622
Càrrega Refr. (w)
14
14
636 w
2.476 w
Factor de calor sensible de la zona (RSHF): 0,694
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 110 w/m²
Pàgina 41 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
CONSULTA METGE1
Ts
DESTINADA A
Salas de curas
DIMENSIONS
22,5 m² x 2,6 m
REF.
MEXA02
LADS02
Supl.
Sup. (m²)
1,125
1,125
REF.
LADS02
180,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
7,5
1,4
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
E
E
Sup. (m²)
E
Pressió
Tac
0,61
4,30
K
17,8
22,6
2,0
2,0
22,5
22,5
Or.
21,0
Diferència
22,8
58,5 m³
TAB008
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana E
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Cerramiento interior 2
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Ventana E
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
1,98
2,13
2,13
2,44
0,66
Cabal
26,7
-1,8
-1,8
9,3
21,0
21,0
21,0
4,3
21,0
Tac
4,0
Cabal
-1,8
Tac
180
-1,8
Càrrega Calef. (w)
117
154
271
Càrrega Calef. (w)
412
0
0
0
914
0
1.326
Càrrega Calef. (w)
30
30
Càrrega Calef. (w)
1.366
1.366
0,0%
0,0%
1,000
2.993 w
133 w/m²
Pàgina 42 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
CURES
CONDICIONS
Ts (°C)
DESTINADA A
Salas de curas
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
15,0 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
39,0 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
TRANSMISSIÓ PARETS I SOSTRE
REF.
Fachada E
Puerta acceso E
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
Or.
MEXA02
PEMP01
EXCEPTE
PARETS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
I
Sup. (m²)
E
E
REF.
5,1
2,2
Sup. (m²)
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
30,9
2,0
1,9
15,0
15,0
Potència
3 Ocupantes
40 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
130,0 m³/h Ventilación
Tsa
36,4
37,8
K
Tac
1,98
2,13
2,13
3,03
0,69
25,0
25,0
25,0
25,0
25,0
Ud.
72,0
15,0
Cabal
K
0,61
2,38
%Ús
3
40
Tec
130
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
34
67
G. Inst. (w)
30
66
101
Càrrega Refr. (w)
G. Inst. (w)
216
600
G. Inst. (w)
312
0
0
0
0
0
0
Càrrega Refr. (w)
216
600
857
Càrrega Refr. (w)
312
312
1.269 w
Potència
3 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Càrrega Refr. (w)
0
0
0
0
0
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Xe (gr/kgr)
11,4
Ud.
148,0
Cabal
130,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
3
Xec
130
100
%Ús
11,4
100
G. Inst. (w)
444
G. Inst. (w)
10
Càrrega Refr. (w)
444
466
Càrrega Refr. (w)
10
10
477 w
1.746 w
Factor de calor sensible de la zona (RSHF): 0,673
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 116 w/m²
Pàgina 43 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
CURES
Ts
DESTINADA A
Salas de curas
DIMENSIONS
15,0 m² x 2,6 m
REF.
MEXA02
PEMP01
Supl.
Sup. (m²)
1,125
1,125
REF.
PEMP01
130,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
5,1
2,2
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
E
E
Sup. (m²)
E
Pressió
26,7
0,61
2,38
K
30,9
2,0
1,9
15,0
15,0
Or.
21,0
Diferència
22,8
39,0 m³
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Puerta acceso E
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Puerta acceso E
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
1,98
2,13
2,13
2,44
0,66
Cabal
Tac
-1,8
-1,8
Tac
21,0
21,0
21,0
4,3
21,0
Tac
127,8
Cabal
-1,8
Tac
130
-1,8
Càrrega Calef. (w)
79
134
214
Càrrega Calef. (w)
0
0
0
610
0
610
Càrrega Calef. (w)
970
970
Càrrega Calef. (w)
987
987
0,0%
0,0%
1,000
2.780 w
185 w/m²
Pàgina 44 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
INFERMERIA
CONDICIONS
Ts (°C)
DESTINADA A
Salas de curas
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
16,6 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
43,2 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana E
TRANSMISSIÓ PARETS I SOSTRE
Fachada E
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
E
REF.
Or.
MEXA02
EXCEPTE
PARETS
Ventana E
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
1,4
0,89
1
K
Tsa
0,61
36,4
K
Tac
2,73
1,98
2,13
2,13
3,03
0,69
32,2
25,0
25,0
25,0
25,0
25,0
Sup. (m²)
E
REF.
6,5
Sup. (m²)
LADS02
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
CALOR SENSIBLE INTERN
1,4
31,3
2,0
2,0
16,6
16,6
Potència
3 Ocupantes
40 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
72,0
16,6
Cabal
130,0 m³/h Ventilación
%Ús
3
40
Tec
130
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
106
G. Inst. (w)
44
G. Inst. (w)
28
0
0
0
0
0
G. Inst. (w)
216
664
G. Inst. (w)
312
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
198
208
Càrrega Refr. (w)
38
40
Càrrega Refr. (w)
20
0
0
0
0
0
21
Càrrega Refr. (w)
216
664
924
Càrrega Refr. (w)
312
312
1.504 w
Potència
3 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
148,0
Cabal
130,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
3
Xec
130
100
%Ús
11,4
100
G. Inst. (w)
444
G. Inst. (w)
10
Càrrega Refr. (w)
444
466
Càrrega Refr. (w)
10
10
477 w
1.981 w
Factor de calor sensible de la zona (RSHF): 0,719
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 119 w/m²
Pàgina 45 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
INFERMERIA
Ts
DESTINADA A
Salas de curas
DIMENSIONS
16,6 m² x 2,6 m
REF.
MEXA02
LADS02
Supl.
Sup. (m²)
1,125
1,125
REF.
LADS02
130,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
6,5
1,4
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
E
E
Sup. (m²)
E
Pressió
Tac
0,61
4,30
K
31,3
2,0
2,0
16,6
16,6
Or.
21,0
Diferència
22,8
43,2 m³
TAB008
PIMP20
PIMP20
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana E
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Ventana E
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
2,13
2,44
0,66
Cabal
26,7
-1,8
-1,8
21,0
21,0
21,0
4,3
21,0
Tac
4,0
Cabal
-1,8
Tac
130
-1,8
Càrrega Calef. (w)
101
154
255
Càrrega Calef. (w)
0
0
0
675
0
675
Càrrega Calef. (w)
30
30
Càrrega Calef. (w)
987
987
0,0%
0,0%
1,000
1.947 w
117 w/m²
Pàgina 46 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
DATA CÀLCUL
15 Hora solar Agosto
ZONA
CONSULTA METGE2
CONDICIONS
Ts (°C)
DESTINADA A
Salas de curas
Exteriors
32,2
21,3
Hr (%)
37,8
DIMENSIONS
20,0 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
52,0 m³
Diferències
7,2
2,3
-19,1
0,1
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana E
TRANSMISSIÓ PARETS I SOSTRE
Fachada E
Fachada S
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
E
REF.
Or.
MEXA02
MEXA02
EXCEPTE
PARETS
Ventana E
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Cerramiento interior 2
Solera 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
1,6
0,89
1
K
Tsa
0,61
0,61
36,4
47,0
K
Tac
2,73
1,98
2,13
2,13
1,98
3,03
0,69
32,2
25,0
25,0
25,0
29,4
25,0
25,0
Sup. (m²)
E
S
REF.
9,0
12,8
Sup. (m²)
LADS02
TAB008
PIMP20
PIMP20
TAB008
SOLE01
FOREX1
CALOR SENSIBLE INTERN
1,6
13,1
2,0
2,0
8,3
20,0
20,0
Potència
4 Ocupantes
30 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
72,0
20,0
Cabal
180,0 m³/h Ventilación
%Ús
4
30
Tec
180
100
100
%Ús
32,2
100
Th (°C)
G. Inst. (w)
121
G. Inst. (w)
61
56
G. Inst. (w)
31
0
0
0
72
0
0
G. Inst. (w)
288
600
G. Inst. (w)
431
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
226
238
Càrrega Refr. (w)
53
53
112
Càrrega Refr. (w)
22
0
0
0
54
0
0
81
Càrrega Refr. (w)
288
600
932
Càrrega Refr. (w)
431
431
1.794 w
Potència
4 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,4
Ud.
148,0
Cabal
180,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
4
Xec
180
100
%Ús
11,4
100
G. Inst. (w)
592
G. Inst. (w)
14
Càrrega Refr. (w)
592
622
Càrrega Refr. (w)
14
14
636 w
2.430 w
Factor de calor sensible de la zona (RSHF): 0,687
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 121 w/m²
Pàgina 47 de 72
EXPEDIENT
13
PROJECTE
CENTRE CIVIC BELL-LLOC PB
DATA
22/01/08
SISTEMA
PLANTA BAIXA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
CONSULTA METGE2
Ts
DESTINADA A
Salas de curas
DIMENSIONS
20,0 m² x 2,6 m
REF.
MEXA02
LADS02
MEXA02
Supl.
Sup. (m²)
1,125
1,125
1,000
REF.
LADS02
180,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
9,0
1,6
12,8
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
E
E
S
Sup. (m²)
E
Pressió
Tac
0,61
4,30
0,61
K
13,1
2,0
2,0
8,3
20,0
20,0
Or.
21,0
Diferència
22,8
52,0 m³
TAB008
PIMP20
PIMP20
TAB008
SOLE01
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana E
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Cerramiento interior 2
Solera 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Ventana E
Fachada S
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
2,13
1,98
2,44
0,66
Cabal
26,7
-1,8
-1,8
-1,8
21,0
21,0
21,0
9,3
4,3
21,0
Tac
4,6
Cabal
-1,8
Tac
180
-1,8
Càrrega Calef. (w)
140
176
177
493
Càrrega Calef. (w)
0
0
0
192
813
0
1.005
Càrrega Calef. (w)
35
35
Càrrega Calef. (w)
1.366
1.366
0,0%
0,0%
1,000
2.899 w
145 w/m²
Pàgina 48 de 72
FULL DE CÀRREGUES PER A REFRIGERACIÓ DEL SISTEMA
PROJECTE:
SISTEMA:
CENTRE CIVIC BELL-LLOC
PLANTA PRIMERA
CONDICIONS DE DISSENY: Estimat per a les 14 hora solar del mes de Agosto.
T.seca
31,6 °C
Exterior:
T.hum.
21,3 °C
H.rel.
40,0 %
H.esp.
11,6 gr/kg
GUANYS DE CALOR:
Ts
(°C)
Th
(°C)
Àrea
(m²)
Vol.
(m³)
NOVES TECNOLOGIES
25,0 19,0 38,8
100,9
LOCAL4
25,0 19,0 26,2
68,1
LOCAL3
25,0 19,0 26,1
67,9
LOCAL2
25,0 19,0 24,9
64,7
LOCAL1
25,0 19,0 25,7
66,8
RECEPCIÓ
25,0 19,0 25,8
67,1
DESPATX SALA D’ACTES
25,0 19,0 8,6
22,4
VESTÍBUL
25,0 19,0 44,5
115,7
BANY DONES
25,0 19,0 25,3
65,8
BANY HOMES
25,0 19,0 21,1
54,9
SALA D’ACTES
25,0 19,0 171,1 513,3
Gsc
(W)
Tpt
(W)
Tept
(W)
Cis
(W)
Aes
(W)
Cil
(W)
Ael
(W)
RSHF C.refr.
(W)
1.162
250
135
2.247
949
725
122
0,840
5.591
897
140
76
2.326
1.265
966
163
0,781
5.832
916
138
77
2.323
1.265
966
163
0,781
5.848
916
132
78
2.292
1.265
966
163
0,780
5.812
916
136
78
2.313
1.265
966
163
0,781
5.836
916
137
78
1.301
816
391
105
0,862
3.744
0
39
58
435
158
97
20
0,846
806
646
293
306
1.448
2.033
1.016
262
0,726
6.006
925
183
80
772
791
508
102
0,794
3.361
0
95
0
706
791
508
102
0,612
2.201
3.477
1.178
275
11.043 5.638
3.864
726
0,805
26.201
1.241
27.206 16.238 10.973 2.090
0,793
71.239
CÀRREGA DE REFRIGERACIÓ TOTAL
438,1 1.207,5 10.771 2.721
Factor de seguretat: 5%
Cabal total d'aire exterior: 7.392 m³/h
Càrrega de refrigeració per unitat de superfície: 163 w/m²
Ts: T emperatura seca interior (°C).
Th: Temperatura humida interior (°C).
Vol.: Volum de la zona.
Gsc: Guany solar vidre.
Tpt: Transmissió parets i sostre.
Tept: Transmissió excepte parets i sostre.
Cis:
Calor intern sensible.
Aes:
Aire exterior sensible.
Cil:
Calor intern latent.
Ael:
Aire exterior latent.
RSHF: Factor de calor sensible de la zona.
C.Refr.: Càrregues de refrigeració.
Pàgina 49 de 72
FULL DE CÀRREGUES PER A CALEFACCIÓ DEL SISTEMA
PROJECTE:
SISTEMA:
CENTRE CIVIC BELL-LLOC
PLANTA PRIMERA
CONDICIONS DE DISSENY:
Temperatura exterior:
Dies grau acumulats:
Orientació del vent dominant:
Velocitat del vent dominant:
-1,8 °C
1163
NO
7,4 m/s
PÈRDUES DE CALOR:
ZONES
NOVES TECNOLOGIES
LOCAL4
LOCAL3
LOCAL2
LOCAL1
RECEPCIÓ
DESPATX SALA D’ACTES
VESTÍBUL
BANY DONES
BANY HOMES
SALA D’ACTES
Tsi
(°C)
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
21,0
CÀRREGA DE CALEFACCIÓ TOTAL
Àrea
(m²)
38,8
26,2
26,1
24,9
25,7
25,8
8,6
44,5
25,3
21,1
171,1
Vol.
(m³)
100,9
68,1
67,9
64,7
66,8
67,1
22,4
115,7
65,8
54,9
513,3
Tae
(W)
1.947
808
812
798
806
811
84
2.298
1.100
206
5.224
Tol
(W)
47
52
52
57
55
55
223
587
0
0
94
438,1
1.207,5 14.895 1.222
Ipv
(W)
218
102
104
104
104
104
0
297
130
0
428
Vae
(W)
3.278
4.371
4.371
4.371
4.371
2.819
546
7.024
2.732
2.732
19.477
C.calef.
(W)
5.490
5.334
5.339
5.331
5.336
3.790
854
10.206
3.963
2.938
25.223
1.592
56.094 73.802
Factor de seguretat: 0,0%
Cabal total d'aire exterior: 7.392 m³/h
Càrrega de calefacció per unitat de superfície: 168 w/m²
Tsi: Temperatura seca interior (°C).
Vol.: Volum de la zona.
Tae: Transmissió ambient exterior.
Tol: Transmissió altres locals.
Ipv:
Infiltracions portes i finestres.
Vae:
Ventilació aire exterior.
C.calef.: Càrregues de calefacció.
ABREVIATURES I UNITATS:
Or.: Orientació del tancament exterior
SQ: Coeficient d'ombrejat (adimensional)
K: Coeficient de transmissió (W/m²·°C)
Tsa: Temperatura Sol-Aire (°C)
Tec: Temperatura exterior corregida (°C)
Tac: Temperatura ambient contigu (°C)
Xec: Humitat específica exterior (gr/kgr)
Ud. Número d'elements del mateix tipus
Cabal: Aire exterior (m³/h)
Sup.: Superfície de tancaments (m²)
Pressió: Pressió del vent (Pa)
Supl.: Suplement per orientació.
G.Inst.: Guanys instantanis (W)
Càrrega.Refr.: Càrregues de refrigeració (W)
Càrrega.Calef.: Càrregues de calefacció (W)
Pàgina 50 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
NOVES TECNOLOGIES
CONDICIONS
Ts (°C)
DESTINADA A
Aulas (sin fumadores)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
38,8 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
100,9 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana N
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada N
Fachada O
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
LADS02
N
S
S
REF.
Or.
MEXA02
MEXA02
MEXA02
CINV01
EXCEPTE
PARETS
Ventana N
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
4,5
2,4
2,4
0,89
0,89
0,89
1
1
1
Sup. (m²)
N
O
S
H
REF.
9,4
22,7
6,4
38,8
Sup. (m²)
LADS02
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
4,5
2,4
2,4
23,7
1,9
38,8
Potència
15 Ocupantes
25 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Cabal
Tsa
36,4
54,3
51,2
67,7
K
Tac
2,73
2,73
2,73
1,98
2,13
0,69
31,6
31,6
31,6
25,0
28,8
25,0
Ud.
78,0
38,8
432,0 m³/h Ventilación
K
0,61
0,61
0,61
0,41
%Ús
15
25
Tec
432
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
388
798
798
G. Inst. (w)
4
23
19
154
G. Inst. (w)
81
43
43
0
15
0
G. Inst. (w)
1.170
970
G. Inst. (w)
949
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
235
436
436
1.162
Càrrega Refr. (w)
7
44
21
166
250
Càrrega Refr. (w)
57
30
30
0
11
0
135
Càrrega Refr. (w)
1.170
970
2.247
Càrrega Refr. (w)
949
949
4.744 w
Potència
15 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
432,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
15
Xec
432
100
%Ús
11,6
100
G. Inst. (w)
690
G. Inst. (w)
122
Càrrega Refr. (w)
690
725
Càrrega Refr. (w)
122
122
847 w
5.591 w
Factor de calor sensible de la zona (RSHF): 0,840
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 144 w/m²
Pàgina 51 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
NOVES TECNOLOGIES
Ts
DESTINADA A
Aulas (sin fumadores)
DIMENSIONS
38,8 m² x 2,6 m
REF.
MEXA02
LADS02
MEXA02
MEXA02
LADS02
LADS02
CINV01
Supl.
Sup. (m²)
1,175
1,175
1,075
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
LADS02
432,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
9,4
4,5
22,7
6,4
2,4
2,4
38,8
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
N
N
O
S
S
S
H
Sup. (m²)
N
S
S
Pressió
33,4
26,7
26,7
0,61
4,30
0,61
0,61
4,30
4,30
0,43
K
23,7
1,9
38,8
Or.
21,0
Diferència
22,8
100,9 m³
TAB008
PIMP20
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana N
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada N
Ventana N
Fachada O
Fachada S
Ventana S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
1,98
2,13
0,66
Cabal
Tac
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
Tac
21,0
9,3
21,0
Tac
14,9
6,9
6,9
Cabal
-1,8
-1,8
-1,8
Tac
432
-1,8
Càrrega Calef. (w)
153
518
337
88
235
235
380
1.947
Càrrega Calef. (w)
0
47
0
47
Càrrega Calef. (w)
113
52
52
218
Càrrega Calef. (w)
3.278
3.278
0,0%
0,0%
1,000
5.490 w
141 w/m²
Pàgina 52 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
LOCAL4
CONDICIONS
Ts (°C)
DESTINADA A
Aulas (sin fumadores)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
26,2 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
68,1 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
S
S
REF.
Or.
MEXA02
CINV01
EXCEPTE
PARETS
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,3
2,4
0,89
0,89
1
1
Sup. (m²)
S
H
REF.
6,6
26,2
Sup. (m²)
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
2,3
2,4
40,4
2,1
26,2
Potència
20 Ocupantes
25 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
576,0 m³/h Ventilación
Tsa
51,2
67,7
K
Tac
2,73
2,73
1,98
2,13
0,69
31,6
31,6
25,0
28,8
25,0
Ud.
78,0
26,2
Cabal
K
0,61
0,41
%Ús
20
25
Tec
576
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
765
798
G. Inst. (w)
20
104
G. Inst. (w)
41
43
0
17
0
G. Inst. (w)
1.560
655
G. Inst. (w)
1.265
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
418
436
897
Càrrega Refr. (w)
21
112
140
Càrrega Refr. (w)
29
30
0
13
0
76
Càrrega Refr. (w)
1.560
655
2.326
Càrrega Refr. (w)
1.265
1.265
4.704 w
Potència
20 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
576,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
20
Xec
576
100
%Ús
11,6
100
G. Inst. (w)
920
G. Inst. (w)
163
Càrrega Refr. (w)
920
966
Càrrega Refr. (w)
163
163
1.129 w
5.832 w
Factor de calor sensible de la zona (RSHF): 0,781
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 223 w/m²
Pàgina 53 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
LOCAL4
Ts
DESTINADA A
Aulas (sin fumadores)
DIMENSIONS
26,2 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
CINV01
Supl.
Sup. (m²)
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
576,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
6,6
2,3
2,4
26,2
Sup. (m²)
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
S
H
S
S
Pressió
Tac
0,61
4,30
4,30
0,43
K
40,4
2,1
26,2
Or.
21,0
Diferència
22,8
68,1 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
0,66
Cabal
26,7
26,7
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
Tac
6,6
6,9
Cabal
-1,8
-1,8
Tac
576
-1,8
Càrrega Calef. (w)
91
225
235
256
808
Càrrega Calef. (w)
0
52
0
52
Càrrega Calef. (w)
50
52
102
Càrrega Calef. (w)
4.371
4.371
0,0%
0,0%
1,000
5.334 w
204 w/m²
Pàgina 54 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
LOCAL3
CONDICIONS
Ts (°C)
DESTINADA A
Aulas (sin fumadores)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
26,1 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
67,9 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
S
S
REF.
Or.
MEXA02
CINV01
EXCEPTE
PARETS
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
2,4
0,89
0,89
1
1
Sup. (m²)
S
H
REF.
6,2
26,1
Sup. (m²)
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
2,4
2,4
40,3
2,1
26,1
Potència
20 Ocupantes
25 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
576,0 m³/h Ventilación
Tsa
51,2
67,7
K
Tac
2,73
2,73
1,98
2,13
0,69
31,6
31,6
25,0
28,8
25,0
Ud.
78,0
26,1
Cabal
K
0,61
0,41
%Ús
20
25
Tec
576
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
798
798
G. Inst. (w)
19
104
G. Inst. (w)
43
43
0
17
0
G. Inst. (w)
1.560
653
G. Inst. (w)
1.265
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
436
436
916
Càrrega Refr. (w)
20
111
138
Càrrega Refr. (w)
30
30
0
13
0
77
Càrrega Refr. (w)
1.560
652
2.323
Càrrega Refr. (w)
1.265
1.265
4.719 w
Potència
20 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
576,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
20
Xec
576
100
%Ús
11,6
100
G. Inst. (w)
920
G. Inst. (w)
163
Càrrega Refr. (w)
920
966
Càrrega Refr. (w)
163
163
1.129 w
5.848 w
Factor de calor sensible de la zona (RSHF): 0,781
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 224 w/m²
Pàgina 55 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
LOCAL3
Ts
DESTINADA A
Aulas (sin fumadores)
DIMENSIONS
26,1 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
CINV01
Supl.
Sup. (m²)
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
576,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
6,2
2,4
2,4
26,1
Sup. (m²)
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
S
H
S
S
Pressió
Tac
0,61
4,30
4,30
0,43
K
40,3
2,1
26,1
Or.
21,0
Diferència
22,8
67,9 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
0,66
Cabal
26,7
26,7
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
Tac
6,9
6,9
Cabal
-1,8
-1,8
Tac
576
-1,8
Càrrega Calef. (w)
86
235
235
255
812
Càrrega Calef. (w)
0
52
0
52
Càrrega Calef. (w)
52
52
104
Càrrega Calef. (w)
4.371
4.371
0,0%
0,0%
1,000
5.339 w
205 w/m²
Pàgina 56 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
LOCAL2
CONDICIONS
Ts (°C)
DESTINADA A
Aulas (sin fumadores)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
24,9 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
64,7 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
S
S
REF.
Or.
MEXA02
CINV01
EXCEPTE
PARETS
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
2,4
0,89
0,89
1
1
Sup. (m²)
S
H
REF.
6,1
24,9
Sup. (m²)
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
2,4
2,4
39,6
2,3
24,9
Potència
20 Ocupantes
25 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
576,0 m³/h Ventilación
Tsa
51,2
67,7
K
Tac
2,73
2,73
1,98
2,13
0,69
31,6
31,6
25,0
28,8
25,0
Ud.
78,0
24,9
Cabal
K
0,61
0,41
%Ús
20
25
Tec
576
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
798
798
G. Inst. (w)
18
99
G. Inst. (w)
43
43
0
19
0
G. Inst. (w)
1.560
623
G. Inst. (w)
1.265
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
436
436
916
Càrrega Refr. (w)
20
106
132
Càrrega Refr. (w)
30
30
0
14
0
78
Càrrega Refr. (w)
1.560
622
2.292
Càrrega Refr. (w)
1.265
1.265
4.684 w
Potència
20 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
576,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
20
Xec
576
100
%Ús
11,6
100
G. Inst. (w)
920
G. Inst. (w)
163
Càrrega Refr. (w)
920
966
Càrrega Refr. (w)
163
163
1.129 w
5.812 w
Factor de calor sensible de la zona (RSHF): 0,780
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 233 w/m²
Pàgina 57 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
LOCAL2
Ts
DESTINADA A
Aulas (sin fumadores)
DIMENSIONS
24,9 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
CINV01
Supl.
Sup. (m²)
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
576,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
6,1
2,4
2,4
24,9
Sup. (m²)
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
S
H
S
S
Pressió
Tac
0,61
4,30
4,30
0,43
K
39,6
2,3
24,9
Or.
21,0
Diferència
22,8
64,7 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
0,66
Cabal
26,7
26,7
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
Tac
6,9
6,9
Cabal
-1,8
-1,8
Tac
576
-1,8
Càrrega Calef. (w)
84
235
235
244
798
Càrrega Calef. (w)
0
57
0
57
Càrrega Calef. (w)
52
52
104
Càrrega Calef. (w)
4.371
4.371
0,0%
0,0%
1,000
5.331 w
214 w/m²
Pàgina 58 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
LOCAL1
CONDICIONS
Ts (°C)
DESTINADA A
Aulas (sin fumadores)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
25,7 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
66,8 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
S
S
REF.
