PROJECTE D’EXECUCIÓ DEL CENTRE CÍVIC I DEPENDÈNCIES SOCIALS A BELL-LLOC D’URGELL SETEMBRE 2009 DOCUMENT 1: MEMÒRIA I ANNEXES PROMOTOR: AJUNTAMENT DE BELL·LLOC D’URGELL AUTOR: COSTA · PORTOLÉS ARQUITECTES, SLP CONTINGUT DEL PROJECTE DOCUMENT 1: MEMÒRIA I ANNEXES 1. MEMÒRIA DESCRIPTIVA 1.1 Dades Bàsiques 1.2 Contingut del Projecte 1.3 Fitxa Urbanística 1.4 Estat actual i disponibilitat de terrenys 1.5 Quadre de superficies 2. MEMÒRIA CONSTRUCTIVA 2.1 Introducció 2.2 Demolicions 2.3 Excavacions i encofrats 2.4 Fonaments 2.5 Solera 2.6 Estructura 2.7 Acabats exteriors 2.8 Impermeabilitzants i aïllants 2.9 Divisions interiors 2.10 Paviments i revestiments 2.11 Fusteries 2.12 Pintura 2.13 Instal·lacions i eficiència energética 3. MEMÒRIA DE L’ESTRUCTURA 4. ANNEX. PROJECTE DE CLIMATITZACIÓ 5. ANNEX. INSTAL·LACIÓ BAIXA TENSIÓ DOCUMENT 2: PLEC DE CONDICIONS DOCUMENT 3: PRESSUPOST DOCUMENT 4: ESTUDI DE SEGURETAT I SALUT DOCUMENT 5: JUSTIFICACIÓ COMPLIMENT DEL CODI TÈCNIC 6. PLÀNOLS - PLÀNOL I01 SITUACIÓ I EMPLAÇAMENT - PLÀNOL E01 ESTRUCTURA EDIFICI ANNEX - PLÀNOL A01 PLANTA BAIXA - DISTRIBUCIÓ - PLÀNOL A02 PLANTA PRIMERA - DISTRIBUCIÓ - PLÀNOL A03 PLANTA COBERTA – DISTRIBUCIÓ - PLÀNOL A04 PLANTA BAIXA – COTES I SUPERFÍCIES - PLÀNOL A05 PLANTA PRIMERA – COTES I SUPERFÍCIES - PLÀNOL A06 PLANTA COBERTA – COTES - PLÀNOL A07 FAÇANES NORD I SUD - PLÀNOL A08 FAÇANA EST I OEST - PLÀNOL A09 SECCIÓ SUD, DETALLS - PLÀNOL A10 SECCIÓ OEST - PLÀNOL A11 FUSTERIES - PLÀNOL INS01 PLANTA BAIXA AIGUA FREDA I CALENTA - PLÀNOL INS02 PLANTA PRIMERA AIGUA FREDA I CALENTA - PLÀNOL INS03 ESQUEMA UNIFILAR - PLÀNOL INS04 PLANTA BAIXA INSTAL·LACIÓ ELÈCTRICA - PLÀNOL INS05 PLANTA PRIMERA INSTAL·LACIÓ ELÈCTRICA - PLÀNOL INS06 PLANTA BAIXA CLIMATITZACIÓ - PLÀNOL INS07 PLANTA PRIMERA CLIMATITZACIÓ - PLÀNOL INS08 PLANTA BAIXA VENTILACIÓ - PLÀNOL INS09 PLANTA PRIMERA VENTILACIÓ - PLÀNOL INS10 PLANTA BAIXA PROTECCIÓ CONTRA INCENDIS - PLÀNOL INS11 PLANTA PRIMERA PROTECCIÓ CONTRA INCENDIS - PLÀNOL INS12 PLANTA BAIXA CEL RAS - PLÀNOL INS13 PLANTA PRIMERA CEL RAS 1 MEMÒRIA DESCRIPTIVA 1.1 DADES BÀSIQUES FINALITAT : La finalitat d’aquesta memòria és la remodelació de l’edifici de les antigues escoles per a ubicar un equipament socio-cultural a la població de Bell-lloc DADES CADASTRALS : Referència cadastral: 4914611CG1141S0001JU Localització: c/ Joan Oró, 3 BELL·LLOC D'URGELL 25220 LLEIDA Classe: Urbana Superfície(*): 807 m2 Ús: Cultural Any construcció local principal: 1965 PROMOTOR : Ajuntament de Bell-lloc d’Urgell EQUIP REDACTOR : Costa · Portolés , arquitectes sl Passeig de Ronda, 162 6è E 25008 Lleida Tel. 973 239 439 David Portolés Martínez, arquitecte urbanista Anna Costa Isern, arquitecta Jael Soro Astals, arquitecte tècnic Joan Capdevila Cebollero, delineant 1.2 FITXA URBANÍSTICA NORMATIVA VIGENT : POUM BELL·LLOC CLASSIFICACIÓ DEL SÒL : SÒL URBÀ QUALIFICACIÓ DEL SOLAR : EQUIPAMENT 1.3 ESTAT ACTUAL I DISPONIBILITAT DE TERRENYS En l’actualitat l’edifici de les escoles es de titularitat municipal. Tot i que no te un ús específic, es utilitzat esporàdicament per realitzar activitats de caràcter educatiu. Es una edificació construïda a l’any 65 amb una configuració característica de les realitzades a les hores per l’estat central amb destí escolar. Es tracta d’un edifici composat de diferents cossos paralepipèdics de planta i pis, articulats al voltant d’un cos específic que alberga l’escala. La estructura portant es mixta, amb pilars d’obra en façana i parets de carrega conformant les distribucions interiors. Els forjats son de ceràmica armada i aquest element es el que es troba més degradat, degut fonamentalment a la seva incorrecta execució, ja que es pot observar el fet que el formigó abocat ‘in situ’ no va acabar de recobrir les armadures metàl·liques, amb la qual cosa aquestes van quedar exposades a un procés de corrosió especialment intens. La coberta es inclinada de teula àrab. En la composició de façana els trets més característics són les fenestracions continues que configuren franges horitzontals on la separació entre finestres es a l’hora l’element portant. La superfície construïda actual es de uns 800 m2 de sostre. 1.4 PROGRAMA I QUADRE DE SUPERFÍCIES Les noves instal·lacions s’han de composar de : - Un centre de dia per a avis, amb les següents dependències: Sala d’estar i d’activitats, menjador, cuina, gimnàs, oficines pels assistents socials, oficina pel podòleg, vestuaris i bugaderia, tot amb les corresponents parts proporcional d’espais de circulació i de serveis adaptats. - Un dispensari mèdic que ha de substituir i fer les funcions del que actualment funciona a la població. - Una sèrie d’aules destinades a ensenyança de noves tecnologies i l’ús de les associacions cíviques i veïnals . - Una biblioteca El projecte es desenvolupa segons el programa i el quadre de superfícies següent : QUADRE DE SUPERFÍCIES CONSTRUIDES PLANTA BAIXA- 723.02 m2 PLANTA PRIMERA- 543.08 m2 PLANTA TERCERA- 87.73 m2 TOTAL- 1353.83 m2 QUADRE DE SUPERFÍCIES ÚTILS Planta baixa Estància Consultori Centre de dia Consulta metge 1 Cures Infermeria Consulta metge 2 Bany personal Arxiu Sala d'espera 2 Passadís 3 Passadís 2 Bany homes Bany dones Rebost Cuina Vestíbul Minibar Menjador Sala d'activitats Passadís 1 Despatx de gestió Podòleg Vestidors personal Vestidors usuaris Gimnàs Fisioteràpia Magatzem Bugaderia Distribuïdor banys Escales Banys geriàtrics Dutxa geriàtrica 1 Dutxa geriàtrica 2 Neteja TOTAL Superfíces 21,23 14,08 15,17 18,94 4,87 12,24 29,06 10,99 14,58 13,21 14,68 8,38 20,67 37,3 8,28 43,69 36,44 60 25,82 21,15 14,15 23,14 22,61 8,49 12,46 17,92 4,86 9,35 13,6 4,14 4,14 2,46 568,1 Planta primera Estància Zona d'acollida i promoció Zona de treball intern Biblioteca Zona general Zona infantil Local 1 Local 2 Sales actes Local 3 Local 4 Local 5 Banys Zones comuns Escales Passadís TOTAL SUPERFÍCIE ÚTIL TOTAL = 1052,96 M2 Superfícies 49,98 23,31 155,55 46,68 23,53 23,53 24,11 24,34 33,56 17,01 13,27 49,99 484,86 2 MEMÒRIA CONSTRUCTIVA 2.1 INTRODUCCIÓ Sota cap concepte es permetrà l’ inici de les obres sense l'autorització de la Direcció Facultativa i signatura del Llibre d’Ordres per part del contractista. Durant tot el procés s'exigirà la presència continua a l'obra d'una persona concreta responsable de la mateixa i interlocutora de la Direcció Facultativa. La zona d'actuació estarà efectivament delimitada, senyalada i tancada a l’accés de persones alienes a l'obra. Aquesta actuació restarà des de l' inici dels treballs fins al final de l'obra. 2.2 MOVIMENT DE TERRES Desprès de netejar el solar, s’hauran de replantejar els fonaments, es farà l’excavació de rases i pous, d’acord amb les especificacions dels plànols. Es preveu una tensió de treball admissible del terreny de 0.07 N /mm2. El moviment de terres es realitzarà per mitjans mecànics fins a la fondària especificada en els plànols, excepte on faci falta realitzar-ho manualment. 2.3 EXCAVACIONS I ENCOFRATS S’excavaran les rases i els pous corresponents als fonaments i a les instal·lacions soterrades, que es col·locaran segons les especificacions dels plànols. Els encofrats tindran en les seves unions i apuntalaments la resistència i rigidesa necessàries per a complir aquesta condició i estaran disposats de la forma que puguin desencofrar-se sense que calgui donar cops que perjudiquin al formigó. Els apuntalaments es disposaran de manera que no es produeixin sobre els elements inferiors de l’estructura, càrregues de treball superiors a 1/3 de la seva resistència. Els motlles s’humitejaran i netejaran immediatament abans del formigonat. La fusta dels encofrats tindrà les fibres rectes sense esquerdes ni nusos. Es permetran encofrats metàl·lics o de melamina homologats. 2.4 FONAMENTS Per les característiques de l’edificació i de l’estudi geotècnic, els fonaments es realitzaran mitjançant una cimentació superficial, de sabates aïllades centrades i arriostrades, sobre pous de cimentació. 2.5 SOLERA Després de netejar i anivellar el terreny interior, es col·locarà una subbase de grava, una làmina de polietilè i una base de 15cm. de formigó armat. 2.6 ESTRUCTURA L’estructura, que en aquesta fase solament es la corresponent al cos d’ampliació destinat a bugaderia serà de murs de carrega amb forjat unidireccional de biguetes autor resistents 2.7 ACABATS EXTERIORS Els acabats exteriors seran de xapa minionda galvanitzada en el cas dels tancaments existents i del volum de la sala d’actes, o de morter monocapa en el cas de les plantes baixes per als tancaments de termoarcilla. 2.8 IMPERMEABILITZANTS I AÏLLANTS Es farà un drenatge horitzontal circunvoltant de tot l’edifici existent. A la coberta invertida la làmina impermeabilitzant serà de betum plastomèric amb doble armadura: feltre de poliester i film de polietilè; col·locada no adherida a la base i doblegada en els punts singulars. En les ampliacions la coberta es realitzarà amb xapa minionda similar a la de façana. Els aïllaments tèrmics es realitzaran amb polieuretà projectat de cela tancada. 2.9 DIVISIONS INTERIORS Els envans no coincidents amb parets de càrrega cerán ceramics de 6 cmts 2.10 PAVIMENTS I REVESTIMENTS El paviment de l’edifici serà de gres ceràmic anti-lliscamentper en les arees humides i paviment continuo vinilic a la resta de locals, amb mides i disposició especificats en els plànols i en els amidaments. 2.11 FUSTERIES La fusteria interior serán de fusta eventualment vidriada El vidre serà laminar de dues capes de 3mm+3mm. 2.12 PINTURA La pintura serà plàstica llisa per l’interior, amb una capa d’imprimació i dues mans d’acabat. A tota la fusta se li farà un tractament insecticida-fungicida, una capa de segellat i dues mans de pintura. 2.13 INSTAL·LACIONS I EFICIÈNCIA ENERGÈTICA El sistema de calefacció es farà a partir d’una caldera de bio-massa. La composició de les façanes es dissenya de tal manera que la inèrcia tèrmica es situa a l’interior de l’edifici. Es preveu la instal·lació de captadors solars d’aigua calenta i de plaques fotovoltaiques. Lleida, setembre de 2009 Anna Costa Isern i David Portolés Martínez, arquitectes. ANNEX. CÀLCUL ESTRUCTURAL Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 ÍNDEX DOCUMENT 1 MEMÒRIA DE CÀLCUL 1.- CARACTERÍSTIQUES DE L'ESTRUCTURA I SOLICITACIONS 0 1.1.- SITUACIÓ. EXPEDIENT. DATA. PROMOTOR 0 1.2.- DEFINICIÓ i JUSTIFICACIÓ DE LA TIPOLOGIA ESTRUCTURAL 0 1.3.- CARACTERÍSTIQUES GEOMÈTRIQUES 0 1.3.1.- CARACTERÍSTIQUES DEL FORJAT 0 GRUIX DEL FORJAT 0 1.4.- JUSTIFICACIÓ D’ACCIONS A L’EDIFICACIÓ (CTE-DB-SE-AE) 0 1.4.1.- CÀRREGUES SUPERFICIALMENT REPARTIDES 0 1.4.1.1.- PLANTA AMB NERVAT SEMIBIGUETA 25+5 0 1.4.1.2.- PLANTA AMB FORJAT COL·LABORANT 0 1.4.2.- CÀRREGUES LINEALMENT REPARTIDES 0 1.4.3.- PES DEL FORJAT 0 1.5.- SOL·LICITACIONS HORITZONTALS: EÒLIQUES i SÍSMIQUES (CTE-DB-SE-AE i NCSE-02) 0 1.5.1.- ACCIÓ EÒLICA (CTE-DB-SE-AE) 0 1.5.2.- JUSTIFICACIÓ DE LA NORMA NCSE-02 0 1.6.- SOL·LICITACIONS ESPECIALS, TÈRMIQUES O REOLÒGIQUES 0 1.7.- CARACTERÍSTIQUES DELS MATERIALS ESTRUCTURALS 0 2.- ELEMENTS ESTRUCTURALS 0 2.1.- DEFINICIÓ DEL PROCÉS DE CÀLCUL (SEGONS CTE-DB-SE; EHE; EFHE; CTEDB-SE-F i CTE-DB-SE-A) 0 2.1.1.- FORMIGÓ ARMAT 0 2.1.2.- MURS DE FÀBRICA DE MAÓ 0 2.1.3.- ESTRUCTURA METÀL.LICA 0 2.1.4.- TIPUS DE CONTROL, COEFICIENTS DE SEGURETAT ADOPTATS(γ) I COEFICIENTS DE COMBINACIÓ(ψ) 0 2.1.5.- PROGRAMES DE CÀLCUL EMPRATS PER LA RESOLUCIÓ D’ESTRUCTURES PER EDIFICACIÓ. 3.- MECÀNICA DEL SÒL MEMÒRIA DE CÀLCUL 0 0 pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 3.1.- DEFINICIÓ I JUSTIFICACIÓ DE LA TIPOLOGIA DE FONAMENTACIÓ 0 3.2.- ESTUDI GEOTÈCNIC 0 3.2.1.- TENSIÓ DE TREBALL DEL TERRENY 0 3.2.2.- NIVELL FREÀTIC 0 3.2.3.- AGRESSIVITATS DEL TERRENY O AIGUA RESPECTE AL FORMIGÓ 0 3.3.- CERTES SITUACIONS ATÍPIQUES 0 4.- REFERÈNCIA A LES NORMATIVES EMPRADES 0 5.- CONSIDERACIONS DEL PROCES CONSTRUCTIU 0 MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 1.- CARACTERÍSTIQUES DE L'ESTRUCTURA I SOLICITACIONS 1.1.- SITUACIÓ. EXPEDIENT. DATA. PROMOTOR Emplaçament edifici: BELL·LLOCH Expedient estructura: EF/1140/0108 Data: MARÇ 2008 Promotors: Tipus d’edifici: CENTRE CIVIC Superfícies de càlcul: SUPERFÍCIE FONAMENTS 341,83 m² SOSTRE PL. BAIXA 572,17 m² COBERTA 528,90 m² TOTAL SUP. HABITATGE MEMÒRIA DE CÀLCUL SUPERFÍCIE 1442,90 m2 pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 1.2.- DEFINICIÓ i JUSTIFICACIÓ DE LA TIPOLOGIA ESTRUCTURAL S’ha escollit la tipologia de sostre unidireccional amb semibigueta que recolzen en murs o jàsseres que recolzen sobre pilars de formigó armat i també s’ha escollit la tipologia de forjat col·laborant recolzat sobre estructura metàl·lica de jàsseres i pilars metàl·lics i amb una capa de formigó armat de 12cm. 1.3.- CARACTERÍSTIQUES GEOMÈTRIQUES 1.3.1.- CARACTERÍSTIQUES DEL FORJAT FORJAT DE NERVAT DE SEMIBIGUETA 25+5 tipus......................................... unidireccional semibigueta suport.......................................pilars de formigó armat intereix......................................70 cm revoltó.......................................prefabricat formigó 70*23*(25)cm gruix del forjat...........................25+5= 30 cm capa superior .......................... 5 cm mallat electrosoldat...................ME 15*30 cm, BØ 5mm. B 500 S encadenat perimetral................segons plànol de jàsseres fletxa permesa.......................... L/500 // 1,00 cm FORJAT COL·LABORANT tipus.........................................forjat col·laborant amb xapa HAIRCOL59 e=0,75mm gruix total del forjat 12cm suport.......................................pilars de metàl·lics intereix......................................revoltó.......................................gruix del forjat...........................12cm + gruix de jàssera metàl·lica capa superior .......................... 12 cm mallat electrosoldat...................ME15*20cm, Ø10mm longitudinal a xapa i Ø6mm transversal a xapa B500S encadenat perimetral................fletxa permesa.......................... L/500 // 1,00 cm MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 FORJAT DE NERVAT DE BIGUETA 25+5 tipus......................................... unidireccional semibigueta suport.......................................pilars de formigó armat intereix......................................70 cm revoltó.......................................prefabricat formigó 70*23*(25)cm gruix del forjat...........................25+5= 30 cm capa superior .......................... 5 cm mallat electrosoldat...................ME 15*30 cm, BØ 5mm. B 500 S encadenat perimetral................segons plànol de jàsseres fletxa permesa.......................... L/500 // 1,00 cm MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 GRUIX DEL FORJAT L’elecció del gruix de la llosa alleugerida ve en funció de les llums entre eixos pilars. Hi ha la banda de llums de 6,00m aproximadament. També respon a la necessitat de limitar notablement la fletxa diferida, mantenint-la en uns valors sensiblement inferiors als habituals en l’edificació. La regla pràctica de no excedir el 1/24 de la llum més desfavorable s’acompleix al adoptar un cantell de 25+5=30. 1.4.- JUSTIFICACIÓ D’ACCIONS A L’EDIFICACIÓ (CTE-DB-SE-AE) 1.4.1.- CÀRREGUES SUPERFICIALMENT REPARTIDES 1.4.1.1.- PLANTA AMB NERVAT SEMIBIGUETA 25+5 ESTAT DE CÀRREGUES pes propi........................ 311 Kg/m2 càrregues permanents..... 110 Kg/m2 sobrecàrrega d’envans... 100 Kg/m2 sobrecàrrega de servei... 300 Kg/m2 sobrecàrrega de vent..... 0 Kg/m2 sobrecàrrega de neu...... 0 Kg/m2 -------------821 Kg/m2 1.4.1.2.- PLANTA AMB NERVAT BIGUETA 25+5 ESTAT DE CÀRREGUES pes propi........................ 311 Kg/m2 càrregues permanents..... 110 Kg/m2 sobrecàrrega d’envans... 000 Kg/m2 sobrecàrrega de servei... 200 Kg/m2 sobrecàrrega de vent..... 0 Kg/m2 sobrecàrrega de neu...... 0 Kg/m2 -------------621 Kg/m2 MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 1.4.1.3.- PLANTA AMB FORJAT COL·LABORANT ESTAT DE CÀRREGUES pes propi........................ 200 kg/m2 càrregues permanents..... 110 Kg/m2 sobrecàrrega d’envans... 100 Kg/m2 sobrecàrrega de servei... 500 Kg/m2 sobrecàrrega de vent..... 000 Kg/m2 sobrecàrrega de neu...... 000 Kg/m2 ------------910 Kg/m2 1.4.2.- CÀRREGUES LINEALMENT REPARTIDES Hi ha tres tipus de càrregues bàsiques d’aquesta modalitat: 1) Els tancaments: paret de maó perforat “totxana”, arrebossat amb cambra d’aire i envà. En planta pis tindrà 2,50 metres: 0,75 T/m.. 2) Les separacions entre veïns amb paret també de maó perforat “calat” “gero” de 15cm revestida. En planta pis tindrà 2,50 metres: 0,56 T/m. 3) Les baranes tindran la consideració o possibilitat que siguin massisses, amb un possible pes propi i una sobrecàrrega, amb una càrrega total màxima de 0,41 T/m. 1.4.3.- PES DEL FORJAT Anant a favor de la seguretat, s’ha pres el valor recomanat per l´Associació de Consultors d´Estructures sobre pesos propis dels forjats habituals a la construcció (Revista Quaderns d’estructures, número 4, novembre de 1999). L´esmentat pes és un cop rectificat per intereix de 70cm es de 311 kg/m2 per al forjat de (25+5)cm i de 200kg/m2 per al forjat col·laborant. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 1.5.- SOL·LICITACIONS HORITZONTALS: EÒLIQUES i SÍSMIQUES (CTE-DB-SE-AE i NCSE-02) 1.5.1.- ACCIÓ EÒLICA (CTE-DB-SE-AE) L'acció del vent es calcula a partir de la pressió estàtica qe que actua en la direcció perpendicular a la superfície exposada, amb l’expressió que s’exposa a continuació: qe = qb·ce·cp On: qb És la pressió dinàmica. ce És el coeficient d'exposició. cp És el coeficient eòlic o de pressió. Per la tipologia i característiques de l’edifici en qüestió s’agafaran els valors simplificats segons l’article 3.3 del CTE-DB-SE-AE (sempre que es puguin aplicar, en cas contrari es farà el càlcul complert). Aquests valors que es detallen a continuació, seran els que s’utilitzaran pel càlcul i/o s’introduiran en el programa de càlcul de l’estructura: - Altura de l'edifici: fins a 8 plantes - Dimensions de l’edifici: segons plànols d’arquitectura - Situació topogràfica: zona urbana en general - 'edifici: fins a 8 plantes - Pressió dinàmica: W= 52 Kg/m² (no simplificat zona C; Velocitat vent: 29 m/seg) - Coeficient d’exposició: 2 - Coeficient d’eòlic o de pressió: Esveltesa de l’edifici (h/b) >0,25 0,50 0,75 1,00 1,25 ≤5,00 Coeficient eòlic de pressió(Cp) 0,70 0,70 0,80 0,80 0,80 0,80 Coeficient eòlic de succió(Cp) -0,30 -0,40 -0,40 -0,50 0,60 0,70 MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 1.5.2.- JUSTIFICACIÓ DE LA NORMA NCSE-02 En compliment del RD 997/2002, de 27 de setembre, o s’aprova la norma de construcció sismoresistent part general i edificació (NCSE-02). On aplicant els següents paràmetres: • MUNICIPI: BELL·LLOCH • CLASSIFICACIÓ DE LA CONSTRUCCIÓ (segons el l’1.2.2 de la NCSE-02): NORMAL • (ab) acceleració sísmica bàsica segons Annex 1 de NCSE-02: < 0,04g Segons el Capítol 1 en el punt 1.2.3. de la Norma sismoresistent NCSE-02 la norma no es d’aplicació en les següent situacions: • Les construccions de importància moderada. • Les edificacions de importància normal o especial quan l’acceleració sísmica bàsica (ab) sigui inferior a 0,04g, essent g la acceleració de la gravetat. • En les construccions de importància normal amb pòrtics ben arriostrats entre ells en totes les direccions quan l’acceleració sísmica bàsica (ab) sigui inferior a 0,08 g. No obstant, la Norma serà de aplicació en els edificis de més de 7 plantes si la acceleració sísmica de càlcul (ac) es igual o major de 0,08g Pel que resolem que no es necessari l’aplicació de la norma en aquesta construcció. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 1.6.- SOL·LICITACIONS ESPECIALS, TÈRMIQUES O REOLÒGIQUES Per estar l’edificació subdividida en unitats de longitud menors de 40m, no s'introdueixen en l'estructura els efectes produïts per l'acció tèrmica, ni els reològics. 1.7.- CARACTERÍSTIQUES DELS MATERIALS ESTRUCTURALS ESTRUCTURA DE FORMIGÓ ARMAT -FORMIGÓ: Resistència característica als 28 dies: 25 N/mm2 Resistència característica als 7 dies: 17.5 N/mm2 Tipus de ciment RC-03: CEM I, 32.5 Tipus d’ambient (agressivitat): fonaments IIa, resta obra I Classe d'àrid: palet de riu Tamany màxim de l'àrid: 16 mm. Additius:No s'admeten sense l'autorització de la Direcció Facultativa. Dosificació per metre cúbic: Ciment: 275 Kg/m3. Aigua: 180 Kg/m3. Sorra: 635 Kg/m3. Grava: 1275 Kg/m3. Docilitat:Consistència tova (denominació B) Assentament en con d'Abrams: 7+1cm. Compactació: per vibrat normal. Control del formigó: Normal. Número de sèrie de provetes per assaig: 1 sèrie. Número de provetes per sèrie: 6 unitats. Freqüència d'assaigs: cada unitat de formigonat. Tipus de provetes: cilíndriques,de d=15cm. h=30cm Edat de ruptura:2 unitats a 7 dies 2 unitats a 28 dies MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 2 unitats a reserva Assaig sistemàtic de con d'Abrams. Tolerància ±1cm -ACER: Tipus: B 500 SD Límit elàstic: 500 N/mm2 Control de l'acer: Normal Coeficient de minoració: 1,15 Resistència de càlcul de les barres: 443,5 N/mm2 -MALLES ELECTROSOLDADES Designació B 500 SD Límit elàstic: 500 N/mm2 AENOR certifica amb conformitat a normes i en aquest cas segons la norma UNE 36092:1996 “Mallas electrosoldadas de acero para armaduras de hormigón armado”, que no considera les xarxes amb diàmetres inferiors a 5mm. Des de l’1 d’abril de 1997 els fabricants de xarxes electrosoldades en possessió de marca “N” d’AENOR empren diàmetres a partir de 5mm. Com a referència a les noves xarxes electrosoldades amb capes de compressió en sostres normals, en substitució de les antigues es poden considerar: Sostres unidireccionals: 200*200*5*5mm., 150*300*5*5mm Sostres bidireccionals: 200*200*5*5mm., 150*150*5*5mm MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 MURS DE FÀBRICA DE MAÓ MAONS Tipus de maons RL-88: perforat Classe de maons RL-88: NV Resistència a compressió: 15 N/mm2 MORTERS Tipus de ciment RC-03: CEM I, 32.5 Tipus de calç: ----Tipus de sorra (rodat/matxucat): natural Tamany màxim de la sorra: 2,5 mm Additius: ----------Tipus de morter: M-40 Resistència a compressió: 4.0 N/mm2 Plasticitat: gras Dosificació: 1:0:6 MURS Classe de mur: aparellat Tipus de paredat: a trencajunt Resistència de càlcul de la fàbrica: 2.2 N/mm2 ACCIONS Cas de càrrega: I Coeficients de ponderació: 1,60 MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 ESTRUCTURA METÀL·LICA Els acers emprats cumpleixen la Norma CTE-DB-SE-A. Característiques mecàniques dels acers: (S275-JR) RESISTÈNCIA A LA TRACCIÓ (KG/MM2) 42-50 LÍMIT DE FLUÈNCIA MÍNIM (KG/MM2) 26 ALLARGAMENT DE RUPTURA(%) 22 Com a valors habituals de càlcul les constants elàstiques de l'acer són: Módul d'elasticitat E= 2.100.000 Kp/cm2 Módul de rigidesa G = 810.000 Kp/cm2 Coeficient de Poisson V = 0,30 Coeficient de dilatació αt= 1,2 x 10-5 m/m Cº La modificació d'aquestes dades haurà de ser aprovada de forma expressa per la Direcció Facultativa. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 2.- ELEMENTS ESTRUCTURALS 2.1.- DEFINICIÓ DEL PROCÉS DE CÀLCUL (SEGONS CTE-DB-SE; EHE; EFHE; CTEDB-SE-F i CTE-DB-SE-A) 2.1.1.- FORMIGÓ ARMAT La determinació de les sol·licitacions s’ha realitzat segons els principis de la Mecànica rotacional, complementats per les teories clàssiques de la Resistència de Materials i de l’Elasticitat. D’acord amb la Norma CTE-DB-SE 1 i 2 amb també va la EHE (Art.49), el procés general de càlcul emprat és el dels estats límits (E.L.U. de trencament. Formigó), en què es tracta de reduir a un valor suficientment baix la probabilitat que s’assoleixin aquells estats límits que posen l’estructura fora de servei. Les comprovacions dels estats límits últims (equilibri, esgotament o trencament, inestabilitat o guerxament, adherència, ancoratge i fatiga) es realitzen per a cada hipòtesi de càrrega, amb accions majorades i propietats resistents dels materials minorades, mitjançant una sèrie de coeficients de seguretat. Les comprovacions dels estats límits d’utilització (fissuració i deformació) es realitzen per a cada hipòtesi de càrrega, amb accions de servei (sense majorar) i propietats resistents dels materials de servei (sense minorar). Per al càlcul dels forjats, s’ha adoptat el diagrama d’envolvents plàstiques de moments flectors, d’acord amb la Norma CTE-DB-SE 1 i 2 amb també EFHE. Les seccions de formigó es calculen considerant el període plàstic del diagrama tensió-deformació, amb distribució parabòlica-rectangular, seguint la teoria dels dominis de la deformació, dins el càlcul de ruptura. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 ARMAT DE SECCIONS Per al dimensionat de les seccions de formigó s’empra el mètode de la paràbola-rectangle. Es respecten les quanties mínimes exigides per CTE-DB-SE 1 i 2 amb també la Instrucció EHE (Art. 42.3.5). El procés general d’armat es basa en l’elecció, dins la taula corresponent, d’un màxim de tres paquets d’armat que cobreixen en cada punt la quantia necessària. ESFORÇ TALLANT S’acompleixen els límits del CTE-DB-SE 1 i 2 amb també la Instrucció EHE (Arts. 44 i 52.5). ANCORATGES DE LES ARMADURES S’empren les longituds d’ancoratge corresponents a l’Article 66.5 de la Instrucció EHE, tenint en compte les reduccions: As necessària/ As real i calculant-se per a cada paquet d’armadures el màxim d’envolvent de les longituds d’ancoratge necessàries per a cada moment que cobreix. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 2.1.2.- MURS DE FÀBRICA DE MAÓ D’acord amb la Norma CTE-DB-SE-F, el càlcul de les sol·licitacions s’ha realitzat pels mètodes generals de la Resistència de Materials. Per a cada element s’ha comprovat que la tensió ponderada general resultant i la tensió ponderada local en les àrees de recolzament no superen la resistència de càlcul especificada. A més, s’han realitzat les comprovacions relatives a l’estabilitat del conjunt, tenint en compte els esforços horitzontals, i en el càlcul de la fonamentació s’han considerat les excentricitats de les càrregues produïdes per aquest tipus d’esforços. 2.1.3.- ESTRUCTURA METÀL.LICA D’acord amb la Norma CTE-DB-SE 1 i 2 amb també el CTE-DB-SE-A, el procés general de càlcul emprat és el dels estats límits (E.L.U. de trencament. Acer laminat), en què es tracta de reduir a un valor suficientment baix la probabilitat que s’assoleixin aquells estats límits que posen l’estructura fora de servei. Les comprovacions dels estats límits últims (equilibri, esgotament o trencament, inestabilitat o guerxament, adherència, ancoratge i fatiga) es realitzen per a cada hipòtesi de càrrega, amb accions majorades i propietats resistents dels materials minorades, mitjançant una sèrie de coeficients de seguretat. Les comprovacions dels estats límits d’utilització (fissuració i deformació) es realitzen per a cada hipòtesi de càrrega, amb accions de servei (sense majorar) i propietats resistents dels materials de servei (sense minorar). MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL 2.1.4.- TIPUS DE PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ CONTROL, COEFICIENTS DE Ref.: EF/1140/0108 SEGURETAT ADOPTATS(γ) I COEFICIENTS DE COMBINACIÓ(ψ) Nivell de control de l’estructura: NORMAL. Per el càlcul de les fletxes dels elements sotmesos a flexió, s’han tingut en compte tant les deformacions instantànies com les diferides, i s’han considerat els moments d’inèrcia equivalents de les seccions fissurades. Els límits de deformació vertical (fletxes) de les bigues i dels forjats, establerts per la compatibilitat de deformacions dels diferents elements estructurals i constructius, son els que assenyala al CTE-DB-SE 1 i 2 la norma EFHE. Per a les diferents situacions de projecte, les combinacions d'accions es definiran d'acord amb els següents criteris: Amb coeficients de combinació ∑γ j ≥1 Gj Gkj + γ Q1Ψ p1Qk1 + ∑ γ Qi Ψ aiQki i >1 Sense coeficients de combinació ∑γ j ≥1 Gj Gkj + ∑ γ QiQki i≥1 On: Gk Qk γG Acció permanent Acció variable Coeficient parcial de seguretat de les accions permanents γQ,1 Coeficient parcial de seguretat de l'acció variable principal γQ,i Coeficient ψp,1 ψa,i parcial de seguretat de les accions variables (i > 1) Coeficient de combinació de l'acció variable principal Coeficient de combinació de les accions variables (i > 1) MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 Per a cada situació de projecte i estat límit, els coeficients a utilitzar seran: E.L.U. de trencament. Formigó: EHE-CTE Persistent o transitòria sense sisme Coeficients parcials de seguretat (γ) Càrrega permanent (G) Coeficients de combinació (ψ) Favorable Desfavorable Principal (ψp) Acompanyament (ψa) 1.00 1.50 1.00 1.00 Sobrecàrrega (Q) 0.00 1.60 1.00 0.70 Vent (Q) 0.00 1.60 1.00 0.60 Neu (Q) 0.00 1.60 1.00 0.50 Sisme (A) E.L.U. de trencament. Acer laminat: CTE DB-SE A Persistent o transitòria sense sisme Coeficients parcials de seguretat (γ) Coeficients de combinació (ψ) Favorable Desfavorable Principal (ψp) Acompanyament (ψa) Càrrega permanent (G) 0.80 1.35 1.00 1.00 Sobrecàrrega (Q) 0.00 1.50 1.00 0.70 Vent (Q) 0.00 1.50 1.00 0.60 Neu (Q) 0.00 1.50 1.00 0.50 Sisme (A) Desplaçaments Accions variables sense sisme Coeficients parcials de seguretat (γ) Favorable Desfavorable Càrrega permanent (G) 1.00 1.00 Sobrecàrrega (Q) 0.00 1.00 Vent (Q) 0.00 1.00 Neu (Q) 0.00 1.00 Sisme (A) MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 2.1.5.