Or.
MEXA02
CINV01
EXCEPTE
PARETS
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
2,4
0,89
0,89
1
1
Sup. (m²)
S
H
REF.
6,1
25,7
Sup. (m²)
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
2,4
2,4
39,5
2,2
25,7
Potència
20 Ocupantes
25 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
576,0 m³/h Ventilación
Tsa
51,2
67,7
K
Tac
2,73
2,73
1,98
2,13
0,69
31,6
31,6
25,0
28,8
25,0
Ud.
78,0
25,7
Cabal
K
0,61
0,41
%Ús
20
25
Tec
576
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
798
798
G. Inst. (w)
18
102
G. Inst. (w)
43
43
0
18
0
G. Inst. (w)
1.560
643
G. Inst. (w)
1.265
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
436
436
916
Càrrega Refr. (w)
20
110
136
Càrrega Refr. (w)
30
30
0
13
0
78
Càrrega Refr. (w)
1.560
642
2.313
Càrrega Refr. (w)
1.265
1.265
4.707 w
Potència
20 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
576,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
20
Xec
576
100
%Ús
11,6
100
G. Inst. (w)
920
G. Inst. (w)
163
Càrrega Refr. (w)
920
966
Càrrega Refr. (w)
163
163
1.129 w
5.836 w
Factor de calor sensible de la zona (RSHF): 0,781
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 227 w/m²
Pàgina 59 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
LOCAL1
Ts
DESTINADA A
Aulas (sin fumadores)
DIMENSIONS
25,7 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
CINV01
Supl.
Sup. (m²)
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
576,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
6,1
2,4
2,4
25,7
Sup. (m²)
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
S
H
S
S
Pressió
Tac
0,61
4,30
4,30
0,43
K
39,5
2,2
25,7
Or.
21,0
Diferència
22,8
66,8 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
0,66
Cabal
26,7
26,7
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
Tac
6,9
6,9
Cabal
-1,8
-1,8
Tac
576
-1,8
Càrrega Calef. (w)
84
235
235
251
806
Càrrega Calef. (w)
0
55
0
55
Càrrega Calef. (w)
52
52
104
Càrrega Calef. (w)
4.371
4.371
0,0%
0,0%
1,000
5.336 w
208 w/m²
Pàgina 60 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
RECEPCIÓ
CONDICIONS
Ts (°C)
DESTINADA A
Espera y recepción (salas)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
25,8 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
67,1 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
S
S
REF.
Or.
MEXA02
CINV01
EXCEPTE
PARETS
Ventana S
Ventana S
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,4
2,4
0,89
0,89
1
1
Sup. (m²)
S
H
REF.
6,4
25,8
Sup. (m²)
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
2,4
2,4
40,4
2,2
25,8
Potència
12 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
371,5 m³/h Ventilación
Tsa
51,2
67,7
K
Tac
2,73
2,73
1,98
2,13
0,69
31,6
31,6
25,0
28,8
25,0
Ud.
71,0
25,8
Cabal
K
0,61
0,41
%Ús
12
15
Tec
372
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
798
798
G. Inst. (w)
19
103
G. Inst. (w)
43
43
0
18
0
G. Inst. (w)
852
387
G. Inst. (w)
816
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
436
436
916
Càrrega Refr. (w)
21
110
137
Càrrega Refr. (w)
30
30
0
13
0
78
Càrrega Refr. (w)
852
387
1.301
Càrrega Refr. (w)
816
816
3.248 w
Potència
12 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
31,0
Cabal
371,5 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
12
Xec
372
100
%Ús
11,6
100
G. Inst. (w)
372
G. Inst. (w)
105
Càrrega Refr. (w)
372
391
Càrrega Refr. (w)
105
105
496 w
3.744 w
Factor de calor sensible de la zona (RSHF): 0,862
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 145 w/m²
Pàgina 61 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
RECEPCIÓ
Ts
DESTINADA A
Espera y recepción (salas)
DIMENSIONS
25,8 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
CINV01
Supl.
Sup. (m²)
1,000
1,000
1,000
1,000
REF.
LADS02
LADS02
371,5 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
6,4
2,4
2,4
25,8
Sup. (m²)
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
S
S
S
H
S
S
Pressió
Tac
0,61
4,30
4,30
0,43
K
40,4
2,2
25,8
Or.
21,0
Diferència
22,8
67,1 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada S
Ventana S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
0,66
Cabal
26,7
26,7
-1,8
-1,8
-1,8
-1,8
21,0
9,3
21,0
Tac
6,9
6,9
Cabal
-1,8
-1,8
Tac
372
-1,8
Càrrega Calef. (w)
88
235
235
252
811
Càrrega Calef. (w)
0
55
0
55
Càrrega Calef. (w)
52
52
104
Càrrega Calef. (w)
2.819
2.819
0,0%
0,0%
1,000
3.790 w
147 w/m²
Pàgina 62 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
DESPATX SALA D’ACTES
CONDICIONS
Ts (°C)
DESTINADA A
Oficinas
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
8,6 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
22,4 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
TRANSMISSIÓ PARETS I SOSTRE
REF.
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
Or.
CINV01
EXCEPTE
PARETS
Cerramiento interior 1
Puerta interior 1
Cerramiento interior 2
Forjado interior 1
I
Sup. (m²)
H
REF.
8,6
Sup. (m²)
TAB008
PIMP20
TAB008
FOREX1
CALOR SENSIBLE INTERN
22,4
2,1
6,8
8,6
Potència
2 Ocupantes
30 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
K
Tsa
0,41
67,7
K
Tac
1,98
2,13
1,98
0,69
25,0
25,0
28,8
28,8
Ud.
78,0
8,6
Cabal
%Ús
2
30
Tec
72,0 m³/h Ventilación
72
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
34
G. Inst. (w)
0
0
51
23
G. Inst. (w)
156
258
G. Inst. (w)
158
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
37
39
Càrrega Refr. (w)
0
0
38
17
58
Càrrega Refr. (w)
156
258
435
Càrrega Refr. (w)
158
158
689 w
Potència
2 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
72,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
2
Xec
72
100
%Ús
11,6
100
G. Inst. (w)
92
G. Inst. (w)
20
Càrrega Refr. (w)
92
97
Càrrega Refr. (w)
20
20
117 w
806 w
Factor de calor sensible de la zona (RSHF): 0,846
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 94 w/m²
Pàgina 63 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
DESPATX SALA D’ACTES
Ts
DESTINADA A
Oficinas
DIMENSIONS
8,6 m² x 2,6 m
VOLUM
REF.
CINV01
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Cerramiento interior 2
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
REF.
TAB008
PIMP20
TAB008
FOREX1
VENTILACIÓ AIRE EXTERIOR
72,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
Or.
H
Supl.
1,000
Interior
-1,8
21,0
Diferència
22,8
22,4 m³
Sup. (m²)
K
8,6
Sup. (m²)
Tac
0,43
K
22,4
2,1
6,8
8,6
-1,8
Tac
1,98
2,13
1,98
0,66
Cabal
21,0
21,0
9,3
9,3
Tac
72
-1,8
Càrrega Calef. (w)
84
84
Càrrega Calef. (w)
0
0
157
66
223
Càrrega Calef. (w)
546
546
0,0%
0,0%
1,000
CÀRREGA TOTAL DE CALEFACCIÓ
854 w
Càrrega de calefacció per unitat de superfície:
99 w/m²
Pàgina 64 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
VESTÍBUL
CONDICIONS
Ts (°C)
DESTINADA A
Vestíbulos
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
44,5 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
115,7 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana N
Ventana N
TRANSMISSIÓ PARETS I SOSTRE
Fachada O
Fachada N
Fachada E
Fachada N
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
N
N
REF.
Or.
MEXA02
MEXA02
MEXA02
MEXA02
CINV01
EXCEPTE
PARETS
Ventana N
Ventana N
Cerramiento interior 1
Puerta interior 1
Cerramiento interior 2
Cerramiento interior 3
Puerta interior 2
Puerta interior 3
Forjado interior 1
I
Sup. (m²)
SC
Ud.
4,8
7,0
0,89
0,89
1
1
Sup. (m²)
O
N
E
N
H
REF.
11,2
4,2
11,0
6,0
44,5
Sup. (m²)
LADS02
LADS02
TAB008
PIMP20
TAB008
TAB008
PIMP20
PIMP20
FOREX1
CALOR SENSIBLE INTERN
4,8
7,0
15,5
1,9
21,4
20,5
1,9
3,7
44,5
Potència
8 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
925,6 m³/h Ventilación
Tsa
54,3
36,4
36,4
36,4
67,7
K
Tac
2,73
2,73
1,98
2,13
1,98
1,98
2,13
2,13
0,69
31,6
31,6
25,0
25,0
28,8
25,0
25,0
28,8
25,0
Ud.
89,0
44,5
Cabal
K
0,61
0,61
0,61
0,61
0,41
%Ús
8
15
Tec
926
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
414
604
G. Inst. (w)
11
2
67
3
177
G. Inst. (w)
86
126
0
0
161
0
0
30
0
G. Inst. (w)
712
668
G. Inst. (w)
2.033
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
250
365
646
Càrrega Refr. (w)
22
3
60
5
190
293
Càrrega Refr. (w)
61
88
0
0
120
0
0
22
0
306
Càrrega Refr. (w)
712
667
1.448
Càrrega Refr. (w)
2.033
2.033
4.728 w
Potència
8 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
121,0
Cabal
925,6 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
8
Xec
926
100
%Ús
11,6
100
G. Inst. (w)
968
G. Inst. (w)
262
Càrrega Refr. (w)
968
1.016
Càrrega Refr. (w)
262
262
1.278 w
6.006 w
Factor de calor sensible de la zona (RSHF): 0,726
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 135 w/m²
Pàgina 65 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
VESTÍBUL
Ts
DESTINADA A
Vestíbulos
DIMENSIONS
44,5 m² x 2,6 m
REF.
MEXA02
MEXA02
LADS02
MEXA02
MEXA02
LADS02
CINV01
Supl.
Sup. (m²)
1,075
1,175
1,175
1,125
1,175
1,175
1,000
REF.
LADS02
LADS02
925,6 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
11,2
4,2
4,8
11,0
6,0
7,0
44,5
REF.
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
O
N
N
E
N
N
H
Sup. (m²)
N
N
Pressió
33,4
33,4
0,61
0,61
4,30
0,61
0,61
4,30
0,43
K
15,5
1,9
21,4
20,5
1,9
3,7
44,5
Or.
21,0
Diferència
22,8
115,7 m³
TAB008
PIMP20
TAB008
TAB008
PIMP20
PIMP20
FOREX1
INFILTRACIÓ PORTES I FINESTRES
Ventana N
Ventana N
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Cerramiento interior 2
Cerramiento interior 3
Puerta interior 2
Puerta interior 3
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada O
Fachada N
Ventana N
Fachada E
Fachada N
Ventana N
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
1,98
2,13
1,98
1,98
2,13
2,13
0,66
Cabal
Tac
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
Tac
21,0
21,0
9,3
21,0
21,0
9,3
21,0
Tac
15,9
23,2
Cabal
-1,8
-1,8
Tac
926
-1,8
Càrrega Calef. (w)
166
68
553
171
97
806
435
2.298
Càrrega Calef. (w)
0
0
495
0
0
92
0
587
Càrrega Calef. (w)
121
176
297
Càrrega Calef. (w)
7.024
7.024
0,0%
0,0%
1,000
10.206 w
229 w/m²
Pàgina 66 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
BANY DONES
CONDICIONS
Ts (°C)
Th (°C)
DESTINADA A
Aseos públicos
vertedero,...)
31,6
21,3
DIMENSIONS
25,3 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
65,8 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
(por
urinario,
GUANY SOLAR VIDRE
Ventana E
Ventana E
Ventana E
TRANSMISSIÓ PARETS I SOSTRE
Fachada E
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
inodoro, Exteriors
REF.
Or.
LADS02
LADS02
LADS02
E
E
E
REF.
Or.
MEXA02
CINV01
EXCEPTE
PARETS
Ventana E
Ventana E
Ventana E
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
SC
Ud.
2,0
2,0
2,0
0,89
0,89
0,89
1
1
1
K
Tsa
0,61
0,41
36,4
67,7
K
Tac
2,73
2,73
2,73
1,98
2,13
0,69
31,6
31,6
31,6
25,0
25,0
25,0
Sup. (m²)
E
H
REF.
12,3
25,3
Sup. (m²)
LADS02
LADS02
LADS02
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
2,0
2,0
2,0
38,0
1,9
25,3
Potència
4 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Ud.
89,0
25,3
Cabal
360,0 m³/h Ventilación
%Ús
4
15
Tec
360
100
100
%Ús
31,6
100
G. Inst. (w)
172
172
172
G. Inst. (w)
75
101
G. Inst. (w)
36
36
36
0
0
0
G. Inst. (w)
356
380
G. Inst. (w)
791
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Xe (gr/kgr)
11,6
Càrrega Refr. (w)
294
294
294
925
Càrrega Refr. (w)
67
108
183
Càrrega Refr. (w)
25
25
25
0
0
0
80
Càrrega Refr. (w)
356
379
772
Càrrega Refr. (w)
791
791
2.751 w
Potència
4 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Hr (%)
40,0
Ud.
121,0
Cabal
360,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
4
Xec
360
100
%Ús
11,6
100
G. Inst. (w)
484
G. Inst. (w)
102
Càrrega Refr. (w)
484
508
Càrrega Refr. (w)
102
102
610 w
3.361 w
Factor de calor sensible de la zona (RSHF): 0,794
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 133 w/m²
Pàgina 67 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
BANY DONES
Ts
DESTINADA A
Aseos públicos (por urinario, inodoro,
vertedero,...)
DIMENSIONS
25,3 m² x 2,6 m
REF.
MEXA02
LADS02
LADS02
LADS02
CINV01
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
E
E
E
E
H
REF.
Supl.
Sup. (m²)
1,125
1,125
1,125
1,125
1,000
LADS02
LADS02
LADS02
360,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
12,3
2,0
2,0
2,0
25,3
Sup. (m²)
E
E
E
Pressió
Tac
0,61
4,30
4,30
4,30
0,43
K
38,0
1,9
25,3
Or.
21,0
Diferència
22,8
65,8 m³
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
Or.
Interior
-1,8
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana E
Ventana E
Ventana E
Exterior
(°C)
VOLUM
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Ventana E
Ventana E
Ventana E
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Tac
1,98
2,13
0,66
Cabal
26,7
26,7
26,7
-1,8
-1,8
-1,8
-1,8
-1,8
21,0
21,0
21,0
Tac
5,7
5,7
5,7
Cabal
-1,8
-1,8
-1,8
Tac
360
-1,8
Càrrega Calef. (w)
191
221
221
221
247
1.100
Càrrega Calef. (w)
0
0
0
0
Càrrega Calef. (w)
43
43
43
130
Càrrega Calef. (w)
2.732
2.732
0,0%
0,0%
1,000
3.963 w
157 w/m²
Pàgina 68 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
BANY HOMES
CONDICIONS
Ts (°C)
Th (°C)
DESTINADA A
Aseos públicos
vertedero,...)
31,6
21,3
DIMENSIONS
21,1 m² x 2,6 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
54,9 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
(por
urinario,
TRANSMISSIÓ PARETS I SOSTRE
REF.
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
inodoro, Exteriors
Or.
CINV01
EXCEPTE
PARETS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
I
Sup. (m²)
H
REF.
21,1
Sup. (m²)
TAB008
PIMP20
FOREX1
CALOR SENSIBLE INTERN
61,4
2,0
21,1
Potència
4 Ocupantes
15 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Cabal
Tsa
0,41
67,7
K
Tac
1,98
2,13
0,69
25,0
25,0
25,0
Ud.
89,0
21,1
360,0 m³/h Ventilación
K
%Ús
4
15
Tec
360
100
100
%Ús
31,6
100
G. Inst. (w)
84
G. Inst. (w)
Càrrega Refr. (w)
90
95
Càrrega Refr. (w)
G. Inst. (w)
356
317
G. Inst. (w)
791
0
0
0
0
Càrrega Refr. (w)
356
316
706
Càrrega Refr. (w)
791
791
1.591 w
Potència
4 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
0
0
0
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Hr (%)
40,0
Ud.
121,0
Cabal
360,0 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
4
Xec
360
100
%Ús
11,6
100
G. Inst. (w)
484
G. Inst. (w)
102
Càrrega Refr. (w)
484
508
Càrrega Refr. (w)
102
102
610 w
2.201 w
Factor de calor sensible de la zona (RSHF): 0,612
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 104 w/m²
Pàgina 69 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
BANY HOMES
Ts
DESTINADA A
Aseos públicos (por urinario, inodoro,
vertedero,...)
DIMENSIONS
21,1 m² x 2,6 m
REF.
CINV01
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Forjado interior 1
REF.
TAB008
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
360,0 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
Càrrega de calefacció per unitat de superfície:
Exterior
(°C)
VOLUM
TRANSMISSIÓ AMBIENT EXTERIOR
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
Or.
H
Supl.
1,000
Interior
-1,8
21,0
Diferència
22,8
54,9 m³
Sup. (m²)
K
21,1
Sup. (m²)
0,43
K
61,4
2,0
21,1
1,98
2,13
0,66
Cabal
Tac
-1,8
Tac
21,0
21,0
21,0
Tac
360
-1,8
Càrrega Calef. (w)
206
206
Càrrega Calef. (w)
0
0
0
0
Càrrega Calef. (w)
2.732
2.732
0,0%
0,0%
1,000
2.938 w
139 w/m²
Pàgina 70 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
DATA CÀLCUL
14 Hora solar Agosto
ZONA
SALA D’ACTES
CONDICIONS
Ts (°C)
DESTINADA A
Aulas (sin fumadores)
Exteriors
31,6
21,3
Hr (%)
40,0
DIMENSIONS
171,1 m² x 3,0 m
Interiors
25,0
19,0
56,9
11,3
VOLUM
513,3 m³
Diferències
6,6
2,3
-17,0
0,3
(Máximas por Sistema)
GUANY SOLAR VIDRE
Ventana S
Ventana O
Ventana S
TRANSMISSIÓ PARETS I SOSTRE
Fachada E
Fachada S
Fachada O
Fachada S
Cubierta 1
TRANSMISSIÓ
SOSTRE
FULL DE CÀRREGUES PER A
REFRIGERACIÓ DE ZONA
REF.
Or.
LADS02
LADS02
LADS02
S
O
S
REF.
Or.
MEXA02
MEXA02
MEXA02
MEXA02
CINV01
EXCEPTE
PARETS
Ventana S
Ventana O
Ventana S
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Forjado interior 1
I
Sup. (m²)
SC
Ud.
9,0
5,1
4,8
0,89
0,89
0,89
1
1
1
Sup. (m²)
E
S
O
S
H
REF.
39,8
21,8
44,7
5,5
171,1
Sup. (m²)
LADS02
LADS02
LADS02
TAB008
PIMP20
PIMP20
FOREX1
CALOR SENSIBLE INTERN
9,0
5,1
4,8
66,6
3,8
2,3
171,1
Potència
80 Ocupantes
25 w/m² Alumbrado AL-i/1w
CALOR SENSIBLE AIRE VENTILACIÓ
Cabal
Tsa
36,4
51,2
54,3
51,2
67,7
K
Tac
2,73
2,73
2,73
1,98
2,13
2,13
0,69
31,6
31,6
31,6
25,0
28,8
25,0
25,0
Ud.
78,0
171,1
2.566,5 m³/h Ventilación
K
0,61
0,61
0,61
0,61
0,41
%Ús
80
25
Tec
2.567
100
100
%Ús
31,6
100
Th (°C)
G. Inst. (w)
2.994
2.057
1.597
G. Inst. (w)
243
65
46
17
681
G. Inst. (w)
162
92
86
0
31
0
0
G. Inst. (w)
6.240
4.278
G. Inst. (w)
5.638
TOTAL CALOR SENSIBLE
CALOR LATENT INTERN
Càrrega Refr. (w)
1.636
803
872
3.477
Càrrega Refr. (w)
216
71
88
18
730
1.178
Càrrega Refr. (w)
114
64
61
0
23
0
0
275
Càrrega Refr. (w)
6.240
4.277
11.043
Càrrega Refr. (w)
5.638
5.638
21.611 w
Potència
80 Ocupantes
CALOR LATENT AIRE VENTILACIÓ
Xe (gr/kgr)
11,6
Ud.
46,0
Cabal
2.566,5 m³/h Ventilación
TOTAL CALOR LATENT
CÀRREGA TOTAL DE REFRIGERACIÓ
%Ús
80
Xec
2.567
100
%Ús
11,6
100
G. Inst. (w)
3.680
G. Inst. (w)
726
Càrrega Refr. (w)
3.680
3.864
Càrrega Refr. (w)
726
726
4.590 w
26.201 w
Factor de calor sensible de la zona (RSHF): 0,805
Factor de seguretat (Aplicat als resultats parcials i al total): 5 %
Càrrega de refrigeració per unitat de superfície: 153 w/m²
Pàgina 71 de 72
EXPEDIENT
13B
PROJECTE
CENTRE CIVIC BELL-LLOC P1
DATA
31/01/08
SISTEMA
PLANTA PRIMERA
CONDICIONS DE CÀLCUL PER A HIVERN
ZONA
SALA D’ACTES
Ts
DESTINADA A
Aulas (sin fumadores)
DIMENSIONS
171,1 m² x 3,0 m
REF.
MEXA02
MEXA02
LADS02
MEXA02
LADS02
MEXA02
LADS02
CINV01
Supl.
Sup. (m²)
1,125
1,000
1,000
1,075
1,075
1,000
1,000
1,000
REF.
LADS02
LADS02
LADS02
2.566,5 m³/h Ventilación
SUPLEMENTS
Per intermitència (Funcionamiento ininterrumpido)
Altres suplements
Coeficient total de majoració
CÀRREGA TOTAL DE CALEFACCIÓ
K
39,8
21,8
9,0
44,7
5,1
5,5
4,8
171,1
Sup. (m²)
TAB008
PIMP20
PIMP20
FOREX1
VENTILACIÓ AIRE EXTERIOR
Càrrega de calefacció per unitat de superfície:
E
S
S
O
O
S
S
H
S
O
S
Pressió
26,7
33,4
26,7
0,61
0,61
4,30
0,61
4,30
0,61
4,30
0,43
K
66,6
3,8
2,3
171,1
Or.
21,0
Diferència
22,8
513,3 m³
REF.
INFILTRACIÓ PORTES I FINESTRES
Ventana S
Ventana O
Ventana S
Or.
Interior
-1,8
VOLUM
TRANSMISSIÓ AMB ALTRES LOCALS
Cerramiento interior 1
Puerta interior 1
Puerta interior 2
Forjado interior 1
Exterior
(°C)
TRANSMISSIÓ AMBIENT EXTERIOR
Fachada E
Fachada S
Ventana S
Fachada O
Ventana O
Fachada S
Ventana S
Cubierta 1
FULL DE CÀRREGUES PER A
CALEFACCIÓ DE ZONA
1,98
2,13
2,13
0,66
Cabal
25,7
16,9
13,7
Cabal
2.567
Tac
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
-1,8
Tac
21,0
9,3
21,0
21,0
Tac
-1,8
-1,8
-1,8
Tac
-1,8
Càrrega Calef. (w)
619
301
882
664
538
76
471
1.674
5.224
Càrrega Calef. (w)
0
94
0
0
94
Càrrega Calef. (w)
195
128
104
428
Càrrega Calef. (w)
19.477
19.477
0,0%
0,0%
1,000
25.223 w
147 w/m²
Pàgina 72 de 72
PROJECTE DE CLIMATITZACIÓ PER AIGUA
1.- MEMÒRIA DE CÀLCUL
1.1.- SELECCIÓ DE LA POTÈNCIA DEL GENERADOR
La potència del generador es determina segons la fórmula:
P = (P + Pt )· f i
On:
P = Potència del generador en watts.
P = Potència calorífica necessària en watts.
Pt = Pèrdues de calor per les canonades en watts.
fi = Augment per inèrcia.
Així, la potència total necessària en el generador és de:
P = ( 188.700 + 7.572 ) · 1,00 = 196.272 w
Per tant, es selecciona la caldera de biomassa FROLING TURBOMAT 220 amb una
potència nominal de 220 kW.
1.1.2.- CÀLCUL DE LA BOMBA DE CIRCULACIÓ
El cabal que ha de subministrar la bomba de circulació ve donat per l'expressió:
Q=
860·Pe
1000·Δt ·C e ·γ
On:
Ce = Calor específic de l'aigua = 1,0 Kcal/h·Kg·°C
γ = Pes específic de l'aigua = 1,0 Kg/dm3
Δt = Salt tèrmic en °C
Pe = Potència instal·lada en els emissors en watts
Amb el que s'obté un cabal de:
Q = (0,86 · 274.960) / 10,0 = 23.646,6 litres/hora
Per al càlcul de les pèrdues de càrrega en les canonades s’ha tingut en compte la fórmula de
Prandtl-Colebrook i es limita la pèrdua de càrrega por unitat de longitut de canonada a 40,0
mm.c.a./m .
La pèrdua de càrrega en el generador i en els radiadors es calcula amb l'equació:
J=
ε ·v 2 ·γ
2· g
On:
J = Pèrdua de pressió en mmca.
ε = Coeficient de resistència.
v = Velocitat en m/s.
γ = Pes específic en kg/m³.
Pàgina 1 de 8
g = Acceleració de la gravetat en m/s².
Usant un coeficient de resistència ε = 2,5 per al generador i de ε = 3,0 per als radiadors.
Les pèrdues de càrrega en les claus i en els plafons es calculen per mitjà dels gràfics del fabricant.
La pèrdua més gran de càrrega es produeix en el circuit de l'emissor Fan-coil biblioteca2 [167140] i és igual a 3,012 mca. La caiguda de pressió en aquest emissor és de 4,000 mca. i la
pèrdua en el generador arriba a 0,318 mca.
Així la pressió total del circulador haurà de ser:
H = 3,012 + 4,000 + 0,318 = 7,330 mca.
Per tant el punt de funcionament de la bomba de circulació ha d'estar entorn a:
Cabal= 23,647 m³/h
Pressió= 7,330 mca.
1.1.3.- CÀLCUL DEL DIPÒSIT D'EXPANSIÓ TANCAT
Aquest procediment de càlcul es basa en la normativa UNE-100-155-88: Càlcul de dipòsits
d’expansió.
El volum o capacitat útil que ha de tenir el dipòsit ha de ser almenys de:
Vu = V · α
On:
Vu = Volum o capacitat útil del dipòsit en litres.
V = Volum d'aigua total de la instal·lació en litres.
α = Coeficient de dilatació de l'aigua en %.
El volum total d'aigua en la instal·lació és la suma del volum el generador i emissors més la
capacitat de les canonades:
V.Total = V.Generador + V.Emissors + V.Canonades
V.Total = 570,0 + 37,4 + 525,6 = 1.133,1 litres.
Prenent un factor de seguretat del 10% s'obté un volum total de:
V = 1.133,1 x 1,1 = 1.246,4 litres.
Per a una temperatura mitja de 70,0 °C i un percentatge de glicol etilenic de 0% es té un increment
de volum del 2,227%.
Per tant el volum útil del dipòsit ha de ser de:
Vu = 1.246,4 · 2,227 / 100 = 27,8 litres.
El coeficient d' pressió del gas relaciona la pressió màxima de treball (PM) i la pressió d'ompliment
de gas (Pm), les dues com a pressions absolutes:
Cp = PM / (PM - Pm)
Pàgina 2 de 8
Donat que l'altura de la instal·lació sobre el dipòsit és de 6,0 m., la pressió d'ompliment de la
càmara de gas serà:
Pm = 1,01325 · 6,0 / 10 = 0,6 bar.
Com a mínim es pren una pressió d'ompliment de ,5 bar. D´altra banda escollint una pressió
màxima de treball PM = 3,0 bar. s'obté:
Cp = (3,0 + 1,01325)/(3,0 - 0,6) = 1,678
Per tant la capacitat total del dipòsit ha de ser:
Vv = Vu / Cu = 27,8 / 1,678 = 46,6 litres
Es tria un dipòsit d'expansió tancat amb els següents característiques:
Capacitat total= 50,0 litres
Pressió màxima de treball= 3,0 bar.
Pressió d'ompliment= 0,6 bar.
Pressió de tarat de la vàlvula de seguretat 3,0 bar.
1.1.4.- MÈTODE DE CÀLCUL PER A CANONADES
El principi de càlcul és el següent:
1- Determinació del cabal de cadascun dels trams, de la fi a l’origen, en funció dels emissors als
que alimenta:
Q=
860·Pe
1000·Δt ·C e ·γ
On:
Ce = Calor específica de l’ aigua = 1,0 Kcal/h·Kg·°C
γ = Pes específic de l’ aigua = 1,0 Kg/dm³
Δt = Salt tèrmic en °C
Pe = Potència instal·lada en els emissors en watts
Es té en compte els següents modes de funcionament:
- Calefacció salt tèrmic 10,0°C i potències individuals màximes.
2- Per al càlcul de les pèrdues de càrrega a les canonades s’ha tingut en compte la fórmula
de Prandtl-Colebrook.
V = −2 ⋅ 2·g ·D·J ·log10 (
ka
2'51·ν
+
)
3'71·D D· 2· g ·D· J
On:
J
D
V
Qr
ka
ν
g
=
=
=
=
=
=
=
Pèrdues de càrrega, en m.c.a./m;
Diàmetre interior de canonades, en m;
Velocitat mitja del aigua, en m/s;
Cabal en m³/s;
Rugositat uniforme equivalent, en m.;
Viscositat cinemàtica del fluid, (1’31x10-6 m²/s per aigua a 10°C);
Acceleració de la gravetat, 9’8 m/s²;
Pàgina 3 de 8
3- Determinació dels diàmetres de canonada en base a admetre una pèrdua de càrrega màxima
per unitat de longitud de canonada igual a 40,0 mm.c.a./m .
4- Es tenen en compte les longituds equivalents a canonada recta del mateix diàmetre als
accessoris (tes, colzes...) i vàlvules connectades entre canonades per a calcular les pèrdues de
càrrega que produeixen.
5- Càlcul de la pèrdua de càrrega a provocar a cadascuna de les vàlvules per a obtenir la
distribució de cabals suposada inicial.
1.2.- MEMÒRIA DE CÀLCUL DEL CIRCUIT TANCAT DE CANONADES
El circuit tancat mes desfavorable correspon al que va des del generador CALDERA BIOMASA [163] fins a l’emissor Fan-coil biblioteca2 [167-140]. Tot seguit es desglossen les pèrdues de càrrega
a cadascun dels elements als trams d’anada i tornada:
TRAMO
N1-N2
N2-N3
Cabal
aigua
(l/h)
Velc.
(m/s)
23.647
11.595
1,28
0,86
Ø Nominal
(mm)
ó
(pulgadas)
3"
2 1/2"
2 1/2"
N3-N4
10.341
1,30
2 1/2"
2"
2"
ΔP
Unitari
(mmca)
Longitut
(m)
19,5
11,2
5,2
1,7
11,2
11,2
33,9
33,9
3,0
5,7
2,7
2,0
N4-N5
9.549
1,20
2"
2"
33,9
29,0
1,6
4,2
N5-N6
8.758
1,10
2"
24,6
4,5
N6-N7
N7-N8
N8-N9
N9-N10
7.967
7.176
6.385
5.130
1,00
0,90
0,80
1,03
2"
2"
2"
1 1/2"
1 1/2"
N10-N11
3.036
0,83
1 1/2"
1 1/4"
1 1/4"
N11-N12
3.036
2,97
N12-N13
3.036
0,83
20,5
16,8
13,4
29,4
29,4
29,4
23,3
23,3
3,9
4,4
8,1
1,1
8,4
0,6
1,1
0,8
1 1/4"
23,3
0,3
1 1/4"
23,5
0,2
1 1/4"
1 1/4"
23,5
23,5
0,5
1,1
Tipo de
accessori
Tubería
Tubería
Te divergencia
Codo
Tubería
Codo
Tubería
Tubería
Te división
Codo
Tubería
Codo
Tubería
Tubería
Te división
Tubería
Te división
Tubería
Te división
Tubería
Te división
Tubería
Te división
Tubería
Te división
Codo
Tubería
Codo
Tubería
Tubería
Te división
Codo
Tubería
Codo
Tubería
Fan-coil
biblioteca2 [167140]
Tubería
Codo
Tubería
Codo
Tubería
Te unión
Longitut
equivalent
accessori
(1)
(m) ó Kv
Longitut
total
(m)
ΔP Total
(mca)
5,15
4,76
0,101
0,053
3,63
0,041
5,71
3,64
0,064
0,123
2,60
0,088
1,58
4,57
0,053
0,133
4,83
0,119
4,23
0,087
4,73
0,079
8,41
0,113
2,06
0,060
9,00
0,264
0,65
3,02
0,019
0,070
1,45
0,034
0,32
0,008
4,000
0,80
0,019
1,12
0,026
1,94
0,046
2,40
0,63
0,63
0,32
0,63
0,63
0,32
0,32
0,32
0,32
0,32
0,32
0,63
0,63
1,25
0,63
0,63
0,62
0,63
0,80
Pàgina 4 de 8
N13-N14
5.130
1,03
1 1/2"
1 1/2"
1 1/2"
N14-N15
N15-N16
N16-N17
N17-N18
N18-N19
N19-N20
6.385
7.176
7.967
8.758
9.549
10.341
0,80
0,90
1,00
1,10
1,20
1,30
2"
2"
2"
2"
2"
2"
2"
2"
N20-N21
11.595
0,86
2 1/2"
2 1/2"
2 1/2"
N21-N22
N22-N23
23.647
23.647
1,28
3"
29,6
29,6
29,6
13,6
16,9
20,7
24,8
29,3
34,1
34,1
34,1
11,3
11,3
11,3
19,7
0,4
8,4
1,0
8,5
4,4
3,9
4,5
4,2
1,3
2,0
3,0
5,4
3,0
1,9
4,9
Tubería
Codo
Tubería
Codo
Tubería
Te unión
Tubería
Te unión
Tubería
Te unión
Tubería
Te unión
Tubería
Te unión
Tubería
Te unión
Tubería
Codo
Tubería
Codo
Tubería
Te unión
Tubería
Codo
Tubería
Codo
Tubería
Te confluencia
Tubería
CALDERA
BIOMASA [1-63]
1,00
0,030
9,02
0,267
1,39
0,041
8,92
0,121
4,81
0,081
4,33
0,090
4,88
0,121
4,64
0,136
1,88
0,064
2,60
0,089
3,42
0,117
5,98
0,068
3,63
0,041
4,31
0,049
4,92
0,097
0,318
0,63
0,63
0,40
0,40
0,40
0,40
0,40
0,40
0,63
0,63
0,40
0,63
0,63
2,40
TOTAL
(1) Kv: Constante válvulas de control.
7,330
1.3.- RELACIÓ DE BATERÍES
Unitat
Potència
(w)
14.590
Temp.
Entrada
(°C)
75,0
Temp.
Sortida
(°C)
65,0
Cabal
aigua
(l/h)
1.254,7
Fan-coil Gimnàs
[144-67]
Fan-coil Despatx
gestió [145-70]
Fan-coil Sala d'estar
[146-73]
Fan-coil Menjador1
[147-76]
Fan-coil Menjador2
[148-79]
Fan-coil Bar [149-82]
Fan-coil Vestíbul
[150-85]
Fan-coil Sala
d'espera1 [151-105]
Fan-coil Servei social
[152-108]
Fan-coil Podòleg
[153-110]
Fan-coil Sala
d'espera2 [154-90]
Fan-coil Consulta
metge1 [155-92]
Fan-coil Cures [15696]
Fan-coil Infermeria
[157-98]
Caiguda
Pressió
Marca y model
pressió d’equilibrat
(mm.c.a.) (mm.c.a.)
1.580,0
4.938,8
GENERAL VOE 73
4.560
75,0
65,0
392,2
1.048,0
4.974,1
GENERAL FME 09
14.590
75,0
65,0
1.254,7
1.580,0
4.117,0
GENERAL VOE 73
14.590
75,0
65,0
1.254,7
1.580,0
3.793,1
GENERAL VOE 73
14.590
75,0
65,0
1.254,7
1.580,0
3.653,0
GENERAL VOE 73
14.590
14.590
75,0
75,0
65,0
65,0
1.254,7
1.254,7
1.580,0
1.580,0
3.448,8
3.209,9
GENERAL VOE 73
GENERAL VPE 73
6.080
75,0
65,0
522,9
1.662,0
2.892,5
GENERAL FME 12
4.560
75,0
65,0
392,2
1.048,0
3.200,4
GENERAL FME 09
4.560
75,0
65,0
392,2
1.048,0
2.958,0
GENERAL FME 09
14.590
75,0
65,0
1.254,7
1.580,0
2.721,8
GENERAL VOE 73
4.560
75,0
65,0
392,2
1.048,0
3.154,9
GENERAL FME 09
4.560
75,0
65,0
392,2
1.048,0
2.952,6
GENERAL FME 09
4.560
75,0
65,0
392,2
1.048,0
2.795,8
GENERAL FME 09
Pàgina 5 de 8
Fan-coil Consulta
metge2 [158-101]
Fan-coil noves
tecnologies [159-115]
Fan-coil local4 [160120]
Fan-coil local3 [161123]
Fan-coil local2 [162126]
Fan-coil local1 [163129]
Fan-coil recepció
[164-132]
Fan-coil vestíbul
[165-134]
Fan-coil biblioteca1
[166-143]
Fan-coil biblioteca2
[167-140]
4.560
75,0
65,0
392,2
1.048,0
2.553,5
GENERAL FME 09
14.590
75,0
65,0
1.254,7
1.580,0
4.833,1
GENERAL VOE 73
9.200
75,0
65,0
791,2
2.531,0
3.289,8
GENERAL FME 18
9.200
75,0
65,0
791,2
2.531,0
3.019,3
GENERAL FME 18
9.200
75,0
65,0
791,2
2.531,0
2.777,3
GENERAL FME 18
9.200
75,0
65,0
791,2
2.531,0
2.610,3
GENERAL FME 18
9.200
75,0
65,0
791,2
2.531,0
2.443,8
GENERAL FME 18
14.590
75,0
65,0
1.254,7
1.580,0
3.243,5
GENERAL VPE 73
24.350
75,0
65,0
2.094,1
2.800,0
826,4
CIATESA KCN-35
35.300
75,0
65,0
3.035,8
4.000,0
0,0
CIATESA KCN-50
1.4.- RELACIÓ DE CANONADES
Descripció
Tramo [1-2]
Tramo [63-64]
Tramo [77-78]
Tramo [80-81]
Tramo [80-83]
Tramo [83-84]
Tramo [83-86]
Tramo [95-97]
Tramo [97-99]
Tramo [86-102]
Tramo [64-65]
Tramo [65-66]
Tramo [66-67]
Tramo [65-68]
Tramo [68-69]
Tramo [69-70]
Tramo [68-71]
Tramo [71-72]
Tramo [72-73]
Tramo [71-74]
Tramo [74-75]
Tramo [75-76]
Tramo [74-77]
Tramo [78-79]
Tramo [77-80]
Tramo [81-82]
Tramo [84-85]
Tramo [86-87]
Tramo [87-88]
Tramo [88-89]
Tramo [89-90]
Tramo [89-91]
Tramo [91-92]
Tramo [91-93]
Tramo [93-94]
Tramo [94-95]
Tramo [95-96]
Tramo [97-98]
Tramo [99-100]
Tramo [100-101]
Tramo [102-103]
Diàmetre
3"
3"
1"
1"
1 1/2"
1"
1 1/2"
3/4"
1/2"
1"
2 1/2"
1"
1"
2"
1/2"
1/2"
2"
1"
1"
2"
1"
1"
2"
1"
2"
1"
1"
1 1/4"
1 1/4"
1 1/4"
1"
1"
1/2"
1"
1"
1"
1/2"
1/2"
1/2"
1/2"
1"
Long.
(m)
5,2
4,9
0,3
2,9
5,0
0,5
0,3
3,0
3,6
5,5
5,0
1,0
0,1
5,9
0,4
0,2
5,1
0,4
0,3
5,8
0,3
0,2
3,0
0,2
3,6
0,1
0,1
7,9
1,5
0,7
1,2
0,8
0,7
2,3
1,5
0,8
0,8
0,8
1,0
0,1
0,4
Leqv.
(m)
0,0
0,0
0,8
0,8
0,4
0,8
0,4
0,4
0,4
0,4
2,4
0,8
0,6
0,4
0,8
0,6
0,4
0,8
0,6
0,4
0,8
0,6
0,4
0,6
0,4
0,6
0,7
0,8
0,0
0,0
0,8
0,4
0,8
0,4
0,6
0,6
0,8
0,8
0,6
0,7
0,6
Cabal
(l/h)
23.646,6
23.646,6
1.254,7
1.254,7
5.385,3
1.254,7
4.130,6
784,3
392,2
1.307,2
12.051,2
1.254,7
1.254,7
10.796,4
392,2
392,2
10.404,3
1.254,7
1.254,7
9.149,5
1.254,7
1.254,7
7.894,8
1.254,7
6.640,1
1.254,7
1.254,7
2.823,4
2.823,4
2.823,4
1.254,7
1.568,6
392,2
1.176,5
1.176,5
1.176,5
392,2
392,2
392,2
392,2
1.307,2
Velc.
(m/s)
1,28
1,28
0,60
0,60
1,08
0,60
0,83
0,59
0,54
0,62
0,90
0,60
0,60
1,35
0,54
0,54
1,31
0,60
0,60
1,15
0,60
0,60
0,99
0,60
0,83
0,60
0,60
0,77
0,77
0,77
0,60
0,74
0,54
0,56
0,56
0,56
0,54
0,54
0,54
0,54
0,62
P.Tot.
(mmca)
100,7
97,0
20,1
66,7
174,2
23,6
14,0
80,6
114,6
114,0
90,3
32,2
12,8
232,9
35,6
22,5
190,7
21,6
15,4
166,9
19,9
14,1
69,8
15,2
57,9
13,5
13,9
179,2
29,9
13,6
35,1
33,9
42,5
42,4
34,3
22,7
45,2
44,7
47,9
22,7
20,2
P.Unit.
(mmca/m)
19,5
19,7
17,9
17,9
32,5
17,9
19,6
23,4
28,7
19,3
12,2
17,9
17,9
37,1
28,7
28,7
34,5
17,9
17,9
27,0
17,9
17,9
20,3
17,9
14,6
17,9
17,9
20,5
20,5
20,5
17,9
27,2
28,7
15,8
15,8
15,8
28,7
28,7
28,7
28,7
19,3
Pàgina 6 de 8
Tramo [103-104]
Tramo [104-105]
Tramo [103-106]
Tramo [106-107]
Tramo [107-108]
Tramo [107-109]
Tramo [109-110]
Tramo [2-3]
Tramo [3-4]
Tramo [4-144]
Tramo [3-5]
Tramo [5-6]
Tramo [6-145]
Tramo [5-7]
Tramo [7-8]
Tramo [8-146]
Tramo [7-9]
Tramo [9-10]
Tramo [10-147]
Tramo [9-11]
Tramo [11-12]
Tramo [12-148]
Tramo [11-13]
Tramo [13-14]
Tramo [14-149]
Tramo [13-15]
Tramo [15-16]
Tramo [16-150]
Tramo [17-18]
Tramo [18-19]
Tramo [18-24]
Tramo [24-151]
Tramo [19-20]
Tramo [20-21]
Tramo [21-22]
Tramo [22-153]
Tramo [20-23]
Tramo [23-152]
Tramo [15-17]
Tramo [17-25]
Tramo [25-26]
Tramo [26-27]
Tramo [27-154]
Tramo [27-28]
Tramo [28-29]
Tramo [29-155]
Tramo [28-30]
Tramo [30-31]
Tramo [31-32]
Tramo [32-33]
Tramo [33-156]
Tramo [32-34]
Tramo [34-35]
Tramo [35-157]
Tramo [34-36]
Tramo [36-37]
Tramo [37-158]
Tramo [2-38]
Tramo [39-40]
Tramo [40-62]
Tramo [43-45]
Tramo [51-53]
Tramo [38-39]
Tramo [64-111]
Tramo [133-134]
Tramo [133-135]
3/4"
3/4"
3/4"
3/4"
1/2"
1/2"
1/2"
2 1/2"
1"
1"
2"
1/2"
1/2"
2"
1"
1"
2"
1"
1"
2"
1"
1"
2"
1"
1"
1 1/2"
1"
1"
1"
3/4"
3/4"
3/4"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
1 1/2"
1 1/4"
1 1/4"
1 1/4"
1"
1"
1/2"
1/2"
1"
1"
1"
1/2"
1/2"
3/4"
1/2"
1/2"
1/2"
1/2"
1/2"
2 1/2"
2 1/2"
1"
2"
2"
2 1/2"
2 1/2"
1"
1 1/2"
0,6
0,3
1,3
1,9
0,8
4,2
0,8
5,6
1,5
0,3
5,9
0,9
0,3
5,1
0,9
0,4
5,8
0,7
0,3
3,0
0,8
0,4
3,6
3,4
0,3
4,6
0,5
0,2
5,2
1,7
1,0
0,1
1,9
4,3
0,9
0,2
0,8
0,2
0,6
8,2
1,5
0,8
1,3
0,5
0,7
0,2
2,3
1,6
0,8
0,8
0,2
3,1
0,8
0,1
3,5
1,1
0,3
1,7
5,7
0,5
4,2
8,1
3,0
1,9
0,1
1,0
0,8
0,7
0,4
0,6
0,8
0,4
0,6
2,4
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
0,3
1,9
1,0
0,0
0,0
1,0
0,6
0,0
1,9
0,0
0,3
1,3
0,0
0,0
1,3
0,3
1,9
0,0
1,0
0,6
0,0
1,9
0,0
0,3
1,9
0,0
1,0
0,6
0,0
3,0
0,0
1,9
0,3
0,3
0,6
2,4
0,8
0,4
522,9
522,9
784,3
784,3
392,2
392,2
392,2
12.051,2
1.254,7
1.254,7
10.796,4
392,2
392,2
10.404,3
1.254,7
1.254,7
9.149,5
1.254,7
1.254,7
7.894,8
1.254,7
1.254,7
6.640,1
1.254,7
1.254,7
5.385,3
1.254,7
1.254,7
1.307,2
784,3
522,9
522,9
784,3
392,2
392,2
392,2
392,2
392,2
4.130,6
2.823,4
2.823,4
2.823,4
1.254,7
1.568,6
392,2
392,2
1.176,5
1.176,5
1.176,5
392,2
392,2
784,3
392,2
392,2
392,2
392,2
392,2
11.595,4
11.595,4
1.254,7
9.549,4
6.384,6
11.595,4
11.595,4
1.254,7
5.129,9
0,39
0,39
0,59
0,59
0,54
0,54
0,54
0,90
0,60
0,60
1,35
0,54
0,54
1,31
0,60
0,60
1,15
0,60
0,60
0,99
0,60
0,60
0,83
0,60
0,60
1,08
0,60
0,60
0,62
0,59
0,39
0,39
0,59
0,54
0,54
0,54
0,54
0,54
0,83
0,77
0,77
0,77
0,60
0,74
0,54
0,54
0,56
0,56
0,56
0,54
0,54
0,59
0,54
0,54
0,54
0,54
0,54
0,86
0,86
0,60
1,20
0,80
0,86
0,86
0,60
1,03
15,5
10,4
39,5
60,0
47,2
133,4
42,4
96,2
59,2
5,0
228,1
78,0
8,9
186,8
48,2
7,4
163,4
46,4
5,7
67,7
46,5
6,8
56,4
92,6
5,7
159,4
42,6
3,9
105,1
82,1
21,3
1,0
44,0
147,3
42,6
5,6
76,2
5,3
17,8
191,8
29,9
15,7
45,0
22,6
74,6
5,4
50,4
34,1
13,1
76,7
6,0
78,2
77,8
3,3
127,1
48,2
7,7
53,4
64,1
41,0
132,6
112,9
40,7
48,8
15,2
41,1
11,0
11,0
23,4
23,4
28,7
28,7
28,7
12,1
17,6
17,6
36,8
28,3
28,3
34,3
17,6
17,6
26,7
17,6
17,6
20,1
17,6
17,6
14,5
17,6
17,6
32,2
17,6
17,6
19,1
23,1
10,8
10,8
23,1
28,3
28,3
28,3
28,3
28,3
19,4
20,3
20,3
20,3
17,6
26,9
28,3
28,3
15,6
15,6
15,6
28,3
28,3
23,1
28,3
28,3
28,3
28,3
28,3
11,2
11,2
17,6
29,0
13,4
11,2
11,3
17,9
29,6
Pàgina 7 de 8
Tramo [111-112]
Tramo [112-113]
Tramo [113-114]
Tramo [114-115]
Tramo [113-116]
Tramo [116-117]
Tramo [117-118]
Tramo [118-119]
Tramo [119-120]
Tramo [118-121]
Tramo [121-122]
Tramo [122-123]
Tramo [121-124]
Tramo [124-125]
Tramo [125-126]
Tramo [124-127]
Tramo [127-128]
Tramo [128-129]
Tramo [127-130]
Tramo [130-131]
Tramo [131-132]
Tramo [130-133]
Tramo [135-136]
Tramo [136-137]
Tramo [137-138]
Tramo [138-139]
Tramo [139-140]
Tramo [137-141]
Tramo [141-142]
Tramo [142-143]
Tramo [40-41]
Tramo [62-159]
Tramo [41-42]
Tramo [42-43]
Tramo [43-44]
Tramo [44-160]
Tramo [45-46]
Tramo [46-161]
Tramo [45-47]
Tramo [47-48]
Tramo [48-162]
Tramo [47-49]
Tramo [49-50]
Tramo [50-163]
Tramo [49-51]
Tramo [51-52]
Tramo [52-164]
Tramo [53-54]
Tramo [54-165]
Tramo [53-55]
Tramo [55-56]
Tramo [56-57]
Tramo [57-58]
Tramo [58-59]
Tramo [59-167]
Tramo [57-60]
Tramo [60-61]
Tramo [61-166]
2 1/2"
2 1/2"
1"
1"
2"
2"
2"
3/4"
3/4"
2"
3/4"
3/4"
2"
3/4"
3/4"
2"
3/4"
3/4"
2"
3/4"
3/4"
2"
1 1/2"
1 1/2"
1 1/4"
1 1/4"
1 1/4"
1"
1"
1"
2"
1"
2"
2"
3/4"
3/4"
3/4"
3/4"
2"
3/4"
3/4"
2"
3/4"
3/4"
2"
3/4"
3/4"
1"
1"
1 1/2"
1 1/2"
1 1/2"
1 1/4"
1 1/4"
1 1/4"
1"
1"
1"