- PROGRAMES DE CÀLCUL EMPRATS PER LA RESOLUCIÓ D’ESTRUCTURES PER EDIFICACIÓ. El despatx d’enginyeria KUBIC CONSULTORIA TECNICA, SL associada a l’Associació de Consultors d’Estructures amb el num. 75, i amb adreça c/Costa de Magdalena, 2, 4rt D, 25007 - LLEIDA; propietari de la llicència del programa CYPECAD i METAL3D vers. 2007.1.d, ha utilitzat aquest per tal de realitzar els calculs dels elements estructurals (pilars, jasseres, forjats i lloses armades) de l’obra objecte d’aquesta memoria. 3.- MECÀNICA DEL SÒL 3.1.- DEFINICIÓ I JUSTIFICACIÓ DE LA TIPOLOGIA DE FONAMENTACIÓ S’ha projectat una fonamentació amb sabates aïllades o corregudes i riostres de formigó, sota els pilars o pantalles o murs de contenció, dimensionats d’acord a les característiques del terreny i a les càrregues en base dels diferents suports que ens trobem en l’obra, segons les consideracions de càlcul (combinacions de càlcul i factors de seguretat) del CTE-DB-SE-C. En el plànol de fonaments es defineixen totes les dimensions dels elements de fonamentació, així com els diferents detalls de muntatge del elements de fonamentació. La resistència característica del formigó serà HA-25 3.2.- ESTUDI GEOTÈCNIC L’estudi geotècnic ha estat realitzat per l’empresa ICEC, S.L. amb el numero d’expedient 08.02/CUA-04/03.01 amb data de febrer de 2008. 3.2.1.- TENSIÓ DE TREBALL DEL TERRENY A partir dels valors obtinguts en assaigs pressiomètrics, i en aplicar la formulació de Mènard pel càlcul de la capacitat mecànica, amb un factor de seguretat F=3, es considera un tensió de treball admissible del terreny de 0,30N/mm² per a les sabates aïllades i de 0,30N/mm2 per a la sabata correguda. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 3.2.2.- NIVELL FREÀTIC NUL. 3.2.3.- AGRESSIVITATS DEL TERRENY O AIGUA RESPECTE AL FORMIGÓ AGRESSIVITAT TERRENY – FORMIGÓ: NUL. AGRESSIVITAT AIGUA – FORMIGÓ: NUL·LA. 3.3.- CERTES SITUACIONS ATÍPIQUES Res fa pensar la presencia de situacions atípiques segons s’observa en el estudi geotècnic. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 4.- REFERÈNCIA A LES NORMATIVES EMPRADES ACCIONS Per al càlcul de les sol·licitacions, s’han considerat, com accions característiques, les establertes en les normes CTE-DB-SE-AE i NCSE-2002. TERRENY Per a l’estimació de les pressions admissibles sobre el terreny i les empentes produïdes per aquest sobre la fonamentació, s’ha seguit l’especificat en els capítols CTE-DB-SE-AE i CTE-DBSE-C. CIMENT Els ciments que s’empraran en l’execució dels elements estructurals acompliran l’especificat en la “Instrucción para la Recepción de Cementos RC-03”. FORMIGÓ ARMAT El disseny i càlcul de la fonamentació i/o l’estructura s’ajusten en tot moment a l’establert a les normes CT-DB-SE-1 i 2 amb la EHE i EFHE, i la seva construcció es realitzarà d’acord amb l’especificat en ambdues normes. MURS DE FÀBRICA DE MAÓ El disseny i el càlcul dels murs resistents d’aquesta estructura s’ajusten en tot moment a l’especificat en la norma CT-DB-SE-1 i 2; i CTE-DB-SE-F. Els maons emprats en els murs acompleixen l’especificat en el “Pliego General para la Recepción de Ladrillos Cerámicos RL-88”. MEMÒRIA DE CÀLCUL pàg. 0 Kubic CONSULTORIA TÈCNICA, SL PROJECTE DE CÀLCUL D’ESTRUCTURA DE FORMIGÓ Ref.: EF/1140/0108 ESTRUCTURA METÀL·LICA El disseny i càlcul dels diferents elements que formen el conjunt de l’estructura de principal del forjat col·laborant s’ajusten en tot moment a l’establert a la CT-DB-SE-1 i 2; i CTE-DB-SE-A i la seva construcció es realitzarà d’acord amb l’especificat en aquesta. 5.- CONSIDERACIONS DEL PROCES CONSTRUCTIU S’insistirà que els processos constructius s’adequaran a les normes vigents i particularment pel que fa a: - Ancoratges. - Recolzaments. - Ritme d’apuntalament i desencofrat. - Velocitat de formigonat. - Curat de formigons. - Control de carregaments dels tancaments en els forjats. - Càrregues degudes al mateix procés de construcció. - Fases construcció Lleida, setembre de 2009 Anna Costa Isern i David Portolés Martínez, arquitectes MEMÒRIA DE CÀLCUL pàg. 0 ANNEX. PROJECTE DE CLIMATITZACIÓ PROJECTE DE CLIMATITZACIÓ 1.- EXPEDIENT I AUTOR DE L'ENCÀRREC 1.1.- EXPEDIENT Referència: Descripció: Data: Adreça: Localitat: Projectat per: CENTRE CIVIC BELL-LLOC 05/03/08 1.2.- AUTOR DE L'ENCÀRREC Propietari: CIF: Adreça: Localitat: Codi postal: Pàgina 1 de 72 2.- MEMÒRIA DESCRIPTIVA 2.1.- DESCRIPCIÓ ARQUITECTÒNICA DE L'EDIFICI L'edifici objecte d'aquest projecte s'ha dividit en les zones tèrmiques que apareixen resumides en la taula següent: Sistema/Zona PLANTA BAIXA GIMNÀS BANY2 DESPATX GESTIÓ SALA D'ESTAR BAR-MENJADOR VESTÍBUL SALA ESPERA1 SERVEI SOCIAL PODÒLEG BANY HOMES BANY DONES SALA D'ESPERA2 CONSULTA METGE1 CURES INFERMERIA CONSULTA METGE2 Sistema/Zona PLANTA PRIMERA NOVES TECNOLOGIES LOCAL4 LOCAL3 LOCAL2 LOCAL1 RECEPCIÓ DESPATX SALA D’ACTES VESTÍBUL BANY DONES BANY HOMES SALA D’ACTES Superfície (m²) 46,0 20,5 15,4 49,7 114,4 44,6 29,1 15,8 18,9 14,5 16,4 42,5 22,5 15,0 16,6 20,0 Altura (m) 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 Volum (m³) 119,6 53,3 40,0 129,2 297,4 116,0 75,7 41,1 49,1 37,7 42,6 110,5 58,5 39,0 43,2 52,0 Superfície (m²) 38,8 26,2 26,1 24,9 25,7 25,8 8,6 44,5 25,3 21,1 171,1 Altura (m) 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 2,6 3,0 Volum (m³) 100,9 68,1 67,9 64,7 66,8 67,1 22,4 115,7 65,8 54,9 513,3 Ús Gimnasios Aseos públicos (por urinario, inodoro, vertedero,...) Oficinas Descanso (salas de) Comedores Vestíbulos Espera y recepción (salas) Oficinas Salas de recuperación Aseos públicos (por urinario, inodoro, vertedero,...) Aseos públicos (por urinario, inodoro, vertedero,...) Espera y recepción (salas) Salas de curas Salas de curas Salas de curas Salas de curas Ús Aulas (sin fumadores) Aulas (sin fumadores) Aulas (sin fumadores) Aulas (sin fumadores) Aulas (sin fumadores) Espera y recepción (salas) Oficinas Vestíbulos Aseos públicos (por urinario, inodoro, vertedero,...) Aseos públicos (por urinario, inodoro, vertedero,...) Aulas (sin fumadores) 2.2.- HORARIS DE FUNCIONAMENT, OCUPACIÓ I NIVELLS DE VENTILACIÓ L'ocupació s'ha estimat en funció de la superfície de cada zona, considerant els metres quadrats per persona típics per al tipus d'activitat que en ella es desenvolupa. Els nivells d'ocupació de cada zona són els descrits en la taula següent: Sistema/Zona Activitat Ocupación TIPICA Núm . pers. 7 m² per pers. 6,6 BANY2 Ocupación TIPICA 4 5,1 Cs (w) 13 9 89 DESPATX GESTIÓ Ocupación TIPICA 2 7,7 78 Cl (w) 38 3 12 1 46 PLANTA BAIXA GIMNÀS SALA D'ESTAR Ocupación TIPICA 16 3,1 71 31 BAR-MENJADOR Ocupación TIPICA 50 2,3 71 91 VESTÍBUL Ocupación TIPICA 6 7,4 89 SALA ESPERA1 Ocupación TIPICA 8 3,6 71 12 1 31 Horari de Funcionament Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Pàgina 2 de 72 SERVEI SOCIAL Ocupación TIPICA 3 5,3 78 46 PODÒLEG Ocupación TIPICA 3 6,3 BANY HOMES Ocupación TIPICA 3 4,8 10 9 89 BANY DONES Ocupación TIPICA 3 5,5 89 SALA D'ESPERA2 Ocupación TIPICA 14 3,0 71 24 8 12 1 12 1 31 CONSULTA METGE1 Ocupación TIPICA 4 5,6 72 CURES Ocupación TIPICA 3 5,0 72 INFERMERIA Ocupación TIPICA 3 5,5 72 CONSULTA METGE2 Ocupación TIPICA 4 5,0 72 14 8 14 8 14 8 14 8 Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Cs: Calor sensible en w aportat per persona a una temperatura ambient de 25°C. Cl: Calor latent en w aportat per persona a una temperatura ambient de 25°C. Sistema/Zona Activitat Ocupación TIPICA Núm . pers. 15 m² per pers. 2,6 Cs (w) 78 Cl (w) 46 PLANTA PRIMERA NOVES TECNOLOGIES LOCAL4 Ocupación TIPICA 20 1,3 78 46 LOCAL3 Ocupación TIPICA 20 1,3 78 46 LOCAL2 Ocupación TIPICA 20 1,2 78 46 LOCAL1 Ocupación TIPICA 20 1,3 78 46 RECEPCIÓ Ocupación TIPICA 12 2,2 71 31 DESPATX SALA D’ACTES Ocupación TIPICA 2 4,3 78 46 VESTÍBUL Ocupación TIPICA 8 5,6 89 BANY DONES Ocupación TIPICA 4 6,3 89 BANY HOMES Ocupación TIPICA 4 5,3 89 SALA D’ACTES Ocupación TIPICA 80 2,1 78 12 1 12 1 12 1 46 Horari de Funcionament Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Cs: Calor sensible en w aportat per persona a una temperatura ambient de 25°C. Cl: Calor latent en w aportat per persona a una temperatura ambient de 25°C. El cabal d'aire de ventilació s'obté en funció de l'ús del local, de la seva superfície i del número d'ocupants, aplicant la Taula 2 de la norma UNE 100011. Els nivells de ventilació assignats a cada zona són els que apareixen en el següent taula: Sistema/Zona PLANTA BAIXA GIMNÀS Per persona (l/s) 12,0 Cabal d'aire exterior Per Per m² local/altres (l/s) (l/s) 4,0 - Valor escollit (m³/h) 358,8 Renov. (1/h) Horari de Funcionament 3,0 Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h BANY2 25,0 - - 360,0 6,8 DESPATX GESTIÓ 10,0 1,0 - 72,0 1,8 SALA D'ESTAR 20,0 15,0 - 1.292,2 10,0 BAR-MENJADOR 10,0 6,0 - 2.974,4 10,0 Pàgina 3 de 72 VESTÍBUL 10,0 15,0 - 1.739,4 15,0 SALA ESPERA1 8,0 4,0 - 418,0 5,5 SERVEI SOCIAL 10,0 1,0 - 82,2 2,0 PODÒLEG 10,0 1,5 - 108,0 2,2 BANY HOMES 25,0 - - 270,0 7,2 BANY DONES 25,0 - - 180,0 4,2 SALA D'ESPERA2 8,0 4,0 - 612,0 5,5 CONSULTA METGE1 12,0 2,0 - 180,0 3,1 CURES 12,0 2,0 - 130,0 3,3 INFERMERIA 12,0 2,0 - 130,0 3,0 CONSULTA METGE2 12,0 2,0 - 180,0 3,5 Valor escollit (m³/h) 432,0 Renov. (1/h) Horari de Funcionament 4,3 Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Sistema/Zona PLANTA PRIMERA NOVES TECNOLOGIES Per persona (l/s) 8,0 Cabal d'aire exterior Per Per m² local/altres (l/s) (l/s) - LOCAL4 8,0 - - 576,0 8,5 LOCAL3 8,0 - - 576,0 8,5 LOCAL2 8,0 - - 576,0 8,9 LOCAL1 8,0 - - 576,0 8,6 RECEPCIÓ 8,0 4,0 - 371,5 5,5 DESPATX SALA D’ACTES 10,0 1,0 - 72,0 3,2 VESTÍBUL 10,0 15,0 - 925,6 8,0 BANY DONES 25,0 - - 360,0 5,5 BANY HOMES 25,0 - - 360,0 6,6 SALA D’ACTES 8,0 - - 2.566,5 5,0 Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Els nivells d'il·luminació i de potència dels equips elèctrics que es faran servir en cada zona estan enumerats a la llista següent: Sistema/Zona Tipus d'il·luminació w Núm . w/m² PLANTA BAIXA GIMNÀS Alumbrado TIPICO 15,0 46 15,0 BANY2 Alumbrado TIPICO 15,0 20 15,0 DESPATX GESTIÓ Alumbrado TIPICO 30,0 15 30,0 SALA D'ESTAR Alumbrado TIPICO 15,0 49 15,0 BAR-MENJADOR Alumbrado TIPICO 30,0 114 30,0 VESTÍBUL Alumbrado TIPICO 15,0 44 15,0 SALA ESPERA1 Alumbrado TIPICO 15,0 29 15,0 Horari de Funcionament Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Pàgina 4 de 72 SERVEI SOCIAL Alumbrado TIPICO 30,0 15 30,0 PODÒLEG Alumbrado TIPICO 20,0 18 20,0 BANY HOMES Alumbrado TIPICO 15,0 14 15,0 BANY DONES Alumbrado TIPICO 15,0 16 15,0 SALA D'ESPERA2 Alumbrado TIPICO 15,0 42 15,0 CONSULTA METGE1 Alumbrado TIPICO 30,0 22 30,0 CURES Alumbrado TIPICO 40,0 15 40,0 INFERMERIA Alumbrado TIPICO 40,0 16 40,0 CONSULTA METGE2 Alumbrado TIPICO 30,0 20 30,0 Tipus d'il·luminació w Núm . w/m² PLANTA PRIMERA NOVES TECNOLOGIES Alumbrado TIPICO 25,0 38 25,0 LOCAL4 Alumbrado TIPICO 25,0 26 25,0 LOCAL3 Alumbrado TIPICO 25,0 26 25,0 LOCAL2 Alumbrado TIPICO 25,0 24 25,0 LOCAL1 Alumbrado TIPICO 25,0 25 25,0 RECEPCIÓ Alumbrado TIPICO 15,0 25 15,0 DESPATX SALA D’ACTES Alumbrado TIPICO 30,0 8 30,0 VESTÍBUL Alumbrado TIPICO 15,0 44 15,0 BANY DONES Alumbrado TIPICO 15,0 25 15,0 BANY HOMES Alumbrado TIPICO 15,0 21 15,0 SALA D’ACTES Alumbrado TIPICO 25,0 171 25,0 Sistema/Zona Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Horari de Funcionament Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Funcionamiento continuo 1-24h Evolució del percentatge de funcionament al llarg del dia per a cada un dels horaris utilitzats: Referència 1 2 3 4 5 6 7 8 9 10 11 Percentatge de càrrega per a cada hora solar 12 13 14 15 16 17 18 19 20 21 22 23 24 Funcionamiento continuo 1-24h 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 2.3.- DESCRIPCIÓ DELS TANCAMENTS En un annex d'aquesta memòria es relacionen els diferents tancaments que delimiten les zones de l'edifici. 2.4.- CONDICIONS EXTERIORS DE PROJECTE Es té en compte la norma UNE 100001 per a la selecció de les condicions exteriors de projecte, que queden definides de la següent manera: Temperatura seca estiu 32,2 °C Pàgina 5 de 72 Temperatura humida estiu Percentil condicions d'estiu Temperatura seca hivern Percentil condicions d'hivern 21,3 °C 5,0 % -1,8 °C 97,5 % Variació diürna de temperatures Graus acumulats en base 15 – 15°C Orientació del vent dominant Velocitat del vent dominant Altura sobre el nivell del mar Latitud 13,1 °C 1163 dies-grau NO 7,4 m/s 202 m 41° 40' Nord En un annex de càlcul apareix l'evolució de les temperatures seques i humides màximes corregides per a tots els mesos de l'any i hores del dia, segons les taules de correcció que recull la norma UNE 100014. 2.5.- CONDICIONS INTERIORS DE CÀLCUL Les condicions climatològiques interiors han estat establertes en funció de l'activitat metabòlica de les persones i del seu grau de vestimenta, sempre d'acord amb la ITE 02 Apartat 2.1. Per a les hores considerades punta han estat seleccionades les següents condicions interiors: Sistema/Zona PLANTA BAIXA GIMNÀS BANY2 DESPATX GESTIÓ SALA D'ESTAR BAR-MENJADOR VESTÍBUL SALA ESPERA1 SERVEI SOCIAL PODÒLEG BANY HOMES BANY DONES SALA D'ESPERA2 CONSULTA METGE1 CURES INFERMERIA CONSULTA METGE2 Sistema/Zona PLANTA PRIMERA NOVES TECNOLOGIES LOCAL4 LOCAL3 LOCAL2 LOCAL1 RECEPCIÓ DESPATX SALA D’ACTES VESTÍBUL BANY DONES BANY HOMES SALA D’ACTES Temperatura seca (°C) 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 Estiu Humitat relativa (%) 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 Temperatura humida (°C) 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 Hivern Temperatura seca (°C) 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 Temperatura seca (°C) 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 25,0 Estiu Humitat relativa (%) 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 56,9 Temperatura humida (°C) 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 19,0 Hivern Temperatura seca (°C) 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 Pàgina 6 de 72 2.6.- MÈTODE DE CÀLCUL DE CÀRREGUES TÈRMIQUES El mètode de càlcul utilitzat TFM (mètode de la funció de transferència) correspon al descrit per ASHRAE en la seva publicació HVAC Fundamentals de 1988. En un annex d'aquest projecte es realitza una breu descripció d'aquest mètode. A continuació es mostra un resum de resultats de càrregues tèrmiques per a cada sistema i cada una de les seves zones. Descripció PLANTA BAIXA GIMNÀS BANY2 DESPATX GESTIÓ SALA D'ESTAR BAR-MENJADOR VESTÍBUL SALA ESPERA1 SERVEI SOCIAL PODÒLEG BANY HOMES BANY DONES SALA D'ESPERA2 CONSULTA METGE1 CURES INFERMERIA CONSULTA METGE2 Descripció PLANTA PRIMERA NOVES TECNOLOGIES LOCAL4 LOCAL3 LOCAL2 LOCAL1 RECEPCIÓ DESPATX SALA D’ACTES VESTÍBUL BANY DONES BANY HOMES SALA D’ACTES Càrrega Refrigeració Simultània (kW) 71,6 6,9 2,3 1,4 7,6 21,0 7,7 2,7 1,3 2,1 2,6 1,6 5,7 2,5 1,7 2,0 2,4 Càrrega Refrigeració Màxima (kW) 7,2 2,3 1,5 7,7 21,2 7,9 2,7 1,4 2,1 2,7 1,6 5,9 2,5 1,8 2,0 2,4 Càrrega Refrigeració Simultània (kW) 71,2 5,6 5,8 5,8 5,8 5,8 3,7 0,8 6,0 3,4 2,2 26,2 Càrrega Refrigeració Màxima (kW) 5,6 5,8 5,8 5,8 5,8 3,7 0,8 6,3 3,5 2,2 26,3 Data per a Màxima Càrrega Individual Calefacció (kW) Volum Ventilació (m³/h) Agosto 15 horas Septiembre 14 horas Junio 16 horas Septiembre 14 horas Agosto 14 horas Julio 15 horas Julio 15 horas Agosto 14 horas Junio 16 horas Julio 15 horas Junio 14 horas Julio 15 horas Julio 16 horas Julio 15 horas Julio 15 horas Junio 14 horas Julio 15 horas 9.087 359 360 72 1.292 2.974 1.739 418 82 108 270 180 612 180 130 130 180 114,9 5,9 4,3 1,6 13,2 32,1 21,7 4,8 1,9 2,5 3,6 2,7 10,1 3,0 2,8 1,9 2,9 Data per a Màxima Càrrega Individual Calefacció (kW) Volum Ventilació (m³/h) Agosto 14 horas Agosto 14 horas Agosto 14 horas Agosto 14 horas Agosto 14 horas Agosto 14 horas Agosto 14 horas Julio 15 horas Junio 15 horas Junio 14 horas Junio 16 horas Agosto 15 horas 7.392 432 576 576 576 576 372 72 926 360 360 2.567 73,8 5,5 5,3 5,3 5,3 5,3 3,8 0,9 10,2 4,0 2,9 25,2 El detall del càlcul de càrregues tèrmiques es recull en un annex d'aquest projecte i conté les taules del càlcul de càrregues tèrmiques per als diferents sistemes, subsistemes i zones en què s'ha dividit l'edifici. 2.7.- DESCRIPCIÓ DELS SISTEMES DE CLIMATITZACIÓ SELECCIONATS El sistema de calefacció de l’edifici estarà format per una caldera de biomassa, un circuit de canonades d’aigua i unitats fan-coil a cada una de les sales a calefactar. A més a més, el sistema es deixa preparat per la instal·lació d’una refredadora d’aigua per una futura climatització de l’edifici. Pàgina 7 de 72 ANNEX 1. MÈTODE DE CÀLCUL DE CÀRREGUES TÈRMIQUES Es segueix el mètode desenvolupat per ASHRAE (American Society o Heating, Refrigerating and Air-conditioning Engineers, Inc.) que basa la conversió de guanys instantanis de calor a càrregues de refrigeració en les anomenades funcions de transferència. 1.1.- Guanys tèrmics instantanis El primer pas consisteix en el càlcul per a cada mes i cada hora del guany de calor instantani degut a cada un dels següents elements: 1.1.1.- Guany solar vidre Insolació a través d'envidraments a l'exterior. QGAN ,t = CS × A × SHGF × n Essent: SHGF = GSd + Ins × GSt que depèn del mes, de l'hora solar i de la latitud. On: QGAN,t = A = CS = n = SHGF = GSt = GSd = Ins = Guany instantani de calor sensible (watts) Àrea de la superfície envidrada (m²) Coeficient d'ombrejat Núm. d'unitats de finestres del mateix tipus Guany solar per al vidre tipus (DSA) Guany solar per radiació directa (watts/m²) Guany solar per radiació difusa (watts/m²) Percentatge d'ombra sobre la superfície envidrada 1.1.2.- Transmissió parets i sostres Tancaments opacs a l'exterior, tret dels que no reben els raigs solars. El guany instantani per a cada hora es calcula usant la següent funció de transferència (ASHRAE): (QGAN ,t −nΔ ) ⎡ ⎤ QGAN ,t = A × ⎢∑ bn × (t sa ,t − nΔ ) − ∑ d n × − t ai × ∑ c n ⎥ A n =1 n =0 ⎣ n =0 ⎦ On: QGAN,t = Guany de calor sensible en l'ambient a través de la superfície interior del sostre o paret (w) A = Àrea de la superfície interior (m²) Tsa,t-nΔ = Temperatura sol aire en l'instant t-nΔ Pàgina 8 de 72 Δ tai bn cn dn = = Increment de temps igual a 1 hora. Temperatura de l'espai interior suposada constant = Coeficients de la funció de transferència segons el tipus de tancament La temperatura sol-aire serveix per corregir l'efecte dels raigs solars sobre la superfície exterior del tancament: t sa = t ec + α × It ΔR −ε × × cos(90° − β ) ho ho On: Tsa Tec It ho α β = = = = = = Temperatura sol-aire per a un mes i una hora donades (°C) Temperatura seca exterior corregida segons mes i hora (°C) Radiació solar incident en la superfície (w/m²) Coeficient de termotransferència de la superfície (w/m² °C) Absorbència de la superfície a la radiació solar (depèn del color) Angle d'inclinació del tancament pel que fa a la vertical (horitzontals = = Emitància hemisfèrica de la superfície. Diferència de radiació superfície/cos negre (w/m²) 90°). ε ΔR 1.1.3.- Transmissió excepte parets i sostres 1.1.3.1.- Tancaments a l'interior Guanys instantanis per transmissió en tancaments opacs interiors i que no estan exposats als raigs solars. QGAN ,t = K × A × (t l − t ai ) On: QGAN,t K A tl tai = = = = = Guany de calor sensible en l'instant t (w) Coeficient de transmissió del tancament (w/m²·°C) Àrea de la superfície interior (m²) Temperatura del local contigu (°C) Temperatura de l'espai interior suposada constant (°C) 1.1.3.2.- Envidraments a l'exterior Guanys instantanis per transmissió en superfícies envidrades a l'exterior. QGAN ,t = K × A × (t ec − t ai ) Pàgina 9 de 72 On: QGAN,t K A tec tai = = = = = Guany de calor sensible en l'instant t (w) Coeficient de transmissió del tancament (w/m²·°C) Àrea de la superfície interior (m²) Temperatura exterior corregida (°C) Temperatura de l'espai interior suposada constant (°C) 1.1.3.3.- Portes a l'exterior Un cas especial són les portes a l'exterior, en les que cal distingir segons la seva orientació: QGAN ,t = K × A × (t l − t ai ) On: QGAN,t K A tai tl = = = = = Guany de calor sensible en l'instant t (w) Coeficient de transmissió del tancament (w/m²·°C) Àrea de la superfície interior (m²) Temperatura de l'espai interior suposada constant (°C) Per a orientació Nord: Temperatura exterior corregida (°C) Excepte orientació Nord:Temperatura sol-aire per a l'instant t (°C) 1.1.4.-Calor intern 1.1.4.1.- Ocupació (persones) Calor generat per les persones que es troben dins de cada local. Aquesta calor és funció principalment del número de persones i del tipus d'activitat que estan desenvolupant. QGAN ,t = Qs × n × 0'01 × Fd t On: QGAN,t Qs n Fdt = = = = Guany de calor sensible en l'instant t (w) Guany sensible per persona (w). Depèn del tipus d'activitat Número d'ocupants Percentatge d'ocupació per a l'instant t (%) Es considera que 67% de la calor sensible es dissipa per radiació i la resta per convecció. QGANl ,t = Ql × n × 0'01 × Fd t On: QGANl,t = Ql = Guany de calor latent en l'instant t (w) Guany latent per persona (w). Depèn del tipus d'activitat Pàgina 10 de 72 n Fdt = = Número d'ocupants Percentatge d'ocupació per a l'instant t (%) 1.1.4.2.- Enllumenat Calor generat pels aparells de llum que es troben dins de cada local. Aquesta calor és funció principalment del número i tipus d'aparells. QGAN ,t = Qs × n × 0'01 × Fd t On: QGAN,t Qs n Fdt = = = = Guany de calor sensible en l'instant t (w) Potència per lluminària (w). Per a fluorescent es multiplica per 1'25. Número de lluminàries. Percentatge de funcionament per a l'instant t (%) 1.1.4.3.- Aparells elèctrics Calor generada pels aparells exclusivament elèctrics que es troben dins de cada local. Aquesta calor és funció principalment del número i tipus d'aparells. QGAN ,t = Qs × n × 0'01 × Fd t On: QGAN,t Qs n Fdt = = = = Guany de calor sensible en l'instant t (w) Guany sensible per aparell (w). Depèn del tipus. Número d'aparells. Percentatge de funcionament per a l'instant t (%) Es considera que el 60% de la calor sensible es dissipa per radiació i la resta per convecció. 1.1.4.4.- Aparells tèrmics Calor generada pels aparells tèrmics que es troben dins de cada local. Aquesta calor és funció principalment del número i tipus d'aparells. QGAN ,t = Qs × n × 0'01 × Fd t On: QGAN,t Qs n Fdt = = = = Guany de calor sensible en l'instant t (w) Guany sensible per aparell (w). Depèn del tipus. Número d'aparells. Percentatge de funcionament per a l'instant t (%) Es considera que el 60% de la calor sensible es dissipa per radiació i la resta per convecció. Pàgina 11 de 72 QGANl ,t = Ql × n × 0'01 × Fd t On: QGANl,t = Ql = n = = Fdt Guany de calor latent en l'instant t (w) Guany latent per aparell (w). Depèn del tipus Número d'aparells Percentatge de funcionament per a l'instant t (%) 1.1.5.- Aire exterior Guanys instantanis de calor a causa de l'aire exterior de ventilació. Aquests guanys passen directament a ser càrregues de refrigeració. QGAN ,t = 0'34 × f a × Vae s × 0'01 × Fd t × (t ec − t ai ) On: QGAN,t fa Vae tec tai Fdt = = = = = = Guany de calor sensible en l'instant t (w) Coeficient corrector per altitud geogràfica. Cabal d'aire exterior (m³/h). Temperatura seca exterior corregida (°C). Temperatura de l'espai interior suposada constant (°C) Percentatge de funcionament per a l'instant t (%) Es considera que el 100% de la calor sensible apareix per convecció. QGANl ,t = 0'83 × f a × Vae s × 0'01 × Fd t × ( X ec − X ai ) On: QGANl,t = fa = Vae = = Xec Xai = = Fdt Guany de calor sensible en l'instant t (w) Coeficient corrector per altitud geogràfica. Cabal d'aire exterior (m³/h). Humitat específica exterior corregida (gr aigua/kg aire). Humitat específica de l'espai interior (gr aigua/kg aire) Percentatge de funcionament per a l'instant t (%) 1.2.- Càrregues de refrigeració La càrrega de refrigeració depèn de la magnitud i naturalesa del guany tèrmic instantani així com del tipus de construcció del local, del seu contingut, tipus d'il·luminació i del seu nivell de circulació d'aire. Els guanys instantanis de calor latent així com les parts corresponents de calor sensible que apareixen per convecció passen directament a ser càrregues de refrigeració. Els guanys deguts a la radiació i transmissió es transformen en càrregues de refrigeració per mitjà de la funció de transferència següent: Pàgina 12 de 72 QREF ,t = v0 × QGAN ,t + v1 × QGAN ,t − Δ + v 2 × QGAN ,t −Δ 2 − w1 × QREF ,t − Δ QREF,t QGAN,t Δ vo, v1 i v2 w1 = Càrrega de refrigeració per a l'instant t (w) = Guany de calor en l'instant t (w) = Increment de temps igual a 1 hora. = Coeficients en funció de la naturalesa del guany tèrmic instantani. = Coeficient en funció del nivell de circulació de l'aire en el local. Pàgina 13 de 72 ANNEX 2. DETALL DEL CÀLCUL TÈRMIC 2.1.- EVOLUCIÓ ANUAL DE TEMPERATURA EXTERIOR SECA MÀXIMA (°C) Hora 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Gen. 3,5 2,9 2,3 1,7 1,2 0,6 2,9 5,2 6,6 8,1 9,5 10,9 12,0 13,1 13,7 13,1 12,5 12,0 10,7 9,4 8,1 6,8 5,4 4,1 Feb. 12,1 11,6 11,0 10,4 9,8 9,3 11,5 13,8 15,3 16,8 18,2 19,6 20,7 21,8 22,4 21,8 21,2 20,7 19,4 18,1 16,8 15,5 14,1 12,7 Mar. 15,0 14,4 13,8 13,3 12,7 12,1 14,4 16,7 18,1 19,6 21,0 22,4 23,5 24,6 25,2 24,6 24,1 23,5 22,2 20,9 19,6 18,3 16,9 15,6 Abr. 17,2 16,6 16,1 15,5 14,9 14,3 16,6 18,9 20,4 21,8 23,2 24,6 25,7 26,8 27,4 26,8 26,3 25,7 24,4 23,2 21,8 20,5 19,2 17,8 Maig. 19,8 19,3 18,7 18,1 17,5 17,0 19,2 21,5 23,0 24,5 25,9 27,3 28,4 29,5 30,1 29,5 28,9 28,4 27,1 25,8 24,5 23,2 21,8 20,4 Jun. 21,4 20,8 20,2 19,7 19,1 18,5 20,8 23,1 24,5 26,0 27,4 28,8 29,9 31,0 31,6 31,0 30,5 29,9 28,6 27,3 26,0 24,7 23,3 22,0 Jul. 22,0 21,4 20,8 20,3 19,7 19,1 21,4 23,7 25,1 26,6 28,0 29,4 30,5 31,6 32,2 31,6 31,1 30,5 29,2 27,9 26,6 25,3 23,9 22,6 Ago. 22,0 21,4 20,8 20,3 19,7 19,1 21,4 23,7 25,1 26,6 28,0 29,4 30,5 31,6 32,2 31,6 31,1 30,5 29,2 27,9 26,6 25,3 23,9 22,6 Set. 20,7 20,2 19,6 19,0 18,4 17,9 20,1 22,4 23,9 25,4 26,8 28,2 29,3 30,4 31,0 30,4 29,8 29,3 28,0 26,7 25,4 24,1 22,7 21,3 Oct. 18,3 17,7 17,2 16,6 16,0 15,4 17,7 20,0 21,5 22,9 24,3 25,7 26,8 27,9 28,5 27,9 27,4 26,8 25,5 24,3 22,9 21,6 20,3 18,9 Nov. 14,5 13,9 13,3 12,8 12,2 11,6 13,9 16,2 17,6 19,1 20,5 21,9 23,0 24,1 24,7 24,1 23,6 23,0 21,7 20,4 19,1 17,8 16,4 15,1 Des. 9,7 9,2 8,6 8,0 7,4 6,9 9,1 11,4 12,9 14,4 15,8 17,2 18,3 19,4 20,0 19,4 18,8 18,3 17,0 15,7 14,4 13,1 11,7 10,3 2.2.- EVOLUCIÓ ANUAL DE TEMPERATURA EXTERIOR HUMIDA MÀXIMA (°C) Hora 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Gen. 10,0 10,0 10,0 10,0 10,0 10,0 10,2 10,4 10,7 10,9 11,5 12,0 12,3 12,6 12,6 12,6 12,3 12,0 11,8 11,5 11,2 10,9 10,5 10,0 Feb. 13,9 13,9 13,9 13,9 13,9 13,9 14,1 14,3 14,6 14,8 15,4 15,9 16,2 16,5 16,5 16,5 16,2 15,9 15,7 15,4 15,1 14,8 14,4 13,9 Mar. 15,3 15,3 15,3 15,3 15,3 15,3 15,5 15,7 15,9 16,2 16,7 17,3 17,6 17,9 17,9 17,9 17,6 17,3 17,0 16,8 16,5 16,2 15,7 15,3 Abr. 16,4 16,4 16,4 16,4 16,4 16,4 16,6 16,8 17,1 17,3 17,9 18,4 18,7 19,0 19,0 19,0 18,7 18,4 18,2 17,9 17,6 17,3 16,9 16,4 Maig. 17,6 17,6 17,6 17,6 17,6 17,6 17,8 18,0 18,3 18,5 19,1 19,6 19,9 20,2 20,2 20,2 19,9 19,6 19,4 19,1 18,8 18,5 18,0 17,6 Jun. 18,7 18,7 18,7 18,7 18,7 18,7 18,9 19,1 19,4 19,6 20,2 20,7 21,0 21,3 21,3 21,3 21,0 20,7 20,5 20,2 19,9 19,6 19,1 18,7 Jul. 18,7 18,7 18,7 18,7 18,7 18,7 18,9 19,1 19,4 19,6 20,2 20,7 21,0 21,3 21,3 21,3 21,0 20,7 20,5 20,2 19,9 19,6 19,1 18,7 Ago. 18,7 18,7 18,7 18,7 18,7 18,7 18,9 19,1 19,4 19,6 20,2 20,7 21,0 21,3 21,3 21,3 21,0 20,7 20,5 20,2 19,9 19,6 19,1 18,7 Set. 17,9 17,9 17,9 17,9 17,9 17,9 18,1 18,4 18,6 18,9 19,4 20,0 20,3 20,6 20,6 20,6 20,3 20,0 19,7 19,5 19,2 18,9 18,4 17,9 Oct. 16,6 16,6 16,6 16,6 16,6 16,6 16,8 17,0 17,3 17,5 18,1 18,6 18,9 19,2 19,2 19,2 18,9 18,6 18,4 18,1 17,8 17,5 17,1 16,6 Nov. 15,1 15,1 15,1 15,1 15,1 15,1 15,3 15,5 15,7 16,0 16,5 17,1 17,4 17,7 17,7 17,7 17,4 17,1 16,8 16,6 16,3 16,0 15,5 15,1 Des. 12,9 12,9 12,9 12,9 12,9 12,9 13,1 13,4 13,6 13,9 14,4 15,0 15,3 15,6 15,6 15,6 15,3 15,0 14,7 14,5 14,2 13,9 13,4 12,9 Pàgina 14 de 72 2.3.