3,0
5,4
0,4
0,3
3,0
2,0
1,3
1,0
0,3
4,2
1,0
0,3
4,5
1,0
0,4
3,9
1,0
0,2
4,4
1,0
0,3
8,5
8,4
0,4
1,1
0,5
0,2
3,2
0,9
0,3
2,7
0,4
2,0
1,6
1,0
0,5
1,0
0,5
4,5
1,0
0,6
3,9
1,0
0,3
4,4
1,0
0,5
0,4
0,3
1,1
8,4
0,6
1,1
0,8
0,3
3,2
0,9
0,4
0,6
0,6
0,8
0,6
0,4
0,6
0,6
0,8
0,6
0,4
0,8
0,6
0,4
0,8
0,6
0,4
0,8
0,6
0,4
0,8
0,6
0,4
0,6
0,6
0,8
0,6
0,6
0,4
0,6
0,6
1,0
0,0
0,6
0,0
1,9
0,0
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
0,3
1,9
0,0
1,9
0,0
1,0
0,6
0,0
1,9
0,6
0,0
1,0
0,6
0,0
11.595,4
11.595,4
1.254,7
1.254,7
10.340,6
10.340,6
10.340,6
791,2
791,2
9.549,4
791,2
791,2
8.758,2
791,2
791,2
7.967,0
791,2
791,2
7.175,8
791,2
791,2
6.384,6
5.129,9
5.129,9
3.035,8
3.035,8
3.035,8
2.094,1
2.094,1
2.094,1
10.340,6
1.254,7
10.340,6
10.340,6
791,2
791,2
791,2
791,2
8.758,2
791,2
791,2
7.967,0
791,2
791,2
7.175,8
791,2
791,2
1.254,7
1.254,7
5.129,9
5.129,9
5.129,9
3.035,8
3.035,8
3.035,8
2.094,1
2.094,1
2.094,1
0,86
0,86
0,60
0,60
1,30
1,30
1,30
0,59
0,59
1,20
0,59
0,59
1,10
0,59
0,59
1,00
0,59
0,59
0,90
0,59
0,59
0,80
1,03
1,03
0,83
0,83
0,83
0,99
0,99
0,99
1,30
0,60
1,30
1,30
0,59
0,59
0,59
0,59
1,10
0,59
0,59
1,00
0,59
0,59
0,90
0,59
0,59
0,60
0,60
1,03
1,03
1,03
0,83
0,83
0,83
0,99
0,99
0,99
41,2
67,8
21,7
15,6
116,7
88,9
64,3
42,3
23,2
135,8
41,9
23,2
121,1
42,1
24,3
89,6
42,1
19,6
81,4
42,1
22,8
120,9
267,3
29,6
45,6
26,4
18,9
170,7
71,9
44,9
123,2
6,9
88,1
53,4
66,6
10,8
68,4
11,5
118,8
67,7
13,0
86,8
68,1
7,9
79,4
67,4
11,2
40,9
4,8
60,4
264,4
19,1
70,3
33,8
7,5
194,4
73,4
20,9
11,3
11,3
17,9
17,9
34,1
34,1
34,1
23,8
23,8
29,3
23,8
23,8
24,8
23,8
23,8
20,7
23,8
23,8
16,9
23,8
23,8
13,6
29,6
29,6
23,5
23,5
23,5
47,1
47,1
47,1
33,9
17,6
33,9
33,9
23,5
23,5
23,5
23,5
24,6
23,5
23,5
20,5
23,5
23,5
16,8
23,5
23,5
17,6
17,6
29,4
29,4
29,4
23,3
23,3
23,3
46,7
46,7
46,7
Pàgina 8 de 8
ANNEX. INSTAL∙LACIÓ BAIXA TENSIÓ INSTALACIÓN DE BAJA TENSIÓN- MEMORIA DESCRIPTIVA
1. ANTECEDENTES.
2. OBJETO DEL PROYECTO.
3. REGLAMENTACION Y DISPOSICIONES OFICIALES Y PARTICULARES.
4. ACOMETIDA.
5. INSTALACIONES DE ENLACE.
5.1. CAJA DE PROTECCIÓN Y MEDIDA.
5.2. DERIVACION INDIVIDUAL.
5.3. DISPOSITIVOS GENERALES E INDIVIDUALES DE MANDO Y PROTECCION.
6. INSTALACIONES INTERIORES.
6.1. CONDUCTORES.
6.2. IDENTIFICACION DE CONDUCTORES.
6.3. SUBDIVISION DE LAS INSTALACIONES.
6.4. EQUILIBRADO DE CARGAS.
6.5. RESISTENCIA DE AISLAMIENTO Y RIGIDEZ DIELECTRICA.
6.6. CONEXIONES.
6.7. SISTEMAS DE INSTALACION.
7. PRESCRIPCIONES PARTICULARES PARA LOCALES DE REUNION.
7.1. ALIMENTACION DE LOS SERVICIOS DE SEGURIDAD.
7.2. ALUMBRADO DE EMERGENCIA.
7.3. PRESCRIPCIONES DE CARACTER GENERAL.
8. PROTECCION CONTRA SOBREINTENSIDADES.
9. PROTECCION CONTRA SOBRETENSIONES.
9.1. CATEGORÍAS DE LAS SOBRETENSIONES.
9.2. MEDIDAS PARA EL CONTROL DE LAS SOBRETENSIONES.
9.3. SELECCIÓN DE LOS MATERIALES EN LA INSTALACIÓN.
10. PROTECCION CONTRA CONTACTOS DIRECTOS E INDIRECTOS.
10.1. PROTECCION CONTRA CONTACTOS DIRECTOS.
Página 1 de 22
10.2. PROTECCION CONTRA CONTACTOS INDIRECTOS.
11. PUESTAS A TIERRA.
11.1. UNIONES A TIERRA.
11.2. RESISTENCIA DE LAS TOMAS DE TIERRA.
11.3. TOMAS DE TIERRA INDEPENDIENTES.
11.4. REVISION DE LAS TOMAS DE TIERRA.
12. RECEPTORES DE ALUMBRADO.
13. RECEPTORES A MOTOR.
Página 2 de 22
MEMORIA DESCRIPTIVA
1. ANTECEDENTES.
Se redacta el presente proyecto de INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN a petición
del EXCMO. AYUNTAMIENTO DE BELL-LLOC D’URGELL, con C.I.F.:
y domicilio
social en
nº
, de
, y a instancia de la
Consejería de Trabajo e Industria, Delegación Provincial de LLEIDA y del Excmo. Ayuntamiento de
BELL-LLOC.
2. OBJETO DEL PROYECTO.
El objeto del presente proyecto es el de exponer ante los Organismos Competentes que la
instalación que nos ocupa reúne las condiciones y garantías mínimas exigidas por la reglamentación
vigente, con el fin de obtener la Autorización Administrativa y la de Ejecución de la instalación, así
como servir de base a la hora de proceder a la ejecución de dicho proyecto.
3. REGLAMENTACION Y DISPOSICIONES OFICIALES Y PARTICULARES.
El presente proyecto recoge las características de los materiales, los cálculos que justifican su
empleo y la forma de ejecución de las obras a realizar, dando con ello cumplimiento a las siguientes
disposiciones:
-
-
Ley 7/1994, de 18 de mayo, de Protección Ambiental.
Reglamento de Calificación Ambiental.
Reglamento Electrotécnico para Baja Tensión e Instrucciones Técnicas Complementarias (Real
Decreto 842/2002 de 2 de Agosto de 2002).
Real Decreto 1955/2000 de 1 de Diciembre, por el que se regulan las Actividades de Transporte,
Distribución, Comercialización, Suministro y Procedimientos de Autorización de Instalaciones de
Energía Eléctrica.
Código Técnico de la Edificación, DB SI sobre Seguridad en caso de incendio.
Código Técnico de la Edificación, DB HE sobre Ahorro de energía.
Código Técnico de la Edificación, DB SU sobre Seguridad de utilización.
NBE CA-88 de Condiciones Acústicas en los Edificios.
Reglamento de Instalaciones Térmicas en los Edificios.
Normas Técnicas para la accesibilidad y la eliminación de barreras arquitectónicas, urbanísticas y
en el transporte.
Ley 31/1995, de 8 de noviembre, de Prevención de Riesgos Laborales.
Real Decreto 1627/1997 de 24 de octubre de 1.997, sobre Disposiciones mínimas de seguridad y
salud en las obras.
Real Decreto 486/1997 de 14 de abril de 1997, sobre Disposiciones mínimas de seguridad y salud
en los lugares de trabajo.
Real Decreto 485/1997 de 14 de abril de 1997, sobre Disposiciones mínimas en materia de
señalización de seguridad y salud en el trabajo.
Real Decreto 1215/1997 de 18 de julio de 1997, sobre Disposiciones mínimas de seguridad y salud
para la utilización por los trabajadores de los equipos de trabajo.
Real Decreto 773/1997 de 30 de mayo de 1997, sobre Disposiciones mínimas de seguridad y salud
relativas a la utilización por los trabajadores de equipos de protección individual.
4. ACOMETIDA.
Es parte de la instalación de la red de distribución, que alimenta la caja general de protección o
unidad funcional equivalente (CGP). Los conductores serán de aluminio. Esta línea está regulada por
la ITC-BT-11.
Página 3 de 22
Atendiendo a su trazado, al sistema de instalación y a las características de la red, la acometida
será:
- Subterránea. Los cables serán aislados, de tensión asignada 0,6/1 kV, y podrán instalarse
directamente enterrados, enterrados bajo tubo o en galerías, atarjeas o canales revisables.
Por último, cabe señalar que la acometida será parte de la instalación constituida por la Empresa
Suministradora, por lo tanto su diseño debe basarse en las normas particulares de ella.
5. INSTALACIONES DE ENLACE.
5.1. CAJA DE PROTECCIÓN Y MEDIDA.
Para el caso de suministros a un único usuario, al no existir línea general de alimentación, se
colocará en un único elemento la caja general de protección y el equipo de medida; dicho elemento se
denominará caja de protección y medida. En consecuencia, el fusible de seguridad ubicado antes del
contador coincide con el fusible que incluye una CGP.
Se instalarán preferentemente sobre las fachadas exteriores de los edificios, en lugares de libre y
permanente acceso. Su situación se fijará de común acuerdo entre la propiedad y la empresa
suministradora.
Se instalará siempre en un nicho en pared, que se cerrará con una puerta preferentemente
metálica, con grado de protección IK 10 según UNE-EN 50.102, revestida exteriormente de acuerdo
con las características del entorno y estará protegida contra la corrosión, disponiendo de una cerradura
o candado normalizado por la empresa suministradora. Los dispositivos de lectura de los equipos de
medida deberán estar situados a una altura comprendida entre 0,70 y 1,80 m.
En el nicho se dejarán previstos los orificios necesarios para alojar los conductos de entrada de
la acometida.
Las cajas de protección y medida a utilizar corresponderán a uno de los tipos recogidos en las
especificaciones técnicas de la empresa suministradora que hayan sido aprobadas por la
Administración Pública competente, en función del número y naturaleza del suministro. Dentro de las
mismas se instalarán cortacircuitos fusibles en todos los conductores de fase o polares, con poder de
corte al menos igual a la corriente de cortocircuito prevista en el punto de su instalación.
Las cajas de protección y medida cumplirán todo lo que sobre el particular se indica en la
Norma UNE-EN 60.439 -1, tendrán grado de inflamabilidad según se indica en la norma UNE-EN
60.439 -3, una vez instaladas tendrán un grado de protección IP43 según UNE 20.324 e IK 09 según
UNE-EN 50.102 y serán precintables.
La envolvente deberá disponer de la ventilación interna necesaria que garantice la no formación
de condensaciones. El material transparente para la lectura será resistente a la acción de los rayos
ultravioleta.
Las disposiciones generales de este tipo de caja quedan recogidas en la ITC-BT-13.
5.2. DERIVACION INDIVIDUAL.
Es la parte de la instalación que, partiendo de la caja de protección y medida, suministra energía
eléctrica a una instalación de usuario. Comprende los fusibles de seguridad, el conjunto de medida y
los dispositivos generales de mando y protección. Está regulada por la ITC-BT-15.
Página 4 de 22
Las derivaciones individuales estarán constituidas por:
- Conductores aislados en el interior de tubos empotrados.
- Conductores aislados en el interior de tubos enterrados.
- Conductores aislados en el interior de tubos en montaje superficial.
- Conductores aislados en el interior de canales protectoras cuya tapa sólo se pueda abrir con la ayuda
de un útil.
Los conductores a utilizar serán de cobre, aislados y normalmente unipolares, siendo su
tensión asignada 450/750 V como mínimo. Para el caso de cables multiconductores o para el caso de
derivaciones individuales en el interior de tubos enterrados, el aislamiento de los conductores será de
tensión asignada 0,6/1 kV. La sección mínima será de 6 mm² para los cables polares, neutro y
protección y de 1,5 mm² para el hilo de mando (para aplicación de las diferentes tarifas), que será de
color rojo.
Los cables serán no propagadores del incendio y con emisión de humos y opacidad reducida.
Los cables con características equivalentes a las de la norma UNE 21.123 parte 4 ó 5 o a la norma
UNE 211002 cumplen con esta prescripción.
La caída de tensión máxima admisible será, para el caso de derivaciones individuales en
suministros para un único usuario en que no existe línea general de alimentación, del 1,5 %.
5.3. DISPOSITIVOS GENERALES E INDIVIDUALES DE MANDO Y PROTECCION.
Los dispositivos generales de mando y protección se situarán lo más cerca posible del punto de
entrada de la derivación individual. En establecimientos en los que proceda, se colocará una caja para
el interruptor de control de potencia, inmediatamente antes de los demás dispositivos, en
compartimento independiente y precintable. Dicha caja se podrá colocar en el mismo cuadro donde se
coloquen los dispositivos generales de mando y protección.
Los dispositivos individuales de mando y protección de cada uno de los circuitos, que son el
origen de la instalación interior, podrán instalarse en cuadros separados y en otros lugares.
En locales de uso común o de pública concurrencia deberán tomarse las precauciones
necesarias para que los dispositivos de mando y protección no sean accesibles al público en general.
La altura a la cual se situarán los dispositivos generales e individuales de mando y protección
de los circuitos, medida desde el nivel del suelo, estará comprendida entre 1 y 2 m.
Las envolventes de los cuadros se ajustarán a las normas UNE 20.451 y UNE-EN 60.439
con un grado de protección mínimo IP 30 según UNE 20.324 e IK07 según UNE-EN 50.102.
envolvente para el interruptor de control de potencia será precintable y sus dimensiones estarán
acuerdo con el tipo de suministro y tarifa a aplicar. Sus características y tipo corresponderán a
modelo oficialmente aprobado.
-3,
La
de
un
El instalador fijará de forma permanente sobre el cuadro de distribución una placa, impresa con
caracteres indelebles, en la que conste su nombre o marca comercial, fecha en que se realizó la
instalación, así como la intensidad asignada del interruptor general automático.
Los dispositivos generales e individuales de mando y protección serán, como mínimo:
- Un interruptor general automático de corte omnipolar, de intensidad nominal mínima 25 A, que
permita su accionamiento manual y que esté dotado de elementos de protección contra sobrecarga y
cortocircuitos (según ITC-BT-22). Tendrá poder de corte suficiente para la intensidad de cortocircuito
que pueda producirse en el punto de su instalación, de 4,5 kA como mínimo. Este interruptor será
independiente del interruptor de control de potencia.
Página 5 de 22
- Un interruptor diferencial general, de intensidad asignada superior o igual a la del interruptor general,
destinado a la protección contra contactos indirectos de todos los circuitos (según ITC-BT-24). Se
cumplirá la siguiente condición:
Ra x Ia ≤ U
donde:
"Ra" es la suma de las resistencias de la toma de tierra y de los conductores de protección de masas.
"Ia" es la corriente que asegura el funcionamiento del dispositivo de protección (corriente diferencialresidual asignada).
"U" es la tensión de contacto límite convencional (50 V en locales secos y 24 V en locales húmedos).
Si por el tipo o carácter de la instalación se instalase un interruptor diferencial por cada circuito
o grupo de circuitos, se podría prescindir del interruptor diferencial general, siempre que queden
protegidos todos los circuitos. En el caso de que se instale más de un interruptor diferencial en serie,
existirá una selectividad entre ellos.
Todas las masas de los equipos eléctricos protegidos por un mismo dispositivo de protección,
deben ser interconectadas y unidas por un conductor de protección a una misma toma de tierra.
- Dispositivos de corte omnipolar, destinados a la protección contra sobrecargas y cortocircuitos de
cada uno de los circuitos interiores (según ITC-BT-22).
- Dispositivo de protección contra sobretensiones, según ITC-BT-23, si fuese necesario.
6. INSTALACIONES INTERIORES.
6.1. CONDUCTORES.
Los conductores y cables que se empleen en las instalaciones serán de cobre y serán siempre
aislados. La tensión asignada no será inferior a 450/750 V. La sección de los conductores a utilizar se
determinará de forma que la caída de tensión entre el origen de la instalación interior y cualquier punto
de utilización sea menor del 3 % para alumbrado y del 5 % para los demás usos.
El valor de la caída de tensión podrá compensarse entre la de la instalación interior (3-5 %) y la
de la derivación individual (1,5 %), de forma que la caída de tensión total sea inferior a la suma de los
valores límites especificados para ambas (4,5-6,5 %). Para instalaciones que se alimenten
directamente en alta tensión, mediante un transformador propio, se considerará que la instalación
interior de baja tensión tiene su origen a la salida del transformador, siendo también en este caso las
caídas de tensión máximas admisibles del 4,5 % para alumbrado y del 6,5 % para los demás usos.
En instalaciones interiores, para tener en cuenta las corrientes armónicas debidas a cargas no
lineales y posibles desequilibrios, salvo justificación por cálculo, la sección del conductor neutro será
como mínimo igual a la de las fases. No se utilizará un mismo conductor neutro para varios circuitos.
Las intensidades máximas admisibles, se regirán en su totalidad por lo indicado en la Norma
UNE 20.460-5-523 y su anexo Nacional.
Los conductores de protección tendrán una sección mínima igual a la fijada en la tabla siguiente:
Sección conductores fase (mm²)
Sf ≤ 16
16 < S f ≤ 35
Sf > 35
Sección conductores protección (mm²)
Sf
16
Sf/2
Página 6 de 22
6.2. IDENTIFICACION DE CONDUCTORES.
Los conductores de la instalación deben ser fácilmente identificables, especialmente por lo que
respecta al conductor neutro y al conductor de protección. Esta identificación se realizará por los
colores que presenten sus aislamientos. Cuando exista conductor neutro en la instalación o se prevea
para un conductor de fase su pase posterior a conductor neutro, se identificarán éstos por el color azul
claro. Al conductor de protección se le identificará por el color verde-amarillo. Todos los conductores de
fase, o en su caso, aquellos para los que no se prevea su pase posterior a neutro, se identificarán por
los colores marrón, negro o gris.
6.3. SUBDIVISION DE LAS INSTALACIONES.
Las instalaciones se subdividirán de forma que las perturbaciones originadas por averías que
puedan producirse en un punto de ellas, afecten solamente a ciertas partes de la instalación, por
ejemplo a un sector del edificio, a una planta, a un solo local, etc., para lo cual los dispositivos de
protección de cada circuito estarán adecuadamente coordinados y serán selectivos con los dispositivos
generales de protección que les precedan.
Toda instalación se dividirá en varios circuitos, según las necesidades, a fin de:
- evitar las interrupciones innecesarias de todo el circuito y limitar las consecuencias de un fallo.
- facilitar las verificaciones, ensayos y mantenimientos.
- evitar los riesgos que podrían resultar del fallo de un solo circuito que pudiera dividirse, como por
ejemplo si solo hay un circuito de alumbrado.
6.4. EQUILIBRADO DE CARGAS.
Para que se mantenga el mayor equilibrio posible en la carga de los conductores que forman
parte de una instalación, se procurará que aquella quede repartida entre sus fases o conductores
polares.
6.5. RESISTENCIA DE AISLAMIENTO Y RIGIDEZ DIELECTRICA.
Las instalaciones deberán presentar una resistencia de aislamiento al menos igual a los valores
indicados en la tabla siguiente:
Tensión nominal instalación Tensión ensayo corriente continua (V)
MBTS o MBTP
≤ 500 V
> 500 V
250
500
1000
Resistencia de aislamiento (MΩ)
≥ 0,25
≥ 0,50
≥ 1,00
La rigidez dieléctrica será tal que, desconectados los aparatos de utilización (receptores), resista
durante 1 minuto una prueba de tensión de 2U + 1000 V a frecuencia industrial, siendo U la tensión
máxima de servicio expresada en voltios, y con un mínimo de 1.500 V.
Las corrientes de fuga no serán superiores, para el conjunto de la instalación o para cada uno de
los circuitos en que ésta pueda dividirse a efectos de su protección, a la sensibilidad que presenten los
interruptores diferenciales instalados como protección contra los contactos indirectos.
6.6. CONEXIONES.
En ningún caso se permitirá la unión de conductores mediante conexiones y/o derivaciones por
simple retorcimiento o arrollamiento entre sí de los conductores, sino que deberá realizarse siempre
utilizando bornes de conexión montados individualmente o constituyendo bloques o regletas de
Página 7 de 22
conexión; puede permitirse asimismo, la utilización de bridas de conexión. Siempre deberán realizarse
en el interior de cajas de empalme y/o de derivación.
Si se trata de conductores de varios alambres cableados, las conexiones se realizarán de
forma que la corriente se reparta por todos los alambres componentes.
6.7. SISTEMAS DE INSTALACION.
6.7.1. Prescripciones Generales.
Varios circuitos pueden encontrarse en el mismo tubo o en el mismo compartimento de canal si
todos los conductores están aislados para la tensión asignada más elevada.
En caso de proximidad de canalizaciones eléctricas con otras no eléctricas, se dispondrán de
forma que entre las superficies exteriores de ambas se mantenga una distancia mínima de 3 cm. En
caso de proximidad con conductos de calefacción, de aire caliente, vapor o humo, las canalizaciones
eléctricas se establecerán de forma que no puedan alcanzar una temperatura peligrosa y, por
consiguiente, se mantendrán separadas por una distancia conveniente o por medio de pantallas
calorífugas.
Las canalizaciones eléctricas no se situarán por debajo de otras canalizaciones que puedan
dar lugar a condensaciones, tales como las destinadas a conducción de vapor, de agua, de gas, etc., a
menos que se tomen las disposiciones necesarias para proteger las canalizaciones eléctricas contra
los efectos de estas condensaciones.
Las canalizaciones deberán estar dispuestas de forma que faciliten su maniobra, inspección y
acceso a sus conexiones. Las canalizaciones eléctricas se establecerán de forma que mediante la
conveniente identificación de sus circuitos y elementos, se pueda proceder en todo momento a
reparaciones, transformaciones, etc.
En toda la longitud de los pasos de canalizaciones a través de elementos de la construcción,
tales como muros, tabiques y techos, no se dispondrán empalmes o derivaciones de cables, estando
protegidas contra los deterioros mecánicos, las acciones químicas y los efectos de la humedad.
Las cubiertas, tapas o envolventes, mandos y pulsadores de maniobra de aparatos tales como
mecanismos, interruptores, bases, reguladores, etc, instalados en los locales húmedos o mojados,
serán de material aislante.
6.7.2. Conductores aislados bajo tubos protectores.
Los cables utilizados serán de tensión asignada no inferior a 450/750 V.
El diámetro exterior mínimo de los tubos, en función del número y la sección de los conductores a
conducir, se obtendrá de las tablas indicadas en la ITC-BT-21, así como las características mínimas
según el tipo de instalación.
Para la ejecución de las canalizaciones bajo tubos protectores, se tendrán en cuenta las
prescripciones generales siguientes:
- El trazado de las canalizaciones se hará siguiendo líneas verticales y horizontales o paralelas a las
aristas de las paredes que limitan el local donde se efectúa la instalación.
- Los tubos se unirán entre sí mediante accesorios adecuados a su clase que aseguren la continuidad
de la protección que proporcionan a los conductores.
- Los tubos aislantes rígidos curvables en caliente podrán ser ensamblados entre sí en caliente,
recubriendo el empalme con una cola especial cuando se precise una unión estanca.
- Las curvas practicadas en los tubos serán continuas y no originarán reducciones de sección
Página 8 de 22
inadmisibles. Los radios mínimos de curvatura para cada clase de tubo serán los especificados por el
fabricante conforme a UNE-EN
- Será posible la fácil introducción y retirada de los conductores en los tubos después de colocarlos y
fijados éstos y sus accesorios, disponiendo para ello los registros que se consideren convenientes, que
en tramos rectos no estarán separados entre sí más de 15 metros. El número de curvas en ángulo
situadas entre dos registros consecutivos no será superior a 3. Los conductores se alojarán
normalmente en los tubos después de colocados éstos.
- Los registros podrán estar destinados únicamente a facilitar la introducción y retirada de los
conductores en los tubos o servir al mismo tiempo como cajas de empalme o derivación.
- Las conexiones entre conductores se realizarán en el interior de cajas apropiadas de material aislante
y no propagador de la llama. Si son metálicas estarán protegidas contra la corrosión. Las dimensiones
de estas cajas serán tales que permitan alojar holgadamente todos los conductores que deban
contener. Su profundidad será al menos igual al diámetro del tubo mayor más un 50 % del mismo, con
un mínimo de 40 mm. Su diámetro o lado interior mínimo será de 60 mm. Cuando se quieran hacer
estancas las entradas de los tubos en las cajas de conexión, deberán emplearse prensaestopas o
racores adecuados.