- FULL DE CÀRREGUES PER A REFRIGERACIÓ DEL SISTEMA PROJECTE: SISTEMA: CENTRE CIVIC BELL-LLOC PLANTA BAIXA CONDICIONS DE DISSENY: Estimat per a les 15 hora solar del mes de Agosto. T.seca 32,2 °C Exterior: T.hum. 21,3 °C H.rel. 37,8 % H.esp. 11,4 gr/kg GUANYS DE CALOR: Ts (°C) Th (°C) Àrea (m²) Vol. (m³) GIMNÀS 25,0 19,0 46,0 119,6 BANY2 25,0 19,0 20,5 53,3 DESPATX GESTIÓ 25,0 19,0 15,4 40,0 SALA D'ESTAR 25,0 19,0 49,7 129,2 BAR-MENJADOR 25,0 19,0 114,4 297,4 VESTÍBUL 25,0 19,0 44,6 116,0 SALA ESPERA1 25,0 19,0 29,1 75,7 SERVEI SOCIAL 25,0 19,0 15,8 41,1 PODÒLEG 25,0 19,0 18,9 49,1 BANY HOMES 25,0 19,0 14,5 37,7 BANY DONES 25,0 19,0 16,4 42,6 SALA D'ESPERA2 25,0 19,0 42,5 110,5 CONSULTA METGE1 25,0 19,0 22,5 58,5 CURES 25,0 19,0 15,0 39,0 INFERMERIA 25,0 19,0 16,6 43,2 CONSULTA METGE2 25,0 19,0 20,0 52,0 Gsc (W) Tpt (W) Tept (W) Cis (W) Aes (W) Cil (W) Ael (W) RSHF C.refr. (W) 1.264 103 119 1.746 860 2.815 29 0,534 6.935 114 32 51 697 863 508 29 0,638 2.294 427 20 52 649 173 97 6 0,922 1.423 1.709 49 156 1.976 3.097 521 103 0,882 7.610 736 228 599 7.331 7.128 4.778 237 0,651 21.037 616 236 556 1.263 4.168 762 138 0,778 7.740 267 72 37 1.055 1.002 260 33 0,846 2.725 147 29 40 743 197 145 7 0,869 1.308 147 15 158 740 259 781 9 0,576 2.109 861 49 100 509 647 381 21 0,799 2.568 0 0 187 539 431 381 14 0,656 1.552 1.111 679 209 1.713 1.467 456 49 0,891 5.683 208 46 143 1.011 431 622 14 0,694 2.476 0 101 0 857 312 466 10 0,673 1.746 208 40 21 924 312 466 10 0,719 1.981 238 112 81 932 431 622 14 0,687 2.430 2.507 22.685 21.777 14.061 723 0,714 71.615 CÀRREGA DE REFRIGERACIÓ TOTAL 501,9 1.304,9 8.053 1.811 Factor de seguretat: 5% Cabal total d'aire exterior: 9.087 m³/h Càrrega de refrigeració per unitat de superfície: 143 w/m² Ts: T emperatura seca interior (°C). Th: Temperatura humida interior (°C). Vol.: Volum de la zona. Gsc: Guany solar vidre. Tpt: Transmissió parets i sostre. Tept: Transmissió excepte parets i sostre. Cis: Calor intern sensible. Aes: Aire exterior sensible. Cil: Calor intern latent. Ael: Aire exterior latent. RSHF: Factor de calor sensible de la zona. C.Refr.: Càrregues de refrigeració. Pàgina 15 de 72 FULL DE CÀRREGUES PER A CALEFACCIÓ DEL SISTEMA PROJECTE: SISTEMA: CENTRE CIVIC BELL-LLOC PLANTA BAIXA CONDICIONS DE DISSENY: Temperatura exterior: Dies grau acumulats: Orientació del vent dominant: Velocitat del vent dominant: -1,8 °C 1163 NO 7,4 m/s PÈRDUES DE CALOR: ZONES GIMNÀS BANY2 DESPATX GESTIÓ SALA D'ESTAR BAR-MENJADOR VESTÍBUL SALA ESPERA1 SERVEI SOCIAL PODÒLEG BANY HOMES BANY DONES SALA D'ESPERA2 CONSULTA METGE1 CURES INFERMERIA CONSULTA METGE2 Tsi (°C) 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 CÀRREGA DE CALEFACCIÓ TOTAL Àrea (m²) 46,0 20,5 15,4 49,7 114,4 44,6 29,1 15,8 18,9 14,5 16,4 42,5 22,5 15,0 16,6 20,0 Vol. (m³) 119,6 53,3 40,0 129,2 297,4 116,0 75,7 41,1 49,1 37,7 42,6 110,5 58,5 39,0 43,2 52,0 Tae (W) 1.142 583 299 1.096 2.331 2.400 366 563 481 763 0 1.237 271 214 255 493 Tol (W) 1.916 900 680 2.069 5.997 3.125 1.232 642 1.166 636 1.297 2.163 1.326 610 675 1.005 Ipv (W) 154 53 52 208 1.178 2.945 33 68 68 126 0 2.080 30 970 30 35 501,9 1.304,9 12.494 25.438 8.030 Vae (W) 2.723 2.732 546 9.806 22.572 13.200 3.172 624 820 2.049 1.366 4.644 1.366 987 987 1.366 C.calef. (W) 5.935 4.268 1.578 13.180 32.078 21.670 4.803 1.897 2.534 3.574 2.663 10.125 2.993 2.780 1.947 2.899 68.959 114.922 Factor de seguretat: 0,0% Cabal total d'aire exterior: 9.087 m³/h Càrrega de calefacció per unitat de superfície: 229 w/m² Tsi: Temperatura seca interior (°C). Vol.: Volum de la zona. Tae: Transmissió ambient exterior. Tol: Transmissió altres locals. Ipv: Infiltracions portes i finestres. Vae: Ventilació aire exterior. C.calef.: Càrregues de calefacció. ABREVIATURES I UNITATS: Or.: Orientació del tancament exterior SQ: Coeficient d'ombrejat (adimensional) K: Coeficient de transmissió (W/m²·°C) Tsa: Temperatura Sol-Aire (°C) Tec: Temperatura exterior corregida (°C) Tac: Temperatura ambient contigu (°C) Xec: Humitat específica exterior (gr/kgr) Ud. Número d'elements del mateix tipus Cabal: Aire exterior (m³/h) Sup.: Superfície de tancaments (m²) Pressió: Pressió del vent (Pa) Supl.: Suplement per orientació. G.Inst.: Guanys instantanis (W) Càrrega.Refr.: Càrregues de refrigeració (W) Càrrega.Calef.: Càrregues de calefacció (W) Pàgina 16 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA GIMNÀS CONDICIONS Ts (°C) DESTINADA A Gimnasios Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 46,0 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 119,6 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada O Fachada S TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 LADS02 S S S REF. Or. MEXA02 MEXA02 EXCEPTE PARETS Ventana S Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 2,4 2,3 0,89 0,89 0,89 1 1 1 Sup. (m²) O S REF. 16,6 14,4 Sup. (m²) LADS02 LADS02 LADS02 TAB007 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 2,4 2,4 2,3 39,0 1,9 46,0 46,0 Potència 7 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 358,8 m³/h Ventilación Tsa 60,5 47,0 K Tac 2,73 2,73 2,73 2,49 2,13 3,03 0,69 32,2 32,2 32,2 25,0 29,4 25,0 25,0 Ud. 139,0 46,0 Cabal K 0,61 0,61 %Ús 7 15 Tec 359 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 551 551 528 G. Inst. (w) 26 63 G. Inst. (w) 47 47 45 0 18 0 0 G. Inst. (w) 973 690 G. Inst. (w) 860 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 407 407 390 1.264 Càrrega Refr. (w) 38 60 103 Càrrega Refr. (w) 34 34 32 0 13 0 0 119 Càrrega Refr. (w) 973 690 1.746 Càrrega Refr. (w) 860 860 4.091 w Potència 7 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 383,0 Cabal 358,8 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 7 Xec 359 100 %Ús 11,4 100 G. Inst. (w) 2.681 G. Inst. (w) 29 Càrrega Refr. (w) 2.681 2.815 Càrrega Refr. (w) 29 29 2.844 w 6.935 w Factor de calor sensible de la zona (RSHF): 0,534 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 151 w/m² Pàgina 17 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA GIMNÀS Ts DESTINADA A Gimnasios DIMENSIONS 46,0 m² x 2,6 m REF. MEXA02 MEXA02 LADS02 LADS02 LADS02 Supl. Sup. (m²) 1,075 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 LADS02 358,8 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 16,6 14,4 2,4 2,4 2,3 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: O S S S S Sup. (m²) S S S Pressió Tac 0,61 0,61 4,30 4,30 4,30 K 39,0 1,9 46,0 46,0 Or. 21,0 Diferència 22,8 119,6 m³ TAB007 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Fachada S Ventana S Ventana S Ventana S FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 2,49 2,13 2,44 0,66 Cabal 26,7 26,7 26,7 -1,8 -1,8 -1,8 -1,8 -1,8 21,0 9,3 4,3 21,0 Tac 6,9 6,9 6,6 Cabal -1,8 -1,8 -1,8 Tac 359 -1,8 Càrrega Calef. (w) 247 199 235 235 225 1.142 Càrrega Calef. (w) 0 47 1.869 0 1.916 Càrrega Calef. (w) 52 52 50 154 Càrrega Calef. (w) 2.723 2.723 0,0% 0,0% 1,000 5.935 w 129 w/m² Pàgina 18 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA BANY2 CONDICIONS Ts (°C) Th (°C) DESTINADA A Aseos públicos vertedero,...) 32,2 21,3 DIMENSIONS 20,5 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 53,3 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) (por urinario, GUANY SOLAR VIDRE Ventana N TRANSMISSIÓ PARETS I SOSTRE Fachada O Fachada N TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA inodoro, Exteriors REF. Or. LADS02 N REF. Or. MEXA02 MEXA02 EXCEPTE PARETS Ventana N Cerramiento interior 1 Puerta interior 1 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,1 0,89 1 K Tsa 0,61 0,61 60,5 36,4 K Tac 2,73 2,49 2,13 3,03 0,69 32,2 25,0 29,4 25,0 25,0 Sup. (m²) O N REF. 5,7 15,8 Sup. (m²) LADS02 TAB007 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 2,1 26,4 2,7 20,5 20,5 Potència 4 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 89,0 20,5 Cabal 360,0 m³/h Ventilación %Ús 4 15 Tec 360 100 100 %Ús 32,2 100 G. Inst. (w) 159 G. Inst. (w) 9 16 G. Inst. (w) 41 0 25 0 0 G. Inst. (w) 356 308 G. Inst. (w) 863 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Xe (gr/kgr) 11,4 Càrrega Refr. (w) 109 114 Càrrega Refr. (w) 13 18 32 Càrrega Refr. (w) 29 0 19 0 0 51 Càrrega Refr. (w) 356 307 697 Càrrega Refr. (w) 863 863 1.757 w Potència 4 Ocupantes CALOR LATENT AIRE VENTILACIÓ Hr (%) 37,8 Ud. 121,0 Cabal 360,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 4 Xec 360 100 %Ús 11,4 100 G. Inst. (w) 484 G. Inst. (w) 29 Càrrega Refr. (w) 484 508 Càrrega Refr. (w) 29 29 537 w 2.294 w Factor de calor sensible de la zona (RSHF): 0,638 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 112 w/m² Pàgina 19 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA BANY2 Ts DESTINADA A Aseos públicos (por urinario, inodoro, vertedero,...) DIMENSIONS 20,5 m² x 2,6 m REF. MEXA02 MEXA02 LADS02 TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Solera 1 Forjado interior 1 O N N REF. LADS02 Supl. Sup. (m²) 1,075 1,175 1,175 360,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 5,7 15,8 2,1 Sup. (m²) N Pressió Tac 0,61 0,61 4,30 K 26,4 2,7 20,5 20,5 Or. 21,0 Diferència 22,8 53,3 m³ TAB007 PIMP20 SOLE01 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: Or. Interior -1,8 REF. INFILTRACIÓ PORTES I FINESTRES Ventana N Exterior (°C) VOLUM TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Fachada N Ventana N FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 2,49 2,13 2,44 0,66 Cabal 33,4 -1,8 -1,8 -1,8 21,0 9,3 4,3 21,0 Tac 7,0 Cabal -1,8 Tac 360 -1,8 Càrrega Calef. (w) 85 257 242 583 Càrrega Calef. (w) 0 67 833 0 900 Càrrega Calef. (w) 53 53 Càrrega Calef. (w) 2.732 2.732 0,0% 0,0% 1,000 4.268 w 208 w/m² Pàgina 20 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA DESPATX GESTIÓ CONDICIONS Ts (°C) DESTINADA A Oficinas Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 15,4 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 40,0 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 S REF. Or. MEXA02 EXCEPTE PARETS Ventana S Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 0,89 1 K Tsa 0,61 47,0 K Tac 2,73 2,49 2,13 2,13 3,03 0,69 32,2 25,0 29,4 25,0 25,0 25,0 Sup. (m²) S REF. 4,6 Sup. (m²) LADS02 TAB007 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 2,4 33,7 2,2 2,0 15,4 15,4 Potència 2 Ocupantes 30 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 78,0 15,4 Cabal %Ús 2 30 Tec 72,0 m³/h Ventilación 72 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 551 G. Inst. (w) 20 G. Inst. (w) 47 0 21 0 0 0 G. Inst. (w) 156 462 G. Inst. (w) 173 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 407 427 Càrrega Refr. (w) 19 20 Càrrega Refr. (w) 34 0 15 0 0 0 52 Càrrega Refr. (w) 156 462 649 Càrrega Refr. (w) 173 173 1.320 w Potència 2 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 46,0 Cabal 72,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 2 Xec 72 100 %Ús 11,4 100 G. Inst. (w) 92 G. Inst. (w) 6 Càrrega Refr. (w) 92 97 Càrrega Refr. (w) 6 6 102 w 1.423 w Factor de calor sensible de la zona (RSHF): 0,922 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 92 w/m² Pàgina 21 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA DESPATX GESTIÓ Ts DESTINADA A Oficinas DIMENSIONS 15,4 m² x 2,6 m REF. MEXA02 LADS02 Supl. Sup. (m²) 1,000 1,000 REF. LADS02 72,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 4,6 2,4 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S Sup. (m²) S Pressió Tac 0,61 4,30 K 33,7 2,2 2,0 15,4 15,4 Or. 21,0 Diferència 22,8 40,0 m³ TAB007 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 2,49 2,13 2,13 2,44 0,66 Cabal 26,7 -1,8 -1,8 21,0 9,3 21,0 4,3 21,0 Tac 6,9 Cabal -1,8 Tac 72 -1,8 Càrrega Calef. (w) 64 235 299 Càrrega Calef. (w) 0 55 0 626 0 680 Càrrega Calef. (w) 52 52 Càrrega Calef. (w) 546 546 0,0% 0,0% 1,000 1.578 w 102 w/m² Pàgina 22 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA SALA D'ESTAR CONDICIONS Ts (°C) DESTINADA A Descanso (salas de) Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 49,7 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 129,2 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 LADS02 LADS02 S S S S REF. Or. MEXA02 EXCEPTE PARETS Ventana S Ventana S Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Puerta interior 3 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 2,4 2,4 2,4 0,89 0,89 0,89 0,89 1 1 1 1 K Tsa 0,61 47,0 K Tac 2,73 2,73 2,73 2,73 2,49 2,13 2,13 2,13 3,03 0,69 32,2 32,2 32,2 32,2 25,0 29,4 25,0 25,0 25,0 25,0 Sup. (m²) S REF. 11,2 Sup. (m²) LADS02 LADS02 LADS02 LADS02 TAB007 PIMP20 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 2,4 2,4 2,4 2,4 42,6 2,0 1,8 7,0 49,7 49,7 Potència 16 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 71,0 49,7 Cabal 1.292,2 m³/h Ventilación %Ús 16 15 Tec 1.292 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 551 551 551 551 G. Inst. (w) 49 G. Inst. (w) 47 47 47 47 0 19 0 0 0 0 G. Inst. (w) 1.136 746 G. Inst. (w) 3.097 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 407 407 407 407 1.709 Càrrega Refr. (w) 47 49 Càrrega Refr. (w) 34 34 34 34 0 14 0 0 0 0 156 Càrrega Refr. (w) 1.136 745 1.976 Càrrega Refr. (w) 3.097 3.097 6.986 w Potència 16 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 31,0 Cabal 1.292,2 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 16 Xec 1.292 100 %Ús 11,4 100 G. Inst. (w) 496 G. Inst. (w) 103 Càrrega Refr. (w) 496 521 Càrrega Refr. (w) 103 103 624 w 7.610 w Factor de calor sensible de la zona (RSHF): 0,882 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 153 w/m² Pàgina 23 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA SALA D'ESTAR Ts DESTINADA A Descanso (salas de) DIMENSIONS 49,7 m² x 2,6 m REF. MEXA02 LADS02 LADS02 LADS02 LADS02 Supl. Sup. (m²) 1,000 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 LADS02 LADS02 1.292,2 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 11,2 2,4 2,4 2,4 2,4 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S S S S Sup. (m²) S S S S Pressió Tac 0,61 4,30 4,30 4,30 4,30 K 42,6 2,0 1,8 7,0 49,7 49,7 Or. 21,0 Diferència 22,8 129,2 m³ TAB007 PIMP20 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Puerta interior 3 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Ventana S Ventana S Ventana S FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 2,49 2,13 2,13 2,13 2,44 0,66 Cabal 26,7 26,7 26,7 26,7 -1,8 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 21,0 4,3 21,0 Tac 6,9 6,9 6,9 6,9 Cabal 1.292 -1,8 -1,8 -1,8 -1,8 Tac -1,8 Càrrega Calef. (w) 155 235 235 235 235 1.096 Càrrega Calef. (w) 0 50 0 0 2.019 0 2.069 Càrrega Calef. (w) 52 52 52 52 208 Càrrega Calef. (w) 9.806 9.806 0,0% 0,0% 1,000 13.180 w 265 w/m² Pàgina 24 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA BAR-MENJADOR CONDICIONS Ts (°C) DESTINADA A Comedores Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 114,4 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 297,4 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana N Ventana N Ventana N TRANSMISSIÓ PARETS I SOSTRE Fachada O Fachada S Puerta acceso S Fachada N TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 LADS02 N N N REF. Or. MEXA02 MEXA02 PEMP03 MEXA02 EXCEPTE PARETS Ventana N Ventana N Ventana N Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Puerta interior 3 Puerta interior 4 Cerramiento interior 2 Puerta interior 5 Puerta interior 6 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 4,5 4,5 4,5 0,89 0,89 0,89 1 1 1 Sup. (m²) O S S N REF. 8,8 24,2 1,9 12,8 Sup. (m²) LADS02 LADS02 LADS02 TAB007 PIMP20 PIMP20 PIMP20 PIMP20 TAB007 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 4,5 4,5 4,5 33,4 1,7 3,8 3,9 2,0 22,6 3,9 7,0 114,4 114,4 Potència 50 Ocupantes 30 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Cabal Tsa 60,5 47,0 47,0 36,4 K Tac 2,73 2,73 2,73 2,49 2,13 2,13 2,13 2,13 2,49 2,13 2,13 3,03 0,69 32,2 32,2 32,2 29,4 29,4 29,4 29,4 29,4 25,0 29,4 25,0 25,0 25,0 Ud. 71,0 114,4 2.974,4 m³/h Ventilación K 0,61 0,61 2,38 0,61 %Ús 50 30 Tec 2.974 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 341 341 341 G. Inst. (w) 14 106 99 13 G. Inst. (w) 88 88 88 366 16 36 37 19 0 37 0 0 0 G. Inst. (w) 3.550 3.432 G. Inst. (w) 7.128 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 234 234 234 736 Càrrega Refr. (w) 20 101 82 14 228 Càrrega Refr. (w) 63 63 63 274 12 27 27 14 0 27 0 0 0 599 Càrrega Refr. (w) 3.550 3.432 7.331 Càrrega Refr. (w) 7.128 7.128 16.023 w Potència 50 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 91,0 Cabal 2.974,4 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 50 Xec 2.974 100 %Ús 11,4 100 G. Inst. (w) 4.550 G. Inst. (w) 237 Càrrega Refr. (w) 4.550 4.778 Càrrega Refr. (w) 237 237 5.014 w 21.037 w Factor de calor sensible de la zona (RSHF): 0,651 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 184 w/m² Pàgina 25 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA BAR-MENJADOR Ts DESTINADA A Comedores DIMENSIONS 114,4 m² x 2,6 m REF. MEXA02 MEXA02 PEMP03 MEXA02 LADS02 LADS02 LADS02 Supl. Sup. (m²) 1,075 1,000 1,000 1,175 1,175 1,175 1,175 REF. PEMP03 LADS02 LADS02 LADS02 2.974,4 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 8,8 24,2 1,9 12,8 4,5 4,5 4,5 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: O S S N N N N Sup. (m²) S N N N Pressió 26,7 33,4 33,4 33,4 0,61 0,61 2,38 0,61 4,30 4,30 4,30 K 33,4 1,7 3,8 3,9 2,0 22,6 3,9 7,0 114,4 114,4 Or. 21,0 Diferència 22,8 297,4 m³ TAB007 PIMP20 PIMP20 PIMP20 PIMP20 TAB007 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Puerta acceso S Ventana N Ventana N Ventana N Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Puerta interior 3 Puerta interior 4 Cerramiento interior 2 Puerta interior 5 Puerta interior 6 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Fachada S Puerta acceso S Fachada N Ventana N Ventana N Ventana N FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 2,49 2,13 2,13 2,13 2,13 2,49 2,13 2,13 2,44 0,66 Cabal 110,4 14,9 14,9 14,9 Cabal 2.974 Tac -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 Tac 9,3 9,3 9,3 9,3 9,3 21,0 9,3 21,0 4,3 21,0 Tac -1,8 -1,8 -1,8 -1,8 Tac -1,8 Càrrega Calef. (w) 131 334 103 208 518 518 518 2.331 Càrrega Calef. (w) 969 42 94 97 50 0 97 0 4.648 0 5.997 Càrrega Calef. (w) 838 113 113 113 1.178 Càrrega Calef. (w) 22.572 22.572 0,0% 0,0% 1,000 32.078 w 280 w/m² Pàgina 26 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA VESTÍBUL CONDICIONS Ts (°C) DESTINADA A Vestíbulos Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 44,6 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 116,0 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana N Ventana N Ventana N Ventana N TRANSMISSIÓ PARETS I SOSTRE Fachada O Fachada N Fachada N Puerta acceso N Fachada E TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 LADS02 LADS02 N N N N REF. Or. MEXA02 MEXA02 MEXA02 PEAP53 MEXA02 EXCEPTE PARETS Ventana N Ventana N Ventana N Ventana N Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Cerramiento interior 2 Puerta interior 3 Puerta interior 4 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 4,6 3,0 1,3 2,4 0,89 0,89 0,89 0,89 1 1 1 1 K Tsa 0,61 0,61 0,61 4,80 0,61 60,5 36,4 36,4 32,2 36,4 K Tac 2,73 2,73 2,73 2,73 2,49 2,13 2,13 2,49 2,13 2,13 3,03 0,69 32,2 32,2 32,2 32,2 29,4 29,4 25,0 25,0 25,0 25,0 25,0 25,0 Sup. (m²) O N N N E REF. 11,1 4,3 1,6 5,2 10,9 Sup. (m²) LADS02 LADS02 LADS02 LADS02 TAB007 PIMP20 PIMP20 TAB007 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 4,6 3,0 1,3 2,4 41,9 3,9 1,9 13,4 2,0 1,9 44,6 44,6 Potència 6 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 89,0 44,6 Cabal 1.739,4 m³/h Ventilación %Ús 6 15 Tec 1.739 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 348 227 98 182 G. Inst. (w) 18 4 2 180 74 G. Inst. (w) 90 59 26 47 459 37 0 0 0 0 0 0 G. Inst. (w) 534 669 G. Inst. (w) 4.168 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 239 156 67 125 616 Càrrega Refr. (w) 25 5 2 128 64 236 Càrrega Refr. (w) 65 42 18 34 343 27 0 0 0 0 0 0 556 Càrrega Refr. (w) 534 669 1.263 Càrrega Refr. (w) 4.168 4.168 6.840 w Potència 6 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 121,0 Cabal 1.739,4 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 6 Xec 1.739 100 %Ús 11,4 100 G. Inst. (w) 726 G. Inst. (w) 138 Càrrega Refr. (w) 726 762 Càrrega Refr. (w) 138 138 901 w 7.740 w Factor de calor sensible de la zona (RSHF): 0,778 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 174 w/m² Pàgina 27 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA VESTÍBUL Ts DESTINADA A Vestíbulos DIMENSIONS 44,6 m² x 2,6 m REF. MEXA02 MEXA02 LADS02 MEXA02 PEAP53 LADS02 LADS02 LADS02 MEXA02 Supl. Sup. (m²) 1,075 1,175 1,175 1,175 1,175 1,175 1,175 1,175 1,125 REF. LADS02 PEAP53 LADS02 LADS02 LADS02 1.739,4 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 11,1 4,3 4,6 1,6 5,2 3,0 1,3 2,4 10,9 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: O N N N N N N N E Sup. (m²) N N N N N Pressió 33,4 33,4 33,4 33,4 33,4 0,61 0,61 4,30 0,61 4,80 4,30 4,30 4,30 0,61 K 41,9 3,9 1,9 13,4 2,0 1,9 44,6 44,6 Or. 21,0 Diferència 22,8 116,0 m³ TAB007 PIMP20 PIMP20 TAB007 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana N Puerta acceso N Ventana N Ventana N Ventana N Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Cerramiento interior 2 Puerta interior 3 Puerta interior 4 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Fachada N Ventana N Fachada N Puerta acceso N Ventana N Ventana N Ventana N Fachada E FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 2,49 2,13 2,13 2,49 2,13 2,13 2,44 0,66 Cabal 15,3 350,6 10,0 4,3 8,0 Cabal 1.739 Tac -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 Tac 9,3 9,3 21,0 21,0 21,0 21,0 4,3 21,0 Tac -1,8 -1,8 -1,8 -1,8 -1,8 Tac -1,8 Càrrega Calef. (w) 165 70 530 26 669 346 150 276 169 2.400 Càrrega Calef. (w) 1.216 97 0 0 0 0 1.812 0 3.125 Càrrega Calef. (w) 116 2.660 76 33 60 2.945 Càrrega Calef. (w) 13.200 13.200 0,0% 0,0% 1,000 21.670 w 486 w/m² Pàgina 28 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA SALA ESPERA1 CONDICIONS Ts (°C) DESTINADA A Espera y recepción (salas) Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 29,1 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 75,7 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S Fachada E Fachada S TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 S REF. Or. MEXA02 MEXA02 MEXA02 EXCEPTE PARETS Ventana S Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Puerta interior 3 Puerta interior 4 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 1,5 0,89 1 K Tsa 0,61 0,61 0,61 47,0 36,4 47,0 K Tac 2,73 2,49 2,13 2,13 2,13 2,13 3,03 0,69 32,2 25,0 25,0 29,4 25,0 25,0 25,0 25,0 Sup. (m²) S E S REF. 12,9 1,8 0,9 Sup. (m²) LADS02 TAB007 PIMP20 PIMP20 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 1,5 32,5 1,9 2,0 2,0 1,9 29,1 29,1 Potència 8 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 71,0 29,1 Cabal 418,0 m³/h Ventilación %Ús 8 15 Tec 418 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 344 G. Inst. (w) 57 12 4 G. Inst. (w) 29 0 0 19 0 0 0 0 G. Inst. (w) 568 437 G. Inst. (w) 1.002 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 254 267 Càrrega Refr. (w) 54 11 4 72 Càrrega Refr. (w) 21 0 0 14 0 0 0 0 37 Càrrega Refr. (w) 568 436 1.055 Càrrega Refr. (w) 1.002 1.002 2.432 w Potència 8 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 31,0 Cabal 418,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 8 Xec 418 100 %Ús 11,4 100 G. Inst. (w) 248 G. Inst. (w) 33 Càrrega Refr. (w) 248 260 Càrrega Refr. (w) 33 33 294 w 2.725 w Factor de calor sensible de la zona (RSHF): 0,846 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 94 w/m² Pàgina 29 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA SALA ESPERA1 Ts DESTINADA A Espera y recepción (salas) DIMENSIONS 29,1 m² x 2,6 m REF. MEXA02 LADS02 MEXA02 MEXA02 Supl. Sup. (m²) 1,000 1,000 1,125 1,000 REF. LADS02 418,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 12,9 1,5 1,8 0,9 Sup. (m²) TAB007 PIMP20 PIMP20 PIMP20 PIMP20 SOLE01 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S E S S Pressió Tac 0,61 4,30 0,61 0,61 K 32,5 1,9 2,0 2,0 1,9 29,1 29,1 Or. 21,0 Diferència 22,8 75,7 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Puerta interior 3 Puerta interior 4 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Fachada E Fachada S FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 2,49 2,13 2,13 2,13 2,13 2,44 0,66 Cabal 26,7 -1,8 -1,8 -1,8 -1,8 21,0 21,0 9,3 21,0 21,0 4,3 21,0 Tac 4,3 Cabal -1,8 Tac 418 -1,8 Càrrega Calef. (w) 178 147 28 12 366 Càrrega Calef. (w) 0 0 50 0 0 1.182 0 1.232 Càrrega Calef. (w) 33 33 Càrrega Calef. (w) 3.172 3.172 0,0% 0,0% 1,000 4.803 w 165 w/m² Pàgina 30 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA SERVEI SOCIAL CONDICIONS Ts (°C) DESTINADA A Oficinas Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 15,8 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 41,1 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana N Ventana N TRANSMISSIÓ PARETS I SOSTRE Fachada O Fachada N TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 N N REF. Or. MEXA02 MEXA02 EXCEPTE PARETS Ventana N Ventana N Cerramiento interior 1 Puerta interior 1 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 1,3 1,4 0,89 0,89 1 1 Sup. (m²) O N REF. 7,9 8,3 Sup. (m²) LADS02 LADS02 TAB007 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 1,3 1,4 21,2 1,9 15,8 15,8 Potència 3 Ocupantes 30 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ K Tsa 0,61 0,61 60,5 36,4 K Tac 2,73 2,73 2,49 2,13 3,03 0,69 32,2 32,2 25,0 25,0 25,0 25,0 Ud. 78,0 15,8 Cabal %Ús 3 30 Tec 82,2 m³/h Ventilación 82 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 98 106 G. Inst. (w) 13 8 G. Inst. (w) 26 28 0 0 0 0 G. Inst. (w) 234 474 G. Inst. (w) 197 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 67 73 147 Càrrega Refr. (w) 18 9 29 Càrrega Refr. (w) 18 20 0 0 0 0 40 Càrrega Refr. (w) 234 474 743 Càrrega Refr. (w) 197 197 1.156 w Potència 3 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 46,0 Cabal 82,2 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 3 Xec 82 100 %Ús 11,4 100 G. Inst. (w) 138 G. Inst. (w) 7 Càrrega Refr. (w) 138 145 Càrrega Refr. (w) 7 7 151 w 1.308 w Factor de calor sensible de la zona (RSHF): 0,869 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 83 w/m² Pàgina 31 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA SERVEI SOCIAL Ts DESTINADA A Oficinas DIMENSIONS 15,8 m² x 2,6 m REF. MEXA02 MEXA02 LADS02 LADS02 Supl. Sup. (m²) 1,075 1,175 1,175 1,175 REF. LADS02 LADS02 82,2 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 7,9 8,3 1,3 1,4 Sup. (m²) TAB007 PIMP20 SOLE01 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: O N N N N N Pressió Tac 0,61 0,61 4,30 4,30 K 21,2 1,9 15,8 15,8 Or. 21,0 Diferència 22,8 41,1 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana N Ventana N Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Fachada N Ventana N Ventana N FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 2,49 2,13 2,44 0,66 Cabal 33,4 33,4 -1,8 -1,8 -1,8 -1,8 21,0 21,0 4,3 21,0 Tac 4,3 4,6 Cabal -1,8 -1,8 Tac 82 -1,8 Càrrega Calef. (w) 117 135 150 161 563 Càrrega Calef. (w) 0 0 642 0 642 Càrrega Calef. (w) 33 35 68 Càrrega Calef. (w) 624 624 0,0% 0,0% 1,000 1.897 w 120 w/m² Pàgina 32 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA PODÒLEG CONDICIONS Ts (°C) DESTINADA A Salas de recuperación Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 18,9 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 49,1 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana N TRANSMISSIÓ PARETS I SOSTRE Fachada N Fachada O Fachada N TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 N REF. Or. MEXA02 MEXA02 MEXA02 EXCEPTE PARETS Ventana N Cerramiento interior 1 Cerramiento interior 2 Puerta interior 1 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,7 0,89 1 K Tsa 0,61 0,61 0,61 36,4 60,5 36,4 K Tac 2,73 1,98 1,98 2,13 3,03 0,69 32,2 29,4 25,0 25,0 25,0 25,0 Sup. (m²) N O N REF. 2,6 1,8 6,2 Sup. (m²) LADS02 TAB008 TAB008 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 2,7 17,2 13,9 2,0 18,9 18,9 Potència 3 Ocupantes 20 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 109,0 18,9 Cabal 108,0 m³/h Ventilación %Ús 3 20 Tec 108 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 205 G. Inst. (w) 3 3 6 G. Inst. (w) 53 150 0 0 0 0 G. Inst. (w) 327 378 G. Inst. (w) 259 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 140 147 Càrrega Refr. (w) 3 4 7 15 Càrrega Refr. (w) 38 112 0 0 0 0 158 Càrrega Refr. (w) 327 378 740 Càrrega Refr. (w) 259 259 1.319 w Potència 3 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 248,0 Cabal 108,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 3 Xec 108 100 %Ús 11,4 100 G. Inst. (w) 744 G. Inst. (w) 9 Càrrega Refr. (w) 744 781 Càrrega Refr. (w) 9 9 790 w 2.109 w Factor de calor sensible de la zona (RSHF): 0,576 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 112 w/m² Pàgina 33 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA PODÒLEG Ts DESTINADA A Salas de recuperación DIMENSIONS 18,9 m² x 2,6 m REF. MEXA02 MEXA02 MEXA02 LADS02 Supl. Sup. (m²) 1,175 1,075 1,175 1,175 REF. LADS02 108,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 2,6 1,8 6,2 2,7 Sup. (m²) TAB008 TAB008 PIMP20 SOLE01 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: N O N N N Pressió Tac 0,61 0,61 0,61 4,30 K 17,2 13,9 2,0 18,9 18,9 Or. 21,0 Diferència 22,8 49,1 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana N Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Cerramiento interior 2 Puerta interior 1 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada N Fachada O Fachada N Ventana N FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 1,98 2,13 2,44 0,66 Cabal 33,4 -1,8 -1,8 -1,8 -1,8 9,3 21,0 21,0 4,3 21,0 Tac 9,0 Cabal -1,8 Tac 108 -1,8 Càrrega Calef. (w) 42 27 101 311 481 Càrrega Calef. (w) 398 0 0 768 0 1.166 Càrrega Calef. (w) 68 68 Càrrega Calef. (w) 820 820 0,0% 0,0% 1,000 2.534 w 134 w/m² Pàgina 34 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA BANY HOMES CONDICIONS Ts (°C) Th (°C) DESTINADA A Aseos públicos vertedero,...) 