- En los tubos metálicos sin aislamiento interior, se tendrá en cuenta la posibilidad de que se produzcan
condensaciones de agua en su interior, para lo cual se elegirá convenientemente el trazado de su
instalación, previendo la evacuación y estableciendo una ventilación apropiada en el interior de los
tubos mediante el sistema adecuado, como puede ser, por ejemplo, el uso de una "T" de la que uno de
los brazos no se emplea.
- Los tubos metálicos que sean accesibles deben ponerse a tierra. Su continuidad eléctrica deberá
quedar convenientemente asegurada. En el caso de utilizar tubos metálicos flexibles, es necesario que
la distancia entre dos puestas a tierra consecutivas de los tubos no exceda de 10 metros.
- No podrán utilizarse los tubos metálicos como conductores de protección o de neutro.
Cuando los tubos se instalen en montaje superficial, se tendrán en cuenta, además, las siguientes
prescripciones:
- Los tubos se fijarán a las paredes o techos por medio de bridas o abrazaderas protegidas contra la
corrosión y sólidamente sujetas. La distancia entre éstas será, como máximo, de 0,50 metros. Se
dispondrán fijaciones de una y otra parte en los cambios de dirección, en los empalmes y en la
proximidad inmediata de las entradas en cajas o aparatos.
- Los tubos se colocarán adaptándose a la superficie sobre la que se instalan, curvándose o usando los
accesorios necesarios.
- En alineaciones rectas, las desviaciones del eje del tubo respecto a la línea que une los puntos
extremos no serán superiores al 2 por 100.
- Es conveniente disponer los tubos, siempre que sea posible, a una altura mínima de 2,50 metros
sobre el suelo, con objeto de protegerlos de eventuales daños mecánicos.
Cuando los tubos se coloquen empotrados, se tendrán en cuenta, además, las siguientes
prescripciones:
- En la instalación de los tubos en el interior de los elementos de la construcción, las rozas no pondrán
en peligro la seguridad de las paredes o techos en que se practiquen. Las dimensiones de las rozas
serán suficientes para que los tubos queden recubiertos por una capa de 1 centímetro de espesor,
como mínimo. En los ángulos, el espesor de esta capa puede reducirse a 0,5 centímetros.
- No se instalarán entre forjado y revestimiento tubos destinados a la instalación eléctrica de las plantas
inferiores.
- Para la instalación correspondiente a la propia planta, únicamente podrán instalarse, entre forjado y
revestimiento, tubos que deberán quedar recubiertos por una capa de hormigón o mortero de 1
centímetro de espesor, como mínimo, además del revestimiento.
- En los cambios de dirección, los tubos estarán convenientemente curvados o bien provistos de codos
o "T" apropiados, pero en este último caso sólo se admitirán los provistos de tapas de registro.
- Las tapas de los registros y de las cajas de conexión quedarán accesibles y desmontables una vez
finalizada la obra. Los registros y cajas quedarán enrasados con la superficie exterior del revestimiento
Página 9 de 22
de la pared o techo cuando no se instalen en el interior de un alojamiento cerrado y practicable.
- En el caso de utilizarse tubos empotrados en paredes, es conveniente disponer los recorridos
horizontales a 50 centímetros como máximo, de suelo o techos y los verticales a una distancia de los
ángulos de esquinas no superior a 20 centímetros.
6.7.3. Conductores aislados fijados directamente sobre las paredes.
Estas instalaciones se establecerán con cables de tensiones asignadas no inferiores a 0,6/1
kV, armados, provistos de aislamiento y cubierta.
Para la ejecución de las canalizaciones se tendrán en cuenta las siguientes prescripciones:
- Se fijarán sobre las paredes por medio de bridas, abrazaderas, o collares de forma que no
perjudiquen las cubiertas de los mismos.
- Con el fin de que los cables no sean susceptibles de doblarse por efecto de su propio peso, los
puntos de fijación de los mismos estarán suficientemente próximos. La distancia entre dos puntos de
fijación sucesivos, no excederá de 0,40 metros.
- Cuando los cables deban disponer de protección mecánica por el lugar y condiciones de instalación
en que se efectúe la misma, se utilizarán cables armados. En caso de no utilizar estos cables, se
establecerá una protección mecánica complementaria sobre los mismos.
- Se evitará curvar los cables con un radio demasiado pequeño y salvo prescripción en contra fijada en
la Norma UNE correspondiente al cable utilizado, este radio no será inferior a 10 veces el diámetro
exterior del cable.
- Los cruces de los cables con canalizaciones no eléctricas se podrán efectuar por la parte anterior o
posterior a éstas, dejando una distancia mínima de 3 cm entre la superficie exterior de la canalización
no eléctrica y la cubierta de los
cables cuando el cruce se efectúe por la parte anterior de aquélla.
- Los extremos de los cables serán estancos cuando las características de los locales o
emplazamientos así lo exijan, utilizándose a este fin cajas u otros dispositivos adecuados. La
estanqueidad podrá quedar asegurada con la ayuda de prensaestopas.
- Los empalmes y conexiones se harán por medio de cajas o dispositivos equivalentes provistos de
tapas desmontables que aseguren a la vez la continuidad de la protección mecánica establecida, el
aislamiento y la inaccesibilidad de las conexiones y permitiendo su verificación en caso necesario.
6.7.4. Conductores aislados en el interior de huecos de la construcción.
Los cables utilizados serán de tensión asignada no inferior a 450/750 V, con cubierta de
protección.
Los cables o tubos podrán instalarse directamente en los huecos de la construcción totalmente
construidos con materiales incombustibles de resistencia al fuego RF-120 como mínimo.
Los huecos en la construcción admisibles para estas canalizaciones podrán estar dispuestos
en muros, paredes, vigas, forjados o techos, adoptando la forma de conductos continuos o bien estarán
comprendidos entre dos superficies paralelas como en el caso de falsos techos o muros con cámaras
de aire.
La sección de los huecos será, como mínimo, igual a cuatro veces la ocupada por los cables o
tubos, y su dimensión más pequeña no será inferior a dos veces el diámetro exterior de mayor sección
de éstos, con un mínimo de 20 milímetros.
Las paredes que separen un hueco que contenga canalizaciones eléctricas de los locales
inmediatos, tendrán suficiente solidez para proteger éstas contra acciones previsibles.
Se evitarán, dentro de lo posible, las asperezas en el interior de los huecos y los cambios de
dirección de los mismos en un número elevado o de pequeño radio de curvatura.
Página 10 de 22
La canalización podrá ser reconocida y conservada sin que sea necesaria la destrucción parcial
de las paredes, techos, etc., o sus guarnecidos y decoraciones.
Los empalmes y derivaciones de los cables serán accesibles, disponiéndose para ellos las
cajas de derivación adecuadas.
Se evitará que puedan producirse infiltraciones, fugas o condensaciones de agua que puedan
penetrar en el interior del hueco, prestando especial atención a la impermeabilidad de sus muros
exteriores, así como a la proximidad de tuberías de conducción de líquidos, penetración de agua al
efectuar la limpieza de suelos, posibilidad de acumulación de aquélla en partes bajas del hueco, etc.
6.7.5. Conductores aislados bajo canales protectoras.
La canal protectora es un material de instalación constituido por un perfil de paredes perforadas
o no, destinado a alojar conductores o cables y cerrado por una tapa desmontable. Los cables
utilizados serán de tensión asignada no inferior a 450/750 V.
Las canales protectoras tendrán un grado de protección IP4X y estarán clasificadas como
"canales con tapa de acceso que sólo pueden abrirse con herramientas". En su interior se podrán
colocar mecanismos tales como interruptores, tomas de corriente, dispositivos de mando y control, etc,
siempre que se fijen de acuerdo con las instrucciones del fabricante. También se podrán realizar
empalmes de conductores en su interior y conexiones a los mecanismos.
Las canales protectoras para aplicaciones no ordinarias deberán tener unas características
mínimas de resistencia al impacto, de temperatura mínima y máxima de instalación y servicio, de
resistencia a la penetración de objetos sólidos y de resistencia a la penetración de agua, adecuadas a
las condiciones del emplazamiento al que se destina; asimismo las canales serán no propagadoras de
la llama. Dichas características serán conformes a las normas de la serie UNE-EN 50.085.
El trazado de las canalizaciones se hará siguiendo preferentemente líneas verticales y
horizontales o paralelas a las aristas de las paredes que limitan al local donde se efectúa la instalación.
Las canales con conductividad eléctrica deben conectarse a la red de tierra, su continuidad
eléctrica quedará convenientemente asegurada.
La tapa de las canales quedará siempre accesible.
7. PRESCRIPCIONES PARTICULARES PARA LOCALES DE REUNION.
7.1. ALIMENTACION DE LOS SERVICIOS DE SEGURIDAD.
Para los servicios de seguridad la fuente de energía debe ser elegida de forma que la
alimentación esté asegurada durante un tiempo apropiado.
Para que los servicios de seguridad funcionen en caso de incendio, los equipos y materiales
utilizados deben presentar, por construcción o por instalación, una resistencia al fuego de duración
apropiada.
Se elegirán preferentemente medidas de protección contra los contactos indirectos sin corte
automático al primer defecto.
Se pueden utilizar las siguientes fuentes de alimentación:
- Baterías de acumuladores.
- Generadores independientes.
- Derivaciones separadas de la red de distribución, independientes de la alimentación normal.
Página 11 de 22
Las fuentes para servicios complementarios o de seguridad deben estar instaladas en lugar fijo
y de forma que no puedan ser afectadas por el fallo de la fuente normal. Además, con excepción de los
equipos autónomos, deberán cumplir las siguientes condiciones:
- se instalarán en emplazamiento apropiado, accesible solamente a las personas cualificadas o
expertas.
- el emplazamiento estará convenientemente ventilado, de forma que los gases y los humos que
produzcan no puedan propagarse en los locales accesibles a las personas.
- no se admiten derivaciones separadas, independientes y alimentadas por una red de distribución
pública, salvo si se asegura que las dos derivaciones no puedan fallar simultáneamente.
- cuando exista una sola fuente para los servicios de seguridad, ésta no debe ser utilizada para otros
usos. Sin embargo, cuando se dispone de varias fuentes, pueden utilizarse igualmente como fuentes
de reemplazamiento, con la condición, de que en caso de fallo de una de ellas, la potencia todavía
disponible sea suficiente para garantizar la puesta en funcionamiento de todos los servicios de
seguridad, siendo necesario generalmente, el corte automático de los equipos no concernientes a la
seguridad.
La puesta en funcionamiento se realizará al producirse la falta de tensión en los circuitos
alimentados por los diferentes suministros procedentes de la Empresa o Empresas distribuidoras de
energía eléctrica, o cuando aquella tensión descienda por debajo del 70% de su valor nominal.
La capacidad mínima de una fuente propia de energía será, como norma general, la precisa
para proveer al alumbrado de seguridad (alumbrado de evacuación, alumbrado ambiente y alumbrado
de zonas de alto riesgo).
Todos los locales de pública concurrencia deberán disponer de alumbrado de emergencia
(alumbrado de seguridad y alumbrado de reemplazamiento, según los casos).
Deberán disponer de suministro de socorro (potencia mínima: 15 % del total contratado) los
locales de espectáculos y actividades recreativas cualquiera que sea su ocupación y los locales de
reunión, trabajo y usos sanitarios con una ocupación prevista de más de 300 personas.
Deberán disponer de suministro de reserva (potencia mínima: 25 % del total contratado):
- Hospitales, clínicas, sanatorios, ambulatorios y centros de salud.
- Estaciones de viajeros y aeropuertos.
- Estacionamientos subterráneos para más de 100 vehículos.
- Establecimientos comerciales o agrupaciones de éstos en centros comerciales de más de 2.000 m²
de superficie.
- Estadios y pabellones deportivos.
7.2. ALUMBRADO DE EMERGENCIA.
Las instalaciones destinadas a alumbrado de emergencia tienen por objeto asegurar, en caso
de fallo de la alimentación al alumbrado normal, la iluminación en los locales y accesos hasta las
salidas, para una eventual evacuación del público o iluminar otros puntos que se señalen.
La alimentación del alumbrado de emergencia será automática con corte breve (alimentación
automática disponible en 0,5 s como máximo).
7.2.1. Alumbrado de seguridad.
Es el alumbrado de emergencia previsto para garantizar la seguridad de las personas que
evacuen una zona o que tienen que terminar un trabajo potencialmente peligroso antes de abandonar
la zona.
Página 12 de 22
El alumbrado de seguridad estará previsto para entrar en funcionamiento automáticamente
cuando se produce el fallo del alumbrado general o cuando la tensión de éste baje a menos del 70% de
su valor nominal.
La instalación de este alumbrado será fija y estará provista de fuentes propias de energía. Sólo
se podrá utilizar el suministro exterior para proceder a su carga, cuando la fuente propia de energía
esté constituida por baterías de acumuladores o aparatos autónomos automáticos.
Alumbrado de evacuación.
Es la parte del alumbrado de seguridad previsto para garantizar el reconocimiento y la
utilización de los medios o rutas de evacuación cuando los locales estén o puedan estar ocupados.
En rutas de evacuación, el alumbrado de evacuación debe proporcionar, a nivel del suelo y en
el eje de los pasos principales, una iluminancia horizontal mínima de 1 lux. En los puntos en los que
estén situados los equipos de las instalaciones de protección contra incendios que exijan utilización
manual y en los cuadros de distribución del alumbrado, la iluminancia mínima será de 5 lux. La relación
entre la iluminancia máxima y la mínima en el eje de los pasos principales será menor de 40.
El alumbrado de evacuación deberá poder funcionar, cuando se produzca el fallo de la
alimentación normal, como mínimo durante una hora, proporcionando la iluminancia prevista.
7.2.2. Alumbrado de reemplazamiento.
Parte del alumbrado de emergencia que permite la continuidad de las actividades normales.
Cuando el alumbrado de reemplazamiento proporcione una iluminancia inferior al alumbrado normal, se
usará únicamente para terminar el trabajo con seguridad.
7.2.3. Lugares en que deberá instalarse alumbrado de emergencia.
Con alumbrado de seguridad.
Es obligatorio situar el alumbrado de seguridad en las siguientes zonas de los locales de
pública concurrencia:
a) en todos los recintos cuya ocupación sea mayor de 100 personas.
b) los recorridos generales de evacuación de zonas destinadas a usos residencial u hospitalario y los
de zonas destinadas a cualquier otro uso que estén previstos para la evacuación de más de 100
personas.
c) en los aseos generales de planta en edificios de acceso público.
d) en los estacionamientos cerrados y cubiertos para más de 5 vehículos, incluidos los pasillos y las
escaleras que conduzcan desde aquellos hasta el exterior o hasta las zonas generales del edificio.
e) en los locales que alberguen equipos generales de las instalaciones de protección.
f) en las salidas de emergencia y en las señales de seguridad reglamentarias.
g) en todo cambio de dirección de la ruta de evacuación.
h) en toda intersección de pasillos con las rutas de evacuación.
i) en el exterior del edificio, en la vecindad inmediata a la salida.
j) a menos de 2 m de las escaleras, de manera que cada tramo de escaleras reciba una iluminación
directa.
k) a menos de 2 m de cada cambio de nivel.
l) a menos de 2 m de cada puesto de primeros auxilios.
m) a menos de 2 m de cada equipo manual destinado a la prevención y extinción de incendios.
n) en los cuadros de distribución de la instalación de alumbrado de las zonas indicadas anteriormente.
En las zonas incluidas en los apartados m) y n), el alumbrado de seguridad proporcionará una
iluminancia mínima de 5 lux al nivel de operación.
Página 13 de 22
Solo se instalará alumbrado de seguridad para zonas de alto riesgo en las zonas que así lo
requieran.
Con alumbrado de reemplazamiento.
En las zonas de hospitalización, la instalación de alumbrado de emergencia proporcionará una
iluminancia no inferior de 5 lux y durante 2 horas como mínimo. Las salas de intervención, las
destinadas a tratamiento intensivo, las salas de curas, paritorios, urgencias dispondrán de un
alumbrado de reemplazamiento que proporcionará un nivel de iluminancia igual al del alumbrado
normal durante 2 horas como mínimo.
7.2.4. Prescripciones de los aparatos para alumbrado de emergencia.
Aparatos autónomos para alumbrado de emergencia.
Luminaria que proporciona alumbrado de emergencia de tipo permanente o no permanente en
la que todos los elementos, tales como la batería, la lámpara, el conjunto de mando y los dispositivos
de verificación y control, si existen, están contenidos dentro de la luminaria o a una distancia inferior a 1
m de ella.
Luminaria alimentada por fuente central.
Luminaria que proporciona alumbrado de emergencia de tipo permanente o no permanente y
que está alimentada a partir de un sistema de alimentación de emergencia central, es decir, no
incorporado en la luminaria.
Las líneas que alimentan directamente los circuitos individuales de los alumbrados de
emergencia alimentados por fuente central, estarán protegidas por interruptores automáticos con una
intensidad nominal de 10 A como máximo. Una misma línea no podrá alimentar más de 12 puntos de
luz o, si en la dependencia o local considerado existiesen varios puntos de luz para alumbrado de
emergencia, éstos deberán ser repartidos, al menos, entre dos líneas diferentes, aunque su número
sea inferior a doce.
Las canalizaciones que alimenten los alumbrados de emergencia alimentados por fuente
central se dispondrán, cuando se instalen sobre paredes o empotradas en ellas, a 5 cm como mínimo,
de otras canalizaciones eléctricas y, cuando se instalen en huecos de la construcción estarán
separadas de éstas por tabiques incombustibles no metálicos.
7.3. PRESCRIPCIONES DE CARACTER GENERAL.
Las instalaciones en los locales de pública concurrencia, cumplirán las condiciones de carácter
general que a continuación se señalan.
- Los aparatos receptores que consuman más de 16 amperios se alimentarán directamente desde el
cuadro general o desde los secundarios.
- El cuadro general de distribución e, igualmente, los cuadros secundarios, se instalarán en lugares a
los que no tenga acceso el público y que estarán separados de los locales donde exista un peligro
acusado de incendio o de pánico (cabinas de proyección, escenarios, salas de público, escaparates,
etc.), por medio de elementos a prueba de incendios y puertas no propagadoras del fuego. Los
contadores podrán instalarse en otro lugar, de acuerdo con la empresa distribuidora de energía
eléctrica, y siempre antes del cuadro general.
- Cerca de cada uno de los interruptores del cuadro se colocará una placa indicadora del circuito al que
pertenecen.
Página 14 de 22
- En las instalaciones para alumbrado de locales o dependencias donde se reúna público, el número de
líneas secundarias y su disposición en relación con el total de lámparas a alimentar deberá ser tal que
el corte de corriente en una cualquiera de ellas no afecte a más de la tercera parte del total de
lámparas instaladas en los locales o dependencias que se iluminan alimentadas por dichas líneas.
Cada una de estas líneas estarán protegidas en su origen contra sobrecargas, cortocircuitos, y si
procede contra contactos indirectos.
- Los cables y sistemas de conducción de cables deben instalarse de manera que no se reduzcan las
características de la estructura del edificio en la seguridad contra incendios.
- Los cables eléctricos a utilizar en las instalaciones de tipo general y en el conexionado interior de
cuadros eléctricos en este tipo de locales, serán no propagadores del incendio y con emisión de humos
y opacidad reducida.
- Las fuentes propias de energía de corriente alterna a 50 Hz, no podrán dar tensión de retorno a la
acometida o acometidas de la red de Baja Tensión pública que alimenten al local de pública
concurrencia.
- A partir del cuadro general de distribución se instalarán líneas distribuidoras generales, accionadas
por medio de interruptores omnipolares, al menos para cada uno de los siguientes grupos de
dependencias o locales:
- Salas de venta o reunión, por planta del edificio
- Escaparates
- Almacenes
- Talleres
- Pasillos, escaleras y vestíbulos
8. PROTECCION CONTRA SOBREINTENSIDADES.
Todo circuito estará protegido contra los efectos de las sobreintensidades que puedan
presentarse en el mismo, para lo cual la interrupción de este circuito se realizará en un tiempo
conveniente o estará dimensionado para las sobreintensidades previsibles.
Las sobreintensidades pueden estar motivadas por:
- Sobrecargas debidas a los aparatos de utilización o defectos de aislamiento de gran impedancia.
- Cortocircuitos.
- Descargas eléctricas atmosféricas.
a) Protección contra sobrecargas. El límite de intensidad de corriente admisible en un conductor ha de
quedar en todo caso garantizada por el dispositivo de protección utilizado. El dispositivo de protección
podrá estar constituido por un interruptor automático de corte omnipolar con curva térmica de corte, o
por cortacircuitos fusibles calibrados de características de funcionamiento adecuadas.
b) Protección contra cortocircuitos. En el origen de todo circuito se establecerá un dispositivo de
protección contra cortocircuitos cuya capacidad de corte estará de acuerdo con la intensidad de
cortocircuito que pueda presentarse en el punto de su conexión. Se admite, no obstante, que cuando
se trate de circuitos derivados de uno principal, cada uno de estos circuitos derivados disponga de
protección contra sobrecargas, mientras que un solo dispositivo general pueda asegurar la protección
contra cortocircuitos para todos los circuitos derivados. Se admiten como dispositivos de protección
contra cortocircuitos los fusibles calibrados de características de funcionamiento adecuadas y los
interruptores automáticos con sistema de corte omnipolar.
La norma UNE 20.460 -4-43 recoge todos los aspectos requeridos para los dispositivos de
protección. La norma UNE 20.460 -4-473 define la aplicación de las medidas de protección expuestas
Página 15 de 22
en la norma UNE 20.460 -4-43 según sea por causa de sobrecargas o cortocircuito, señalando en cada
caso su emplazamiento u omisión.
9. PROTECCION CONTRA SOBRETENSIONES.
9.1. CATEGORÍAS DE LAS SOBRETENSIONES.
Las categorías indican los valores de tensión soportada a la onda de choque de sobretensión
que deben de tener los equipos, determinando, a su vez, el valor límite máximo de tensión residual que
deben permitir los diferentes dispositivos de protección de cada zona para evitar el posible daño de
dichos equipos.
Se distinguen 4 categorías diferentes, indicando en cada caso el nivel de tensión soportada a
impulsos, en kV, según la tensión nominal de la instalación.
Tensión nominal instalación
Tensión soportada a impulsos 1,2/50 (kV)
Sistemas III Sistemas II
Categoría IV Categoría III Categoría II Categoría I
230/400
230
400/690
1000
6
4
2,5
1,5
8
6
4
2,5
Categoría I
Se aplica a los equipos muy sensibles a las sobretensiones y que están destinados a ser
conectados a la instalación eléctrica fija (ordenadores, equipos electrónicos muy sensibles, etc). En
este caso, las medidas de protección se toman fuera de los equipos a proteger, ya sea en la instalación
fija o entre la instalación fija y los equipos, con objeto de limitar las sobretensiones a un nivel
específico.
Categoría II
Se aplica a los equipos destinados a conectarse a una instalación eléctrica fija
(electrodomésticos, herramientas portátiles y otros equipos similares).
Categoría III
Se aplica a los equipos y materiales que forman parte de la instalación eléctrica fija y a otros
equipos para los cuales se requiere un alto nivel de fiabilidad (armarios de distribución, embarrados,
aparamenta: interruptores, seccionadores, tomas de corriente, etc, canalizaciones y sus accesorios:
cables, caja de derivación, etc, motores con conexión eléctrica fija: ascensores, máquinas industriales,
etc.
Categoría IV
Se aplica a los equipos y materiales que se conectan en el origen o muy próximos al origen de
la instalación, aguas arriba del cuadro de distribución (contadores de energía, aparatos de telemedida,
equipos principales de protección contra sobreintensidades, etc).
9.2. MEDIDAS PARA EL CONTROL DE LAS SOBRETENSIONES.
Se pueden presentar dos situaciones diferentes:
- Situación natural: cuando no es preciso la protección contra las sobretensiones transitorias, pues se
Página 16 de 22
prevé un bajo riesgo de sobretensiones en la instalación (debido a que está alimentada por una red
subterránea en su totalidad). En este caso se considera suficiente la resistencia a las sobretensiones
de los equipos indicada en la tabla de categorías, y no se requiere ninguna protección suplementaria
contra las sobretensiones transitorias.
- Situación controlada: cuando es preciso la protección contra las sobretensiones transitorias en el
origen de la instalación, pues la instalación se alimenta por, o incluye, una línea aérea con conductores
desnudos o aislados.
También se considera situación controlada aquella situación natural en que es conveniente
incluir dispositivos de protección para una mayor seguridad (continuidad de servicio, valor económico
de los equipos, pérdidas irreparables, etc.).
Los dispositivos de protección contra sobretensiones de origen atmosférico deben
seleccionarse de forma que su nivel de protección sea inferior a la tensión soportada a impulso de la
categoría de los equipos y materiales que se prevé que se vayan a instalar.
Los descargadores se conectarán entre cada uno de los conductores, incluyendo el neutro o
compensador y la tierra de la instalación.
9.3. SELECCIÓN DE LOS MATERIALES EN LA INSTALACIÓN.
Los equipos y materiales deben escogerse de manera que su tensión soportada a impulsos no
sea inferior a la tensión soportada prescrita en la tabla anterior, según su categoría.
Los equipos y materiales que tengan una tensión soportada a impulsos inferior a la indicada en
la tabla, se pueden utilizar, no obstante:
- en situación natural, cuando el riesgo sea aceptable.
- en situación controlada, si la protección contra las sobretensiones es adecuada.
10. PROTECCION CONTRA CONTACTOS DIRECTOS E INDIRECTOS.
10.1. PROTECCION CONTRA CONTACTOS DIRECTOS.
Protección por aislamiento de las partes activas.
Las partes activas deberán estar recubiertas de un aislamiento que no pueda ser eliminado más
que destruyéndolo.
Protección por medio de barreras o envolventes.
Las partes activas deben estar situadas en el interior de las envolventes o detrás de barreras
que posean, como mínimo, el grado de protección IP XXB, según UNE20.324. Si se necesitan
aberturas mayores para la reparación de piezas o para el buen funcionamiento de los equipos, se
adoptarán precauciones apropiadas para impedir que las personas o animales domésticos toquen las
partes activas y se garantizará que las personas sean conscientes del hecho de que las partes activas
no deben ser tocadas voluntariamente.
Las superficies superiores de las barreras o envolventes horizontales que son fácilmente
accesibles, deben responder como mínimo al grado de protección IP4X o IP XXD.
Las barreras o envolventes deben fijarse de manera segura y ser de una robustez y durabilidad
suficientes para mantener los grados de protección exigidos, con una separación suficiente de las
partes activas en las condiciones normales de servicio, teniendo en cuenta las influencias externas.
Página 17 de 22
Cuando sea necesario suprimir las barreras, abrir las envolventes o quitar partes de éstas, esto
no debe ser posible más que:
- bien con la ayuda de una llave o de una herramienta;
- o bien, después de quitar la tensión de las partes activas protegidas por estas barreras o estas
envolventes, no pudiendo ser restablecida la tensión hasta después de volver a colocar las barreras o
las envolventes;
- o bien, si hay interpuesta una segunda barrera que posee como mínimo el grado de protección IP2X o
IP XXB, que no pueda ser quitada más que con la ayuda de una llave o de una herramienta y que
impida todo contacto con las partes activas.
Protección complementaria por dispositivos de corriente diferencial-residual.
Esta medida de protección está destinada solamente a complementar otras medidas de
protección contra los contactos directos.
El empleo de dispositivos de corriente diferencial-residual, cuyo valor de corriente diferencial
asignada de funcionamiento sea inferior o igual a 30 mA, se reconoce como medida de protección
complementaria en caso de fallo de otra medida de protección contra los contactos directos o en caso
de imprudencia de los usuarios.
10.2. PROTECCION CONTRA CONTACTOS INDIRECTOS.
La protección contra contactos indirectos se conseguirá mediante "corte automático de la
alimentación". Esta medida consiste en impedir, después de la aparición de un fallo, que una tensión de
contacto de valor suficiente se mantenga durante un tiempo tal que pueda dar como resultado un
riesgo. La tensión límite convencional es igual a 50 V, valor eficaz en corriente alterna, en condiciones
normales y a 24 V en locales húmedos.
Todas las masas de los equipos eléctricos protegidos por un mismo dispositivo de protección,
deben ser interconectadas y unidas por un conductor de protección a una misma toma de tierra. El
punto neutro de cada generador o transformador debe ponerse a tierra.
Se cumplirá la siguiente condición:
Ra x Ia ≤ U
donde:
- Ra es la suma de las resistencias de la toma de tierra y de los conductores de protección de masas.
- Ia es la corriente que asegura el funcionamiento automático del dispositivo de protección. Cuando el
dispositivo de protección es un dispositivo de corriente diferencial-residual es la corriente diferencialresidual asignada.
- U es la tensión de contacto límite convencional (50 ó 24V).
11. PUESTAS A TIERRA.
Las puestas a tierra se establecen principalmente con objeto de limitar la tensión que, con
respecto a tierra, puedan presentar en un momento dado las masas metálicas, asegurar la actuación
de las protecciones y eliminar o disminuir el riesgo que supone una avería en los materiales eléctricos
utilizados.
La puesta o conexión a tierra es la unión eléctrica directa, sin fusibles ni protección alguna, de
una parte del circuito eléctrico o de una parte conductora no perteneciente al mismo, mediante una
toma de tierra con un electrodo o grupo de electrodos enterrados en el suelo.
Página 18 de 22
Mediante la instalación de puesta a tierra se deberá conseguir que en el conjunto de
instalaciones, edificios y superficie próxima del terreno no aparezcan diferencias de potencial
peligrosas y que, al mismo tiempo, permita el paso a tierra de las corrientes de defecto o las de
descarga de origen atmosférico.
La elección e instalación de los materiales que aseguren la puesta a tierra deben ser tales que:
- El valor de la resistencia de puesta a tierra esté conforme con las normas de protección y de
funcionamiento de la instalación y se mantenga de esta manera a lo largo del tiempo.
- Las corrientes de defecto a tierra y las corrientes de fuga puedan circular sin peligro, particularmente
desde el punto de vista de solicitaciones térmicas, mecánicas y eléctricas.
- La solidez o la protección mecánica quede asegurada con independencia de las condiciones
estimadas de influencias externas.
- Contemplen los posibles riesgos debidos a electrólisis que pudieran afectar a otras partes metálicas.
11.1. UNIONES A TIERRA.
Tomas de tierra.
Para la toma de tierra se pueden utilizar electrodos formados por:
- barras, tubos;
- pletinas, conductores desnudos;
- placas;
- anillos o mallas metálicas constituidos por los elementos anteriores o sus combinaciones;
- armaduras de hormigón enterradas; con excepción de las armaduras pretensadas;
- otras estructuras enterradas que se demuestre que son apropiadas.
Los conductores de cobre utilizados como electrodos serán de construcción y resistencia
eléctrica según la clase 2 de la norma UNE 21.022.
El tipo y la profundidad de enterramiento de las tomas de tierra deben ser tales que la posible
pérdida de humedad del suelo, la presencia del hielo u otros efectos climáticos, no aumenten la
resistencia de la toma de tierra por encima del valor previsto. La profundidad nunca será inferior a 0,50
m.
Conductores de tierra.
La sección de los conductores de tierra, cuando estén enterrados, deberán estar de acuerdo
con los valores indicados en la tabla siguiente. La sección no será inferior a la mínima exigida para los
conductores de protección.
Tipo
Protegido mecánicamente
No protegido mecánicamente
Protegido contra
la corrosión
Igual a conductores
protección apdo. 7.7.1
16 mm² Cu
16 mm² Acero Galvanizado
No protegido contra
la corrosión
25 mm² Cu
50 mm² Hierro
25 mm² Cu
50 mm² Hierro
* La protección contra la corrosión puede obtenerse mediante una envolvente.
Durante la ejecución de las uniones entre conductores de tierra y electrodos de tierra debe
extremarse el cuidado para que resulten eléctricamente correctas. Debe cuidarse, en especial, que las
conexiones, no dañen ni a los conductores ni a los electrodos de tierra.
Página 19 de 22
Bornes de puesta a tierra.
En toda instalación de puesta a tierra debe preverse un borne principal de tierra, al cual deben
unirse los conductores siguientes:
- Los conductores de tierra.
- Los conductores de protección.
- Los conductores de unión equipotencial principal.
- Los conductores de puesta a tierra funcional, si son necesarios.
Debe preverse sobre los conductores de tierra y en lugar accesible, un dispositivo que permita
medir la resistencia de la toma de tierra correspondiente. Este dispositivo puede estar combinado con
el borne principal de tierra, debe ser desmontable necesariamente por medio de un útil, tiene que ser
mecánicamente seguro y debe asegurar la continuidad eléctrica.
Conductores de protección.
Los conductores de protección sirven para unir eléctricamente las masas de una instalación
con el borne de tierra, con el fin de asegurar la protección contra contactos indirectos.
Los conductores de protección tendrán una sección mínima igual a la fijada en la tabla siguiente:
Sección conductores fase (mm²)
Sf ≤ 16
16 < S f ≤ 35
Sf > 35
Sección conductores protección (mm²)
Sf
16
Sf/2
En todos los casos, los conductores de protección que no forman parte de la canalización de
alimentación serán de cobre con una sección, al menos de:
- 2,5 mm2, si los conductores de protección disponen de una protección mecánica.
- 4 mm2, si los conductores de protección no disponen de una protección mecánica.
Como conductores de protección pueden utilizarse:
- conductores en los cables multiconductores, o
- conductores aislados o desnudos que posean una envolvente común con los conductores activos, o
- conductores separados desnudos o aislados.
Ningún aparato deberá ser intercalado en el conductor de protección. Las masas de los
equipos a unir con los conductores de protección no deben ser conectadas en serie en un circuito de
protección.
11.2. RESISTENCIA DE LAS TOMAS DE TIERRA.
El valor de resistencia de tierra será tal que cualquier masa no pueda dar lugar a tensiones de
contacto superiores a:
- 24 V en local o emplazamiento conductor
- 50 V en los demás casos.
Si las condiciones de la instalación son tales que pueden dar lugar a tensiones de contacto
superiores a los valores señalados anteriormente, se asegurará la rápida eliminación de la falta
mediante dispositivos de corte adecuados a la corriente de servicio.
Página 20 de 22
La resistencia de un electrodo depende de sus dimensiones, de su forma y de la resistividad
del terreno en el que se establece. Esta resistividad varía frecuentemente de un punto a otro del
terreno, y varía también con la profundidad.
11.3. TOMAS DE TIERRA INDEPENDIENTES.
Se considerará independiente una toma de tierra respecto a otra, cuando una de las tomas de
tierra, no alcance, respecto a un punto de potencial cero, una tensión superior a 50 V cuando por la
otra circula la máxima corriente de defecto a tierra prevista.
11.4. REVISION DE LAS TOMAS DE TIERRA.
Por la importancia que ofrece, desde el punto de vista de la seguridad cualquier instalación de
toma de tierra, deberá ser obligatoriamente comprobada por el Director de la Obra o Instalador
Autorizado en el momento de dar de alta la instalación para su puesta en marcha o en funcionamiento.
Personal técnicamente competente efectuará la comprobación de la instalación de puesta a
tierra, al menos anualmente, en la época en la que el terreno esté mas seco. Para ello, se medirá la
resistencia de tierra, y se repararán con carácter urgente los defectos que se encuentren.
En los lugares en que el terreno no sea favorable a la buena conservación de los electrodos,
éstos y los conductores de enlace entre ellos hasta el punto de puesta a tierra, se pondrán al
descubierto para su examen, al menos una vez cada cinco años.
12. RECEPTORES DE ALUMBRADO.
Las luminarias serán conformes a los requisitos establecidos en las normas de la serie UNE-EN
60598.
La masa de las luminarias suspendidas excepcionalmente de cables flexibles no deben
exceder de 5 kg. Los conductores, que deben ser capaces de soportar este peso, no deben presentar
empalmes intermedios y el esfuerzo deberá realizarse sobre un elemento distinto del borne de
conexión.
Las partes metálicas accesibles de las luminarias que no sean de Clase II o Clase III, deberán
tener un elemento de conexión para su puesta a tierra, que irá conectado de manera fiable y
permanente al conductor de protección del circuito.
El uso de lámparas de gases con descargas a alta tensión (neón, etc), se permitirá cuando su
ubicación esté fuera del volumen de accesibilidad o cuando se instalen barreras o envolventes
separadoras.
Los circuitos de alimentación estarán previstos para transportar la carga debida a los propios
receptores, a sus elementos asociados y a sus corrientes armónicas y de arranque. Para receptores
con lámparas de descarga, la carga mínima prevista en voltiamperios será de 1,8 veces la potencia en
vatios de las lámparas. En el caso de distribuciones monofásicas, el conductor neutro tendrá la misma
sección que los de fase. Será aceptable un coeficiente diferente para el cálculo de la sección de los
conductores, siempre y cuando el factor de potencia de cada receptor sea mayor o igual a 0,9 y si se
conoce la carga que supone cada uno de los elementos asociados a las lámparas y las corrientes de
arranque, que tanto éstas como aquéllos puedan producir. En este caso, el coeficiente será el que
resulte.
En el caso de receptores con lámparas de descarga será obligatoria la compensación del factor
de potencia hasta un valor mínimo de 0,9.
Página 21 de 22
En instalaciones con lámparas de muy baja tensión (p.e. 12 V) debe preverse la utilización de
transformadores adecuados, para asegurar una adecuada protección térmica, contra cortocircuitos y
sobrecargas y contra los choques eléctricos.
Para los rótulos luminosos y para instalaciones que los alimentan con tensiones asignadas de
salida en vacío comprendidas entre 1 y 10 kV se aplicará lo dispuesto en la norma UNE-EN 50.107.
13. RECEPTORES A MOTOR.
Los motores deben instalarse de manera que la aproximación a sus partes en movimiento no
pueda ser causa de accidente. Los motores no deben estar en contacto con materias fácilmente
combustibles y se situarán de manera que no puedan provocar la ignición de estas.
Los conductores de conexión que alimentan a un solo motor deben estar dimensionados para
una intensidad del 125 % de la intensidad a plena carga del motor. Los conductores de conexión que
alimentan a varios motores, deben estar dimensionados para una intensidad no inferior a la suma del
125 % de la intensidad a plena carga del motor de mayor potencia, más la intensidad a plena carga de
todos los demás.
Los motores deben estar protegidos contra cortocircuitos y contra sobrecargas en todas sus
fases, debiendo esta última protección ser de tal naturaleza que cubra, en los motores trifásicos, el
riesgo de la falta de tensión en una de sus fases. En el caso de motores con arrancador estrellatriángulo, se asegurará la protección, tanto para la conexión en estrella como en triángulo.
Los motores deben estar protegidos contra la falta de tensión por un dispositivo de corte
automático de la alimentación, cuando el arranque espontáneo del motor, como consecuencia del
restablecimiento de la tensión, pueda provocar accidentes, o perjudicar el motor, de acuerdo con la
norma UNE 20.460 -4-45.
Los motores deben tener limitada la intensidad absorbida en el arranque, cuando se pudieran
producir efectos que perjudicasen a la instalación u ocasionasen perturbaciones inaceptables al
funcionamiento de otros receptores o instalaciones.
En general, los motores de potencia superior a 0,75 kilovatios deben estar provistos de
reóstatos de arranque o dispositivos equivalentes que no permitan que la relación de corriente entre el
período de arranque y el de marcha normal que corresponda a su plena carga, según las
características del motor que debe indicar su placa, sea superior a la señalada en el cuadro siguiente:
De 0,75 kW a 1,5 kW: 4,5
De 1,50 kW a 5 kW: 3,0
De 5 kW a 15 kW: 2
Más de 15 kW: 1,5
Página 22 de 22
CUADRO GENERAL DE MANDO Y PROTECCION
Fórmulas
Emplearemos las siguientes:
Sistema Trifásico
I = Pc / 1,732 x U x Cosϕ x R = amp (A)
e = (L x Pc / k x U x n x S x R) + (L x Pc x Xu x Senϕ / 1000 x U x n x R x Cosϕ) = voltios (V)
Sistema Monofásico:
I = Pc / U x Cosϕ x R = amp (A)
e = (2 x L x Pc / k x U x n x S x R) + (2 x L x Pc x Xu x Senϕ / 1000 x U x n x R x Cosϕ) = voltios
(V)
En donde:
Pc = Potencia de Cálculo en Watios.
L = Longitud de Cálculo en metros.
e = Caída de tensión en Voltios.
K = Conductividad.
I = Intensidad en Amperios.
U = Tensión de Servicio en Voltios (Trifásica ó Monofásica).
S = Sección del conductor en mm².
Cos ϕ = Coseno de fi. Factor de potencia.
R = Rendimiento. (Para líneas motor).
n = Nº de conductores por fase.
Xu = Reactancia por unidad de longitud en mΩ/m.
Fórmula Conductividad Eléctrica
K = 1/ρ
ρ = ρ20[1+α (T-20)]
T = T0 + [(Tmax-T0) (I/Imax)²]
Siendo,
K = Conductividad del conductor a la temperatura T.
ρ = Resistividad del conductor a la temperatura T.
ρ20 = Resistividad del conductor a 20ºC.
Cu = 0.018
Al = 0.029
α = Coeficiente de temperatura:
Cu = 0.00392
Al = 0.00403
T = Temperatura del conductor (ºC).
T0 = Temperatura ambiente (ºC):
Cables enterrados = 25ºC
Cables al aire = 40ºC
Tmax = Temperatura máxima admisible del conductor (ºC):
XLPE, EPR = 90ºC
PVC = 70ºC
I = Intensidad prevista por el conductor (A).
Imax = Intensidad máxima admisible del conductor (A).
Fórmulas Sobrecargas
Ib ≤ In ≤ Iz
Página 1 de 59
I2 ≤ 1,45 Iz
Donde:
Ib: intensidad utilizada en el circuito.
Iz: intensidad admisible de la canalización según la norma UNE 20-460/5-523.
In: intensidad nominal del dispositivo de protección. Para los dispositivos de protección regulables, In es la
intensidad de regulación escogida.
I2: intensidad que asegura efectivamente el funcionamiento del dispositivo de protección. En la práctica I2 se
toma igual:
- a la intensidad de funcionamiento en el tiempo convencional, para los interruptores automáticos
(1,45 In como máximo).
- a la intensidad de fusión en el tiempo convencional, para los fusibles (1,6 In).
Fórmulas compensación energía reactiva
cosØ = P/√(P²+ Q²).
tgØ = Q/P.
Qc = Px(tgØ1-tgØ2).
C = Qcx1000/U²xω; (Monofásico - Trifásico conexión estrella).
C = Qcx1000/3xU²xω; (Trifásico conexión triángulo).
Siendo:
P = Potencia activa instalación (kW).
Q = Potencia reactiva instalación (kVAr).
Qc = Potencia reactiva a compensar (kVAr).
Ø1 = Angulo de desfase de la instalación sin compensar.
Ø2 = Angulo de desfase que se quiere conseguir.
U = Tensión compuesta (V).
ω = 2xPixf ; f = 50 Hz.
C = Capacidad condensadores (F); cx1000000(µF).
Fórmulas Cortocircuito
* IpccI = Ct U / √3 Zt
Siendo,
IpccI: intensidad permanente de c.c. en inicio de línea en kA.
Ct: Coeficiente de tensión.
U: Tensión trifásica en V.
Zt: Impedancia total en mohm, aguas arriba del punto de c.c. (sin incluir la línea o circuito en estudio).
* IpccF = Ct UF / 2 Zt
Siendo,
IpccF: Intensidad permanente de c.c. en fin de línea en kA.
Ct: Coeficiente de tensión.
UF: Tensión monofásica en V.
Zt: Impedancia total en mohm, incluyendo la propia de la línea o circuito (por tanto es igual a la impedancia
en origen mas la propia del conductor o línea).
* La impedancia total hasta el punto de cortocircuito será:
Zt = (Rt² + Xt²)½
Siendo,
Rt: R1 + R2 + ................+ Rn (suma de las resistencias de las líneas aguas arriba hasta el punto de c.c.)
Página 2 de 59
Xt: X1 + X2 + .............. + Xn (suma de las reactancias de las líneas aguas arriba hasta el punto de c.c.)
(mohm)
R = L · 1000 · CR / K · S · n
X = Xu · L / n
(mohm)
R: Resistencia de la línea en mohm.
X: Reactancia de la línea en mohm.
L: Longitud de la línea en m.
CR: Coeficiente de resistividad.
K: Conductividad del metal.
S: Sección de la línea en mm².
Xu: Reactancia de la línea, en mohm por metro.
n: nº de conductores por fase.
* tmcicc = Cc · S² / IpccF²
Siendo,
tmcicc: Tiempo máximo en sg que un conductor soporta una Ipcc.
Cc= Constante que depende de la naturaleza del conductor y de su aislamiento.
S: Sección de la línea en mm².
IpccF: Intensidad permanente de c.c. en fin de línea en A.
* tficc = cte. fusible / IpccF²
Siendo,
tficc: tiempo de fusión de un fusible para una determinada intensidad de cortocircuito.
IpccF: Intensidad permanente de c.c. en fin de línea en A.
* Lmax = 0,8 UF / 2 · IF5 · √(1,5 / K· S · n)² + (Xu / n · 1000)²
Siendo,
Lmax: Longitud máxima de conductor protegido a c.c. (m) (para protección por fusibles)
UF: Tensión de fase (V)
K: Conductividad
S: Sección del conductor (mm²)
Xu: Reactancia por unidad de longitud (mohm/m). En conductores aislados suele ser 0,1.
n: nº de conductores por fase
Ct= 0,8: Es el coeficiente de tensión.
CR = 1,5: Es el coeficiente de resistencia.
IF5 = Intensidad de fusión en amperios de fusibles en 5 sg.
* Curvas válidas.(Para protección de Interruptores automáticos dotados de Relé electromagnético).
CURVA B
CURVA C
CURVA D Y MA
IMAG = 5 In
IMAG = 10 In
IMAG = 20 In
Fórmulas Embarrados
Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n)
Siendo,
σmax: Tensión máxima en las pletinas (kg/cm²)
Ipcc: Intensidad permanente de c.c. (kA)
Página 3 de 59
L: Separación entre apoyos (cm)
d: Separación entre pletinas (cm)
n: nº de pletinas por fase
Wy: Módulo resistente por pletina eje y-y (cm³)
σadm: Tensión admisible material (kg/cm²)
Comprobación por solicitación térmica en cortocircuito
Icccs = Kc · S / ( 1000 · √tcc)
Siendo,
Ipcc: Intensidad permanente de c.c. (kA)
Icccs: Intensidad de c.c. soportada por el conductor durante el tiempo de duración del c.c. (kA)
S: Sección total de las pletinas (mm²)
tcc: Tiempo de duración del cortocircuito (s)
Kc: Constante del conductor: Cu = 164, Al = 107
DEMANDA DE POTENCIAS
- Potencia total instalada:
EMERG.
AL. GYM
T.C. GYM
F/C GYM
BAR
F/C Z. COMUN
EMERG
BAÑOS GYM
BAÑOS GRAL.
VESTIBL Z. COMUNES
SALA CALDERAS
MEDICO
PODOLOGO
1ª PLANTA
TOTAL....
100 W
500 W
2000 W
150 W
24200 W
800 W
250 W
250 W
350 W
400 W
87600 W
5700 W
6850 W
23050 W
152200 W
- Potencia Instalada Alumbrado (W): 12450
- Potencia Instalada Fuerza (W): 139750
- Potencia Máxima Admisible (W): 138560
Cálculo de la ACOMETIDA
- Tensión de servicio: 400 V.
- Canalización: Enterrados Bajo Tubo (R.Subt)
- Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 152200 W.
- Potencia de cálculo: (Según ITC-BT-44):
162160 W.(Coef. de Simult.: 1 )
I=162160/1,732x400x0.8=292.58 A.
Se eligen conductores Unipolares 3x185/95mm²Al
Nivel Aislamiento, Aislamiento: 0.6/1 kV, XLPE. Desig. UNE: RV-Al
I.ad. a 25°C (Fc=0.8) 300 A. según ITC-BT-07
Diámetro exterior tubo: 180 mm.
Página 4 de 59
Caída de tensión:
Temperatura cable (ºC): 86.82
e(parcial)=20x162160/27.17x400x185=1.61 V.=0.4 %
e(total)=0.4% ADMIS (2% MAX.)
Cálculo de la LINEA GENERAL DE ALIMENTACION
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 152200 W.
- Potencia de cálculo: (Según ITC-BT-44):
162160 W.(Coef. de Simult.: 1 )
I=162160/1,732x400x0.8=292.58 A.
Se eligen conductores Unipolares 4x240+TTx120mm²Cu
Nivel Aislamiento, Aislamiento: 0.6/1 kV, XLPE+Pol - No propagador incendio y emisión humos y opacidad
reducida -. Desig. UNE: RZ1-K(AS)
I.ad. a 40°C (Fc=1) 401 A. según ITC-BT-19
Diámetro exterior tubo: 200 mm.
Caída de tensión:
Temperatura cable (ºC): 66.62
e(parcial)=10x162160/46.97x400x240=0.36 V.=0.09 %
e(total)=0.09% ADMIS (4.5% MAX.)
Prot. Térmica:
Fusibles Int. 315 A.
Cálculo de la DERIVACION INDIVIDUAL
- Tensión de servicio: 400 V.
- Canalización: Enterrados Bajo Tubo (R.Subt)
- Longitud: 15 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 152200 W.
- Potencia de cálculo: (Según ITC-BT-44):
129728 W.(Coef. de Simult.: 0.8 )
I=129728/1,732x400x0.8=234.06 A.
Se eligen conductores Unipolares 4x95+TTx50mm²Cu
Nivel Aislamiento, Aislamiento: 0.6/1 kV, XLPE+Pol - No propagador incendio y emisión humos y opacidad
reducida -. Desig. UNE: RZ1-K(AS)
I.ad. a 25°C (Fc=0.8) 268 A. según ITC-BT-07
Diámetro exterior tubo: 125 mm.
Caída de tensión:
Temperatura cable (ºC): 74.58
e(parcial)=15x129728/45.76x400x95=1.12 V.=0.28 %
e(total)=0.37% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Aut./Tet. In.: 250 A. Térmico reg. Int.Reg.: 250 A.
Página 5 de 59
Cálculo de la Línea: GYM
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2750 W.
- Potencia de cálculo: (Según ITC-BT-44):
1938 W.(Coef. de Simult.: 0.6 )
I=1938/230x0.8=10.53 A.
Se eligen conductores Unipolares 2x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 46.29
e(parcial)=2x0.3x1938/50.36x230x2.5=0.04 V.=0.02 %
e(total)=0.39% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: EMERG.
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 100 W.
- Potencia de cálculo: (Según ITC-BT-44):
100x1.8=180 W.
I=180/230x1=0.78 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.08
e(parcial)=2x20x180/51.5x230x1.5=0.41 V.=0.18 %
e(total)=0.56% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. GYM
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 500 W.
- Potencia de cálculo: (Según ITC-BT-44):
500x1.8=900 W.