32,2 21,3 DIMENSIONS 14,5 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 37,7 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) (por urinario, GUANY SOLAR VIDRE Ventana E Ventana E Ventana E TRANSMISSIÓ PARETS I SOSTRE Fachada E TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA inodoro, Exteriors REF. Or. LADS02 LADS02 LADS02 E E E REF. Or. MEXA02 EXCEPTE PARETS Ventana E Ventana E Ventana E Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 1,9 1,9 2,0 0,89 0,89 0,89 1 1 1 K Tsa 0,61 36,4 K Tac 2,73 2,73 2,73 1,98 2,13 2,13 3,03 0,69 32,2 32,2 32,2 25,0 29,4 25,0 25,0 25,0 Sup. (m²) E REF. 7,9 Sup. (m²) LADS02 LADS02 LADS02 TAB008 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 1,9 1,9 2,0 29,5 1,9 2,0 14,5 14,5 Potència 3 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 89,0 14,5 Cabal 270,0 m³/h Ventilación %Ús 3 15 Tec 270 100 100 %Ús 32,2 100 G. Inst. (w) 144 144 151 G. Inst. (w) 53 G. Inst. (w) 37 37 39 0 18 0 0 0 G. Inst. (w) 267 218 G. Inst. (w) 647 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Xe (gr/kgr) 11,4 Càrrega Refr. (w) 269 269 283 861 Càrrega Refr. (w) 47 49 Càrrega Refr. (w) 27 27 28 0 13 0 0 0 100 Càrrega Refr. (w) 267 217 509 Càrrega Refr. (w) 647 647 2.166 w Potència 3 Ocupantes CALOR LATENT AIRE VENTILACIÓ Hr (%) 37,8 Ud. 121,0 Cabal 270,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 3 Xec 270 100 %Ús 11,4 100 G. Inst. (w) 363 G. Inst. (w) 21 Càrrega Refr. (w) 363 381 Càrrega Refr. (w) 21 21 403 w 2.568 w Factor de calor sensible de la zona (RSHF): 0,799 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 177 w/m² Pàgina 35 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA BANY HOMES Ts DESTINADA A Aseos públicos (por urinario, inodoro, vertedero,...) DIMENSIONS 14,5 m² x 2,6 m REF. MEXA02 LADS02 LADS02 LADS02 TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 E E E E REF. LADS02 LADS02 LADS02 Supl. Sup. (m²) 1,125 1,125 1,125 1,125 270,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 7,9 1,9 1,9 2,0 Sup. (m²) E E E Pressió Tac 0,61 4,30 4,30 4,30 K 29,5 1,9 2,0 14,5 14,5 Or. 21,0 Diferència 22,8 37,7 m³ REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: Or. Interior -1,8 TAB008 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana E Ventana E Ventana E Exterior (°C) VOLUM TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Ventana E Ventana E Ventana E FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 2,13 2,44 0,66 Cabal 26,7 26,7 26,7 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 4,3 21,0 Tac 5,4 5,4 5,7 Cabal -1,8 -1,8 -1,8 Tac 270 -1,8 Càrrega Calef. (w) 123 210 210 221 763 Càrrega Calef. (w) 0 47 0 589 0 636 Càrrega Calef. (w) 41 41 43 126 Càrrega Calef. (w) 2.049 2.049 0,0% 0,0% 1,000 3.574 w 246 w/m² Pàgina 36 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA BANY DONES CONDICIONS Ts (°C) Th (°C) DESTINADA A Aseos públicos vertedero,...) 32,2 21,3 DIMENSIONS 16,4 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 42,6 m³ Diferències 7,2 2,3 -19,1 0,1 TRANSMISSIÓ SOSTRE EXCEPTE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA (Máximas por Sistema) (por PARETS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Cerramiento interior 2 Solera 1 Forjado interior 1 urinario, I inodoro, Exteriors REF. Sup. (m²) TAB008 PIMP20 PIMP20 TAB008 SOLE01 FOREX1 CALOR SENSIBLE INTERN 25,2 2,0 1,9 18,4 16,4 16,4 Potència 3 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Cabal Tac 1,98 2,13 2,13 1,98 3,03 0,69 29,4 25,0 29,4 25,0 25,0 25,0 Ud. 89,0 16,4 180,0 m³/h Ventilación K %Ús 3 15 Tec 180 100 100 %Ús 32,2 100 G. Inst. (w) 220 0 18 0 0 0 G. Inst. (w) 267 246 G. Inst. (w) 431 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Xe (gr/kgr) 11,4 Càrrega Refr. (w) 165 0 13 0 0 0 187 Càrrega Refr. (w) 267 246 539 Càrrega Refr. (w) 431 431 1.157 w Potència 3 Ocupantes CALOR LATENT AIRE VENTILACIÓ Hr (%) 37,8 Ud. 121,0 Cabal 180,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 3 Xec 180 100 %Ús 11,4 100 G. Inst. (w) 363 G. Inst. (w) 14 Càrrega Refr. (w) 363 381 Càrrega Refr. (w) 14 14 395 w 1.552 w Factor de calor sensible de la zona (RSHF): 0,656 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 95 w/m² Pàgina 37 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA BANY DONES Ts DESTINADA A Aseos públicos (por urinario, inodoro, vertedero,...) DIMENSIONS 16,4 m² x 2,6 m REF. TAB008 PIMP20 PIMP20 TAB008 SOLE01 FOREX1 VENTILACIÓ AIRE EXTERIOR 180,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ Càrrega de calefacció per unitat de superfície: Exterior (°C) VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Cerramiento interior 2 Solera 1 Forjado interior 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Interior -1,8 21,0 Diferència 22,8 42,6 m³ Sup. (m²) K 25,2 2,0 1,9 18,4 16,4 16,4 1,98 2,13 2,13 1,98 2,44 0,66 Cabal Tac 9,3 21,0 9,3 21,0 4,3 21,0 Tac 180 -1,8 Càrrega Calef. (w) 583 0 47 0 666 0 1.297 Càrrega Calef. (w) 1.366 1.366 0,0% 0,0% 1,000 2.663 w 162 w/m² Pàgina 38 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA SALA D'ESPERA2 CONDICIONS Ts (°C) DESTINADA A Espera y recepción (salas) Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 42,5 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 110,5 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana O TRANSMISSIÓ PARETS I SOSTRE Fachada O Puerta acceso O TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 O REF. Or. MEXA02 PEAP53 EXCEPTE PARETS Ventana O Cerramiento interior 1 Puerta interior 6 Puerta interior 7 Cerramiento interior 2 Puerta interior 1 Puerta interior 2 Puerta interior 3 Puerta interior 4 Puerta interior 5 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 5,4 0,89 1 K Tsa 0,61 4,80 60,5 70,0 K Tac 2,73 1,98 2,13 2,13 1,98 2,13 2,13 2,13 2,13 2,13 3,03 0,69 32,2 29,4 29,4 29,4 25,0 29,4 25,0 25,0 25,0 25,0 25,0 25,0 Sup. (m²) O O REF. 14,9 3,8 Sup. (m²) LADS02 TAB008 PIMP20 PIMP20 TAB008 PIMP20 PIMP20 PIMP20 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 5,4 12,4 2,0 2,0 30,4 2,0 1,9 2,0 1,9 1,9 42,5 42,5 Potència 14 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 71,0 42,5 Cabal 612,0 m³/h Ventilación %Ús 14 15 Tec 612 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 2.869 G. Inst. (w) 24 821 G. Inst. (w) 106 108 19 19 0 19 0 0 0 0 0 0 G. Inst. (w) 994 638 G. Inst. (w) 1.467 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 1.058 1.111 Càrrega Refr. (w) 34 613 679 Càrrega Refr. (w) 76 81 14 14 0 14 0 0 0 0 0 0 209 Càrrega Refr. (w) 994 637 1.713 Càrrega Refr. (w) 1.467 1.467 5.179 w Potència 14 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 31,0 Cabal 612,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 14 Xec 612 100 %Ús 11,4 100 G. Inst. (w) 434 G. Inst. (w) 49 Càrrega Refr. (w) 434 456 Càrrega Refr. (w) 49 49 504 w 5.683 w Factor de calor sensible de la zona (RSHF): 0,891 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 134 w/m² Pàgina 39 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA SALA D'ESPERA2 Ts DESTINADA A Espera y recepción (salas) DIMENSIONS 42,5 m² x 2,6 m REF. MEXA02 PEAP53 LADS02 Supl. Sup. (m²) 1,075 1,075 1,075 REF. PEAP53 LADS02 612,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 14,9 3,8 5,4 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: O O O Sup. (m²) O O Pressió 33,4 33,4 0,61 4,80 4,30 K 12,4 2,0 2,0 30,4 2,0 1,9 2,0 1,9 1,9 42,5 42,5 Or. 21,0 Diferència 22,8 110,5 m³ TAB008 PIMP20 PIMP20 TAB008 PIMP20 PIMP20 PIMP20 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Puerta acceso O Ventana O Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 6 Puerta interior 7 Cerramiento interior 2 Puerta interior 1 Puerta interior 2 Puerta interior 3 Puerta interior 4 Puerta interior 5 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Puerta acceso O Ventana O FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 1,98 2,13 2,13 1,98 2,13 2,13 2,13 2,13 2,13 2,44 0,66 Cabal Tac -1,8 -1,8 -1,8 Tac 9,3 9,3 9,3 21,0 9,3 21,0 21,0 21,0 21,0 4,3 21,0 Tac 256,2 17,9 Cabal -1,8 -1,8 Tac 612 -1,8 Càrrega Calef. (w) 221 447 569 1.237 Càrrega Calef. (w) 287 50 50 0 50 0 0 0 0 1.727 0 2.163 Càrrega Calef. (w) 1.944 136 2.080 Càrrega Calef. (w) 4.644 4.644 0,0% 0,0% 1,000 10.125 w 238 w/m² Pàgina 40 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA CONSULTA METGE1 CONDICIONS Ts (°C) DESTINADA A Salas de curas Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 22,5 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 58,5 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana E TRANSMISSIÓ PARETS I SOSTRE Fachada E TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 E REF. Or. MEXA02 EXCEPTE PARETS Ventana E Cerramiento interior 1 Cerramiento interior 2 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 1,4 0,89 1 K Tsa 0,61 36,4 K Tac 2,73 1,98 1,98 2,13 2,13 3,03 0,69 32,2 29,4 25,0 25,0 25,0 25,0 25,0 Sup. (m²) E REF. 7,5 Sup. (m²) LADS02 TAB008 TAB008 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 1,4 17,8 22,6 2,0 2,0 22,5 22,5 Potència 4 Ocupantes 30 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 72,0 22,5 Cabal 180,0 m³/h Ventilación %Ús 4 30 Tec 180 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 106 G. Inst. (w) 51 G. Inst. (w) 28 155 0 0 0 0 0 G. Inst. (w) 288 675 G. Inst. (w) 431 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 198 208 Càrrega Refr. (w) 44 46 Càrrega Refr. (w) 20 116 0 0 0 0 0 143 Càrrega Refr. (w) 288 675 1.011 Càrrega Refr. (w) 431 431 1.840 w Potència 4 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 148,0 Cabal 180,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 4 Xec 180 100 %Ús 11,4 100 G. Inst. (w) 592 G. Inst. (w) 14 Càrrega Refr. (w) 592 622 Càrrega Refr. (w) 14 14 636 w 2.476 w Factor de calor sensible de la zona (RSHF): 0,694 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 110 w/m² Pàgina 41 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA CONSULTA METGE1 Ts DESTINADA A Salas de curas DIMENSIONS 22,5 m² x 2,6 m REF. MEXA02 LADS02 Supl. Sup. (m²) 1,125 1,125 REF. LADS02 180,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 7,5 1,4 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: E E Sup. (m²) E Pressió Tac 0,61 4,30 K 17,8 22,6 2,0 2,0 22,5 22,5 Or. 21,0 Diferència 22,8 58,5 m³ TAB008 TAB008 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana E Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Cerramiento interior 2 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Ventana E FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 1,98 2,13 2,13 2,44 0,66 Cabal 26,7 -1,8 -1,8 9,3 21,0 21,0 21,0 4,3 21,0 Tac 4,0 Cabal -1,8 Tac 180 -1,8 Càrrega Calef. (w) 117 154 271 Càrrega Calef. (w) 412 0 0 0 914 0 1.326 Càrrega Calef. (w) 30 30 Càrrega Calef. (w) 1.366 1.366 0,0% 0,0% 1,000 2.993 w 133 w/m² Pàgina 42 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA CURES CONDICIONS Ts (°C) DESTINADA A Salas de curas Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 15,0 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 39,0 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) TRANSMISSIÓ PARETS I SOSTRE REF. Fachada E Puerta acceso E TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA Or. MEXA02 PEMP01 EXCEPTE PARETS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 I Sup. (m²) E E REF. 5,1 2,2 Sup. (m²) TAB008 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 30,9 2,0 1,9 15,0 15,0 Potència 3 Ocupantes 40 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 130,0 m³/h Ventilación Tsa 36,4 37,8 K Tac 1,98 2,13 2,13 3,03 0,69 25,0 25,0 25,0 25,0 25,0 Ud. 72,0 15,0 Cabal K 0,61 2,38 %Ús 3 40 Tec 130 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 34 67 G. Inst. (w) 30 66 101 Càrrega Refr. (w) G. Inst. (w) 216 600 G. Inst. (w) 312 0 0 0 0 0 0 Càrrega Refr. (w) 216 600 857 Càrrega Refr. (w) 312 312 1.269 w Potència 3 Ocupantes CALOR LATENT AIRE VENTILACIÓ Càrrega Refr. (w) 0 0 0 0 0 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Xe (gr/kgr) 11,4 Ud. 148,0 Cabal 130,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 3 Xec 130 100 %Ús 11,4 100 G. Inst. (w) 444 G. Inst. (w) 10 Càrrega Refr. (w) 444 466 Càrrega Refr. (w) 10 10 477 w 1.746 w Factor de calor sensible de la zona (RSHF): 0,673 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 116 w/m² Pàgina 43 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA CURES Ts DESTINADA A Salas de curas DIMENSIONS 15,0 m² x 2,6 m REF. MEXA02 PEMP01 Supl. Sup. (m²) 1,125 1,125 REF. PEMP01 130,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 5,1 2,2 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: E E Sup. (m²) E Pressió 26,7 0,61 2,38 K 30,9 2,0 1,9 15,0 15,0 Or. 21,0 Diferència 22,8 39,0 m³ TAB008 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Puerta acceso E Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Puerta acceso E FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 1,98 2,13 2,13 2,44 0,66 Cabal Tac -1,8 -1,8 Tac 21,0 21,0 21,0 4,3 21,0 Tac 127,8 Cabal -1,8 Tac 130 -1,8 Càrrega Calef. (w) 79 134 214 Càrrega Calef. (w) 0 0 0 610 0 610 Càrrega Calef. (w) 970 970 Càrrega Calef. (w) 987 987 0,0% 0,0% 1,000 2.780 w 185 w/m² Pàgina 44 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA INFERMERIA CONDICIONS Ts (°C) DESTINADA A Salas de curas Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 16,6 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 43,2 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana E TRANSMISSIÓ PARETS I SOSTRE Fachada E TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 E REF. Or. MEXA02 EXCEPTE PARETS Ventana E Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 1,4 0,89 1 K Tsa 0,61 36,4 K Tac 2,73 1,98 2,13 2,13 3,03 0,69 32,2 25,0 25,0 25,0 25,0 25,0 Sup. (m²) E REF. 6,5 Sup. (m²) LADS02 TAB008 PIMP20 PIMP20 SOLE01 FOREX1 CALOR SENSIBLE INTERN 1,4 31,3 2,0 2,0 16,6 16,6 Potència 3 Ocupantes 40 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 72,0 16,6 Cabal 130,0 m³/h Ventilación %Ús 3 40 Tec 130 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 106 G. Inst. (w) 44 G. Inst. (w) 28 0 0 0 0 0 G. Inst. (w) 216 664 G. Inst. (w) 312 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 198 208 Càrrega Refr. (w) 38 40 Càrrega Refr. (w) 20 0 0 0 0 0 21 Càrrega Refr. (w) 216 664 924 Càrrega Refr. (w) 312 312 1.504 w Potència 3 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 148,0 Cabal 130,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 3 Xec 130 100 %Ús 11,4 100 G. Inst. (w) 444 G. Inst. (w) 10 Càrrega Refr. (w) 444 466 Càrrega Refr. (w) 10 10 477 w 1.981 w Factor de calor sensible de la zona (RSHF): 0,719 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 119 w/m² Pàgina 45 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA INFERMERIA Ts DESTINADA A Salas de curas DIMENSIONS 16,6 m² x 2,6 m REF. MEXA02 LADS02 Supl. Sup. (m²) 1,125 1,125 REF. LADS02 130,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 6,5 1,4 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: E E Sup. (m²) E Pressió Tac 0,61 4,30 K 31,3 2,0 2,0 16,6 16,6 Or. 21,0 Diferència 22,8 43,2 m³ TAB008 PIMP20 PIMP20 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana E Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Ventana E FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 2,13 2,44 0,66 Cabal 26,7 -1,8 -1,8 21,0 21,0 21,0 4,3 21,0 Tac 4,0 Cabal -1,8 Tac 130 -1,8 Càrrega Calef. (w) 101 154 255 Càrrega Calef. (w) 0 0 0 675 0 675 Càrrega Calef. (w) 30 30 Càrrega Calef. (w) 987 987 0,0% 0,0% 1,000 1.947 w 117 w/m² Pàgina 46 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA DATA CÀLCUL 15 Hora solar Agosto ZONA CONSULTA METGE2 CONDICIONS Ts (°C) DESTINADA A Salas de curas Exteriors 32,2 21,3 Hr (%) 37,8 DIMENSIONS 20,0 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 52,0 m³ Diferències 7,2 2,3 -19,1 0,1 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana E TRANSMISSIÓ PARETS I SOSTRE Fachada E Fachada S TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 E REF. Or. MEXA02 MEXA02 EXCEPTE PARETS Ventana E Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Cerramiento interior 2 Solera 1 Forjado interior 1 I Sup. (m²) SC Ud. 1,6 0,89 1 K Tsa 0,61 0,61 36,4 47,0 K Tac 2,73 1,98 2,13 2,13 1,98 3,03 0,69 32,2 25,0 25,0 25,0 29,4 25,0 25,0 Sup. (m²) E S REF. 9,0 12,8 Sup. (m²) LADS02 TAB008 PIMP20 PIMP20 TAB008 SOLE01 FOREX1 CALOR SENSIBLE INTERN 1,6 13,1 2,0 2,0 8,3 20,0 20,0 Potència 4 Ocupantes 30 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 72,0 20,0 Cabal 180,0 m³/h Ventilación %Ús 4 30 Tec 180 100 100 %Ús 32,2 100 Th (°C) G. Inst. (w) 121 G. Inst. (w) 61 56 G. Inst. (w) 31 0 0 0 72 0 0 G. Inst. (w) 288 600 G. Inst. (w) 431 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 226 238 Càrrega Refr. (w) 53 53 112 Càrrega Refr. (w) 22 0 0 0 54 0 0 81 Càrrega Refr. (w) 288 600 932 Càrrega Refr. (w) 431 431 1.794 w Potència 4 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,4 Ud. 148,0 Cabal 180,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 4 Xec 180 100 %Ús 11,4 100 G. Inst. (w) 592 G. Inst. (w) 14 Càrrega Refr. (w) 592 622 Càrrega Refr. (w) 14 14 636 w 2.430 w Factor de calor sensible de la zona (RSHF): 0,687 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 121 w/m² Pàgina 47 de 72 EXPEDIENT 13 PROJECTE CENTRE CIVIC BELL-LLOC PB DATA 22/01/08 SISTEMA PLANTA BAIXA CONDICIONS DE CÀLCUL PER A HIVERN ZONA CONSULTA METGE2 Ts DESTINADA A Salas de curas DIMENSIONS 20,0 m² x 2,6 m REF. MEXA02 LADS02 MEXA02 Supl. Sup. (m²) 1,125 1,125 1,000 REF. LADS02 180,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 9,0 1,6 12,8 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: E E S Sup. (m²) E Pressió Tac 0,61 4,30 0,61 K 13,1 2,0 2,0 8,3 20,0 20,0 Or. 21,0 Diferència 22,8 52,0 m³ TAB008 PIMP20 PIMP20 TAB008 SOLE01 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana E Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Cerramiento interior 2 Solera 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Ventana E Fachada S FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 2,13 1,98 2,44 0,66 Cabal 26,7 -1,8 -1,8 -1,8 21,0 21,0 21,0 9,3 4,3 21,0 Tac 4,6 Cabal -1,8 Tac 180 -1,8 Càrrega Calef. (w) 140 176 177 493 Càrrega Calef. (w) 0 0 0 192 813 0 1.005 Càrrega Calef. (w) 35 35 Càrrega Calef. (w) 1.366 1.366 0,0% 0,0% 1,000 2.899 w 145 w/m² Pàgina 48 de 72 FULL DE CÀRREGUES PER A REFRIGERACIÓ DEL SISTEMA PROJECTE: SISTEMA: CENTRE CIVIC BELL-LLOC PLANTA PRIMERA CONDICIONS DE DISSENY: Estimat per a les 14 hora solar del mes de Agosto. T.seca 31,6 °C Exterior: T.hum. 21,3 °C H.rel. 40,0 % H.esp. 11,6 gr/kg GUANYS DE CALOR: Ts (°C) Th (°C) Àrea (m²) Vol. (m³) NOVES TECNOLOGIES 25,0 19,0 38,8 100,9 LOCAL4 25,0 19,0 26,2 68,1 LOCAL3 25,0 19,0 26,1 67,9 LOCAL2 25,0 19,0 24,9 64,7 LOCAL1 25,0 19,0 25,7 66,8 RECEPCIÓ 25,0 19,0 25,8 67,1 DESPATX SALA D’ACTES 25,0 19,0 8,6 22,4 VESTÍBUL 25,0 19,0 44,5 115,7 BANY DONES 25,0 19,0 25,3 65,8 BANY HOMES 25,0 19,0 21,1 54,9 SALA D’ACTES 25,0 19,0 171,1 513,3 Gsc (W) Tpt (W) Tept (W) Cis (W) Aes (W) Cil (W) Ael (W) RSHF C.refr. (W) 1.162 250 135 2.247 949 725 122 0,840 5.591 897 140 76 2.326 1.265 966 163 0,781 5.832 916 138 77 2.323 1.265 966 163 0,781 5.848 916 132 78 2.292 1.265 966 163 0,780 5.812 916 136 78 2.313 1.265 966 163 0,781 5.836 916 137 78 1.301 816 391 105 0,862 3.744 0 39 58 435 158 97 20 0,846 806 646 293 306 1.448 2.033 1.016 262 0,726 6.006 925 183 80 772 791 508 102 0,794 3.361 0 95 0 706 791 508 102 0,612 2.201 3.477 1.178 275 11.043 5.638 3.864 726 0,805 26.201 1.241 27.206 16.238 10.973 2.090 0,793 71.239 CÀRREGA DE REFRIGERACIÓ TOTAL 438,1 1.207,5 10.771 2.721 Factor de seguretat: 5% Cabal total d'aire exterior: 7.392 m³/h Càrrega de refrigeració per unitat de superfície: 163 w/m² Ts: T emperatura seca interior (°C). Th: Temperatura humida interior (°C). Vol.: Volum de la zona. Gsc: Guany solar vidre. Tpt: Transmissió parets i sostre. Tept: Transmissió excepte parets i sostre. Cis: Calor intern sensible. Aes: Aire exterior sensible. Cil: Calor intern latent. Ael: Aire exterior latent. RSHF: Factor de calor sensible de la zona. C.Refr.: Càrregues de refrigeració. Pàgina 49 de 72 FULL DE CÀRREGUES PER A CALEFACCIÓ DEL SISTEMA PROJECTE: SISTEMA: CENTRE CIVIC BELL-LLOC PLANTA PRIMERA CONDICIONS DE DISSENY: Temperatura exterior: Dies grau acumulats: Orientació del vent dominant: Velocitat del vent dominant: -1,8 °C 1163 NO 7,4 m/s PÈRDUES DE CALOR: ZONES NOVES TECNOLOGIES LOCAL4 LOCAL3 LOCAL2 LOCAL1 RECEPCIÓ DESPATX SALA D’ACTES VESTÍBUL BANY DONES BANY HOMES SALA D’ACTES Tsi (°C) 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 21,0 CÀRREGA DE CALEFACCIÓ TOTAL Àrea (m²) 38,8 26,2 26,1 24,9 25,7 25,8 8,6 44,5 25,3 21,1 171,1 Vol. (m³) 100,9 68,1 67,9 64,7 66,8 67,1 22,4 115,7 65,8 54,9 513,3 Tae (W) 1.947 808 812 798 806 811 84 2.298 1.100 206 5.224 Tol (W) 47 52 52 57 55 55 223 587 0 0 94 438,1 1.207,5 14.895 1.222 Ipv (W) 218 102 104 104 104 104 0 297 130 0 428 Vae (W) 3.278 4.371 4.371 4.371 4.371 2.819 546 7.024 2.732 2.732 19.477 C.calef. (W) 5.490 5.334 5.339 5.331 5.336 3.790 854 10.206 3.963 2.938 25.223 1.592 56.094 73.802 Factor de seguretat: 0,0% Cabal total d'aire exterior: 7.392 m³/h Càrrega de calefacció per unitat de superfície: 168 w/m² Tsi: Temperatura seca interior (°C). Vol.: Volum de la zona. Tae: Transmissió ambient exterior. Tol: Transmissió altres locals. Ipv: Infiltracions portes i finestres. Vae: Ventilació aire exterior. C.calef.: Càrregues de calefacció. ABREVIATURES I UNITATS: Or.: Orientació del tancament exterior SQ: Coeficient d'ombrejat (adimensional) K: Coeficient de transmissió (W/m²·°C) Tsa: Temperatura Sol-Aire (°C) Tec: Temperatura exterior corregida (°C) Tac: Temperatura ambient contigu (°C) Xec: Humitat específica exterior (gr/kgr) Ud. Número d'elements del mateix tipus Cabal: Aire exterior (m³/h) Sup.: Superfície de tancaments (m²) Pressió: Pressió del vent (Pa) Supl.: Suplement per orientació. G.Inst.: Guanys instantanis (W) Càrrega.Refr.: Càrregues de refrigeració (W) Càrrega.Calef.: Càrregues de calefacció (W) Pàgina 50 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA NOVES TECNOLOGIES CONDICIONS Ts (°C) DESTINADA A Aulas (sin fumadores) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 38,8 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 100,9 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana N Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada N Fachada O Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 LADS02 N S S REF. Or. MEXA02 MEXA02 MEXA02 CINV01 EXCEPTE PARETS Ventana N Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 4,5 2,4 2,4 0,89 0,89 0,89 1 1 1 Sup. (m²) N O S H REF. 9,4 22,7 6,4 38,8 Sup. (m²) LADS02 LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 4,5 2,4 2,4 23,7 1,9 38,8 Potència 15 Ocupantes 25 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Cabal Tsa 36,4 54,3 51,2 67,7 K Tac 2,73 2,73 2,73 1,98 2,13 0,69 31,6 31,6 31,6 25,0 28,8 25,0 Ud. 78,0 38,8 432,0 m³/h Ventilación K 0,61 0,61 0,61 0,41 %Ús 15 25 Tec 432 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 388 798 798 G. Inst. (w) 4 23 19 154 G. Inst. (w) 81 43 43 0 15 0 G. Inst. (w) 1.170 970 G. Inst. (w) 949 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 235 436 436 1.162 Càrrega Refr. (w) 7 44 21 166 250 Càrrega Refr. (w) 57 30 30 0 11 0 135 Càrrega Refr. (w) 1.170 970 2.247 Càrrega Refr. (w) 949 949 4.744 w Potència 15 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 432,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 15 Xec 432 100 %Ús 11,6 100 G. Inst. (w) 690 G. Inst. (w) 122 Càrrega Refr. (w) 690 725 Càrrega Refr. (w) 122 122 847 w 5.591 w Factor de calor sensible de la zona (RSHF): 0,840 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 144 w/m² Pàgina 51 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA NOVES TECNOLOGIES Ts DESTINADA A Aulas (sin fumadores) DIMENSIONS 38,8 m² x 2,6 m REF. MEXA02 LADS02 MEXA02 MEXA02 LADS02 LADS02 CINV01 Supl. Sup. (m²) 1,175 1,175 1,075 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 LADS02 432,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 9,4 4,5 22,7 6,4 2,4 2,4 38,8 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: N N O S S S H Sup. (m²) N S S Pressió 33,4 26,7 26,7 0,61 4,30 0,61 0,61 4,30 4,30 0,43 K 23,7 1,9 38,8 Or. 21,0 Diferència 22,8 100,9 m³ TAB008 PIMP20 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana N Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada N Ventana N Fachada O Fachada S Ventana S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 1,98 2,13 0,66 Cabal Tac -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 Tac 21,0 9,3 21,0 Tac 14,9 6,9 6,9 Cabal -1,8 -1,8 -1,8 Tac 432 -1,8 Càrrega Calef. (w) 153 518 337 88 235 235 380 1.947 Càrrega Calef. (w) 0 47 0 47 Càrrega Calef. (w) 113 52 52 218 Càrrega Calef. (w) 3.278 3.278 0,0% 0,0% 1,000 5.490 w 141 w/m² Pàgina 52 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA LOCAL4 CONDICIONS Ts (°C) DESTINADA A Aulas (sin fumadores) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 26,2 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 68,1 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 S S REF. Or. MEXA02 CINV01 EXCEPTE PARETS Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,3 2,4 0,89 0,89 1 1 Sup. (m²) S H REF. 6,6 26,2 Sup. (m²) LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 2,3 2,4 40,4 2,1 26,2 Potència 20 Ocupantes 25 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 576,0 m³/h Ventilación Tsa 51,2 67,7 K Tac 2,73 2,73 1,98 2,13 0,69 31,6 31,6 25,0 28,8 25,0 Ud. 78,0 26,2 Cabal K 0,61 0,41 %Ús 20 25 Tec 576 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 765 798 G. Inst. (w) 20 104 G. Inst. (w) 41 43 0 17 0 G. Inst. (w) 1.560 655 G. Inst. (w) 1.265 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 418 436 897 Càrrega Refr. (w) 21 112 140 Càrrega Refr. (w) 29 30 0 13 0 76 Càrrega Refr. (w) 1.560 655 2.326 Càrrega Refr. (w) 1.265 1.265 4.704 w Potència 20 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 576,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 20 Xec 576 100 %Ús 11,6 100 G. Inst. (w) 920 G. Inst. (w) 163 Càrrega Refr. (w) 920 966 Càrrega Refr. (w) 163 163 1.129 w 5.832 w Factor de calor sensible de la zona (RSHF): 0,781 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 223 w/m² Pàgina 53 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA LOCAL4 Ts DESTINADA A Aulas (sin fumadores) DIMENSIONS 26,2 m² x 2,6 m REF. MEXA02 LADS02 LADS02 CINV01 Supl. Sup. (m²) 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 576,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 6,6 2,3 2,4 26,2 Sup. (m²) TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S S H S S Pressió Tac 0,61 4,30 4,30 0,43 K 40,4 2,1 26,2 Or. 21,0 Diferència 22,8 68,1 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 0,66 Cabal 26,7 26,7 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 Tac 6,6 6,9 Cabal -1,8 -1,8 Tac 576 -1,8 Càrrega Calef. (w) 91 225 235 256 808 Càrrega Calef. (w) 0 52 0 52 Càrrega Calef. (w) 50 52 102 Càrrega Calef. (w) 4.371 4.371 0,0% 0,0% 1,000 5.334 w 204 w/m² Pàgina 54 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA LOCAL3 CONDICIONS Ts (°C) DESTINADA A Aulas (sin fumadores) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 26,1 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 67,9 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 S S REF. Or. MEXA02 CINV01 EXCEPTE PARETS Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 2,4 0,89 0,89 1 1 Sup. (m²) S H REF. 6,2 26,1 Sup. (m²) LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 2,4 2,4 40,3 2,1 26,1 Potència 20 Ocupantes 25 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 576,0 m³/h Ventilación Tsa 51,2 67,7 K Tac 2,73 2,73 1,98 2,13 0,69 31,6 31,6 25,0 28,8 25,0 Ud. 78,0 26,1 Cabal K 0,61 0,41 %Ús 20 25 Tec 576 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 798 798 G. Inst. (w) 19 104 G. Inst. (w) 43 43 0 17 0 G. Inst. (w) 1.560 653 G. Inst. (w) 1.265 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 436 436 916 Càrrega Refr. (w) 20 111 138 Càrrega Refr. (w) 30 30 0 13 0 77 Càrrega Refr. (w) 1.560 652 2.323 Càrrega Refr. (w) 1.265 1.265 4.719 w Potència 20 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 576,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 20 Xec 576 100 %Ús 11,6 100 G. Inst. (w) 920 G. Inst. (w) 163 Càrrega Refr. (w) 920 966 Càrrega Refr. (w) 163 163 1.129 w 5.848 w Factor de calor sensible de la zona (RSHF): 0,781 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 224 w/m² Pàgina 55 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA LOCAL3 Ts DESTINADA A Aulas (sin fumadores) DIMENSIONS 26,1 m² x 2,6 m REF. MEXA02 LADS02 LADS02 CINV01 Supl. Sup. (m²) 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 576,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 6,2 2,4 2,4 26,1 Sup. (m²) TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S S H S S Pressió Tac 0,61 4,30 4,30 0,43 K 40,3 2,1 26,1 Or. 21,0 Diferència 22,8 67,9 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 0,66 Cabal 26,7 26,7 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 Tac 6,9 6,9 Cabal -1,8 -1,8 Tac 576 -1,8 Càrrega Calef. (w) 86 235 235 255 812 Càrrega Calef. (w) 0 52 0 52 Càrrega Calef. (w) 52 52 104 Càrrega Calef. (w) 4.371 4.371 0,0% 0,0% 1,000 5.339 w 205 w/m² Pàgina 56 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA LOCAL2 CONDICIONS Ts (°C) DESTINADA A Aulas (sin fumadores) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 24,9 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 64,7 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 S S REF. Or. MEXA02 CINV01 EXCEPTE PARETS Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 2,4 0,89 0,89 1 1 Sup. (m²) S H REF. 6,1 24,9 Sup. (m²) LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 2,4 2,4 39,6 2,3 24,9 Potència 20 Ocupantes 25 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 576,0 m³/h Ventilación Tsa 51,2 67,7 K Tac 2,73 2,73 1,98 2,13 0,69 31,6 31,6 25,0 28,8 25,0 Ud. 78,0 24,9 Cabal K 0,61 0,41 %Ús 20 25 Tec 576 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 798 798 G. Inst. (w) 18 99 G. Inst. (w) 43 43 0 19 0 G. Inst. (w) 1.560 623 G. Inst. (w) 1.265 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 436 436 916 Càrrega Refr. (w) 20 106 132 Càrrega Refr. (w) 30 30 0 14 0 78 Càrrega Refr. (w) 1.560 622 2.292 Càrrega Refr. (w) 1.265 1.265 4.684 w Potència 20 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 576,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 20 Xec 576 100 %Ús 11,6 100 G. Inst. (w) 920 G. Inst. (w) 163 Càrrega Refr. (w) 920 966 Càrrega Refr. (w) 163 163 1.129 w 5.812 w Factor de calor sensible de la zona (RSHF): 0,780 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 233 w/m² Pàgina 57 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA LOCAL2 Ts DESTINADA A Aulas (sin fumadores) DIMENSIONS 24,9 m² x 2,6 m REF. MEXA02 LADS02 LADS02 CINV01 Supl. Sup. (m²) 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 576,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 6,1 2,4 2,4 24,9 Sup. (m²) TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S S H S S Pressió Tac 0,61 4,30 4,30 0,43 K 39,6 2,3 24,9 Or. 21,0 Diferència 22,8 64,7 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 0,66 Cabal 26,7 26,7 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 Tac 6,9 6,9 Cabal -1,8 -1,8 Tac 576 -1,8 Càrrega Calef. (w) 84 235 235 244 798 Càrrega Calef. (w) 0 57 0 57 Càrrega Calef. (w) 52 52 104 Càrrega Calef. (w) 4.371 4.371 0,0% 0,0% 1,000 5.331 w 214 w/m² Pàgina 58 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA LOCAL1 CONDICIONS Ts (°C) DESTINADA A Aulas (sin fumadores) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 25,7 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 66,8 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 S S REF. Or. MEXA02 CINV01 EXCEPTE PARETS Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 2,4 0,89 0,89 1 1 Sup. (m²) S H REF. 6,1 25,7 Sup. (m²) LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 2,4 2,4 39,5 2,2 25,7 Potència 20 Ocupantes 25 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 576,0 m³/h Ventilación Tsa 51,2 67,7 K Tac 2,73 2,73 1,98 2,13 0,69 31,6 31,6 25,0 28,8 25,0 Ud. 78,0 25,7 Cabal K 0,61 0,41 %Ús 20 25 Tec 576 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 798 798 G. Inst. (w) 18 102 G. Inst. (w) 43 43 0 18 0 G. Inst. (w) 1.560 643 G. Inst. (w) 1.265 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 436 436 916 Càrrega Refr. (w) 20 110 136 Càrrega Refr. (w) 30 30 0 13 0 78 Càrrega Refr. (w) 1.560 642 2.313 Càrrega Refr. (w) 1.265 1.265 4.707 w Potència 20 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 576,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 20 Xec 576 100 %Ús 11,6 100 G. Inst. (w) 920 G. Inst. (w) 163 Càrrega Refr. (w) 920 966 Càrrega Refr. (w) 163 163 1.129 w 5.836 w Factor de calor sensible de la zona (RSHF): 0,781 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 227 w/m² Pàgina 59 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA LOCAL1 Ts DESTINADA A Aulas (sin fumadores) DIMENSIONS 25,7 m² x 2,6 m REF. MEXA02 LADS02 LADS02 CINV01 Supl. Sup. (m²) 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 576,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 6,1 2,4 2,4 25,7 Sup. (m²) TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S S H S S Pressió Tac 0,61 4,30 4,30 0,43 K 39,5 2,2 25,7 Or. 21,0 Diferència 22,8 66,8 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 0,66 Cabal 26,7 26,7 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 Tac 6,9 6,9 Cabal -1,8 -1,8 Tac 576 -1,8 Càrrega Calef. (w) 84 235 235 251 806 Càrrega Calef. (w) 0 55 0 55 Càrrega Calef. (w) 52 52 104 Càrrega Calef. (w) 4.371 4.371 0,0% 0,0% 1,000 5.336 w 208 w/m² Pàgina 60 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA RECEPCIÓ CONDICIONS Ts (°C) DESTINADA A Espera y recepción (salas) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 25,8 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 67,1 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 S S REF. Or. MEXA02 CINV01 EXCEPTE PARETS Ventana S Ventana S Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,4 2,4 0,89 0,89 1 1 Sup. (m²) S H REF. 6,4 25,8 Sup. (m²) LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 2,4 2,4 40,4 2,2 25,8 Potència 12 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 371,5 m³/h Ventilación Tsa 51,2 67,7 K Tac 2,73 2,73 1,98 2,13 0,69 31,6 31,6 25,0 28,8 25,0 Ud. 71,0 25,8 Cabal K 0,61 0,41 %Ús 12 15 Tec 372 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 798 798 G. Inst. (w) 19 103 G. Inst. (w) 43 43 0 18 0 G. Inst. (w) 852 387 G. Inst. (w) 816 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 436 436 916 Càrrega Refr. (w) 21 110 137 Càrrega Refr. (w) 30 30 0 13 0 78 Càrrega Refr. (w) 852 387 1.301 Càrrega Refr. (w) 816 816 3.248 w Potència 12 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 31,0 Cabal 371,5 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 12 Xec 372 100 %Ús 11,6 100 G. Inst. (w) 372 G. Inst. (w) 105 Càrrega Refr. (w) 372 391 Càrrega Refr. (w) 105 105 496 w 3.744 w Factor de calor sensible de la zona (RSHF): 0,862 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 145 w/m² Pàgina 61 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA RECEPCIÓ Ts DESTINADA A Espera y recepción (salas) DIMENSIONS 25,8 m² x 2,6 m REF. MEXA02 LADS02 LADS02 CINV01 Supl. Sup. (m²) 1,000 1,000 1,000 1,000 REF. LADS02 LADS02 371,5 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 6,4 2,4 2,4 25,8 Sup. (m²) TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: S S S H S S Pressió Tac 0,61 4,30 4,30 0,43 K 40,4 2,2 25,8 Or. 21,0 Diferència 22,8 67,1 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada S Ventana S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 0,66 Cabal 26,7 26,7 -1,8 -1,8 -1,8 -1,8 21,0 9,3 21,0 Tac 6,9 6,9 Cabal -1,8 -1,8 Tac 372 -1,8 Càrrega Calef. (w) 88 235 235 252 811 Càrrega Calef. (w) 0 55 0 55 Càrrega Calef. (w) 52 52 104 Càrrega Calef. (w) 2.819 2.819 0,0% 0,0% 1,000 3.790 w 147 w/m² Pàgina 62 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA DESPATX SALA D’ACTES CONDICIONS Ts (°C) DESTINADA A Oficinas Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 8,6 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 22,4 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) TRANSMISSIÓ PARETS I SOSTRE REF. Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA Or. CINV01 EXCEPTE PARETS Cerramiento interior 1 Puerta interior 1 Cerramiento interior 2 Forjado interior 1 I Sup. (m²) H REF. 8,6 Sup. (m²) TAB008 PIMP20 TAB008 FOREX1 CALOR SENSIBLE INTERN 22,4 2,1 6,8 8,6 Potència 2 Ocupantes 30 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ K Tsa 0,41 67,7 K Tac 1,98 2,13 1,98 0,69 25,0 25,0 28,8 28,8 Ud. 78,0 8,6 Cabal %Ús 2 30 Tec 72,0 m³/h Ventilación 72 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 34 G. Inst. (w) 0 0 51 23 G. Inst. (w) 156 258 G. Inst. (w) 158 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 37 39 Càrrega Refr. (w) 0 0 38 17 58 Càrrega Refr. (w) 156 258 435 Càrrega Refr. (w) 158 158 689 w Potència 2 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 72,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 2 Xec 72 100 %Ús 11,6 100 G. Inst. (w) 92 G. Inst. (w) 20 Càrrega Refr. (w) 92 97 Càrrega Refr. (w) 20 20 117 w 806 w Factor de calor sensible de la zona (RSHF): 0,846 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 94 w/m² Pàgina 63 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA DESPATX SALA D’ACTES Ts DESTINADA A Oficinas DIMENSIONS 8,6 m² x 2,6 m VOLUM REF. CINV01 TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Cerramiento interior 2 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA REF. TAB008 PIMP20 TAB008 FOREX1 VENTILACIÓ AIRE EXTERIOR 72,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració Or. H Supl. 1,000 Interior -1,8 21,0 Diferència 22,8 22,4 m³ Sup. (m²) K 8,6 Sup. (m²) Tac 0,43 K 22,4 2,1 6,8 8,6 -1,8 Tac 1,98 2,13 1,98 0,66 Cabal 21,0 21,0 9,3 9,3 Tac 72 -1,8 Càrrega Calef. (w) 84 84 Càrrega Calef. (w) 0 0 157 66 223 Càrrega Calef. (w) 546 546 0,0% 0,0% 1,000 CÀRREGA TOTAL DE CALEFACCIÓ 854 w Càrrega de calefacció per unitat de superfície: 99 w/m² Pàgina 64 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA VESTÍBUL CONDICIONS Ts (°C) DESTINADA A Vestíbulos Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 44,5 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 115,7 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana N Ventana N TRANSMISSIÓ PARETS I SOSTRE Fachada O Fachada N Fachada E Fachada N Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 N N REF. Or. MEXA02 MEXA02 MEXA02 MEXA02 CINV01 EXCEPTE PARETS Ventana N Ventana N Cerramiento interior 1 Puerta interior 1 Cerramiento interior 2 Cerramiento interior 3 Puerta interior 2 Puerta interior 3 Forjado interior 1 I Sup. (m²) SC Ud. 4,8 7,0 0,89 0,89 1 1 Sup. (m²) O N E N H REF. 11,2 4,2 11,0 6,0 44,5 Sup. (m²) LADS02 LADS02 TAB008 PIMP20 TAB008 TAB008 PIMP20 PIMP20 FOREX1 CALOR SENSIBLE INTERN 4,8 7,0 15,5 1,9 21,4 20,5 1,9 3,7 44,5 Potència 8 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ 925,6 m³/h Ventilación Tsa 54,3 36,4 36,4 36,4 67,7 K Tac 2,73 2,73 1,98 2,13 1,98 1,98 2,13 2,13 0,69 31,6 31,6 25,0 25,0 28,8 25,0 25,0 28,8 25,0 Ud. 89,0 44,5 Cabal K 0,61 0,61 0,61 0,61 0,41 %Ús 8 15 Tec 926 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 414 604 G. Inst. (w) 11 2 67 3 177 G. Inst. (w) 86 126 0 0 161 0 0 30 0 G. Inst. (w) 712 668 G. Inst. (w) 2.033 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 250 365 646 Càrrega Refr. (w) 22 3 60 5 190 293 Càrrega Refr. (w) 61 88 0 0 120 0 0 22 0 306 Càrrega Refr. (w) 712 667 1.448 Càrrega Refr. (w) 2.033 2.033 4.728 w Potència 8 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 121,0 Cabal 925,6 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 8 Xec 926 100 %Ús 11,6 100 G. Inst. (w) 968 G. Inst. (w) 262 Càrrega Refr. (w) 968 1.016 Càrrega Refr. (w) 262 262 1.278 w 6.006 w Factor de calor sensible de la zona (RSHF): 0,726 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 135 w/m² Pàgina 65 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA VESTÍBUL Ts DESTINADA A Vestíbulos DIMENSIONS 44,5 m² x 2,6 m REF. MEXA02 MEXA02 LADS02 MEXA02 MEXA02 LADS02 CINV01 Supl. Sup. (m²) 1,075 1,175 1,175 1,125 1,175 1,175 1,000 REF. LADS02 LADS02 925,6 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 11,2 4,2 4,8 11,0 6,0 7,0 44,5 REF. VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: O N N E N N H Sup. (m²) N N Pressió 33,4 33,4 0,61 0,61 4,30 0,61 0,61 4,30 0,43 K 15,5 1,9 21,4 20,5 1,9 3,7 44,5 Or. 21,0 Diferència 22,8 115,7 m³ TAB008 PIMP20 TAB008 TAB008 PIMP20 PIMP20 FOREX1 INFILTRACIÓ PORTES I FINESTRES Ventana N Ventana N Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Cerramiento interior 2 Cerramiento interior 3 Puerta interior 2 Puerta interior 3 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada O Fachada N Ventana N Fachada E Fachada N Ventana N Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 1,98 2,13 1,98 1,98 2,13 2,13 0,66 Cabal Tac -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 Tac 21,0 21,0 9,3 21,0 21,0 9,3 21,0 Tac 15,9 23,2 Cabal -1,8 -1,8 Tac 926 -1,8 Càrrega Calef. (w) 166 68 553 171 97 806 435 2.298 Càrrega Calef. (w) 0 0 495 0 0 92 0 587 Càrrega Calef. (w) 121 176 297 Càrrega Calef. (w) 7.024 7.024 0,0% 0,0% 1,000 10.206 w 229 w/m² Pàgina 66 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA BANY DONES CONDICIONS Ts (°C) Th (°C) DESTINADA A Aseos públicos vertedero,...) 31,6 21,3 DIMENSIONS 25,3 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 65,8 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) (por urinario, GUANY SOLAR VIDRE Ventana E Ventana E Ventana E TRANSMISSIÓ PARETS I SOSTRE Fachada E Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA inodoro, Exteriors REF. Or. LADS02 LADS02 LADS02 E E E REF. Or. MEXA02 CINV01 EXCEPTE PARETS Ventana E Ventana E Ventana E Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) SC Ud. 2,0 2,0 2,0 0,89 0,89 0,89 1 1 1 K Tsa 0,61 0,41 36,4 67,7 K Tac 2,73 2,73 2,73 1,98 2,13 0,69 31,6 31,6 31,6 25,0 25,0 25,0 Sup. (m²) E H REF. 12,3 25,3 Sup. (m²) LADS02 LADS02 LADS02 TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 2,0 2,0 2,0 38,0 1,9 25,3 Potència 4 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Ud. 89,0 25,3 Cabal 360,0 m³/h Ventilación %Ús 4 15 Tec 360 100 100 %Ús 31,6 100 G. Inst. (w) 172 172 172 G. Inst. (w) 75 101 G. Inst. (w) 36 36 36 0 0 0 G. Inst. (w) 356 380 G. Inst. (w) 791 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Xe (gr/kgr) 11,6 Càrrega Refr. (w) 294 294 294 925 Càrrega Refr. (w) 67 108 183 Càrrega Refr. (w) 25 25 25 0 0 0 80 Càrrega Refr. (w) 356 379 772 Càrrega Refr. (w) 791 791 2.751 w Potència 4 Ocupantes CALOR LATENT AIRE VENTILACIÓ Hr (%) 40,0 Ud. 121,0 Cabal 360,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 4 Xec 360 100 %Ús 11,6 100 G. Inst. (w) 484 G. Inst. (w) 102 Càrrega Refr. (w) 484 508 Càrrega Refr. (w) 102 102 610 w 3.361 w Factor de calor sensible de la zona (RSHF): 0,794 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 133 w/m² Pàgina 67 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA BANY DONES Ts DESTINADA A Aseos públicos (por urinario, inodoro, vertedero,...) DIMENSIONS 25,3 m² x 2,6 m REF. MEXA02 LADS02 LADS02 LADS02 CINV01 TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 E E E E H REF. Supl. Sup. (m²) 1,125 1,125 1,125 1,125 1,000 LADS02 LADS02 LADS02 360,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 12,3 2,0 2,0 2,0 25,3 Sup. (m²) E E E Pressió Tac 0,61 4,30 4,30 4,30 0,43 K 38,0 1,9 25,3 Or. 21,0 Diferència 22,8 65,8 m³ TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: Or. Interior -1,8 REF. INFILTRACIÓ PORTES I FINESTRES Ventana E Ventana E Ventana E Exterior (°C) VOLUM TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Ventana E Ventana E Ventana E Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Tac 1,98 2,13 0,66 Cabal 26,7 26,7 26,7 -1,8 -1,8 -1,8 -1,8 -1,8 21,0 21,0 21,0 Tac 5,7 5,7 5,7 Cabal -1,8 -1,8 -1,8 Tac 360 -1,8 Càrrega Calef. (w) 191 221 221 221 247 1.100 Càrrega Calef. (w) 0 0 0 0 Càrrega Calef. (w) 43 43 43 130 Càrrega Calef. (w) 2.732 2.732 0,0% 0,0% 1,000 3.963 w 157 w/m² Pàgina 68 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA BANY HOMES CONDICIONS Ts (°C) Th (°C) DESTINADA A Aseos públicos vertedero,...) 31,6 21,3 DIMENSIONS 21,1 m² x 2,6 m Interiors 25,0 19,0 56,9 11,3 VOLUM 54,9 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) (por urinario, TRANSMISSIÓ PARETS I SOSTRE REF. Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA inodoro, Exteriors Or. CINV01 EXCEPTE PARETS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 I Sup. (m²) H REF. 21,1 Sup. (m²) TAB008 PIMP20 FOREX1 CALOR SENSIBLE INTERN 61,4 2,0 21,1 Potència 4 Ocupantes 15 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Cabal Tsa 0,41 67,7 K Tac 1,98 2,13 0,69 25,0 25,0 25,0 Ud. 89,0 21,1 360,0 m³/h Ventilación K %Ús 4 15 Tec 360 100 100 %Ús 31,6 100 G. Inst. (w) 84 G. Inst. (w) Càrrega Refr. (w) 90 95 Càrrega Refr. (w) G. Inst. (w) 356 317 G. Inst. (w) 791 0 0 0 0 Càrrega Refr. (w) 356 316 706 Càrrega Refr. (w) 791 791 1.591 w Potència 4 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 0 0 0 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Hr (%) 40,0 Ud. 121,0 Cabal 360,0 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 4 Xec 360 100 %Ús 11,6 100 G. Inst. (w) 484 G. Inst. (w) 102 Càrrega Refr. (w) 484 508 Càrrega Refr. (w) 102 102 610 w 2.201 w Factor de calor sensible de la zona (RSHF): 0,612 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 104 w/m² Pàgina 69 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA BANY HOMES Ts DESTINADA A Aseos públicos (por urinario, inodoro, vertedero,...) DIMENSIONS 21,1 m² x 2,6 m REF. CINV01 TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Forjado interior 1 REF. TAB008 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR 360,0 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ Càrrega de calefacció per unitat de superfície: Exterior (°C) VOLUM TRANSMISSIÓ AMBIENT EXTERIOR Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA Or. H Supl. 1,000 Interior -1,8 21,0 Diferència 22,8 54,9 m³ Sup. (m²) K 21,1 Sup. (m²) 0,43 K 61,4 2,0 21,1 1,98 2,13 0,66 Cabal Tac -1,8 Tac 21,0 21,0 21,0 Tac 360 -1,8 Càrrega Calef. (w) 206 206 Càrrega Calef. (w) 0 0 0 0 Càrrega Calef. (w) 2.732 2.732 0,0% 0,0% 1,000 2.938 w 139 w/m² Pàgina 70 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA DATA CÀLCUL 14 Hora solar Agosto ZONA SALA D’ACTES CONDICIONS Ts (°C) DESTINADA A Aulas (sin fumadores) Exteriors 31,6 21,3 Hr (%) 40,0 DIMENSIONS 171,1 m² x 3,0 m Interiors 25,0 19,0 56,9 11,3 VOLUM 513,3 m³ Diferències 6,6 2,3 -17,0 0,3 (Máximas por Sistema) GUANY SOLAR VIDRE Ventana S Ventana O Ventana S TRANSMISSIÓ PARETS I SOSTRE Fachada E Fachada S Fachada O Fachada S Cubierta 1 TRANSMISSIÓ SOSTRE FULL DE CÀRREGUES PER A REFRIGERACIÓ DE ZONA REF. Or. LADS02 LADS02 LADS02 S O S REF. Or. MEXA02 MEXA02 MEXA02 MEXA02 CINV01 EXCEPTE PARETS Ventana S Ventana O Ventana S Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Forjado interior 1 I Sup. (m²) SC Ud. 9,0 5,1 4,8 0,89 0,89 0,89 1 1 1 Sup. (m²) E S O S H REF. 39,8 21,8 44,7 5,5 171,1 Sup. (m²) LADS02 LADS02 LADS02 TAB008 PIMP20 PIMP20 FOREX1 CALOR SENSIBLE INTERN 9,0 5,1 4,8 66,6 3,8 2,3 171,1 Potència 80 Ocupantes 25 w/m² Alumbrado AL-i/1w CALOR SENSIBLE AIRE VENTILACIÓ Cabal Tsa 36,4 51,2 54,3 51,2 67,7 K Tac 2,73 2,73 2,73 1,98 2,13 2,13 0,69 31,6 31,6 31,6 25,0 28,8 25,0 25,0 Ud. 78,0 171,1 2.566,5 m³/h Ventilación K 0,61 0,61 0,61 0,61 0,41 %Ús 80 25 Tec 2.567 100 100 %Ús 31,6 100 Th (°C) G. Inst. (w) 2.994 2.057 1.597 G. Inst. (w) 243 65 46 17 681 G. Inst. (w) 162 92 86 0 31 0 0 G. Inst. (w) 6.240 4.278 G. Inst. (w) 5.638 TOTAL CALOR SENSIBLE CALOR LATENT INTERN Càrrega Refr. (w) 1.636 803 872 3.477 Càrrega Refr. (w) 216 71 88 18 730 1.178 Càrrega Refr. (w) 114 64 61 0 23 0 0 275 Càrrega Refr. (w) 6.240 4.277 11.043 Càrrega Refr. (w) 5.638 5.638 21.611 w Potència 80 Ocupantes CALOR LATENT AIRE VENTILACIÓ Xe (gr/kgr) 11,6 Ud. 46,0 Cabal 2.566,5 m³/h Ventilación TOTAL CALOR LATENT CÀRREGA TOTAL DE REFRIGERACIÓ %Ús 80 Xec 2.567 100 %Ús 11,6 100 G. Inst. (w) 3.680 G. Inst. (w) 726 Càrrega Refr. (w) 3.680 3.864 Càrrega Refr. (w) 726 726 4.590 w 26.201 w Factor de calor sensible de la zona (RSHF): 0,805 Factor de seguretat (Aplicat als resultats parcials i al total): 5 % Càrrega de refrigeració per unitat de superfície: 153 w/m² Pàgina 71 de 72 EXPEDIENT 13B PROJECTE CENTRE CIVIC BELL-LLOC P1 DATA 31/01/08 SISTEMA PLANTA PRIMERA CONDICIONS DE CÀLCUL PER A HIVERN ZONA SALA D’ACTES Ts DESTINADA A Aulas (sin fumadores) DIMENSIONS 171,1 m² x 3,0 m REF. MEXA02 MEXA02 LADS02 MEXA02 LADS02 MEXA02 LADS02 CINV01 Supl. Sup. (m²) 1,125 1,000 1,000 1,075 1,075 1,000 1,000 1,000 REF. LADS02 LADS02 LADS02 2.566,5 m³/h Ventilación SUPLEMENTS Per intermitència (Funcionamiento ininterrumpido) Altres suplements Coeficient total de majoració CÀRREGA TOTAL DE CALEFACCIÓ K 39,8 21,8 9,0 44,7 5,1 5,5 4,8 171,1 Sup. (m²) TAB008 PIMP20 PIMP20 FOREX1 VENTILACIÓ AIRE EXTERIOR Càrrega de calefacció per unitat de superfície: E S S O O S S H S O S Pressió 26,7 33,4 26,7 0,61 0,61 4,30 0,61 4,30 0,61 4,30 0,43 K 66,6 3,8 2,3 171,1 Or. 21,0 Diferència 22,8 513,3 m³ REF. INFILTRACIÓ PORTES I FINESTRES Ventana S Ventana O Ventana S Or. Interior -1,8 VOLUM TRANSMISSIÓ AMB ALTRES LOCALS Cerramiento interior 1 Puerta interior 1 Puerta interior 2 Forjado interior 1 Exterior (°C) TRANSMISSIÓ AMBIENT EXTERIOR Fachada E Fachada S Ventana S Fachada O Ventana O Fachada S Ventana S Cubierta 1 FULL DE CÀRREGUES PER A CALEFACCIÓ DE ZONA 1,98 2,13 2,13 0,66 Cabal 25,7 16,9 13,7 Cabal 2.567 Tac -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 -1,8 Tac 21,0 9,3 21,0 21,0 Tac -1,8 -1,8 -1,8 Tac -1,8 Càrrega Calef. (w) 619 301 882 664 538 76 471 1.674 5.224 Càrrega Calef. (w) 0 94 0 0 94 Càrrega Calef. (w) 195 128 104 428 Càrrega Calef. (w) 19.477 19.477 0,0% 0,0% 1,000 25.223 w 147 w/m² Pàgina 72 de 72 PROJECTE DE CLIMATITZACIÓ PER AIGUA 1.- MEMÒRIA DE CÀLCUL 1.1.- SELECCIÓ DE LA POTÈNCIA DEL GENERADOR La potència del generador es determina segons la fórmula: P = (P + Pt )· f i On: P = Potència del generador en watts. P = Potència calorífica necessària en watts. Pt = Pèrdues de calor per les canonades en watts. fi = Augment per inèrcia. Així, la potència total necessària en el generador és de: P = ( 188.700 + 7.572 ) · 1,00 = 196.272 w Per tant, es selecciona la caldera de biomassa FROLING TURBOMAT 220 amb una potència nominal de 220 kW. 1.1.2.- CÀLCUL DE LA BOMBA DE CIRCULACIÓ El cabal que ha de subministrar la bomba de circulació ve donat per l'expressió: Q= 860·Pe 1000·Δt ·C e ·γ On: Ce = Calor específic de l'aigua = 1,0 Kcal/h·Kg·°C γ = Pes específic de l'aigua = 1,0 Kg/dm3 Δt = Salt tèrmic en °C Pe = Potència instal·lada en els emissors en watts Amb el que s'obté un cabal de: Q = (0,86 · 274.960) / 10,0 = 23.646,6 litres/hora Per al càlcul de les pèrdues de càrrega en les canonades s’ha tingut en compte la fórmula de Prandtl-Colebrook i es limita la pèrdua de càrrega por unitat de longitut de canonada a 40,0 mm.c.a./m . La pèrdua de càrrega en el generador i en els radiadors es calcula amb l'equació: J= ε ·v 2 ·γ 2· g On: J = Pèrdua de pressió en mmca. ε = Coeficient de resistència. v = Velocitat en m/s. γ = Pes específic en kg/m³. Pàgina 1 de 8 g = Acceleració de la gravetat en m/s². Usant un coeficient de resistència ε = 2,5 per al generador i de ε = 3,0 per als radiadors. Les pèrdues de càrrega en les claus i en els plafons es calculen per mitjà dels gràfics del fabricant. La pèrdua més gran de càrrega es produeix en el circuit de l'emissor Fan-coil biblioteca2 [167140] i és igual a 3,012 mca. La caiguda de pressió en aquest emissor és de 4,000 mca. i la pèrdua en el generador arriba a 0,318 mca. Així la pressió total del circulador haurà de ser: H = 3,012 + 4,000 + 0,318 = 7,330 mca. Per tant el punt de funcionament de la bomba de circulació ha d'estar entorn a: Cabal= 23,647 m³/h Pressió= 7,330 mca. 1.1.3.- CÀLCUL DEL DIPÒSIT D'EXPANSIÓ TANCAT Aquest procediment de càlcul es basa en la normativa UNE-100-155-88: Càlcul de dipòsits d’expansió. El volum o capacitat útil que ha de tenir el dipòsit ha de ser almenys de: Vu = V · α On: Vu = Volum o capacitat útil del dipòsit en litres. V = Volum d'aigua total de la instal·lació en litres. α = Coeficient de dilatació de l'aigua en %. El volum total d'aigua en la instal·lació és la suma del volum el generador i emissors més la capacitat de les canonades: V.Total = V.Generador + V.Emissors + V.Canonades V.Total = 570,0 + 37,4 + 525,6 = 1.133,1 litres. Prenent un factor de seguretat del 10% s'obté un volum total de: V = 1.133,1 x 1,1 = 1.246,4 litres. Per a una temperatura mitja de 70,0 °C i un percentatge de glicol etilenic de 0% es té un increment de volum del 2,227%. Per tant el volum útil del dipòsit ha de ser de: Vu = 1.246,4 · 2,227 / 100 = 27,8 litres. El coeficient d' pressió del gas relaciona la pressió màxima de treball (PM) i la pressió d'ompliment de gas (Pm), les dues com a pressions absolutes: Cp = PM / (PM - Pm) Pàgina 2 de 8 Donat que l'altura de la instal·lació sobre el dipòsit és de 6,0 m., la pressió d'ompliment de la càmara de gas serà: Pm = 1,01325 · 6,0 / 10 = 0,6 bar. Com a mínim es pren una pressió d'ompliment de ,5 bar. D´altra banda escollint una pressió màxima de treball PM = 3,0 bar. s'obté: Cp = (3,0 + 1,01325)/(3,0 - 0,6) = 1,678 Per tant la capacitat total del dipòsit ha de ser: Vv = Vu / Cu = 27,8 / 1,678 = 46,6 litres Es tria un dipòsit d'expansió tancat amb els següents característiques: Capacitat total= 50,0 litres Pressió màxima de treball= 3,0 bar. Pressió d'ompliment= 0,6 bar. Pressió de tarat de la vàlvula de seguretat 3,0 bar. 1.1.4.- MÈTODE DE CÀLCUL PER A CANONADES El principi de càlcul és el següent: 1- Determinació del cabal de cadascun dels trams, de la fi a l’origen, en funció dels emissors als que alimenta: Q= 860·Pe 1000·Δt ·C e ·γ On: Ce = Calor específica de l’ aigua = 1,0 Kcal/h·Kg·°C γ = Pes específic de l’ aigua = 1,0 Kg/dm³ Δt = Salt tèrmic en °C Pe = Potència instal·lada en els emissors en watts Es té en compte els següents modes de funcionament: - Calefacció salt tèrmic 10,0°C i potències individuals màximes. 