Página 6 de 59
I=900/230x1=3.91 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 42.04
e(parcial)=2x20x900/51.14x230x1.5=2.04 V.=0.89 %
e(total)=1.27% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: T.C. GYM
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 25 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x25x2000/50.05x230x2.5=3.47 V.=1.51 %
e(total)=1.9% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: F/C GYM
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 150 W.
- Potencia de cálculo: 150 W.
I=150/230x0.8=0.82 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.05
e(parcial)=2x10x150/51.51x230x2.5=0.1 V.=0.04 %
e(total)=0.43% ADMIS (6.5% MAX.)
Página 7 de 59
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: BAR
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 24200 W.
- Potencia de cálculo: (Según ITC-BT-44):
18284 W.(Coef. de Simult.: 0.7 )
I=18284/1,732x400x0.8=32.99 A.
Se eligen conductores Unipolares 4x10+TTx10mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 44 A. según ITC-BT-19
Diámetro exterior tubo: 32 mm.
Caída de tensión:
Temperatura cable (ºC): 56.86
e(parcial)=10x18284/48.54x400x10=0.94 V.=0.24 %
e(total)=0.61% ADMIS (4.5% MAX.)
Protección Termica en Principio de Línea
I. Mag. Tetrapolar Int. 40 A.
SUBCUADRO
BAR
DEMANDA DE POTENCIAS
- Potencia total instalada:
EMERG
AL. ESTAR I
AL. ESTAR II
EMERG
AL. COMEDOR I
AL. COMEDOR II
EMERG
AL. COCINA
AL. BARRA
F/C BAR COMEDOR
EXTRACTOR
TC. DESPACHO BAR
CAFETERA
BOTELLEROS
T.C. COCINA I
T.C. COCINA II
T.C. COCINA III
PLANCHA/FREID
TOTAL....
200 W
300 W
300 W
200 W
300 W
300 W
200 W
300 W
300 W
800 W
1000 W
2000 W
5000 W
2000 W
2000 W
3000 W
3000 W
3000 W
24200 W
- Potencia Instalada Alumbrado (W): 2400
- Potencia Instalada Fuerza (W): 21800
Página 8 de 59
Cálculo de la Línea:
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 800 W.
- Potencia de cálculo: (Según ITC-BT-44):
864 W.(Coef. de Simult.: 0.6 )
I=864/1,732x400x0.8=1.56 A.
Se eligen conductores Unipolares 4x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 40.17
e(parcial)=0.3x864/51.49x400x2.5=0.01 V.=0 %
e(total)=0.61% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 10 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 200 W.
- Potencia de cálculo: (Según ITC-BT-44):
200x1.8=360 W.
I=360/230x1=1.57 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.17
e(parcial)=2x8x360/51.49x230x2.5=0.19 V.=0.08 %
e(total)=0.69% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. ESTAR I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
Página 9 de 59
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.37
e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 %
e(total)=0.73% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. ESTAR II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.37
e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 %
e(total)=0.73% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 800 W.
- Potencia de cálculo: (Según ITC-BT-44):
864 W.(Coef. de Simult.: 0.6 )
I=864/1,732x400x0.8=1.56 A.
Se eligen conductores Unipolares 4x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 40.17
e(parcial)=0.3x864/51.49x400x2.5=0.01 V.=0 %
e(total)=0.61% ADMIS (4.5% MAX.)
Página 10 de 59
Prot. Térmica:
I. Mag. Tetrapolar Int. 10 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 200 W.
- Potencia de cálculo: (Según ITC-BT-44):
200x1.8=360 W.
I=360/230x1=1.57 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.17
e(parcial)=2x8x360/51.49x230x2.5=0.19 V.=0.08 %
e(total)=0.69% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. COMEDOR I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.37
e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 %
e(total)=0.73% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. COMEDOR II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
Página 11 de 59
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.37
e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 %
e(total)=0.73% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 800 W.
- Potencia de cálculo: (Según ITC-BT-44):
864 W.(Coef. de Simult.: 0.6 )
I=864/1,732x400x0.8=1.56 A.
Se eligen conductores Unipolares 4x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 40.17
e(parcial)=0.3x864/51.49x400x2.5=0.01 V.=0 %
e(total)=0.61% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 10 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 200 W.
- Potencia de cálculo: (Según ITC-BT-44):
200x1.8=360 W.
I=360/230x1=1.57 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
Página 12 de 59
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.17
e(parcial)=2x8x360/51.49x230x2.5=0.19 V.=0.08 %
e(total)=0.69% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. COCINA
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.37
e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 %
e(total)=0.73% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. BARRA
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.37
e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 %
e(total)=0.73% ADMIS (4.5% MAX.)
Prot. Térmica:
Página 13 de 59
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 10800 W.
- Potencia de cálculo:
10800 W.(Coef. de Simult.: 1 )
I=10800/1,732x400x0.8=19.49 A.
Se eligen conductores Unipolares 4x4mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 27 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 55.63
e(parcial)=0.3x10800/48.75x400x4=0.04 V.=0.01 %
e(total)=0.62% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 20 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: F/C BAR COMEDOR
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 800 W.
- Potencia de cálculo: 800 W.
I=800/230x0.8=4.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 41.29
e(parcial)=2x15x800/51.28x230x2.5=0.81 V.=0.35 %
e(total)=0.97% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: EXTRACTOR
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1000 W.
- Potencia de cálculo: 1000 W.
Página 14 de 59
I=1000/1,732x400x0.8=1.8 A.
Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.29
e(parcial)=10x1000/51.46x400x2.5=0.19 V.=0.05 %
e(total)=0.66% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea: TC. DESPACHO BAR
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x20x2000/50.05x230x2.5=2.78 V.=1.21 %
e(total)=1.82% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: CAFETERA
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 5 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 5000 W.
- Potencia de cálculo: 5000 W.
I=5000/1,732x400x0.8=9.02 A.
Se eligen conductores Unipolares 4x4+TTx4mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 24 A. según ITC-BT-19
Diámetro exterior tubo: 25 mm.
Caída de tensión:
Temperatura cable (ºC): 44.24
e(parcial)=5x5000/50.73x400x4=0.31 V.=0.08 %
e(total)=0.69% ADMIS (6.5% MAX.)
Página 15 de 59
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea: BOTELLEROS
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/1,732x400x0.8=3.61 A.
Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 41.14
e(parcial)=10x2000/51.3x400x2.5=0.39 V.=0.1 %
e(total)=0.71% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea:
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 11000 W.
- Potencia de cálculo:
7700 W.(Coef. de Simult.: 0.7 )
I=7700/1,732x400x0.8=13.89 A.
Se eligen conductores Unipolares 4x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 53.13
e(parcial)=0.3x7700/49.17x400x2.5=0.05 V.=0.01 %
e(total)=0.62% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: T.C. COCINA I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
Página 16 de 59
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 %
e(total)=1.22% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: T.C. COCINA II
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 3000 W.
- Potencia de cálculo: 3000 W.
I=3000/1,732x400x0.8=5.41 A.
Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.57
e(parcial)=10x3000/51.04x400x2.5=0.59 V.=0.15 %
e(total)=0.76% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea: T.C. COCINA III
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 3000 W.
- Potencia de cálculo: 3000 W.
I=3000/1,732x400x0.8=5.41 A.
Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.57
e(parcial)=10x3000/51.04x400x2.5=0.59 V.=0.15 %
Página 17 de 59
e(total)=0.76% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea: PLANCHA/FREID
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 3000 W.
- Potencia de cálculo: 3000 W.
I=3000/1,732x400x0.8=5.41 A.
Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.57
e(parcial)=8x3000/51.04x400x2.5=0.47 V.=0.12 %
e(total)=0.73% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
CALCULO DE EMBARRADO BAR
Datos
- Metal: Cu
- Estado pletinas: desnudas
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 45
- Ancho (mm): 15
- Espesor (mm): 3
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.112, 0.084, 0.022, 0.003
- I. admisible del embarrado (A): 170
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =4.57² · 25² /(60 · 10 · 0.022 · 1) = 989.437 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 32.99 A
Iadm = 170 A
Página 18 de 59
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 4.57 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 45 · 1 / (1000 · √0.5) = 10.44 kA
Cálculo de la Línea: AL. GEN P_BA
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2050 W.
- Potencia de cálculo: (Según ITC-BT-44):
1830 W.(Coef. de Simult.: 0.6 )
I=1830/1,732x400x0.8=3.3 A.
Se eligen conductores Unipolares 4x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 40.74
e(parcial)=0.3x1830/51.38x400x2.5=0.01 V.=0 %
e(total)=0.37% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: F/C Z. COMUN
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 800 W.
- Potencia de cálculo: 800 W.
I=800/230x0.8=4.35 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 41.29
e(parcial)=2x20x800/51.28x230x2.5=1.09 V.=0.47 %
e(total)=0.84% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
Página 19 de 59
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 250 W.
- Potencia de cálculo: (Según ITC-BT-44):
250x1.8=450 W.
I=450/230x1=1.96 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.51
e(parcial)=2x15x450/51.42x230x1.5=0.76 V.=0.33 %
e(total)=0.7% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: BAÑOS GYM
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 25 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 250 W.
- Potencia de cálculo: (Según ITC-BT-44):
250x1.8=450 W.
I=450/230x1=1.96 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.51
e(parcial)=2x25x450/51.42x230x1.5=1.27 V.=0.55 %
e(total)=0.92% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: BAÑOS GRAL.
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 350 W.
- Potencia de cálculo: (Según ITC-BT-44):
350x1.8=630 W.
I=630/230x1=2.74 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
Página 20 de 59
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.51
e(parcial)=2x10x630/51.42x230x2.5=0.43 V.=0.19 %
e(total)=0.56% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: VESTIBL Z. COMUNES
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x20x720/51.27x230x1.5=1.63 V.=0.71 %
e(total)=1.08% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: SALA CALDERAS
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 25 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 87600 W.
- Potencia de cálculo: (Según ITC-BT-44):
88880 W.(Coef. de Simult.: 1 )
I=88880/1,732x400x0.8=160.36 A.
Se eligen conductores Unipolares 4x95+TTx50mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 180 A. según ITC-BT-19
Diámetro exterior tubo: 75 mm.
Caída de tensión:
Temperatura cable (ºC): 63.81
e(parcial)=25x88880/47.41x400x95=1.23 V.=0.31 %
e(total)=0.68% ADMIS (4.5% MAX.)
Página 21 de 59
Protección Termica en Principio de Línea
I. Aut./Tet. In.: 250 A. Térmico reg. Int.Reg.: 170 A.
SUBCUADRO
SALA CALDERAS
DEMANDA DE POTENCIAS
- Potencia total instalada:
RESERVA ENFRIADORA
VENTILACION
CALDERA
T.C. S. CALD
EMERG
A.L. AZOTEA
AL. S. CALD
AL. EXT I
AL. EXT I
TOTAL....
80000 W
3000 W
1000 W
2000 W
200 W
300 W
300 W
400 W
400 W
87600 W
- Potencia Instalada Alumbrado (W): 1600
- Potencia Instalada Fuerza (W): 86000
Cálculo de la Línea: RESERVA ENFRIADORA
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 80000 W.
- Potencia de cálculo: 80000 W.
I=80000/1,732x400x0.8=144.34 A.
Se eligen conductores Unipolares 4x70+TTx35mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 149 A. según ITC-BT-19
Diámetro exterior tubo: 63 mm.
Caída de tensión:
Temperatura cable (ºC): 68.15
e(parcial)=10x80000/46.73x400x70=0.61 V.=0.15 %
e(total)=0.83% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Aut./Tet. In.: 160 A. Térmico reg. Int.Reg.: 147 A.
Protección diferencial:
Relé y Transfor. Diferencial Sens.: 30 mA.
Cálculo de la Línea: LF. GENERAL
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
Página 22 de 59
- Potencia a instalar: 6000 W.
- Potencia de cálculo:
3600 W.(Coef. de Simult.: 0.6 )
I=3600/1,732x400x0.8=6.5 A.
Se eligen conductores Unipolares 4x6mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 36 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 40.98
e(parcial)=0.3x3600/51.33x400x6=0.01 V.=0 %
e(total)=0.68% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: VENTILACION
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 25 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 3000 W.
- Potencia de cálculo: 3000 W.
I=3000/1,732x400x0.8=5.41 A.
Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.57
e(parcial)=25x3000/51.04x400x2.5=1.47 V.=0.37 %
e(total)=1.05% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea: CALDERA
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1000 W.
- Potencia de cálculo: 1000 W.
I=1000/230x0.8=5.43 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Página 23 de 59
Caída de tensión:
Temperatura cable (ºC): 42.01
e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 %
e(total)=0.98% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: T.C. S. CALD
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 5 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/1,732x400x0.8=3.61 A.
Se eligen conductores Unipolares 4x6+TTx6mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 32 A. según ITC-BT-19
Diámetro exterior tubo: 25 mm.
Caída de tensión:
Temperatura cable (ºC): 40.38
e(parcial)=5x2000/51.45x400x6=0.08 V.=0.02 %
e(total)=0.7% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 16 A.
Cálculo de la Línea: LA. GENERAL
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1600 W.
- Potencia de cálculo: (Según ITC-BT-44):
1728 W.(Coef. de Simult.: 0.6 )
I=1728/230x0.8=9.39 A.
Se eligen conductores Unipolares 2x1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 49.72
e(parcial)=2x0.3x1728/49.76x230x1.5=0.06 V.=0.03 %
e(total)=0.7% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Página 24 de 59
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 200 W.
- Potencia de cálculo: (Según ITC-BT-44):
200x1.8=360 W.
I=360/230x1=1.57 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.33
e(parcial)=2x20x360/51.46x230x1.5=0.81 V.=0.35 %
e(total)=1.06% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: A.L. AZOTEA
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.73
e(parcial)=2x20x540/51.38x230x1.5=1.22 V.=0.53 %
e(total)=1.23% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. S. CALD
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
Página 25 de 59
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.73
e(parcial)=2x10x540/51.38x230x1.5=0.61 V.=0.26 %
e(total)=0.97% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. EXT I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x20x720/51.27x230x1.5=1.63 V.=0.71 %
e(total)=1.41% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. EXT I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x20x720/51.27x230x1.5=1.63 V.=0.71 %
Página 26 de 59
e(total)=1.41% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
CALCULO DE EMBARRADO SALA CALDERAS
Datos
- Metal: Cu
- Estado pletinas: desnudas
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 120
- Ancho (mm): 40
- Espesor (mm): 3
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.8, 1.6, 0.06, 0.009
- I. admisible del embarrado (A): 420
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =7.43² · 25² /(60 · 10 · 0.06 · 1) = 957.283 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 160.36 A
Iadm = 420 A
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 7.43 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 120 · 1 / (1000 · √0.5) = 27.83 kA
Cálculo de la Línea: MEDICO
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 5700 W.
- Potencia de cálculo: (Según ITC-BT-44):
4662 W.(Coef. de Simult.: 0.7 )
I=4662/230x0.8=25.34 A.
Se eligen conductores Unipolares 2x6+TTx6mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 36 A. según ITC-BT-19
Diámetro exterior tubo: 25 mm.
Página 27 de 59
Caída de tensión:
Temperatura cable (ºC): 54.86
e(parcial)=2x10x4662/48.88x230x6=1.38 V.=0.6 %
e(total)=0.97% ADMIS (4.5% MAX.)
Protección Termica en Principio de Línea
I. Mag. Bipolar Int. 30 A.
SUBCUADRO
MEDICO
DEMANDA DE POTENCIAS
- Potencia total instalada:
AL. COMUN
AL. CONSULTAS
AL. ENFER - CURAS
EMERG
TC. MEDIC II
TC. MEDIC I
TC. RESTO
TOTAL....
300 W
350 W
350 W
200 W
1500 W
1500 W
1500 W
5700 W
- Potencia Instalada Alumbrado (W): 1200
- Potencia Instalada Fuerza (W): 4500
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1200 W.
- Potencia de cálculo: (Según ITC-BT-44):
2160 W.(Coef. de Simult.: 1 )
I=2160/230x0.8=11.74 A.
Se eligen conductores Unipolares 2x1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 55.19
e(parcial)=2x0.3x2160/48.82x230x1.5=0.08 V.=0.03 %
e(total)=1% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: AL. COMUN
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
Página 28 de 59
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.73
e(parcial)=2x15x540/51.38x230x1.5=0.91 V.=0.4 %
e(total)=1.4% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. CONSULTAS
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 350 W.
- Potencia de cálculo: (Según ITC-BT-44):
350x1.8=630 W.
I=630/230x1=2.74 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41
e(parcial)=2x10x630/51.33x230x1.5=0.71 V.=0.31 %
e(total)=1.31% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. ENFER - CURAS
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 350 W.
- Potencia de cálculo: (Según ITC-BT-44):
350x1.8=630 W.
I=630/230x1=2.74 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Página 29 de 59
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41
e(parcial)=2x10x630/51.33x230x1.5=0.71 V.=0.31 %
e(total)=1.31% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 200 W.
- Potencia de cálculo: (Según ITC-BT-44):
200x1.8=360 W.
I=360/230x1=1.57 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.33
e(parcial)=2x15x360/51.46x230x1.5=0.61 V.=0.26 %
e(total)=1.27% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 4500 W.
- Potencia de cálculo:
4500 W.(Coef. de Simult.: 1 )
I=4500/230x0.8=24.46 A.
Se eligen conductores Unipolares 2x4mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 31 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 58.67
e(parcial)=2x0.3x4500/48.24x230x4=0.06 V.=0.03 %
e(total)=1% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 25 A.
Protección diferencial:
Página 30 de 59
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: TC. MEDIC II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=1.44% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC. MEDIC I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=1.44% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC. RESTO
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Página 31 de 59
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=1.44% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
CALCULO DE EMBARRADO MEDICO
Datos
- Metal: Cu
- Estado pletinas: desnudas
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 30
- Ancho (mm): 15
- Espesor (mm): 2
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.075, 0.0562, 0.01, 0.001
- I. admisible del embarrado (A): 140
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =3.38² · 25² /(60 · 10 · 0.01 · 1) = 1191.4 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 25.34 A
Iadm = 140 A
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 3.38 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 30 · 1 / (1000 · √0.5) = 6.96 kA
Cálculo de la Línea: PODOLOGO
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 6850 W.
- Potencia de cálculo: (Según ITC-BT-44): 5271 W.(Coef. de Simult.: 0.7 )
Página 32 de 59
I=5271/230x0.8=28.65 A.
Se eligen conductores Unipolares 2x10+TTx10mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 50 A. según ITC-BT-19
Diámetro exterior tubo: 25 mm.
Caída de tensión:
Temperatura cable (ºC): 49.85
e(parcial)=2x20x5271/49.74x230x10=1.84 V.=0.8 %
e(total)=1.17% ADMIS (4.5% MAX.)
Protección Termica en Principio de Línea
I. Mag. Bipolar Int. 40 A.
SUBCUADRO
PODOLOGO
DEMANDA DE POTENCIAS
- Potencia total instalada:
AL. COMUN
AL. CONSULTAS
EMERG
TC. LAVAND
TC. CONSULT
TC. RESTO
TOTAL....
300 W
350 W
200 W
3000 W
1500 W
1500 W
6850 W
- Potencia Instalada Alumbrado (W): 850
- Potencia Instalada Fuerza (W): 6000
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 850 W.
- Potencia de cálculo: (Según ITC-BT-44):
1530 W.(Coef. de Simult.: 1 )
I=1530/230x0.8=8.32 A.
Se eligen conductores Unipolares 2x1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 47.62
e(parcial)=2x0.3x1530/50.13x230x1.5=0.05 V.=0.02 %
e(total)=1.19% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Página 33 de 59
Cálculo de la Línea: AL. COMUN
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 300 W.
- Potencia de cálculo: (Según ITC-BT-44):
300x1.8=540 W.
I=540/230x1=2.35 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.73
e(parcial)=2x15x540/51.38x230x1.5=0.91 V.=0.4 %
e(total)=1.59% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AL. CONSULTAS
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 350 W.
- Potencia de cálculo: (Según ITC-BT-44):
350x1.8=630 W.
I=630/230x1=2.74 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41
e(parcial)=2x10x630/51.33x230x1.5=0.71 V.=0.31 %
e(total)=1.5% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 200 W.
- Potencia de cálculo: (Según ITC-BT-44):
200x1.8=360 W.
Página 34 de 59
I=360/230x1=1.57 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.33
e(parcial)=2x15x360/51.46x230x1.5=0.61 V.=0.26 %
e(total)=1.46% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 6000 W.
- Potencia de cálculo:
6000 W.(Coef. de Simult.: 1 )
I=6000/230x0.8=32.61 A.
Se eligen conductores Unipolares 2x6mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 40 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 59.94
e(parcial)=2x0.3x6000/48.04x230x6=0.05 V.=0.02 %
e(total)=1.19% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 40 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: TC. LAVAND
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 3000 W.
- Potencia de cálculo: 3000 W.
I=3000/230x0.8=16.3 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 58.08
e(parcial)=2x10x3000/48.34x230x2.5=2.16 V.=0.94 %
Página 35 de 59
e(total)=2.13% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 20 A.
Cálculo de la Línea: TC. CONSULT
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=1.64% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC. RESTO
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=1.64% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
CALCULO DE EMBARRADO PODOLOGO
Datos
- Metal: Cu
- Estado pletinas: desnudas
Página 36 de 59
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 24
- Ancho (mm): 12
- Espesor (mm): 2
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.048, 0.0288, 0.008, 0.0008
- I. admisible del embarrado (A): 110
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =2.99² · 25² /(60 · 10 · 0.008 · 1) = 1165.256 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 28.65 A
Iadm = 110 A
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 2.99 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 24 · 1 / (1000 · √0.5) = 5.57 kA
Cálculo de la Línea: 1ª PLANTA
- Tensión de servicio: 400 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 23050 W.
- Potencia de cálculo: (Según ITC-BT-44):
18683 W.(Coef. de Simult.: 0.7 )
I=18683/1,732x400x0.8=33.71 A.
Se eligen conductores Unipolares 4x10+TTx10mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 44 A. según ITC-BT-19
Diámetro exterior tubo: 32 mm.
Caída de tensión:
Temperatura cable (ºC): 57.61
e(parcial)=10x18683/48.42x400x10=0.96 V.=0.24 %
e(total)=0.61% ADMIS (4.5% MAX.)
Protección Termica en Principio de Línea
I. Mag. Tetrapolar Int. 40 A.
Protección Térmica en Final de Línea
I. Mag. Tetrapolar Int. 40 A.
Protección diferencial en Principio de Línea
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Página 37 de 59
SUBCUADRO
1ª PLANTA
DEMANDA DE POTENCIAS
- Potencia total instalada:
BIBLIO I
BIBLIO II
BIBLIO III
BAÑOS/COMUN
EMERG
TC BIBL I
TC BIBL I
TC BIBL I
TC DESP BIB
AULA
EMERG
SALA I
SALA II
SALA III
SALA IV
TC SALA I
TC SALA II
TC SALA III
TC SALA IV
TOTAL....
400 W
400 W
400 W
350 W
250 W
1000 W
1000 W
1000 W
1500 W
6900 W
250 W
400 W
400 W
400 W
400 W
2000 W
2000 W
2000 W
2000 W
23050 W
- Potencia Instalada Alumbrado (W): 4550
- Potencia Instalada Fuerza (W): 18500
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1800 W.
- Potencia de cálculo: (Según ITC-BT-44):
2592 W.(Coef. de Simult.: 0.8 )
I=2592/230x0.8=14.09 A.
Se eligen conductores Unipolares 2x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 51.25
e(parcial)=2x0.3x2592/49.49x230x2.5=0.05 V.=0.02 %
e(total)=0.63% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Página 38 de 59
Cálculo de la Línea: BIBLIO I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.17% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: BIBLIO II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.17% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: BIBLIO III
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
Página 39 de 59
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.17% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: BAÑOS/COMUN
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 350 W.
- Potencia de cálculo: (Según ITC-BT-44):
350x1.8=630 W.
I=630/230x1=2.74 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 40.51
e(parcial)=2x8x630/51.42x230x2.5=0.34 V.=0.15 %
e(total)=0.78% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 250 W.
- Potencia de cálculo: (Según ITC-BT-44):
250x1.8=450 W.
I=450/230x1=1.96 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.51
e(parcial)=2x10x450/51.42x230x1.5=0.51 V.=0.22 %
Página 40 de 59
e(total)=0.86% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 4500 W.
- Potencia de cálculo:
2700 W.(Coef. de Simult.: 0.6 )
I=2700/230x0.8=14.67 A.
Se eligen conductores Unipolares 2x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 52.21
e(parcial)=2x0.3x2700/49.33x230x2.5=0.06 V.=0.02 %
e(total)=0.64% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: TC BIBL I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1000 W.
- Potencia de cálculo: 1000 W.
I=1000/230x0.8=5.43 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.01
e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 %
e(total)=0.93% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC BIBL I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
Página 41 de 59
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1000 W.
- Potencia de cálculo: 1000 W.
I=1000/230x0.8=5.43 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.01
e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 %
e(total)=0.93% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC BIBL I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1000 W.
- Potencia de cálculo: 1000 W.
I=1000/230x0.8=5.43 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 42.01
e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 %
e(total)=0.93% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC DESP BIB
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Página 42 de 59
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=1.08% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: AULA
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 6900 W.
- Potencia de cálculo: (Según ITC-BT-44):
5334 W.(Coef. de Simult.: 0.7 )
I=5334/230x0.8=28.99 A.
Se eligen conductores Unipolares 2x6+TTx6mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 36 A. según ITC-BT-19
Diámetro exterior tubo: 25 mm.