2- Per al càlcul de les pèrdues de càrrega a les canonades s’ha tingut en compte la fórmula de Prandtl-Colebrook. V = −2 ⋅ 2·g ·D·J ·log10 ( ka 2'51·ν + ) 3'71·D D· 2· g ·D· J On: J D V Qr ka ν g = = = = = = = Pèrdues de càrrega, en m.c.a./m; Diàmetre interior de canonades, en m; Velocitat mitja del aigua, en m/s; Cabal en m³/s; Rugositat uniforme equivalent, en m.; Viscositat cinemàtica del fluid, (1’31x10-6 m²/s per aigua a 10°C); Acceleració de la gravetat, 9’8 m/s²; Pàgina 3 de 8 3- Determinació dels diàmetres de canonada en base a admetre una pèrdua de càrrega màxima per unitat de longitud de canonada igual a 40,0 mm.c.a./m . 4- Es tenen en compte les longituds equivalents a canonada recta del mateix diàmetre als accessoris (tes, colzes...) i vàlvules connectades entre canonades per a calcular les pèrdues de càrrega que produeixen. 5- Càlcul de la pèrdua de càrrega a provocar a cadascuna de les vàlvules per a obtenir la distribució de cabals suposada inicial. 1.2.- MEMÒRIA DE CÀLCUL DEL CIRCUIT TANCAT DE CANONADES El circuit tancat mes desfavorable correspon al que va des del generador CALDERA BIOMASA [163] fins a l’emissor Fan-coil biblioteca2 [167-140]. Tot seguit es desglossen les pèrdues de càrrega a cadascun dels elements als trams d’anada i tornada: TRAMO N1-N2 N2-N3 Cabal aigua (l/h) Velc. (m/s) 23.647 11.595 1,28 0,86 Ø Nominal (mm) ó (pulgadas) 3" 2 1/2" 2 1/2" N3-N4 10.341 1,30 2 1/2" 2" 2" ΔP Unitari (mmca) Longitut (m) 19,5 11,2 5,2 1,7 11,2 11,2 33,9 33,9 3,0 5,7 2,7 2,0 N4-N5 9.549 1,20 2" 2" 33,9 29,0 1,6 4,2 N5-N6 8.758 1,10 2" 24,6 4,5 N6-N7 N7-N8 N8-N9 N9-N10 7.967 7.176 6.385 5.130 1,00 0,90 0,80 1,03 2" 2" 2" 1 1/2" 1 1/2" N10-N11 3.036 0,83 1 1/2" 1 1/4" 1 1/4" N11-N12 3.036 2,97 N12-N13 3.036 0,83 20,5 16,8 13,4 29,4 29,4 29,4 23,3 23,3 3,9 4,4 8,1 1,1 8,4 0,6 1,1 0,8 1 1/4" 23,3 0,3 1 1/4" 23,5 0,2 1 1/4" 1 1/4" 23,5 23,5 0,5 1,1 Tipo de accessori Tubería Tubería Te divergencia Codo Tubería Codo Tubería Tubería Te división Codo Tubería Codo Tubería Tubería Te división Tubería Te división Tubería Te división Tubería Te división Tubería Te división Tubería Te división Codo Tubería Codo Tubería Tubería Te división Codo Tubería Codo Tubería Fan-coil biblioteca2 [167140] Tubería Codo Tubería Codo Tubería Te unión Longitut equivalent accessori (1) (m) ó Kv Longitut total (m) ΔP Total (mca) 5,15 4,76 0,101 0,053 3,63 0,041 5,71 3,64 0,064 0,123 2,60 0,088 1,58 4,57 0,053 0,133 4,83 0,119 4,23 0,087 4,73 0,079 8,41 0,113 2,06 0,060 9,00 0,264 0,65 3,02 0,019 0,070 1,45 0,034 0,32 0,008 4,000 0,80 0,019 1,12 0,026 1,94 0,046 2,40 0,63 0,63 0,32 0,63 0,63 0,32 0,32 0,32 0,32 0,32 0,32 0,63 0,63 1,25 0,63 0,63 0,62 0,63 0,80 Pàgina 4 de 8 N13-N14 5.130 1,03 1 1/2" 1 1/2" 1 1/2" N14-N15 N15-N16 N16-N17 N17-N18 N18-N19 N19-N20 6.385 7.176 7.967 8.758 9.549 10.341 0,80 0,90 1,00 1,10 1,20 1,30 2" 2" 2" 2" 2" 2" 2" 2" N20-N21 11.595 0,86 2 1/2" 2 1/2" 2 1/2" N21-N22 N22-N23 23.647 23.647 1,28 3" 29,6 29,6 29,6 13,6 16,9 20,7 24,8 29,3 34,1 34,1 34,1 11,3 11,3 11,3 19,7 0,4 8,4 1,0 8,5 4,4 3,9 4,5 4,2 1,3 2,0 3,0 5,4 3,0 1,9 4,9 Tubería Codo Tubería Codo Tubería Te unión Tubería Te unión Tubería Te unión Tubería Te unión Tubería Te unión Tubería Te unión Tubería Codo Tubería Codo Tubería Te unión Tubería Codo Tubería Codo Tubería Te confluencia Tubería CALDERA BIOMASA [1-63] 1,00 0,030 9,02 0,267 1,39 0,041 8,92 0,121 4,81 0,081 4,33 0,090 4,88 0,121 4,64 0,136 1,88 0,064 2,60 0,089 3,42 0,117 5,98 0,068 3,63 0,041 4,31 0,049 4,92 0,097 0,318 0,63 0,63 0,40 0,40 0,40 0,40 0,40 0,40 0,63 0,63 0,40 0,63 0,63 2,40 TOTAL (1) Kv: Constante válvulas de control. 7,330 1.3.- RELACIÓ DE BATERÍES Unitat Potència (w) 14.590 Temp. Entrada (°C) 75,0 Temp. Sortida (°C) 65,0 Cabal aigua (l/h) 1.254,7 Fan-coil Gimnàs [144-67] Fan-coil Despatx gestió [145-70] Fan-coil Sala d'estar [146-73] Fan-coil Menjador1 [147-76] Fan-coil Menjador2 [148-79] Fan-coil Bar [149-82] Fan-coil Vestíbul [150-85] Fan-coil Sala d'espera1 [151-105] Fan-coil Servei social [152-108] Fan-coil Podòleg [153-110] Fan-coil Sala d'espera2 [154-90] Fan-coil Consulta metge1 [155-92] Fan-coil Cures [15696] Fan-coil Infermeria [157-98] Caiguda Pressió Marca y model pressió d’equilibrat (mm.c.a.) (mm.c.a.) 1.580,0 4.938,8 GENERAL VOE 73 4.560 75,0 65,0 392,2 1.048,0 4.974,1 GENERAL FME 09 14.590 75,0 65,0 1.254,7 1.580,0 4.117,0 GENERAL VOE 73 14.590 75,0 65,0 1.254,7 1.580,0 3.793,1 GENERAL VOE 73 14.590 75,0 65,0 1.254,7 1.580,0 3.653,0 GENERAL VOE 73 14.590 14.590 75,0 75,0 65,0 65,0 1.254,7 1.254,7 1.580,0 1.580,0 3.448,8 3.209,9 GENERAL VOE 73 GENERAL VPE 73 6.080 75,0 65,0 522,9 1.662,0 2.892,5 GENERAL FME 12 4.560 75,0 65,0 392,2 1.048,0 3.200,4 GENERAL FME 09 4.560 75,0 65,0 392,2 1.048,0 2.958,0 GENERAL FME 09 14.590 75,0 65,0 1.254,7 1.580,0 2.721,8 GENERAL VOE 73 4.560 75,0 65,0 392,2 1.048,0 3.154,9 GENERAL FME 09 4.560 75,0 65,0 392,2 1.048,0 2.952,6 GENERAL FME 09 4.560 75,0 65,0 392,2 1.048,0 2.795,8 GENERAL FME 09 Pàgina 5 de 8 Fan-coil Consulta metge2 [158-101] Fan-coil noves tecnologies [159-115] Fan-coil local4 [160120] Fan-coil local3 [161123] Fan-coil local2 [162126] Fan-coil local1 [163129] Fan-coil recepció [164-132] Fan-coil vestíbul [165-134] Fan-coil biblioteca1 [166-143] Fan-coil biblioteca2 [167-140] 4.560 75,0 65,0 392,2 1.048,0 2.553,5 GENERAL FME 09 14.590 75,0 65,0 1.254,7 1.580,0 4.833,1 GENERAL VOE 73 9.200 75,0 65,0 791,2 2.531,0 3.289,8 GENERAL FME 18 9.200 75,0 65,0 791,2 2.531,0 3.019,3 GENERAL FME 18 9.200 75,0 65,0 791,2 2.531,0 2.777,3 GENERAL FME 18 9.200 75,0 65,0 791,2 2.531,0 2.610,3 GENERAL FME 18 9.200 75,0 65,0 791,2 2.531,0 2.443,8 GENERAL FME 18 14.590 75,0 65,0 1.254,7 1.580,0 3.243,5 GENERAL VPE 73 24.350 75,0 65,0 2.094,1 2.800,0 826,4 CIATESA KCN-35 35.300 75,0 65,0 3.035,8 4.000,0 0,0 CIATESA KCN-50 1.4.- RELACIÓ DE CANONADES Descripció Tramo [1-2] Tramo [63-64] Tramo [77-78] Tramo [80-81] Tramo [80-83] Tramo [83-84] Tramo [83-86] Tramo [95-97] Tramo [97-99] Tramo [86-102] Tramo [64-65] Tramo [65-66] Tramo [66-67] Tramo [65-68] Tramo [68-69] Tramo [69-70] Tramo [68-71] Tramo [71-72] Tramo [72-73] Tramo [71-74] Tramo [74-75] Tramo [75-76] Tramo [74-77] Tramo [78-79] Tramo [77-80] Tramo [81-82] Tramo [84-85] Tramo [86-87] Tramo [87-88] Tramo [88-89] Tramo [89-90] Tramo [89-91] Tramo [91-92] Tramo [91-93] Tramo [93-94] Tramo [94-95] Tramo [95-96] Tramo [97-98] Tramo [99-100] Tramo [100-101] Tramo [102-103] Diàmetre 3" 3" 1" 1" 1 1/2" 1" 1 1/2" 3/4" 1/2" 1" 2 1/2" 1" 1" 2" 1/2" 1/2" 2" 1" 1" 2" 1" 1" 2" 1" 2" 1" 1" 1 1/4" 1 1/4" 1 1/4" 1" 1" 1/2" 1" 1" 1" 1/2" 1/2" 1/2" 1/2" 1" Long. (m) 5,2 4,9 0,3 2,9 5,0 0,5 0,3 3,0 3,6 5,5 5,0 1,0 0,1 5,9 0,4 0,2 5,1 0,4 0,3 5,8 0,3 0,2 3,0 0,2 3,6 0,1 0,1 7,9 1,5 0,7 1,2 0,8 0,7 2,3 1,5 0,8 0,8 0,8 1,0 0,1 0,4 Leqv. (m) 0,0 0,0 0,8 0,8 0,4 0,8 0,4 0,4 0,4 0,4 2,4 0,8 0,6 0,4 0,8 0,6 0,4 0,8 0,6 0,4 0,8 0,6 0,4 0,6 0,4 0,6 0,7 0,8 0,0 0,0 0,8 0,4 0,8 0,4 0,6 0,6 0,8 0,8 0,6 0,7 0,6 Cabal (l/h) 23.646,6 23.646,6 1.254,7 1.254,7 5.385,3 1.254,7 4.130,6 784,3 392,2 1.307,2 12.051,2 1.254,7 1.254,7 10.796,4 392,2 392,2 10.404,3 1.254,7 1.254,7 9.149,5 1.254,7 1.254,7 7.894,8 1.254,7 6.640,1 1.254,7 1.254,7 2.823,4 2.823,4 2.823,4 1.254,7 1.568,6 392,2 1.176,5 1.176,5 1.176,5 392,2 392,2 392,2 392,2 1.307,2 Velc. (m/s) 1,28 1,28 0,60 0,60 1,08 0,60 0,83 0,59 0,54 0,62 0,90 0,60 0,60 1,35 0,54 0,54 1,31 0,60 0,60 1,15 0,60 0,60 0,99 0,60 0,83 0,60 0,60 0,77 0,77 0,77 0,60 0,74 0,54 0,56 0,56 0,56 0,54 0,54 0,54 0,54 0,62 P.Tot. (mmca) 100,7 97,0 20,1 66,7 174,2 23,6 14,0 80,6 114,6 114,0 90,3 32,2 12,8 232,9 35,6 22,5 190,7 21,6 15,4 166,9 19,9 14,1 69,8 15,2 57,9 13,5 13,9 179,2 29,9 13,6 35,1 33,9 42,5 42,4 34,3 22,7 45,2 44,7 47,9 22,7 20,2 P.Unit. (mmca/m) 19,5 19,7 17,9 17,9 32,5 17,9 19,6 23,4 28,7 19,3 12,2 17,9 17,9 37,1 28,7 28,7 34,5 17,9 17,9 27,0 17,9 17,9 20,3 17,9 14,6 17,9 17,9 20,5 20,5 20,5 17,9 27,2 28,7 15,8 15,8 15,8 28,7 28,7 28,7 28,7 19,3 Pàgina 6 de 8 Tramo [103-104] Tramo [104-105] Tramo [103-106] Tramo [106-107] Tramo [107-108] Tramo [107-109] Tramo [109-110] Tramo [2-3] Tramo [3-4] Tramo [4-144] Tramo [3-5] Tramo [5-6] Tramo [6-145] Tramo [5-7] Tramo [7-8] Tramo [8-146] Tramo [7-9] Tramo [9-10] Tramo [10-147] Tramo [9-11] Tramo [11-12] Tramo [12-148] Tramo [11-13] Tramo [13-14] Tramo [14-149] Tramo [13-15] Tramo [15-16] Tramo [16-150] Tramo [17-18] Tramo [18-19] Tramo [18-24] Tramo [24-151] Tramo [19-20] Tramo [20-21] Tramo [21-22] Tramo [22-153] Tramo [20-23] Tramo [23-152] Tramo [15-17] Tramo [17-25] Tramo [25-26] Tramo [26-27] Tramo [27-154] Tramo [27-28] Tramo [28-29] Tramo [29-155] Tramo [28-30] Tramo [30-31] Tramo [31-32] Tramo [32-33] Tramo [33-156] Tramo [32-34] Tramo [34-35] Tramo [35-157] Tramo [34-36] Tramo [36-37] Tramo [37-158] Tramo [2-38] Tramo [39-40] Tramo [40-62] Tramo [43-45] Tramo [51-53] Tramo [38-39] Tramo [64-111] Tramo [133-134] Tramo [133-135] 3/4" 3/4" 3/4" 3/4" 1/2" 1/2" 1/2" 2 1/2" 1" 1" 2" 1/2" 1/2" 2" 1" 1" 2" 1" 1" 2" 1" 1" 2" 1" 1" 1 1/2" 1" 1" 1" 3/4" 3/4" 3/4" 3/4" 1/2" 1/2" 1/2" 1/2" 1/2" 1 1/2" 1 1/4" 1 1/4" 1 1/4" 1" 1" 1/2" 1/2" 1" 1" 1" 1/2" 1/2" 3/4" 1/2" 1/2" 1/2" 1/2" 1/2" 2 1/2" 2 1/2" 1" 2" 2" 2 1/2" 2 1/2" 1" 1 1/2" 0,6 0,3 1,3 1,9 0,8 4,2 0,8 5,6 1,5 0,3 5,9 0,9 0,3 5,1 0,9 0,4 5,8 0,7 0,3 3,0 0,8 0,4 3,6 3,4 0,3 4,6 0,5 0,2 5,2 1,7 1,0 0,1 1,9 4,3 0,9 0,2 0,8 0,2 0,6 8,2 1,5 0,8 1,3 0,5 0,7 0,2 2,3 1,6 0,8 0,8 0,2 3,1 0,8 0,1 3,5 1,1 0,3 1,7 5,7 0,5 4,2 8,1 3,0 1,9 0,1 1,0 0,8 0,7 0,4 0,6 0,8 0,4 0,6 2,4 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 0,3 1,9 1,0 0,0 0,0 1,0 0,6 0,0 1,9 0,0 0,3 1,3 0,0 0,0 1,3 0,3 1,9 0,0 1,0 0,6 0,0 1,9 0,0 0,3 1,9 0,0 1,0 0,6 0,0 3,0 0,0 1,9 0,3 0,3 0,6 2,4 0,8 0,4 522,9 522,9 784,3 784,3 392,2 392,2 392,2 12.051,2 1.254,7 1.254,7 10.796,4 392,2 392,2 10.404,3 1.254,7 1.254,7 9.149,5 1.254,7 1.254,7 7.894,8 1.254,7 1.254,7 6.640,1 1.254,7 1.254,7 5.385,3 1.254,7 1.254,7 1.307,2 784,3 522,9 522,9 784,3 392,2 392,2 392,2 392,2 392,2 4.130,6 2.823,4 2.823,4 2.823,4 1.254,7 1.568,6 392,2 392,2 1.176,5 1.176,5 1.176,5 392,2 392,2 784,3 392,2 392,2 392,2 392,2 392,2 11.595,4 11.595,4 1.254,7 9.549,4 6.384,6 11.595,4 11.595,4 1.254,7 5.129,9 0,39 0,39 0,59 0,59 0,54 0,54 0,54 0,90 0,60 0,60 1,35 0,54 0,54 1,31 0,60 0,60 1,15 0,60 0,60 0,99 0,60 0,60 0,83 0,60 0,60 1,08 0,60 0,60 0,62 0,59 0,39 0,39 0,59 0,54 0,54 0,54 0,54 0,54 0,83 0,77 0,77 0,77 0,60 0,74 0,54 0,54 0,56 0,56 0,56 0,54 0,54 0,59 0,54 0,54 0,54 0,54 0,54 0,86 0,86 0,60 1,20 0,80 0,86 0,86 0,60 1,03 15,5 10,4 39,5 60,0 47,2 133,4 42,4 96,2 59,2 5,0 228,1 78,0 8,9 186,8 48,2 7,4 163,4 46,4 5,7 67,7 46,5 6,8 56,4 92,6 5,7 159,4 42,6 3,9 105,1 82,1 21,3 1,0 44,0 147,3 42,6 5,6 76,2 5,3 17,8 191,8 29,9 15,7 45,0 22,6 74,6 5,4 50,4 34,1 13,1 76,7 6,0 78,2 77,8 3,3 127,1 48,2 7,7 53,4 64,1 41,0 132,6 112,9 40,7 48,8 15,2 41,1 11,0 11,0 23,4 23,4 28,7 28,7 28,7 12,1 17,6 17,6 36,8 28,3 28,3 34,3 17,6 17,6 26,7 17,6 17,6 20,1 17,6 17,6 14,5 17,6 17,6 32,2 17,6 17,6 19,1 23,1 10,8 10,8 23,1 28,3 28,3 28,3 28,3 28,3 19,4 20,3 20,3 20,3 17,6 26,9 28,3 28,3 15,6 15,6 15,6 28,3 28,3 23,1 28,3 28,3 28,3 28,3 28,3 11,2 11,2 17,6 29,0 13,4 11,2 11,3 17,9 29,6 Pàgina 7 de 8 Tramo [111-112] Tramo [112-113] Tramo [113-114] Tramo [114-115] Tramo [113-116] Tramo [116-117] Tramo [117-118] Tramo [118-119] Tramo [119-120] Tramo [118-121] Tramo [121-122] Tramo [122-123] Tramo [121-124] Tramo [124-125] Tramo [125-126] Tramo [124-127] Tramo [127-128] Tramo [128-129] Tramo [127-130] Tramo [130-131] Tramo [131-132] Tramo [130-133] Tramo [135-136] Tramo [136-137] Tramo [137-138] Tramo [138-139] Tramo [139-140] Tramo [137-141] Tramo [141-142] Tramo [142-143] Tramo [40-41] Tramo [62-159] Tramo [41-42] Tramo [42-43] Tramo [43-44] Tramo [44-160] Tramo [45-46] Tramo [46-161] Tramo [45-47] Tramo [47-48] Tramo [48-162] Tramo [47-49] Tramo [49-50] Tramo [50-163] Tramo [49-51] Tramo [51-52] Tramo [52-164] Tramo [53-54] Tramo [54-165] Tramo [53-55] Tramo [55-56] Tramo [56-57] Tramo [57-58] Tramo [58-59] Tramo [59-167] Tramo [57-60] Tramo [60-61] Tramo [61-166] 2 1/2" 2 1/2" 1" 1" 2" 2" 2" 3/4" 3/4" 2" 3/4" 3/4" 2" 3/4" 3/4" 2" 3/4" 3/4" 2" 3/4" 3/4" 2" 1 1/2" 1 1/2" 1 1/4" 1 1/4" 1 1/4" 1" 1" 1" 2" 1" 2" 2" 3/4" 3/4" 3/4" 3/4" 2" 3/4" 3/4" 2" 3/4" 3/4" 2" 3/4" 3/4" 1" 1" 1 1/2" 1 1/2" 1 1/2" 1 1/4" 1 1/4" 1 1/4" 1" 1" 1" 3,0 5,4 0,4 0,3 3,0 2,0 1,3 1,0 0,3 4,2 1,0 0,3 4,5 1,0 0,4 3,9 1,0 0,2 4,4 1,0 0,3 8,5 8,4 0,4 1,1 0,5 0,2 3,2 0,9 0,3 2,7 0,4 2,0 1,6 1,0 0,5 1,0 0,5 4,5 1,0 0,6 3,9 1,0 0,3 4,4 1,0 0,5 0,4 0,3 1,1 8,4 0,6 1,1 0,8 0,3 3,2 0,9 0,4 0,6 0,6 0,8 0,6 0,4 0,6 0,6 0,8 0,6 0,4 0,8 0,6 0,4 0,8 0,6 0,4 0,8 0,6 0,4 0,8 0,6 0,4 0,6 0,6 0,8 0,6 0,6 0,4 0,6 0,6 1,0 0,0 0,6 0,0 1,9 0,0 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 0,3 1,9 0,0 1,9 0,0 1,0 0,6 0,0 1,9 0,6 0,0 1,0 0,6 0,0 11.595,4 11.595,4 1.254,7 1.254,7 10.340,6 10.340,6 10.340,6 791,2 791,2 9.549,4 791,2 791,2 8.758,2 791,2 791,2 7.967,0 791,2 791,2 7.175,8 791,2 791,2 6.384,6 5.129,9 5.129,9 3.035,8 3.035,8 3.035,8 2.094,1 2.094,1 2.094,1 10.340,6 1.254,7 10.340,6 10.340,6 791,2 791,2 791,2 791,2 8.758,2 791,2 791,2 7.967,0 791,2 791,2 7.175,8 791,2 791,2 1.254,7 1.254,7 5.129,9 5.129,9 5.129,9 3.035,8 3.035,8 3.035,8 2.094,1 2.094,1 2.094,1 0,86 0,86 0,60 0,60 1,30 1,30 1,30 0,59 0,59 1,20 0,59 0,59 1,10 0,59 0,59 1,00 0,59 0,59 0,90 0,59 0,59 0,80 1,03 1,03 0,83 0,83 0,83 0,99 0,99 0,99 1,30 0,60 1,30 1,30 0,59 0,59 0,59 0,59 1,10 0,59 0,59 1,00 0,59 0,59 0,90 0,59 0,59 0,60 0,60 1,03 1,03 1,03 0,83 0,83 0,83 0,99 0,99 0,99 41,2 67,8 21,7 15,6 116,7 88,9 64,3 42,3 23,2 135,8 41,9 23,2 121,1 42,1 24,3 89,6 42,1 19,6 81,4 42,1 22,8 120,9 267,3 29,6 45,6 26,4 18,9 170,7 71,9 44,9 123,2 6,9 88,1 53,4 66,6 10,8 68,4 11,5 118,8 67,7 13,0 86,8 68,1 7,9 79,4 67,4 11,2 40,9 4,8 60,4 264,4 19,1 70,3 33,8 7,5 194,4 73,4 20,9 11,3 11,3 17,9 17,9 34,1 34,1 34,1 23,8 23,8 29,3 23,8 23,8 24,8 23,8 23,8 20,7 23,8 23,8 16,9 23,8 23,8 13,6 29,6 29,6 23,5 23,5 23,5 47,1 47,1 47,1 33,9 17,6 33,9 33,9 23,5 23,5 23,5 23,5 24,6 23,5 23,5 20,5 23,5 23,5 16,8 23,5 23,5 17,6 17,6 29,4 29,4 29,4 23,3 23,3 23,3 46,7 46,7 46,7 Pàgina 8 de 8 ANNEX. INSTAL∙LACIÓ BAIXA TENSIÓ INSTALACIÓN DE BAJA TENSIÓN- MEMORIA DESCRIPTIVA 1. ANTECEDENTES. 2. OBJETO DEL PROYECTO. 3. REGLAMENTACION Y DISPOSICIONES OFICIALES Y PARTICULARES. 4. ACOMETIDA. 5. INSTALACIONES DE ENLACE. 5.1. CAJA DE PROTECCIÓN Y MEDIDA. 5.2. DERIVACION INDIVIDUAL. 5.3. DISPOSITIVOS GENERALES E INDIVIDUALES DE MANDO Y PROTECCION. 6. INSTALACIONES INTERIORES. 6.1. CONDUCTORES. 6.2. IDENTIFICACION DE CONDUCTORES. 6.3. SUBDIVISION DE LAS INSTALACIONES. 6.4. EQUILIBRADO DE CARGAS. 6.5. RESISTENCIA DE AISLAMIENTO Y RIGIDEZ DIELECTRICA. 6.6. CONEXIONES. 6.7. SISTEMAS DE INSTALACION. 7. PRESCRIPCIONES PARTICULARES PARA LOCALES DE REUNION. 7.1. ALIMENTACION DE LOS SERVICIOS DE SEGURIDAD. 7.2. ALUMBRADO DE EMERGENCIA. 7.3. PRESCRIPCIONES DE CARACTER GENERAL. 8. PROTECCION CONTRA SOBREINTENSIDADES. 9. PROTECCION CONTRA SOBRETENSIONES. 9.1. CATEGORÍAS DE LAS SOBRETENSIONES. 9.2. MEDIDAS PARA EL CONTROL DE LAS SOBRETENSIONES. 9.3. SELECCIÓN DE LOS MATERIALES EN LA INSTALACIÓN. 10. PROTECCION CONTRA CONTACTOS DIRECTOS E INDIRECTOS. 10.1. PROTECCION CONTRA CONTACTOS DIRECTOS. Página 1 de 22 10.2. PROTECCION CONTRA CONTACTOS INDIRECTOS. 11. PUESTAS A TIERRA. 11.1. UNIONES A TIERRA. 11.2. RESISTENCIA DE LAS TOMAS DE TIERRA. 11.3. TOMAS DE TIERRA INDEPENDIENTES. 11.4. REVISION DE LAS TOMAS DE TIERRA. 12. RECEPTORES DE ALUMBRADO. 13. RECEPTORES A MOTOR. Página 2 de 22 MEMORIA DESCRIPTIVA 1. ANTECEDENTES. Se redacta el presente proyecto de INSTALACIÓN ELÉCTRICA DE BAJA TENSIÓN a petición del EXCMO. AYUNTAMIENTO DE BELL-LLOC D’URGELL, con C.I.F.: y domicilio social en nº , de , y a instancia de la Consejería de Trabajo e Industria, Delegación Provincial de LLEIDA y del Excmo. Ayuntamiento de BELL-LLOC. 2. OBJETO DEL PROYECTO. El objeto del presente proyecto es el de exponer ante los Organismos Competentes que la instalación que nos ocupa reúne las condiciones y garantías mínimas exigidas por la reglamentación vigente, con el fin de obtener la Autorización Administrativa y la de Ejecución de la instalación, así como servir de base a la hora de proceder a la ejecución de dicho proyecto. 3. REGLAMENTACION Y DISPOSICIONES OFICIALES Y PARTICULARES. El presente proyecto recoge las características de los materiales, los cálculos que justifican su empleo y la forma de ejecución de las obras a realizar, dando con ello cumplimiento a las siguientes disposiciones: - - Ley 7/1994, de 18 de mayo, de Protección Ambiental. Reglamento de Calificación Ambiental. Reglamento Electrotécnico para Baja Tensión e Instrucciones Técnicas Complementarias (Real Decreto 842/2002 de 2 de Agosto de 2002). Real Decreto 1955/2000 de 1 de Diciembre, por el que se regulan las Actividades de Transporte, Distribución, Comercialización, Suministro y Procedimientos de Autorización de Instalaciones de Energía Eléctrica. Código Técnico de la Edificación, DB SI sobre Seguridad en caso de incendio. Código Técnico de la Edificación, DB HE sobre Ahorro de energía. Código Técnico de la Edificación, DB SU sobre Seguridad de utilización. NBE CA-88 de Condiciones Acústicas en los Edificios. Reglamento de Instalaciones Térmicas en los Edificios. Normas Técnicas para la accesibilidad y la eliminación de barreras arquitectónicas, urbanísticas y en el transporte. Ley 31/1995, de 8 de noviembre, de Prevención de Riesgos Laborales. Real Decreto 1627/1997 de 24 de octubre de 1.997, sobre Disposiciones mínimas de seguridad y salud en las obras. Real Decreto 486/1997 de 14 de abril de 1997, sobre Disposiciones mínimas de seguridad y salud en los lugares de trabajo. Real Decreto 485/1997 de 14 de abril de 1997, sobre Disposiciones mínimas en materia de señalización de seguridad y salud en el trabajo. Real Decreto 1215/1997 de 18 de julio de 1997, sobre Disposiciones mínimas de seguridad y salud para la utilización por los trabajadores de los equipos de trabajo. Real Decreto 773/1997 de 30 de mayo de 1997, sobre Disposiciones mínimas de seguridad y salud relativas a la utilización por los trabajadores de equipos de protección individual. 4. ACOMETIDA. Es parte de la instalación de la red de distribución, que alimenta la caja general de protección o unidad funcional equivalente (CGP). Los conductores serán de aluminio. Esta línea está regulada por la ITC-BT-11. Página 3 de 22 Atendiendo a su trazado, al sistema de instalación y a las características de la red, la acometida será: - Subterránea. Los cables serán aislados, de tensión asignada 0,6/1 kV, y podrán instalarse directamente enterrados, enterrados bajo tubo o en galerías, atarjeas o canales revisables. Por último, cabe señalar que la acometida será parte de la instalación constituida por la Empresa Suministradora, por lo tanto su diseño debe basarse en las normas particulares de ella. 5. INSTALACIONES DE ENLACE. 5.1. CAJA DE PROTECCIÓN Y MEDIDA. Para el caso de suministros a un único usuario, al no existir línea general de alimentación, se colocará en un único elemento la caja general de protección y el equipo de medida; dicho elemento se denominará caja de protección y medida. En consecuencia, el fusible de seguridad ubicado antes del contador coincide con el fusible que incluye una CGP. Se instalarán preferentemente sobre las fachadas exteriores de los edificios, en lugares de libre y permanente acceso. Su situación se fijará de común acuerdo entre la propiedad y la empresa suministradora. Se instalará siempre en un nicho en pared, que se cerrará con una puerta preferentemente metálica, con grado de protección IK 10 según UNE-EN 50.102, revestida exteriormente de acuerdo con las características del entorno y estará protegida contra la corrosión, disponiendo de una cerradura o candado normalizado por la empresa suministradora. Los dispositivos de lectura de los equipos de medida deberán estar situados a una altura comprendida entre 0,70 y 1,80 m. En el nicho se dejarán previstos los orificios necesarios para alojar los conductos de entrada de la acometida. Las cajas de protección y medida a utilizar corresponderán a uno de los tipos recogidos en las especificaciones técnicas de la empresa suministradora que hayan sido aprobadas por la Administración Pública competente, en función del número y naturaleza del suministro. Dentro de las mismas se instalarán cortacircuitos fusibles en todos los conductores de fase o polares, con poder de corte al menos igual a la corriente de cortocircuito prevista en el punto de su instalación. Las cajas de protección y medida cumplirán todo lo que sobre el particular se indica en la Norma UNE-EN 60.439 -1, tendrán grado de inflamabilidad según se indica en la norma UNE-EN 60.439 -3, una vez instaladas tendrán un grado de protección IP43 según UNE 20.324 e IK 09 según UNE-EN 50.102 y serán precintables. La envolvente deberá disponer de la ventilación interna necesaria que garantice la no formación de condensaciones. El material transparente para la lectura será resistente a la acción de los rayos ultravioleta. Las disposiciones generales de este tipo de caja quedan recogidas en la ITC-BT-13. 5.2. DERIVACION INDIVIDUAL. Es la parte de la instalación que, partiendo de la caja de protección y medida, suministra energía eléctrica a una instalación de usuario. Comprende los fusibles de seguridad, el conjunto de medida y los dispositivos generales de mando y protección. Está regulada por la ITC-BT-15. Página 4 de 22 Las derivaciones individuales estarán constituidas por: - Conductores aislados en el interior de tubos empotrados. - Conductores aislados en el interior de tubos enterrados. - Conductores aislados en el interior de tubos en montaje superficial. - Conductores aislados en el interior de canales protectoras cuya tapa sólo se pueda abrir con la ayuda de un útil. Los conductores a utilizar serán de cobre, aislados y normalmente unipolares, siendo su tensión asignada 450/750 V como mínimo. Para el caso de cables multiconductores o para el caso de derivaciones individuales en el interior de tubos enterrados, el aislamiento de los conductores será de tensión asignada 0,6/1 kV. La sección mínima será de 6 mm² para los cables polares, neutro y protección y de 1,5 mm² para el hilo de mando (para aplicación de las diferentes tarifas), que será de color rojo. Los cables serán no propagadores del incendio y con emisión de humos y opacidad reducida. Los cables con características equivalentes a las de la norma UNE 21.123 parte 4 ó 5 o a la norma UNE 211002 cumplen con esta prescripción. La caída de tensión máxima admisible será, para el caso de derivaciones individuales en suministros para un único usuario en que no existe línea general de alimentación, del 1,5 %. 5.3. DISPOSITIVOS GENERALES E INDIVIDUALES DE MANDO Y PROTECCION. Los dispositivos generales de mando y protección se situarán lo más cerca posible del punto de entrada de la derivación individual. En establecimientos en los que proceda, se colocará una caja para el interruptor de control de potencia, inmediatamente antes de los demás dispositivos, en compartimento independiente y precintable. Dicha caja se podrá colocar en el mismo cuadro donde se coloquen los dispositivos generales de mando y protección. Los dispositivos individuales de mando y protección de cada uno de los circuitos, que son el origen de la instalación interior, podrán instalarse en cuadros separados y en otros lugares. En locales de uso común o de pública concurrencia deberán tomarse las precauciones necesarias para que los dispositivos de mando y protección no sean accesibles al público en general. La altura a la cual se situarán los dispositivos generales e individuales de mando y protección de los circuitos, medida desde el nivel del suelo, estará comprendida entre 1 y 2 m. Las envolventes de los cuadros se ajustarán a las normas UNE 20.451 y UNE-EN 60.439 con un grado de protección mínimo IP 30 según UNE 20.324 e IK07 según UNE-EN 50.102. envolvente para el interruptor de control de potencia será precintable y sus dimensiones estarán acuerdo con el tipo de suministro y tarifa a aplicar. Sus características y tipo corresponderán a modelo oficialmente aprobado. -3, La de un El instalador fijará de forma permanente sobre el cuadro de distribución una placa, impresa con caracteres indelebles, en la que conste su nombre o marca comercial, fecha en que se realizó la instalación, así como la intensidad asignada del interruptor general automático. Los dispositivos generales e individuales de mando y protección serán, como mínimo: - Un interruptor general automático de corte omnipolar, de intensidad nominal mínima 25 A, que permita su accionamiento manual y que esté dotado de elementos de protección contra sobrecarga y cortocircuitos (según ITC-BT-22). Tendrá poder de corte suficiente para la intensidad de cortocircuito que pueda producirse en el punto de su instalación, de 4,5 kA como mínimo. Este interruptor será independiente del interruptor de control de potencia. Página 5 de 22 - Un interruptor diferencial general, de intensidad asignada superior o igual a la del interruptor general, destinado a la protección contra contactos indirectos de todos los circuitos (según ITC-BT-24). Se cumplirá la siguiente condición: Ra x Ia ≤ U donde: "Ra" es la suma de las resistencias de la toma de tierra y de los conductores de protección de masas. "Ia" es la corriente que asegura el funcionamiento del dispositivo de protección (corriente diferencialresidual asignada). "U" es la tensión de contacto límite convencional (50 V en locales secos y 24 V en locales húmedos). Si por el tipo o carácter de la instalación se instalase un interruptor diferencial por cada circuito o grupo de circuitos, se podría prescindir del interruptor diferencial general, siempre que queden protegidos todos los circuitos. En el caso de que se instale más de un interruptor diferencial en serie, existirá una selectividad entre ellos. Todas las masas de los equipos eléctricos protegidos por un mismo dispositivo de protección, deben ser interconectadas y unidas por un conductor de protección a una misma toma de tierra. - Dispositivos de corte omnipolar, destinados a la protección contra sobrecargas y cortocircuitos de cada uno de los circuitos interiores (según ITC-BT-22). - Dispositivo de protección contra sobretensiones, según ITC-BT-23, si fuese necesario. 6. INSTALACIONES INTERIORES. 6.1. CONDUCTORES. Los conductores y cables que se empleen en las instalaciones serán de cobre y serán siempre aislados. La tensión asignada no será inferior a 450/750 V. La sección de los conductores a utilizar se determinará de forma que la caída de tensión entre el origen de la instalación interior y cualquier punto de utilización sea menor del 3 % para alumbrado y del 5 % para los demás usos. El valor de la caída de tensión podrá compensarse entre la de la instalación interior (3-5 %) y la de la derivación individual (1,5 %), de forma que la caída de tensión total sea inferior a la suma de los valores límites especificados para ambas (4,5-6,5 %). Para instalaciones que se alimenten directamente en alta tensión, mediante un transformador propio, se considerará que la instalación interior de baja tensión tiene su origen a la salida del transformador, siendo también en este caso las caídas de tensión máximas admisibles del 4,5 % para alumbrado y del 6,5 % para los demás usos. En instalaciones interiores, para tener en cuenta las corrientes armónicas debidas a cargas no lineales y posibles desequilibrios, salvo justificación por cálculo, la sección del conductor neutro será como mínimo igual a la de las fases. No se utilizará un mismo conductor neutro para varios circuitos. Las intensidades máximas admisibles, se regirán en su totalidad por lo indicado en la Norma UNE 20.460-5-523 y su anexo Nacional. Los conductores de protección tendrán una sección mínima igual a la fijada en la tabla siguiente: Sección conductores fase (mm²) Sf ≤ 16 16 < S f ≤ 35 Sf > 35 Sección conductores protección (mm²) Sf 16 Sf/2 Página 6 de 22 6.2. IDENTIFICACION DE CONDUCTORES. Los conductores de la instalación deben ser fácilmente identificables, especialmente por lo que respecta al conductor neutro y al conductor de protección. Esta identificación se realizará por los colores que presenten sus aislamientos. Cuando exista conductor neutro en la instalación o se prevea para un conductor de fase su pase posterior a conductor neutro, se identificarán éstos por el color azul claro. Al conductor de protección se le identificará por el color verde-amarillo. Todos los conductores de fase, o en su caso, aquellos para los que no se prevea su pase posterior a neutro, se identificarán por los colores marrón, negro o gris. 6.3. SUBDIVISION DE LAS INSTALACIONES. Las instalaciones se subdividirán de forma que las perturbaciones originadas por averías que puedan producirse en un punto de ellas, afecten solamente a ciertas partes de la instalación, por ejemplo a un sector del edificio, a una planta, a un solo local, etc., para lo cual los dispositivos de protección de cada circuito estarán adecuadamente coordinados y serán selectivos con los dispositivos generales de protección que les precedan. Toda instalación se dividirá en varios circuitos, según las necesidades, a fin de: - evitar las interrupciones innecesarias de todo el circuito y limitar las consecuencias de un fallo. - facilitar las verificaciones, ensayos y mantenimientos. - evitar los riesgos que podrían resultar del fallo de un solo circuito que pudiera dividirse, como por ejemplo si solo hay un circuito de alumbrado. 6.4. EQUILIBRADO DE CARGAS. Para que se mantenga el mayor equilibrio posible en la carga de los conductores que forman parte de una instalación, se procurará que aquella quede repartida entre sus fases o conductores polares. 6.5. RESISTENCIA DE AISLAMIENTO Y RIGIDEZ DIELECTRICA. Las instalaciones deberán presentar una resistencia de aislamiento al menos igual a los valores indicados en la tabla siguiente: Tensión nominal instalación Tensión ensayo corriente continua (V) MBTS o MBTP ≤ 500 V > 500 V 250 500 1000 Resistencia de aislamiento (MΩ) ≥ 0,25 ≥ 0,50 ≥ 1,00 La rigidez dieléctrica será tal que, desconectados los aparatos de utilización (receptores), resista durante 1 minuto una prueba de tensión de 2U + 1000 V a frecuencia industrial, siendo U la tensión máxima de servicio expresada en voltios, y con un mínimo de 1.500 V. Las corrientes de fuga no serán superiores, para el conjunto de la instalación o para cada uno de los circuitos en que ésta pueda dividirse a efectos de su protección, a la sensibilidad que presenten los interruptores diferenciales instalados como protección contra los contactos indirectos. 6.6. CONEXIONES. En ningún caso se permitirá la unión de conductores mediante conexiones y/o derivaciones por simple retorcimiento o arrollamiento entre sí de los conductores, sino que deberá realizarse siempre utilizando bornes de conexión montados individualmente o constituyendo bloques o regletas de Página 7 de 22 conexión; puede permitirse asimismo, la utilización de bridas de conexión. Siempre deberán realizarse en el interior de cajas de empalme y/o de derivación. Si se trata de conductores de varios alambres cableados, las conexiones se realizarán de forma que la corriente se reparta por todos los alambres componentes. 6.7. SISTEMAS DE INSTALACION. 6.7.1. Prescripciones Generales. Varios circuitos pueden encontrarse en el mismo tubo o en el mismo compartimento de canal si todos los conductores están aislados para la tensión asignada más elevada. En caso de proximidad de canalizaciones eléctricas con otras no eléctricas, se dispondrán de forma que entre las superficies exteriores de ambas se mantenga una distancia mínima de 3 cm. En caso de proximidad con conductos de calefacción, de aire caliente, vapor o humo, las canalizaciones eléctricas se establecerán de forma que no puedan alcanzar una temperatura peligrosa y, por consiguiente, se mantendrán separadas por una distancia conveniente o por medio de pantallas calorífugas. Las canalizaciones eléctricas no se situarán por debajo de otras canalizaciones que puedan dar lugar a condensaciones, tales como las destinadas a conducción de vapor, de agua, de gas, etc., a menos que se tomen las disposiciones necesarias para proteger las canalizaciones eléctricas contra los efectos de estas condensaciones. Las canalizaciones deberán estar dispuestas de forma que faciliten su maniobra, inspección y acceso a sus conexiones. Las canalizaciones eléctricas se establecerán de forma que mediante la conveniente identificación de sus circuitos y elementos, se pueda proceder en todo momento a reparaciones, transformaciones, etc. En toda la longitud de los pasos de canalizaciones a través de elementos de la construcción, tales como muros, tabiques y techos, no se dispondrán empalmes o derivaciones de cables, estando protegidas contra los deterioros mecánicos, las acciones químicas y los efectos de la humedad. Las cubiertas, tapas o envolventes, mandos y pulsadores de maniobra de aparatos tales como mecanismos, interruptores, bases, reguladores, etc, instalados en los locales húmedos o mojados, serán de material aislante. 6.7.2. Conductores aislados bajo tubos protectores. Los cables utilizados serán de tensión asignada no inferior a 450/750 V. El diámetro exterior mínimo de los tubos, en función del número y la sección de los conductores a conducir, se obtendrá de las tablas indicadas en la ITC-BT-21, así como las características mínimas según el tipo de instalación. Para la ejecución de las canalizaciones bajo tubos protectores, se tendrán en cuenta las prescripciones generales siguientes: - El trazado de las canalizaciones se hará siguiendo líneas verticales y horizontales o paralelas a las aristas de las paredes que limitan el local donde se efectúa la instalación. - Los tubos se unirán entre sí mediante accesorios adecuados a su clase que aseguren la continuidad de la protección que proporcionan a los conductores. - Los tubos aislantes rígidos curvables en caliente podrán ser ensamblados entre sí en caliente, recubriendo el empalme con una cola especial cuando se precise una unión estanca. - Las curvas practicadas en los tubos serán continuas y no originarán reducciones de sección Página 8 de 22 inadmisibles. Los radios mínimos de curvatura para cada clase de tubo serán los especificados por el fabricante conforme a UNE-EN - Será posible la fácil introducción y retirada de los conductores en los tubos después de colocarlos y fijados éstos y sus accesorios, disponiendo para ello los registros que se consideren convenientes, que en tramos rectos no estarán separados entre sí más de 15 metros. El número de curvas en ángulo situadas entre dos registros consecutivos no será superior a 3. Los conductores se alojarán normalmente en los tubos después de colocados éstos. - Los registros podrán estar destinados únicamente a facilitar la introducción y retirada de los conductores en los tubos o servir al mismo tiempo como cajas de empalme o derivación. - Las conexiones entre conductores se realizarán en el interior de cajas apropiadas de material aislante y no propagador de la llama. Si son metálicas estarán protegidas contra la corrosión. Las dimensiones de estas cajas serán tales que permitan alojar holgadamente todos los conductores que deban contener. Su profundidad será al menos igual al diámetro del tubo mayor más un 50 % del mismo, con un mínimo de 40 mm. Su diámetro o lado interior mínimo será de 60 mm. Cuando se quieran hacer estancas las entradas de los tubos en las cajas de conexión, deberán emplearse prensaestopas o racores adecuados. - En los tubos metálicos sin aislamiento interior, se tendrá en cuenta la posibilidad de que se produzcan condensaciones de agua en su interior, para lo cual se elegirá convenientemente el trazado de su instalación, previendo la evacuación y estableciendo una ventilación apropiada en el interior de los tubos mediante el sistema adecuado, como puede ser, por ejemplo, el uso de una "T" de la que uno de los brazos no se emplea. - Los tubos metálicos que sean accesibles deben ponerse a tierra. Su continuidad eléctrica deberá quedar convenientemente asegurada. En el caso de utilizar tubos metálicos flexibles, es necesario que la distancia entre dos puestas a tierra consecutivas de los tubos no exceda de 10 metros. - No podrán utilizarse los tubos metálicos como conductores de protección o de neutro. Cuando los tubos se instalen en montaje superficial, se tendrán en cuenta, además, las siguientes prescripciones: - Los tubos se fijarán a las paredes o techos por medio de bridas o abrazaderas protegidas contra la corrosión y sólidamente sujetas. La distancia entre éstas será, como máximo, de 0,50 metros. Se dispondrán fijaciones de una y otra parte en los cambios de dirección, en los empalmes y en la proximidad inmediata de las entradas en cajas o aparatos. - Los tubos se colocarán adaptándose a la superficie sobre la que se instalan, curvándose o usando los accesorios necesarios. - En alineaciones rectas, las desviaciones del eje del tubo respecto a la línea que une los puntos extremos no serán superiores al 2 por 100. - Es conveniente disponer los tubos, siempre que sea posible, a una altura mínima de 2,50 metros sobre el suelo, con objeto de protegerlos de eventuales daños mecánicos. Cuando los tubos se coloquen empotrados, se tendrán en cuenta, además, las siguientes prescripciones: - En la instalación de los tubos en el interior de los elementos de la construcción, las rozas no pondrán en peligro la seguridad de las paredes o techos en que se practiquen. Las dimensiones de las rozas serán suficientes para que los tubos queden recubiertos por una capa de 1 centímetro de espesor, como mínimo. En los ángulos, el espesor de esta capa puede reducirse a 0,5 centímetros. - No se instalarán entre forjado y revestimiento tubos destinados a la instalación eléctrica de las plantas inferiores. - Para la instalación correspondiente a la propia planta, únicamente podrán instalarse, entre forjado y revestimiento, tubos que deberán quedar recubiertos por una capa de hormigón o mortero de 1 centímetro de espesor, como mínimo, además del revestimiento. - En los cambios de dirección, los tubos estarán convenientemente curvados o bien provistos de codos o "T" apropiados, pero en este último caso sólo se admitirán los provistos de tapas de registro. - Las tapas de los registros y de las cajas de conexión quedarán accesibles y desmontables una vez finalizada la obra. Los registros y cajas quedarán enrasados con la superficie exterior del revestimiento Página 9 de 22 de la pared o techo cuando no se instalen en el interior de un alojamiento cerrado y practicable. - En el caso de utilizarse tubos empotrados en paredes, es conveniente disponer los recorridos horizontales a 50 centímetros como máximo, de suelo o techos y los verticales a una distancia de los ángulos de esquinas no superior a 20 centímetros. 6.7.3. Conductores aislados fijados directamente sobre las paredes. Estas instalaciones se establecerán con cables de tensiones asignadas no inferiores a 0,6/1 kV, armados, provistos de aislamiento y cubierta. Para la ejecución de las canalizaciones se tendrán en cuenta las siguientes prescripciones: - Se fijarán sobre las paredes por medio de bridas, abrazaderas, o collares de forma que no perjudiquen las cubiertas de los mismos. - Con el fin de que los cables no sean susceptibles de doblarse por efecto de su propio peso, los puntos de fijación de los mismos estarán suficientemente próximos. La distancia entre dos puntos de fijación sucesivos, no excederá de 0,40 metros. - Cuando los cables deban disponer de protección mecánica por el lugar y condiciones de instalación en que se efectúe la misma, se utilizarán cables armados. En caso de no utilizar estos cables, se establecerá una protección mecánica complementaria sobre los mismos. - Se evitará curvar los cables con un radio demasiado pequeño y salvo prescripción en contra fijada en la Norma UNE correspondiente al cable utilizado, este radio no será inferior a 10 veces el diámetro exterior del cable. - Los cruces de los cables con canalizaciones no eléctricas se podrán efectuar por la parte anterior o posterior a éstas, dejando una distancia mínima de 3 cm entre la superficie exterior de la canalización no eléctrica y la cubierta de los cables cuando el cruce se efectúe por la parte anterior de aquélla. - Los extremos de los cables serán estancos cuando las características de los locales o emplazamientos así lo exijan, utilizándose a este fin cajas u otros dispositivos adecuados. La estanqueidad podrá quedar asegurada con la ayuda de prensaestopas. - Los empalmes y conexiones se harán por medio de cajas o dispositivos equivalentes provistos de tapas desmontables que aseguren a la vez la continuidad de la protección mecánica establecida, el aislamiento y la inaccesibilidad de las conexiones y permitiendo su verificación en caso necesario. 6.7.4. Conductores aislados en el interior de huecos de la construcción. Los cables utilizados serán de tensión asignada no inferior a 450/750 V, con cubierta de protección. Los cables o tubos podrán instalarse directamente en los huecos de la construcción totalmente construidos con materiales incombustibles de resistencia al fuego RF-120 como mínimo. Los huecos en la construcción admisibles para estas canalizaciones podrán estar dispuestos en muros, paredes, vigas, forjados o techos, adoptando la forma de conductos continuos o bien estarán comprendidos entre dos superficies paralelas como en el caso de falsos techos o muros con cámaras de aire. La sección de los huecos será, como mínimo, igual a cuatro veces la ocupada por los cables o tubos, y su dimensión más pequeña no será inferior a dos veces el diámetro exterior de mayor sección de éstos, con un mínimo de 20 milímetros. Las paredes que separen un hueco que contenga canalizaciones eléctricas de los locales inmediatos, tendrán suficiente solidez para proteger éstas contra acciones previsibles. Se evitarán, dentro de lo posible, las asperezas en el interior de los huecos y los cambios de dirección de los mismos en un número elevado o de pequeño radio de curvatura. Página 10 de 22 La canalización podrá ser reconocida y conservada sin que sea necesaria la destrucción parcial de las paredes, techos, etc., o sus guarnecidos y decoraciones. Los empalmes y derivaciones de los cables serán accesibles, disponiéndose para ellos las cajas de derivación adecuadas. Se evitará que puedan producirse infiltraciones, fugas o condensaciones de agua que puedan penetrar en el interior del hueco, prestando especial atención a la impermeabilidad de sus muros exteriores, así como a la proximidad de tuberías de conducción de líquidos, penetración de agua al efectuar la limpieza de suelos, posibilidad de acumulación de aquélla en partes bajas del hueco, etc. 6.7.5. Conductores aislados bajo canales protectoras. La canal protectora es un material de instalación constituido por un perfil de paredes perforadas o no, destinado a alojar conductores o cables y cerrado por una tapa desmontable. Los cables utilizados serán de tensión asignada no inferior a 450/750 V. Las canales protectoras tendrán un grado de protección IP4X y estarán clasificadas como "canales con tapa de acceso que sólo pueden abrirse con herramientas". En su interior se podrán colocar mecanismos tales como interruptores, tomas de corriente, dispositivos de mando y control, etc, siempre que se fijen de acuerdo con las instrucciones del fabricante. También se podrán realizar empalmes de conductores en su interior y conexiones a los mecanismos. Las canales protectoras para aplicaciones no ordinarias deberán tener unas características mínimas de resistencia al impacto, de temperatura mínima y máxima de instalación y servicio, de resistencia a la penetración de objetos sólidos y de resistencia a la penetración de agua, adecuadas a las condiciones del emplazamiento al que se destina; asimismo las canales serán no propagadoras de la llama. Dichas características serán conformes a las normas de la serie UNE-EN 50.085. El trazado de las canalizaciones se hará siguiendo preferentemente líneas verticales y horizontales o paralelas a las aristas de las paredes que limitan al local donde se efectúa la instalación. Las canales con conductividad eléctrica deben conectarse a la red de tierra, su continuidad eléctrica quedará convenientemente asegurada. La tapa de las canales quedará siempre accesible. 7. PRESCRIPCIONES PARTICULARES PARA LOCALES DE REUNION. 7.1. ALIMENTACION DE LOS SERVICIOS DE SEGURIDAD. Para los servicios de seguridad la fuente de energía debe ser elegida de forma que la alimentación esté asegurada durante un tiempo apropiado. Para que los servicios de seguridad funcionen en caso de incendio, los equipos y materiales utilizados deben presentar, por construcción o por instalación, una resistencia al fuego de duración apropiada. Se elegirán preferentemente medidas de protección contra los contactos indirectos sin corte automático al primer defecto. Se pueden utilizar las siguientes fuentes de alimentación: - Baterías de acumuladores. - Generadores independientes. - Derivaciones separadas de la red de distribución, independientes de la alimentación normal. Página 11 de 22 Las fuentes para servicios complementarios o de seguridad deben estar instaladas en lugar fijo y de forma que no puedan ser afectadas por el fallo de la fuente normal. Además, con excepción de los equipos autónomos, deberán cumplir las siguientes condiciones: - se instalarán en emplazamiento apropiado, accesible solamente a las personas cualificadas o expertas. - el emplazamiento estará convenientemente ventilado, de forma que los gases y los humos que produzcan no puedan propagarse en los locales accesibles a las personas. - no se admiten derivaciones separadas, independientes y alimentadas por una red de distribución pública, salvo si se asegura que las dos derivaciones no puedan fallar simultáneamente. - cuando exista una sola fuente para los servicios de seguridad, ésta no debe ser utilizada para otros usos. Sin embargo, cuando se dispone de varias fuentes, pueden utilizarse igualmente como fuentes de reemplazamiento, con la condición, de que en caso de fallo de una de ellas, la potencia todavía disponible sea suficiente para garantizar la puesta en funcionamiento de todos los servicios de seguridad, siendo necesario generalmente, el corte automático de los equipos no concernientes a la seguridad. La puesta en funcionamiento se realizará al producirse la falta de tensión en los circuitos alimentados por los diferentes suministros procedentes de la Empresa o Empresas distribuidoras de energía eléctrica, o cuando aquella tensión descienda por debajo del 70% de su valor nominal. La capacidad mínima de una fuente propia de energía será, como norma general, la precisa para proveer al alumbrado de seguridad (alumbrado de evacuación, alumbrado ambiente y alumbrado de zonas de alto riesgo). Todos los locales de pública concurrencia deberán disponer de alumbrado de emergencia (alumbrado de seguridad y alumbrado de reemplazamiento, según los casos). Deberán disponer de suministro de socorro (potencia mínima: 15 % del total contratado) los locales de espectáculos y actividades recreativas cualquiera que sea su ocupación y los locales de reunión, trabajo y usos sanitarios con una ocupación prevista de más de 300 personas. Deberán disponer de suministro de reserva (potencia mínima: 25 % del total contratado): - Hospitales, clínicas, sanatorios, ambulatorios y centros de salud. - Estaciones de viajeros y aeropuertos. - Estacionamientos subterráneos para más de 100 vehículos. - Establecimientos comerciales o agrupaciones de éstos en centros comerciales de más de 2.000 m² de superficie. - Estadios y pabellones deportivos. 7.2. ALUMBRADO DE EMERGENCIA. Las instalaciones destinadas a alumbrado de emergencia tienen por objeto asegurar, en caso de fallo de la alimentación al alumbrado normal, la iluminación en los locales y accesos hasta las salidas, para una eventual evacuación del público o iluminar otros puntos que se señalen. La alimentación del alumbrado de emergencia será automática con corte breve (alimentación automática disponible en 0,5 s como máximo). 7.2.1. Alumbrado de seguridad. Es el alumbrado de emergencia previsto para garantizar la seguridad de las personas que evacuen una zona o que tienen que terminar un trabajo potencialmente peligroso antes de abandonar la zona. Página 12 de 22 El alumbrado de seguridad estará previsto para entrar en funcionamiento automáticamente cuando se produce el fallo del alumbrado general o cuando la tensión de éste baje a menos del 70% de su valor nominal. La instalación de este alumbrado será fija y estará provista de fuentes propias de energía. Sólo se podrá utilizar el suministro exterior para proceder a su carga, cuando la fuente propia de energía esté constituida por baterías de acumuladores o aparatos autónomos automáticos. Alumbrado de evacuación. Es la parte del alumbrado de seguridad previsto para garantizar el reconocimiento y la utilización de los medios o rutas de evacuación cuando los locales estén o puedan estar ocupados. En rutas de evacuación, el alumbrado de evacuación debe proporcionar, a nivel del suelo y en el eje de los pasos principales, una iluminancia horizontal mínima de 1 lux. En los puntos en los que estén situados los equipos de las instalaciones de protección contra incendios que exijan utilización manual y en los cuadros de distribución del alumbrado, la iluminancia mínima será de 5 lux. La relación entre la iluminancia máxima y la mínima en el eje de los pasos principales será menor de 40. El alumbrado de evacuación deberá poder funcionar, cuando se produzca el fallo de la alimentación normal, como mínimo durante una hora, proporcionando la iluminancia prevista. 7.2.2. Alumbrado de reemplazamiento. Parte del alumbrado de emergencia que permite la continuidad de las actividades normales. Cuando el alumbrado de reemplazamiento proporcione una iluminancia inferior al alumbrado normal, se usará únicamente para terminar el trabajo con seguridad. 7.2.3. Lugares en que deberá instalarse alumbrado de emergencia. Con alumbrado de seguridad. Es obligatorio situar el alumbrado de seguridad en las siguientes zonas de los locales de pública concurrencia: a) en todos los recintos cuya ocupación sea mayor de 100 personas. b) los recorridos generales de evacuación de zonas destinadas a usos residencial u hospitalario y los de zonas destinadas a cualquier otro uso que estén previstos para la evacuación de más de 100 personas. c) en los aseos generales de planta en edificios de acceso público. d) en los estacionamientos cerrados y cubiertos para más de 5 vehículos, incluidos los pasillos y las escaleras que conduzcan desde aquellos hasta el exterior o hasta las zonas generales del edificio. e) en los locales que alberguen equipos generales de las instalaciones de protección. f) en las salidas de emergencia y en las señales de seguridad reglamentarias. g) en todo cambio de dirección de la ruta de evacuación. h) en toda intersección de pasillos con las rutas de evacuación. i) en el exterior del edificio, en la vecindad inmediata a la salida. j) a menos de 2 m de las escaleras, de manera que cada tramo de escaleras reciba una iluminación directa. k) a menos de 2 m de cada cambio de nivel. l) a menos de 2 m de cada puesto de primeros auxilios. m) a menos de 2 m de cada equipo manual destinado a la prevención y extinción de incendios. n) en los cuadros de distribución de la instalación de alumbrado de las zonas indicadas anteriormente. En las zonas incluidas en los apartados m) y n), el alumbrado de seguridad proporcionará una iluminancia mínima de 5 lux al nivel de operación. Página 13 de 22 Solo se instalará alumbrado de seguridad para zonas de alto riesgo en las zonas que así lo requieran. Con alumbrado de reemplazamiento. En las zonas de hospitalización, la instalación de alumbrado de emergencia proporcionará una iluminancia no inferior de 5 lux y durante 2 horas como mínimo. Las salas de intervención, las destinadas a tratamiento intensivo, las salas de curas, paritorios, urgencias dispondrán de un alumbrado de reemplazamiento que proporcionará un nivel de iluminancia igual al del alumbrado normal durante 2 horas como mínimo. 7.2.4. Prescripciones de los aparatos para alumbrado de emergencia. Aparatos autónomos para alumbrado de emergencia. Luminaria que proporciona alumbrado de emergencia de tipo permanente o no permanente en la que todos los elementos, tales como la batería, la lámpara, el conjunto de mando y los dispositivos de verificación y control, si existen, están contenidos dentro de la luminaria o a una distancia inferior a 1 m de ella. Luminaria alimentada por fuente central. Luminaria que proporciona alumbrado de emergencia de tipo permanente o no permanente y que está alimentada a partir de un sistema de alimentación de emergencia central, es decir, no incorporado en la luminaria. Las líneas que alimentan directamente los circuitos individuales de los alumbrados de emergencia alimentados por fuente central, estarán protegidas por interruptores automáticos con una intensidad nominal de 10 A como máximo. Una misma línea no podrá alimentar más de 12 puntos de luz o, si en la dependencia o local considerado existiesen varios puntos de luz para alumbrado de emergencia, éstos deberán ser repartidos, al menos, entre dos líneas diferentes, aunque su número sea inferior a doce. Las canalizaciones que alimenten los alumbrados de emergencia alimentados por fuente central se dispondrán, cuando se instalen sobre paredes o empotradas en ellas, a 5 cm como mínimo, de otras canalizaciones eléctricas y, cuando se instalen en huecos de la construcción estarán separadas de éstas por tabiques incombustibles no metálicos. 7.3. PRESCRIPCIONES DE CARACTER GENERAL. Las instalaciones en los locales de pública concurrencia, cumplirán las condiciones de carácter general que a continuación se señalan. - Los aparatos receptores que consuman más de 16 amperios se alimentarán directamente desde el cuadro general o desde los secundarios. - El cuadro general de distribución e, igualmente, los cuadros secundarios, se instalarán en lugares a los que no tenga acceso el público y que estarán separados de los locales donde exista un peligro acusado de incendio o de pánico (cabinas de proyección, escenarios, salas de público, escaparates, etc.), por medio de elementos a prueba de incendios y puertas no propagadoras del fuego. Los contadores podrán instalarse en otro lugar, de acuerdo con la empresa distribuidora de energía eléctrica, y siempre antes del cuadro general. - Cerca de cada uno de los interruptores del cuadro se colocará una placa indicadora del circuito al que pertenecen. Página 14 de 22 - En las instalaciones para alumbrado de locales o dependencias donde se reúna público, el número de líneas secundarias y su disposición en relación con el total de lámparas a alimentar deberá ser tal que el corte de corriente en una cualquiera de ellas no afecte a más de la tercera parte del total de lámparas instaladas en los locales o dependencias que se iluminan alimentadas por dichas líneas. Cada una de estas líneas estarán protegidas en su origen contra sobrecargas, cortocircuitos, y si procede contra contactos indirectos. - Los cables y sistemas de conducción de cables deben instalarse de manera que no se reduzcan las características de la estructura del edificio en la seguridad contra incendios. - Los cables eléctricos a utilizar en las instalaciones de tipo general y en el conexionado interior de cuadros eléctricos en este tipo de locales, serán no propagadores del incendio y con emisión de humos y opacidad reducida. - Las fuentes propias de energía de corriente alterna a 50 Hz, no podrán dar tensión de retorno a la acometida o acometidas de la red de Baja Tensión pública que alimenten al local de pública concurrencia. - A partir del cuadro general de distribución se instalarán líneas distribuidoras generales, accionadas por medio de interruptores omnipolares, al menos para cada uno de los siguientes grupos de dependencias o locales: - Salas de venta o reunión, por planta del edificio - Escaparates - Almacenes - Talleres - Pasillos, escaleras y vestíbulos 8. PROTECCION CONTRA SOBREINTENSIDADES. Todo circuito estará protegido contra los efectos de las sobreintensidades que puedan presentarse en el mismo, para lo cual la interrupción de este circuito se realizará en un tiempo conveniente o estará dimensionado para las sobreintensidades previsibles. Las sobreintensidades pueden estar motivadas por: - Sobrecargas debidas a los aparatos de utilización o defectos de aislamiento de gran impedancia. - Cortocircuitos. - Descargas eléctricas atmosféricas. a) Protección contra sobrecargas. El límite de intensidad de corriente admisible en un conductor ha de quedar en todo caso garantizada por el dispositivo de protección utilizado. El dispositivo de protección podrá estar constituido por un interruptor automático de corte omnipolar con curva térmica de corte, o por cortacircuitos fusibles calibrados de características de funcionamiento adecuadas. b) Protección contra cortocircuitos. En el origen de todo circuito se establecerá un dispositivo de protección contra cortocircuitos cuya capacidad de corte estará de acuerdo con la intensidad de cortocircuito que pueda presentarse en el punto de su conexión. Se admite, no obstante, que cuando se trate de circuitos derivados de uno principal, cada uno de estos circuitos derivados disponga de protección contra sobrecargas, mientras que un solo dispositivo general pueda asegurar la protección contra cortocircuitos para todos los circuitos derivados. Se admiten como dispositivos de protección contra cortocircuitos los fusibles calibrados de características de funcionamiento adecuadas y los interruptores automáticos con sistema de corte omnipolar. La norma UNE 20.460 -4-43 recoge todos los aspectos requeridos para los dispositivos de protección. La norma UNE 20.460 -4-473 define la aplicación de las medidas de protección expuestas Página 15 de 22 en la norma UNE 20.460 -4-43 según sea por causa de sobrecargas o cortocircuito, señalando en cada caso su emplazamiento u omisión. 