Caída de tensión:
Temperatura cable (ºC): 59.45
e(parcial)=2x20x5334/48.11x230x6=3.21 V.=1.4 %
e(total)=2.01% ADMIS (4.5% MAX.)
Protección Termica en Principio de Línea
I. Mag. Bipolar Int. 30 A.
SUBCUADRO
AULA
DEMANDA DE POTENCIAS
- Potencia total instalada:
EMERG
AULA II
AULA I
TC I
TC II
TC III
RACK
TOTAL....
100 W
400 W
400 W
1500 W
1500 W
1500 W
1500 W
6900 W
- Potencia Instalada Alumbrado (W): 900
- Potencia Instalada Fuerza (W): 6000
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
Página 43 de 59
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 900 W.
- Potencia de cálculo: (Según ITC-BT-44):
1620 W.(Coef. de Simult.: 1 )
I=1620/230x0.8=8.8 A.
Se eligen conductores Unipolares 2x1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 48.54
e(parcial)=2x0.3x1620/49.97x230x1.5=0.06 V.=0.02 %
e(total)=2.03% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 100 W.
- Potencia de cálculo: (Según ITC-BT-44):
100x1.8=180 W.
I=180/230x1=0.78 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 40.08
e(parcial)=2x8x180/51.5x230x1.5=0.16 V.=0.07 %
e(total)=2.1% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AULA II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
Página 44 de 59
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x10x720/51.27x230x1.5=0.81 V.=0.35 %
e(total)=2.39% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: AULA I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x8x720/51.27x230x1.5=0.65 V.=0.28 %
e(total)=2.32% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 6000 W.
- Potencia de cálculo:
3600 W.(Coef. de Simult.: 0.6 )
I=3600/230x0.8=19.57 A.
Se eligen conductores Unipolares 2x2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 61.71
e(parcial)=2x0.3x3600/47.75x230x2.5=0.08 V.=0.03 %
e(total)=2.04% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 20 A.
Página 45 de 59
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: TC I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=2.49% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=2.49% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC III
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
Página 46 de 59
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=2.49% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: RACK
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1500 W.
- Potencia de cálculo: 1500 W.
I=1500/230x0.8=8.15 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 44.52
e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 %
e(total)=2.49% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
CALCULO DE EMBARRADO AULA
Datos
- Metal: Cu
- Estado pletinas: desnudas
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 24
- Ancho (mm): 12
- Espesor (mm): 2
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.048, 0.0288, 0.008, 0.0008
- I. admisible del embarrado (A): 110
Página 47 de 59
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =1.65² · 25² /(60 · 10 · 0.008 · 1) = 355.465 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 28.99 A
Iadm = 110 A
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 1.65 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 24 · 1 / (1000 · √0.5) = 5.57 kA
Cálculo de la Línea:
- Tensión de servicio: 400 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 1850 W.
- Potencia de cálculo: (Según ITC-BT-44):
3330 W.(Coef. de Simult.: 1 )
I=3330/1,732x400x0.8=6.01 A.
Se eligen conductores Unipolares 4x1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 44.81
e(parcial)=0.3x3330/50.63x400x1.5=0.03 V.=0.01 %
e(total)=0.62% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Tetrapolar Int. 10 A.
Protección diferencial:
Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: EMERG
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 250 W.
- Potencia de cálculo: (Según ITC-BT-44):
250x1.8=450 W.
I=450/230x1=1.96 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Página 48 de 59
Caída de tensión:
Temperatura cable (ºC): 40.51
e(parcial)=2x15x450/51.42x230x1.5=0.76 V.=0.33 %
e(total)=0.95% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: SALA I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.15% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: SALA II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.15% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Página 49 de 59
Cálculo de la Línea: SALA III
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.15% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea: SALA IV
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0;
- Potencia a instalar: 400 W.
- Potencia de cálculo: (Según ITC-BT-44):
400x1.8=720 W.
I=720/230x1=3.13 A.
Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19
Diámetro exterior tubo: 16 mm.
Caída de tensión:
Temperatura cable (ºC): 41.31
e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 %
e(total)=1.15% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 10 A.
Cálculo de la Línea:
- Tensión de servicio: 230 V.
- Canalización: C-Unip.o Mult.sobre Pared
- Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 8000 W.
- Potencia de cálculo:
4800 W.(Coef. de Simult.: 0.6 )
Página 50 de 59
I=4800/230x0.8=26.09 A.
Se eligen conductores Unipolares 2x4mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 31 A. según ITC-BT-19
Caída de tensión:
Temperatura cable (ºC): 61.24
e(parcial)=2x0.3x4800/47.82x230x4=0.07 V.=0.03 %
e(total)=0.64% ADMIS (4.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 30 A.
Protección diferencial:
Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA.
Cálculo de la Línea: TC SALA I
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 %
e(total)=1.24% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC SALA II
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 %
e(total)=1.24% ADMIS (6.5% MAX.)
Página 51 de 59
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC SALA III
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 %
e(total)=1.24% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
Cálculo de la Línea: TC SALA IV
- Tensión de servicio: 230 V.
- Canalización: B1-Unip.Tubos Superf.o Emp.Obra
- Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0;
- Potencia a instalar: 2000 W.
- Potencia de cálculo: 2000 W.
I=2000/230x0.8=10.87 A.
Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu
Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K
I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19
Diámetro exterior tubo: 20 mm.
Caída de tensión:
Temperatura cable (ºC): 48.04
e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 %
e(total)=1.24% ADMIS (6.5% MAX.)
Prot. Térmica:
I. Mag. Bipolar Int. 16 A.
CALCULO DE EMBARRADO 1ª PLANTA
Datos
- Metal: Cu
- Estado pletinas: desnudas
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
Página 52 de 59
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 45
- Ancho (mm): 15
- Espesor (mm): 3
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.112, 0.084, 0.022, 0.003
- I. admisible del embarrado (A): 170
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =4.57² · 25² /(60 · 10 · 0.022 · 1) = 989.437 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 33.71 A
Iadm = 170 A
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 4.57 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 45 · 1 / (1000 · √0.5) = 10.44 kA
CALCULO DE EMBARRADO CUADRO GENERAL DE MANDO Y PROTECCION
Datos
- Metal: Cu
- Estado pletinas: desnudas
- nº pletinas por fase: 1
- Separación entre pletinas, d(cm): 10
- Separación entre apoyos, L(cm): 25
- Tiempo duración c.c. (s): 0.5
Pletina adoptada
- Sección (mm²): 100
- Ancho (mm): 20
- Espesor (mm): 5
- Wx, Ix, Wy, Iy (cm3,cm4) : 0.333, 0.333, 0.083, 0.0208
- I. admisible del embarrado (A): 290
a) Cálculo electrodinámico
σmax = Ipcc² · L² / ( 60 · d · Wy · n) =9.5² · 25² /(60 · 10 · 0.083 · 1) = 1131.527 <= 1200 kg/cm² Cu
b) Cálculo térmico, por intensidad admisible
Ical = 234.06 A
Iadm = 290 A
Página 53 de 59
c) Comprobación por solicitación térmica en cortocircuito
Ipcc = 9.5 kA
Icccs = Kc · S / ( 1000 · √tcc) = 164 · 100 · 1 / (1000 · √0.5) = 23.19 kA
Los resultados obtenidos se reflejan en las siguientes tablas:
Cuadro General de Mando y Protección
Denominación
ACOMETIDA
LINEA GENERAL ALIMENT.
DERIVACION IND.
GYM
EMERG.
AL. GYM
T.C. GYM
F/C GYM
BAR
AL. GEN P_BA
F/C Z. COMUN
EMERG
BAÑOS GYM
BAÑOS GRAL.
VESTIBL Z. COMUNES
SALA CALDERAS
MEDICO
PODOLOGO
1ª PLANTA
P.Cálculo
(W)
162160
162160
129728
1938
180
900
2000
150
18284
1830
800
450
450
630
720
88880
4662
5271
18683
Dist.Cálc
(m)
Sección
(mm²)
I.Cálculo
(A)
20
10
15
0.3
20
20
25
10
10
0.3
20
15
25
10
20
25
10
20
10
3x185/95Al
4x240+TTx120Cu
4x95+TTx50Cu
2x2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x10+TTx10Cu
4x2.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
4x95+TTx50Cu
2x6+TTx6Cu
2x10+TTx10Cu
4x10+TTx10Cu
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
292.58
292.58
234.06
10.53
0.78
3.91
10.87
0.82
32.99
3.3
4.35
1.96
1.96
2.74
3.13
160.36
25.34
28.65
33.71
300
401
268
23
15
15
21
21
44
21
21
15
15
21
15
180
36
50
44
0.4
0.09
0.28
0.02
0.18
0.89
1.51
0.04
0.24
0
0.47
0.33
0.55
0.19
0.71
0.31
0.6
0.8
0.24
0.4
0.09
0.37
0.39
0.56
1.27
1.9
0.43
0.61
0.37
0.84
0.7
0.92
0.56
1.08
0.68
0.97
1.17
0.61
180
200
125
16
16
20
20
32
20
16
16
20
16
75
25
25
32
Cortocircuito
Denominación
Longitud
(m)
LINEA GENERAL ALIMENT. 10
DERIVACION IND.
15
GYM
0.3
EMERG.
20
AL. GYM
20
T.C. GYM
25
F/C GYM
10
BAR
10
AL. GEN P_BA
0.3
F/C Z. COMUN
20
EMERG
15
BAÑOS GYM
25
BAÑOS GRAL.
10
VESTIBL Z. COMUNES
20
SALA CALDERAS
25
MEDICO
10
PODOLOGO
20
1ª PLANTA
10
Sección
(mm²)
IpccI
(kA)
4x240+TTx120Cu
4x95+TTx50Cu
2x2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x10+TTx10Cu
4x2.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
4x95+TTx50Cu
2x6+TTx6Cu
2x10+TTx10Cu
4x10+TTx10Cu
12
11.39
9.53
8.47
8.47
8.47
8.47
9.53
9.53
8.47
8.47
8.47
8.47
8.47
9.53
9.53
9.53
9.53
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
tficc
(sg)
Lmáx
(m)
50
15
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
5673.62
4747.63
4215.15
299.99
299.99
391.04
861.43
2285.66
4215.15
478.1
391.04
243.33
861.43
299.99
3712.8
1690.96
1495.76
2285.66
36.59
8.19
0.752
374.69
0.33
0.33
0.54
0.11
0.25
0.36
0.19
0.5
0.11
0.33
8.66
0.17
0.59
0.25
Curvas válidas
315
250;B,C
16
10;B,C,D
10;B,C,D
16;B,C,D
16;B,C,D
40;B,C,D
16
16;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
250;B,C
30;B,C,D
40;B,C,D
40;B,C,D
Subcuadro BAR
Denominación
EMERG
AL. ESTAR I
AL. ESTAR II
P.Cálculo
(W)
864
360
540
540
864
Dist.Cálc
(m)
Sección
(mm²)
0.3
8
8
8
0.3
4x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x2.5Cu
I.Cálculo
(A)
1.56
1.57
2.35
2.35
1.56
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
21
21
21
21
21
0
0.08
0.13
0.13
0
0.61
0.69
0.73
0.73
0.61
Página 54 de 59
20
20
20
EMERG
AL. COMEDOR I
AL. COMEDOR II
EMERG
AL. COCINA
AL. BARRA
F/C BAR COMEDOR
EXTRACTOR
TC. DESPACHO BAR
CAFETERA
BOTELLEROS
T.C. COCINA I
T.C. COCINA II
T.C. COCINA III
PLANCHA/FREID
360
540
540
864
360
540
540
10800
800
1000
2000
5000
2000
7700
2000
3000
3000
3000
8
8
8
0.3
8
8
8
0.3
15
10
20
5
10
0.3
10
10
10
8
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x4Cu
2x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x4+TTx4Cu
4x2.5+TTx2.5Cu
4x2.5Cu
2x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
1.57
2.35
2.35
1.56
1.57
2.35
2.35
19.49
4.35
1.8
10.87
9.02
3.61
13.89
10.87
5.41
5.41
5.41
21
21
21
21
21
21
21
27
21
18.5
21
24
18.5
21
21
18.5
18.5
18.5
0.08
0.13
0.13
0
0.08
0.13
0.13
0.01
0.35
0.05
1.21
0.08
0.1
0.01
0.6
0.15
0.15
0.12
0.69
0.73
0.73
0.61
0.69
0.73
0.73
0.62
0.97
0.66
1.82
0.69
0.71
0.62
1.22
0.76
0.76
0.73
20
20
20
20
20
20
20
20
20
25
20
20
20
20
20
Cortocircuito
Denominación
EMERG
AL. ESTAR I
AL. ESTAR II
EMERG
AL. COMEDOR I
AL. COMEDOR II
EMERG
AL. COCINA
AL. BARRA
F/C BAR COMEDOR
EXTRACTOR
TC. DESPACHO BAR
CAFETERA
BOTELLEROS
T.C. COCINA I
T.C. COCINA II
T.C. COCINA III
PLANCHA/FREID
Longitud
(m)
0.3
8
8
8
0.3
8
8
8
0.3
8
8
8
0.3
15
10
20
5
10
0.3
10
10
10
8
Sección
(mm²)
IpccI
(kA)
4x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x4Cu
2x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x4+TTx4Cu
4x2.5+TTx2.5Cu
4x2.5Cu
2x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
4x2.5+TTx2.5Cu
4.59
4.32
4.32
4.32
4.59
4.32
4.32
4.32
4.59
4.32
4.32
4.32
4.59
4.42
4.42
4.42
4.42
4.42
4.59
4.32
4.32
4.32
4.32
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
6
4.5
4.5
4.5
6
4.5
4.5
4.5
6
4.5
4.5
4.5
6
4.5
4.5
4.5
4.5
4.5
6
4.5
4.5
4.5
4.5
2149.9
828.25
828.25
828.25
2149.9
828.25
828.25
828.25
2149.9
828.25
828.25
828.25
2198.9
541.01
723.08
432.16
1344.27
723.08
2149.9
717.65
717.65
717.65
828.25
0.02
0.12
0.12
0.12
0.02
0.12
0.12
0.12
0.02
0.12
0.12
0.12
0.04
0.28
0.16
0.44
0.12
0.16
0.02
0.16
0.16
0.16
0.12
tficc
(sg)
Lmáx
(m)
Curvas válidas
10
10;B,C,D
10;B,C,D
10;B,C,D
10
10;B,C,D
10;B,C,D
10;B,C,D
10
10;B,C,D
10;B,C,D
10;B,C,D
20
16;B,C,D
16;B,C,D
16;B,C,D
16;B,C,D
16;B,C,D
16
16;B,C,D
16;B,C,D
16;B,C,D
16;B,C,D
Subcuadro SALA CALDERAS
Denominación
RESERVA ENFRIADORA
LF. GENERAL
VENTILACION
CALDERA
T.C. S. CALD
LA. GENERAL
EMERG
A.L. AZOTEA
AL. S. CALD
AL. EXT I
AL. EXT I
P.Cálculo
(W)
80000
3600
3000
1000
2000
1728
360
540
540
720
720
Dist.Cálc
(m)
Sección
(mm²)
10
0.3
25
10
5
0.3
20
20
10
20
20
4x70+TTx35Cu
4x6Cu
4x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x6+TTx6Cu
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
I.Cálculo
(A)
144.34
6.5
5.41
5.43
3.61
9.39
1.57
2.35
2.35
3.13
3.13
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
149
36
18.5
21
32
16.5
15
15
15
15
15
0.15
0
0.37
0.3
0.02
0.03
0.35
0.53
0.26
0.71
0.71
0.83
0.68
1.05
0.98
0.7
0.7
1.06
1.23
0.97
1.41
1.41
Página 55 de 59
63
20
20
25
16
16
16
16
16
Cortocircuito
Denominación
Longitud
(m)
RESERVA ENFRIADORA
LF. GENERAL
VENTILACION
CALDERA
T.C. S. CALD
LA. GENERAL
EMERG
A.L. AZOTEA
AL. S. CALD
AL. EXT I
AL. EXT I
10
0.3
25
10
5
0.3
20
20
10
20
20
Sección
(mm²)
IpccI
(kA)
4x70+TTx35Cu
4x6Cu
4x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
4x6+TTx6Cu
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
7.46
7.46
7.16
7.16
7.16
7.46
6.38
6.38
6.38
6.38
6.38
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
10
10
10
10
10
10
10
10
10
10
10
3315.21
3563.56
384.28
829.35
2122.05
3178.47
292.97
292.97
537.31
292.97
292.97
5.9
0.04
0.56
0.12
0.11
tficc
(sg)
Lmáx
(m)
Curvas válidas
160;B,C,D
16
16;B,C,D
16;B,C,D
16;B,C,D
10
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
0.35
0.35
0.1
0.35
0.35
Subcuadro MEDICO
Denominación
P.Cálculo
(W)
2160
540
630
630
360
4500
1500
1500
1500
AL. COMUN
AL. CONSULTAS
AL. ENFER - CURAS
EMERG
TC. MEDIC II
TC. MEDIC I
TC. RESTO
Dist.Cálc
(m)
Sección
(mm²)
I.Cálculo
(A)
0.3
15
10
10
15
0.3
10
10
10
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
11.74
2.35
2.74
2.74
1.57
24.46
8.15
8.15
8.15
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
16.5
15
15
15
15
31
21
21
21
0.03
0.4
0.31
0.31
0.26
0.03
0.45
0.45
0.45
1
1.4
1.31
1.31
1.27
1
1.44
1.44
1.44
16
16
16
16
20
20
20
Cortocircuito
Denominación
Longitud
(m)
0.3
15
10
10
15
0.3
10
10
10
AL. COMUN
AL. CONSULTAS
AL. ENFER - CURAS
EMERG
TC. MEDIC II
TC. MEDIC I
TC. RESTO
Sección
(mm²)
IpccI
(kA)
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
3.4
3.15
3.15
3.15
3.15
3.4
3.3
3.3
3.3
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
1568.2
337.38
457.07
457.07
337.38
1642.75
650.16
650.16
650.16
0.01
0.26
0.14
0.14
0.26
0.08
0.2
0.2
0.2
tficc
(sg)
Lmáx
(m)
Curvas válidas
16
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
25
16;B,C,D
16;B,C,D
16;B,C,D
Subcuadro PODOLOGO
Denominación
P.Cálculo
(W)
1530
540
630
360
6000
3000
1500
1500
AL. COMUN
AL. CONSULTAS
EMERG
TC. LAVAND
TC. CONSULT
TC. RESTO
Dist.Cálc
(m)
Sección
(mm²)
I.Cálculo
(A)
0.3
15
10
15
0.3
10
10
10
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x6Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
8.32
2.35
2.74
1.57
32.61
16.3
8.15
8.15
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
16.5
15
15
15
40
21
21
21
0.02
0.4
0.31
0.26
0.02
0.94
0.45
0.45
1.19
1.59
1.5
1.46
1.19
2.13
1.64
1.64
16
16
16
20
20
20
Cortocircuito
Denominación
AL. COMUN
AL. CONSULTAS
EMERG
Longitud
(m)
0.3
15
10
15
Sección
(mm²)
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
IpccI
(kA)
3
2.81
2.81
2.81
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
4.5
4.5
4.5
4.5
1398.77
328.78
441.41
328.78
0.02
0.28
0.15
0.28
tficc
(sg)
Lmáx
(m)
Curvas válidas
10
10;B,C,D
10;B,C,D
10;B,C,D
Página 56 de 59
TC. LAVAND
TC. CONSULT
TC. RESTO
0.3
10
10
10
2x6Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
3
2.95
2.95
2.95
4.5
4.5
4.5
4.5
1470.28
621.19
621.19
621.19
0.22
0.21
0.21
0.21
40
20;B,C,D
16;B,C,D
16;B,C,D
Subcuadro 1ª PLANTA
Denominación
P.Cálculo
(W)
2592
720
720
720
630
450
2700
1000
1000
1000
1500
5334
3330
450
720
720
720
720
4800
2000
2000
2000
2000
BIBLIO I
BIBLIO II
BIBLIO III
BAÑOS/COMUN
EMERG
TC BIBL I
TC BIBL I
TC BIBL I
TC DESP BIB
AULA
EMERG
SALA I
SALA II
SALA III
SALA IV
TC SALA I
TC SALA II
TC SALA III
TC SALA IV
Dist.Cálc
(m)
Sección
(mm²)
I.Cálculo
(A)
0.3
15
15
15
8
10
0.3
10
10
10
10
20
0.3
15
15
15
15
15
0.3
10
10
10
10
2x2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
2x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x6+TTx6Cu
4x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
14.09
3.13
3.13
3.13
2.74
1.96
14.67
5.43
5.43
5.43
8.15
28.99
6.01
1.96
3.13
3.13
3.13
3.13
26.09
10.87
10.87
10.87
10.87
23
15
15
15
21
15
23
21
21
21
21
36
15
15
15
15
15
15
31
21
21
21
21
0.02
0.53
0.53
0.53
0.15
0.22
0.02
0.3
0.3
0.3
0.45
1.4
0.01
0.33
0.53
0.53
0.53
0.53
0.03
0.6
0.6
0.6
0.6
0.63
1.17
1.17
1.17
0.78
0.86
0.64
0.93
0.93
0.93
1.08
2.01
0.62
0.95
1.15
1.15
1.15
1.15
0.64
1.24
1.24
1.24
1.24
16
16
16
20
16
20
20
20
20
25
16
16
16
16
16
20
20
20
20
Cortocircuito
Denominación
BIBLIO I
BIBLIO II
BIBLIO III
BAÑOS/COMUN
EMERG
TC BIBL I
TC BIBL I
TC BIBL I
TC DESP BIB
AULA
EMERG
SALA I
SALA II
SALA III
SALA IV
TC SALA I
TC SALA II
TC SALA III
TC SALA IV
Longitud
(m)
0.3
15
15
15
8
10
0.3
10
10
10
10
20
0.3
15
15
15
15
15
0.3
10
10
10
10
Sección
(mm²)
2x2.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5+TTx2.5Cu
2x1.5+TTx1.5Cu
2x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x6+TTx6Cu
4x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x4Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
IpccI
(kA)
4.59
4.32
4.32
4.32
4.32
4.32
4.59
4.32
4.32
4.32
4.32
4.59
4.59
4.15
4.15
4.15
4.15
4.15
4.59
4.42
4.42
4.42
4.42
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
6
4.5
4.5
4.5
4.5
4.5
6
4.5
4.5
4.5
4.5
6
6
4.5
4.5
4.5
4.5
4.5
6
4.5
4.5
4.5
4.5
2149.9
358.41
358.41
358.41
828.25
496.52
2149.9
717.65
717.65
717.65
717.65
826.13
2067.93
356.03
356.03
356.03
356.03
356.03
2198.9
723.08
723.08
723.08
723.08
0.02
0.23
0.23
0.23
0.12
0.12
0.02
0.16
0.16
0.16
0.16
0.7
0.01
0.23
0.23
0.23
0.23
0.23
0.04
0.16
0.16
0.16
0.16
tficc
(sg)
Lmáx
(m)
Curvas válidas
16
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
16
16;B,C,D
16;B,C,D
16;B,C,D
16;B,C,D
30;B,C,D
10
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
10;B,C,D
30
16;B,C,D
16;B,C,D
16;B,C,D
16;B,C,D
Página 57 de 59
Subcuadro AULA
Denominación
P.Cálculo
(W)
1620
180
720
720
3600
1500
1500
1500
1500
EMERG
AULA II
AULA I
TC I
TC II
TC III
RACK
Dist.Cálc
(m)
Sección
(mm²)
I.Cálculo
(A)
0.3
8
10
8
0.3
10
10
10
10
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
8.8
0.78
3.13
3.13
19.57
8.15
8.15
8.15
8.15
I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm)
(A)
(%)
(%)
Tubo,Canal,Band.
16.5
15
15
15
23
21
21
21
21
0.02
0.07
0.35
0.28
0.03
0.45
0.45
0.45
0.45
2.03
2.1
2.39
2.32
2.04
2.49
2.49
2.49
2.49
16
16
16
20
20
20
20
Cortocircuito
Denominación
EMERG
AULA II
AULA I
TC I
TC II
TC III
RACK
Longitud
(m)
0.3
8
10
8
0.3
10
10
10
10
Sección
(mm²)
2x1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x1.5+TTx1.5Cu
2x2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
2x2.5+TTx2.5Cu
IpccI
(kA)
1.66
1.6
1.6
1.6
1.66
1.62
1.62
1.62
1.62
P de C
(kA)
IpccF
(A)
tmcicc
(sg)
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
795.56
400.28
356.03
400.28
807.51
460.99
460.99
460.99
460.99
0.05
0.19
0.23
0.19
0.13
0.39
0.39
0.39
0.39
tficc
(sg)
Lmáx
(m)
Curvas válidas
10
10;B,C,D
10;B,C,D
10;B,C,D
20
16;B,C,D
16;B,C,D
16;B,C,D
16;B,C,D
Página 58 de 59
CALCULO DE LA PUESTA A TIERRA
- La resistividad del terreno es 300 ohmiosxm.
- El electrodo en la puesta a tierra del edificio, se constituye con los siguientes elementos:
M. conductor de Cu desnudo
M. conductor de Acero galvanizado
35 mm² 30 m.
95 mm²
Picas verticales de Cobre
de Acero recubierto Cu
de Acero galvanizado
14 mm
14 mm 1 picas de 2m.
25 mm
Con lo que se obtendrá una Resistencia de tierra de 17.65 ohmios.
Los conductores de protección, se calcularon adecuadamente y según la ITC-BT-18, en el apartado del
cálculo de circuitos.
Así mismo cabe señalar que la linea principal de tierra no será inferior a 16 mm² en Cu, y la linea de enlace
con tierra, no será inferior a 25 mm² en Cu.
Página 59 de 59
Descargar