9. PROTECCION CONTRA SOBRETENSIONES. 9.1. CATEGORÍAS DE LAS SOBRETENSIONES. Las categorías indican los valores de tensión soportada a la onda de choque de sobretensión que deben de tener los equipos, determinando, a su vez, el valor límite máximo de tensión residual que deben permitir los diferentes dispositivos de protección de cada zona para evitar el posible daño de dichos equipos. Se distinguen 4 categorías diferentes, indicando en cada caso el nivel de tensión soportada a impulsos, en kV, según la tensión nominal de la instalación. Tensión nominal instalación Tensión soportada a impulsos 1,2/50 (kV) Sistemas III Sistemas II Categoría IV Categoría III Categoría II Categoría I 230/400 230 400/690 1000 6 4 2,5 1,5 8 6 4 2,5 Categoría I Se aplica a los equipos muy sensibles a las sobretensiones y que están destinados a ser conectados a la instalación eléctrica fija (ordenadores, equipos electrónicos muy sensibles, etc). En este caso, las medidas de protección se toman fuera de los equipos a proteger, ya sea en la instalación fija o entre la instalación fija y los equipos, con objeto de limitar las sobretensiones a un nivel específico. Categoría II Se aplica a los equipos destinados a conectarse a una instalación eléctrica fija (electrodomésticos, herramientas portátiles y otros equipos similares). Categoría III Se aplica a los equipos y materiales que forman parte de la instalación eléctrica fija y a otros equipos para los cuales se requiere un alto nivel de fiabilidad (armarios de distribución, embarrados, aparamenta: interruptores, seccionadores, tomas de corriente, etc, canalizaciones y sus accesorios: cables, caja de derivación, etc, motores con conexión eléctrica fija: ascensores, máquinas industriales, etc. Categoría IV Se aplica a los equipos y materiales que se conectan en el origen o muy próximos al origen de la instalación, aguas arriba del cuadro de distribución (contadores de energía, aparatos de telemedida, equipos principales de protección contra sobreintensidades, etc). 9.2. MEDIDAS PARA EL CONTROL DE LAS SOBRETENSIONES. Se pueden presentar dos situaciones diferentes: - Situación natural: cuando no es preciso la protección contra las sobretensiones transitorias, pues se Página 16 de 22 prevé un bajo riesgo de sobretensiones en la instalación (debido a que está alimentada por una red subterránea en su totalidad). En este caso se considera suficiente la resistencia a las sobretensiones de los equipos indicada en la tabla de categorías, y no se requiere ninguna protección suplementaria contra las sobretensiones transitorias. - Situación controlada: cuando es preciso la protección contra las sobretensiones transitorias en el origen de la instalación, pues la instalación se alimenta por, o incluye, una línea aérea con conductores desnudos o aislados. También se considera situación controlada aquella situación natural en que es conveniente incluir dispositivos de protección para una mayor seguridad (continuidad de servicio, valor económico de los equipos, pérdidas irreparables, etc.). Los dispositivos de protección contra sobretensiones de origen atmosférico deben seleccionarse de forma que su nivel de protección sea inferior a la tensión soportada a impulso de la categoría de los equipos y materiales que se prevé que se vayan a instalar. Los descargadores se conectarán entre cada uno de los conductores, incluyendo el neutro o compensador y la tierra de la instalación. 9.3. SELECCIÓN DE LOS MATERIALES EN LA INSTALACIÓN. Los equipos y materiales deben escogerse de manera que su tensión soportada a impulsos no sea inferior a la tensión soportada prescrita en la tabla anterior, según su categoría. Los equipos y materiales que tengan una tensión soportada a impulsos inferior a la indicada en la tabla, se pueden utilizar, no obstante: - en situación natural, cuando el riesgo sea aceptable. - en situación controlada, si la protección contra las sobretensiones es adecuada. 10. PROTECCION CONTRA CONTACTOS DIRECTOS E INDIRECTOS. 10.1. PROTECCION CONTRA CONTACTOS DIRECTOS. Protección por aislamiento de las partes activas. Las partes activas deberán estar recubiertas de un aislamiento que no pueda ser eliminado más que destruyéndolo. Protección por medio de barreras o envolventes. Las partes activas deben estar situadas en el interior de las envolventes o detrás de barreras que posean, como mínimo, el grado de protección IP XXB, según UNE20.324. Si se necesitan aberturas mayores para la reparación de piezas o para el buen funcionamiento de los equipos, se adoptarán precauciones apropiadas para impedir que las personas o animales domésticos toquen las partes activas y se garantizará que las personas sean conscientes del hecho de que las partes activas no deben ser tocadas voluntariamente. Las superficies superiores de las barreras o envolventes horizontales que son fácilmente accesibles, deben responder como mínimo al grado de protección IP4X o IP XXD. Las barreras o envolventes deben fijarse de manera segura y ser de una robustez y durabilidad suficientes para mantener los grados de protección exigidos, con una separación suficiente de las partes activas en las condiciones normales de servicio, teniendo en cuenta las influencias externas. Página 17 de 22 Cuando sea necesario suprimir las barreras, abrir las envolventes o quitar partes de éstas, esto no debe ser posible más que: - bien con la ayuda de una llave o de una herramienta; - o bien, después de quitar la tensión de las partes activas protegidas por estas barreras o estas envolventes, no pudiendo ser restablecida la tensión hasta después de volver a colocar las barreras o las envolventes; - o bien, si hay interpuesta una segunda barrera que posee como mínimo el grado de protección IP2X o IP XXB, que no pueda ser quitada más que con la ayuda de una llave o de una herramienta y que impida todo contacto con las partes activas. Protección complementaria por dispositivos de corriente diferencial-residual. Esta medida de protección está destinada solamente a complementar otras medidas de protección contra los contactos directos. El empleo de dispositivos de corriente diferencial-residual, cuyo valor de corriente diferencial asignada de funcionamiento sea inferior o igual a 30 mA, se reconoce como medida de protección complementaria en caso de fallo de otra medida de protección contra los contactos directos o en caso de imprudencia de los usuarios. 10.2. PROTECCION CONTRA CONTACTOS INDIRECTOS. La protección contra contactos indirectos se conseguirá mediante "corte automático de la alimentación". Esta medida consiste en impedir, después de la aparición de un fallo, que una tensión de contacto de valor suficiente se mantenga durante un tiempo tal que pueda dar como resultado un riesgo. La tensión límite convencional es igual a 50 V, valor eficaz en corriente alterna, en condiciones normales y a 24 V en locales húmedos. Todas las masas de los equipos eléctricos protegidos por un mismo dispositivo de protección, deben ser interconectadas y unidas por un conductor de protección a una misma toma de tierra. El punto neutro de cada generador o transformador debe ponerse a tierra. Se cumplirá la siguiente condición: Ra x Ia ≤ U donde: - Ra es la suma de las resistencias de la toma de tierra y de los conductores de protección de masas. - Ia es la corriente que asegura el funcionamiento automático del dispositivo de protección. Cuando el dispositivo de protección es un dispositivo de corriente diferencial-residual es la corriente diferencialresidual asignada. - U es la tensión de contacto límite convencional (50 ó 24V). 11. PUESTAS A TIERRA. Las puestas a tierra se establecen principalmente con objeto de limitar la tensión que, con respecto a tierra, puedan presentar en un momento dado las masas metálicas, asegurar la actuación de las protecciones y eliminar o disminuir el riesgo que supone una avería en los materiales eléctricos utilizados. La puesta o conexión a tierra es la unión eléctrica directa, sin fusibles ni protección alguna, de una parte del circuito eléctrico o de una parte conductora no perteneciente al mismo, mediante una toma de tierra con un electrodo o grupo de electrodos enterrados en el suelo. Página 18 de 22 Mediante la instalación de puesta a tierra se deberá conseguir que en el conjunto de instalaciones, edificios y superficie próxima del terreno no aparezcan diferencias de potencial peligrosas y que, al mismo tiempo, permita el paso a tierra de las corrientes de defecto o las de descarga de origen atmosférico. La elección e instalación de los materiales que aseguren la puesta a tierra deben ser tales que: - El valor de la resistencia de puesta a tierra esté conforme con las normas de protección y de funcionamiento de la instalación y se mantenga de esta manera a lo largo del tiempo. - Las corrientes de defecto a tierra y las corrientes de fuga puedan circular sin peligro, particularmente desde el punto de vista de solicitaciones térmicas, mecánicas y eléctricas. - La solidez o la protección mecánica quede asegurada con independencia de las condiciones estimadas de influencias externas. - Contemplen los posibles riesgos debidos a electrólisis que pudieran afectar a otras partes metálicas. 11.1. UNIONES A TIERRA. Tomas de tierra. Para la toma de tierra se pueden utilizar electrodos formados por: - barras, tubos; - pletinas, conductores desnudos; - placas; - anillos o mallas metálicas constituidos por los elementos anteriores o sus combinaciones; - armaduras de hormigón enterradas; con excepción de las armaduras pretensadas; - otras estructuras enterradas que se demuestre que son apropiadas. Los conductores de cobre utilizados como electrodos serán de construcción y resistencia eléctrica según la clase 2 de la norma UNE 21.022. El tipo y la profundidad de enterramiento de las tomas de tierra deben ser tales que la posible pérdida de humedad del suelo, la presencia del hielo u otros efectos climáticos, no aumenten la resistencia de la toma de tierra por encima del valor previsto. La profundidad nunca será inferior a 0,50 m. Conductores de tierra. La sección de los conductores de tierra, cuando estén enterrados, deberán estar de acuerdo con los valores indicados en la tabla siguiente. La sección no será inferior a la mínima exigida para los conductores de protección. Tipo Protegido mecánicamente No protegido mecánicamente Protegido contra la corrosión Igual a conductores protección apdo. 7.7.1 16 mm² Cu 16 mm² Acero Galvanizado No protegido contra la corrosión 25 mm² Cu 50 mm² Hierro 25 mm² Cu 50 mm² Hierro * La protección contra la corrosión puede obtenerse mediante una envolvente. Durante la ejecución de las uniones entre conductores de tierra y electrodos de tierra debe extremarse el cuidado para que resulten eléctricamente correctas. Debe cuidarse, en especial, que las conexiones, no dañen ni a los conductores ni a los electrodos de tierra. Página 19 de 22 Bornes de puesta a tierra. En toda instalación de puesta a tierra debe preverse un borne principal de tierra, al cual deben unirse los conductores siguientes: - Los conductores de tierra. - Los conductores de protección. - Los conductores de unión equipotencial principal. - Los conductores de puesta a tierra funcional, si son necesarios. Debe preverse sobre los conductores de tierra y en lugar accesible, un dispositivo que permita medir la resistencia de la toma de tierra correspondiente. Este dispositivo puede estar combinado con el borne principal de tierra, debe ser desmontable necesariamente por medio de un útil, tiene que ser mecánicamente seguro y debe asegurar la continuidad eléctrica. Conductores de protección. Los conductores de protección sirven para unir eléctricamente las masas de una instalación con el borne de tierra, con el fin de asegurar la protección contra contactos indirectos. Los conductores de protección tendrán una sección mínima igual a la fijada en la tabla siguiente: Sección conductores fase (mm²) Sf ≤ 16 16 < S f ≤ 35 Sf > 35 Sección conductores protección (mm²) Sf 16 Sf/2 En todos los casos, los conductores de protección que no forman parte de la canalización de alimentación serán de cobre con una sección, al menos de: - 2,5 mm2, si los conductores de protección disponen de una protección mecánica. - 4 mm2, si los conductores de protección no disponen de una protección mecánica. Como conductores de protección pueden utilizarse: - conductores en los cables multiconductores, o - conductores aislados o desnudos que posean una envolvente común con los conductores activos, o - conductores separados desnudos o aislados. Ningún aparato deberá ser intercalado en el conductor de protección. Las masas de los equipos a unir con los conductores de protección no deben ser conectadas en serie en un circuito de protección. 11.2. RESISTENCIA DE LAS TOMAS DE TIERRA. El valor de resistencia de tierra será tal que cualquier masa no pueda dar lugar a tensiones de contacto superiores a: - 24 V en local o emplazamiento conductor - 50 V en los demás casos. Si las condiciones de la instalación son tales que pueden dar lugar a tensiones de contacto superiores a los valores señalados anteriormente, se asegurará la rápida eliminación de la falta mediante dispositivos de corte adecuados a la corriente de servicio. Página 20 de 22 La resistencia de un electrodo depende de sus dimensiones, de su forma y de la resistividad del terreno en el que se establece. Esta resistividad varía frecuentemente de un punto a otro del terreno, y varía también con la profundidad. 11.3. TOMAS DE TIERRA INDEPENDIENTES. Se considerará independiente una toma de tierra respecto a otra, cuando una de las tomas de tierra, no alcance, respecto a un punto de potencial cero, una tensión superior a 50 V cuando por la otra circula la máxima corriente de defecto a tierra prevista. 11.4. REVISION DE LAS TOMAS DE TIERRA. Por la importancia que ofrece, desde el punto de vista de la seguridad cualquier instalación de toma de tierra, deberá ser obligatoriamente comprobada por el Director de la Obra o Instalador Autorizado en el momento de dar de alta la instalación para su puesta en marcha o en funcionamiento. Personal técnicamente competente efectuará la comprobación de la instalación de puesta a tierra, al menos anualmente, en la época en la que el terreno esté mas seco. Para ello, se medirá la resistencia de tierra, y se repararán con carácter urgente los defectos que se encuentren. En los lugares en que el terreno no sea favorable a la buena conservación de los electrodos, éstos y los conductores de enlace entre ellos hasta el punto de puesta a tierra, se pondrán al descubierto para su examen, al menos una vez cada cinco años. 12. RECEPTORES DE ALUMBRADO. Las luminarias serán conformes a los requisitos establecidos en las normas de la serie UNE-EN 60598. La masa de las luminarias suspendidas excepcionalmente de cables flexibles no deben exceder de 5 kg. Los conductores, que deben ser capaces de soportar este peso, no deben presentar empalmes intermedios y el esfuerzo deberá realizarse sobre un elemento distinto del borne de conexión. Las partes metálicas accesibles de las luminarias que no sean de Clase II o Clase III, deberán tener un elemento de conexión para su puesta a tierra, que irá conectado de manera fiable y permanente al conductor de protección del circuito. El uso de lámparas de gases con descargas a alta tensión (neón, etc), se permitirá cuando su ubicación esté fuera del volumen de accesibilidad o cuando se instalen barreras o envolventes separadoras. Los circuitos de alimentación estarán previstos para transportar la carga debida a los propios receptores, a sus elementos asociados y a sus corrientes armónicas y de arranque. Para receptores con lámparas de descarga, la carga mínima prevista en voltiamperios será de 1,8 veces la potencia en vatios de las lámparas. En el caso de distribuciones monofásicas, el conductor neutro tendrá la misma sección que los de fase. Será aceptable un coeficiente diferente para el cálculo de la sección de los conductores, siempre y cuando el factor de potencia de cada receptor sea mayor o igual a 0,9 y si se conoce la carga que supone cada uno de los elementos asociados a las lámparas y las corrientes de arranque, que tanto éstas como aquéllos puedan producir. En este caso, el coeficiente será el que resulte. En el caso de receptores con lámparas de descarga será obligatoria la compensación del factor de potencia hasta un valor mínimo de 0,9. Página 21 de 22 En instalaciones con lámparas de muy baja tensión (p.e. 12 V) debe preverse la utilización de transformadores adecuados, para asegurar una adecuada protección térmica, contra cortocircuitos y sobrecargas y contra los choques eléctricos. Para los rótulos luminosos y para instalaciones que los alimentan con tensiones asignadas de salida en vacío comprendidas entre 1 y 10 kV se aplicará lo dispuesto en la norma UNE-EN 50.107. 13. RECEPTORES A MOTOR. Los motores deben instalarse de manera que la aproximación a sus partes en movimiento no pueda ser causa de accidente. Los motores no deben estar en contacto con materias fácilmente combustibles y se situarán de manera que no puedan provocar la ignición de estas. Los conductores de conexión que alimentan a un solo motor deben estar dimensionados para una intensidad del 125 % de la intensidad a plena carga del motor. Los conductores de conexión que alimentan a varios motores, deben estar dimensionados para una intensidad no inferior a la suma del 125 % de la intensidad a plena carga del motor de mayor potencia, más la intensidad a plena carga de todos los demás. Los motores deben estar protegidos contra cortocircuitos y contra sobrecargas en todas sus fases, debiendo esta última protección ser de tal naturaleza que cubra, en los motores trifásicos, el riesgo de la falta de tensión en una de sus fases. En el caso de motores con arrancador estrellatriángulo, se asegurará la protección, tanto para la conexión en estrella como en triángulo. Los motores deben estar protegidos contra la falta de tensión por un dispositivo de corte automático de la alimentación, cuando el arranque espontáneo del motor, como consecuencia del restablecimiento de la tensión, pueda provocar accidentes, o perjudicar el motor, de acuerdo con la norma UNE 20.460 -4-45. Los motores deben tener limitada la intensidad absorbida en el arranque, cuando se pudieran producir efectos que perjudicasen a la instalación u ocasionasen perturbaciones inaceptables al funcionamiento de otros receptores o instalaciones. En general, los motores de potencia superior a 0,75 kilovatios deben estar provistos de reóstatos de arranque o dispositivos equivalentes que no permitan que la relación de corriente entre el período de arranque y el de marcha normal que corresponda a su plena carga, según las características del motor que debe indicar su placa, sea superior a la señalada en el cuadro siguiente: De 0,75 kW a 1,5 kW: 4,5 De 1,50 kW a 5 kW: 3,0 De 5 kW a 15 kW: 2 Más de 15 kW: 1,5 Página 22 de 22 CUADRO GENERAL DE MANDO Y PROTECCION Fórmulas Emplearemos las siguientes: Sistema Trifásico I = Pc / 1,732 x U x Cosϕ x R = amp (A) e = (L x Pc / k x U x n x S x R) + (L x Pc x Xu x Senϕ / 1000 x U x n x R x Cosϕ) = voltios (V) Sistema Monofásico: I = Pc / U x Cosϕ x R = amp (A) e = (2 x L x Pc / k x U x n x S x R) + (2 x L x Pc x Xu x Senϕ / 1000 x U x n x R x Cosϕ) = voltios (V) En donde: Pc = Potencia de Cálculo en Watios. L = Longitud de Cálculo en metros. e = Caída de tensión en Voltios. K = Conductividad. I = Intensidad en Amperios. U = Tensión de Servicio en Voltios (Trifásica ó Monofásica). S = Sección del conductor en mm². Cos ϕ = Coseno de fi. Factor de potencia. R = Rendimiento. (Para líneas motor). n = Nº de conductores por fase. Xu = Reactancia por unidad de longitud en mΩ/m. Fórmula Conductividad Eléctrica K = 1/ρ ρ = ρ20[1+α (T-20)] T = T0 + [(Tmax-T0) (I/Imax)²] Siendo, K = Conductividad del conductor a la temperatura T. ρ = Resistividad del conductor a la temperatura T. ρ20 = Resistividad del conductor a 20ºC. Cu = 0.018 Al = 0.029 α = Coeficiente de temperatura: Cu = 0.00392 Al = 0.00403 T = Temperatura del conductor (ºC). T0 = Temperatura ambiente (ºC): Cables enterrados = 25ºC Cables al aire = 40ºC Tmax = Temperatura máxima admisible del conductor (ºC): XLPE, EPR = 90ºC PVC = 70ºC I = Intensidad prevista por el conductor (A). Imax = Intensidad máxima admisible del conductor (A). Fórmulas Sobrecargas Ib ≤ In ≤ Iz Página 1 de 59 I2 ≤ 1,45 Iz Donde: Ib: intensidad utilizada en el circuito. Iz: intensidad admisible de la canalización según la norma UNE 20-460/5-523. In: intensidad nominal del dispositivo de protección. Para los dispositivos de protección regulables, In es la intensidad de regulación escogida. I2: intensidad que asegura efectivamente el funcionamiento del dispositivo de protección. En la práctica I2 se toma igual: - a la intensidad de funcionamiento en el tiempo convencional, para los interruptores automáticos (1,45 In como máximo). - a la intensidad de fusión en el tiempo convencional, para los fusibles (1,6 In). Fórmulas compensación energía reactiva cosØ = P/√(P²+ Q²). tgØ = Q/P. Qc = Px(tgØ1-tgØ2). C = Qcx1000/U²xω; (Monofásico - Trifásico conexión estrella). C = Qcx1000/3xU²xω; (Trifásico conexión triángulo). Siendo: P = Potencia activa instalación (kW). Q = Potencia reactiva instalación (kVAr). Qc = Potencia reactiva a compensar (kVAr). Ø1 = Angulo de desfase de la instalación sin compensar. Ø2 = Angulo de desfase que se quiere conseguir. U = Tensión compuesta (V). ω = 2xPixf ; f = 50 Hz. C = Capacidad condensadores (F); cx1000000(µF). Fórmulas Cortocircuito * IpccI = Ct U / √3 Zt Siendo, IpccI: intensidad permanente de c.c. en inicio de línea en kA. Ct: Coeficiente de tensión. U: Tensión trifásica en V. Zt: Impedancia total en mohm, aguas arriba del punto de c.c. (sin incluir la línea o circuito en estudio). * IpccF = Ct UF / 2 Zt Siendo, IpccF: Intensidad permanente de c.c. en fin de línea en kA. Ct: Coeficiente de tensión. UF: Tensión monofásica en V. Zt: Impedancia total en mohm, incluyendo la propia de la línea o circuito (por tanto es igual a la impedancia en origen mas la propia del conductor o línea). * La impedancia total hasta el punto de cortocircuito será: Zt = (Rt² + Xt²)½ Siendo, Rt: R1 + R2 + ................+ Rn (suma de las resistencias de las líneas aguas arriba hasta el punto de c.c.) Página 2 de 59 Xt: X1 + X2 + .............. + Xn (suma de las reactancias de las líneas aguas arriba hasta el punto de c.c.) (mohm) R = L · 1000 · CR / K · S · n X = Xu · L / n (mohm) R: Resistencia de la línea en mohm. X: Reactancia de la línea en mohm. L: Longitud de la línea en m. CR: Coeficiente de resistividad. K: Conductividad del metal. S: Sección de la línea en mm². Xu: Reactancia de la línea, en mohm por metro. n: nº de conductores por fase. * tmcicc = Cc · S² / IpccF² Siendo, tmcicc: Tiempo máximo en sg que un conductor soporta una Ipcc. Cc= Constante que depende de la naturaleza del conductor y de su aislamiento. S: Sección de la línea en mm². IpccF: Intensidad permanente de c.c. en fin de línea en A. * tficc = cte. fusible / IpccF² Siendo, tficc: tiempo de fusión de un fusible para una determinada intensidad de cortocircuito. IpccF: Intensidad permanente de c.c. en fin de línea en A. * Lmax = 0,8 UF / 2 · IF5 · √(1,5 / K· S · n)² + (Xu / n · 1000)² Siendo, Lmax: Longitud máxima de conductor protegido a c.c. (m) (para protección por fusibles) UF: Tensión de fase (V) K: Conductividad S: Sección del conductor (mm²) Xu: Reactancia por unidad de longitud (mohm/m). En conductores aislados suele ser 0,1. n: nº de conductores por fase Ct= 0,8: Es el coeficiente de tensión. CR = 1,5: Es el coeficiente de resistencia. IF5 = Intensidad de fusión en amperios de fusibles en 5 sg. * Curvas válidas.(Para protección de Interruptores automáticos dotados de Relé electromagnético). CURVA B CURVA C CURVA D Y MA IMAG = 5 In IMAG = 10 In IMAG = 20 In Fórmulas Embarrados Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) Siendo, σmax: Tensión máxima en las pletinas (kg/cm²) Ipcc: Intensidad permanente de c.c. (kA) Página 3 de 59 L: Separación entre apoyos (cm) d: Separación entre pletinas (cm) n: nº de pletinas por fase Wy: Módulo resistente por pletina eje y-y (cm³) σadm: Tensión admisible material (kg/cm²) Comprobación por solicitación térmica en cortocircuito Icccs = Kc · S / ( 1000 · √tcc) Siendo, Ipcc: Intensidad permanente de c.c. (kA) Icccs: Intensidad de c.c. soportada por el conductor durante el tiempo de duración del c.c. (kA) S: Sección total de las pletinas (mm²) tcc: Tiempo de duración del cortocircuito (s) Kc: Constante del conductor: Cu = 164, Al = 107 DEMANDA DE POTENCIAS - Potencia total instalada: EMERG. AL. GYM T.C. GYM F/C GYM BAR F/C Z. COMUN EMERG BAÑOS GYM BAÑOS GRAL. VESTIBL Z. COMUNES SALA CALDERAS MEDICO PODOLOGO 1ª PLANTA TOTAL.... 100 W 500 W 2000 W 150 W 24200 W 800 W 250 W 250 W 350 W 400 W 87600 W 5700 W 6850 W 23050 W 152200 W - Potencia Instalada Alumbrado (W): 12450 - Potencia Instalada Fuerza (W): 139750 - Potencia Máxima Admisible (W): 138560 Cálculo de la ACOMETIDA - Tensión de servicio: 400 V. - Canalización: Enterrados Bajo Tubo (R.Subt) - Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 152200 W. - Potencia de cálculo: (Según ITC-BT-44): 162160 W.(Coef. de Simult.: 1 ) I=162160/1,732x400x0.8=292.58 A. Se eligen conductores Unipolares 3x185/95mm²Al Nivel Aislamiento, Aislamiento: 0.6/1 kV, XLPE. Desig. UNE: RV-Al I.ad. a 25°C (Fc=0.8) 300 A. según ITC-BT-07 Diámetro exterior tubo: 180 mm. Página 4 de 59 Caída de tensión: Temperatura cable (ºC): 86.82 e(parcial)=20x162160/27.17x400x185=1.61 V.=0.4 % e(total)=0.4% ADMIS (2% MAX.) Cálculo de la LINEA GENERAL DE ALIMENTACION - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 152200 W. - Potencia de cálculo: (Según ITC-BT-44): 162160 W.(Coef. de Simult.: 1 ) I=162160/1,732x400x0.8=292.58 A. Se eligen conductores Unipolares 4x240+TTx120mm²Cu Nivel Aislamiento, Aislamiento: 0.6/1 kV, XLPE+Pol - No propagador incendio y emisión humos y opacidad reducida -. Desig. UNE: RZ1-K(AS) I.ad. a 40°C (Fc=1) 401 A. según ITC-BT-19 Diámetro exterior tubo: 200 mm. Caída de tensión: Temperatura cable (ºC): 66.62 e(parcial)=10x162160/46.97x400x240=0.36 V.=0.09 % e(total)=0.09% ADMIS (4.5% MAX.) Prot. Térmica: Fusibles Int. 315 A. Cálculo de la DERIVACION INDIVIDUAL - Tensión de servicio: 400 V. - Canalización: Enterrados Bajo Tubo (R.Subt) - Longitud: 15 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 152200 W. - Potencia de cálculo: (Según ITC-BT-44): 129728 W.(Coef. de Simult.: 0.8 ) I=129728/1,732x400x0.8=234.06 A. Se eligen conductores Unipolares 4x95+TTx50mm²Cu Nivel Aislamiento, Aislamiento: 0.6/1 kV, XLPE+Pol - No propagador incendio y emisión humos y opacidad reducida -. Desig. UNE: RZ1-K(AS) I.ad. a 25°C (Fc=0.8) 268 A. según ITC-BT-07 Diámetro exterior tubo: 125 mm. Caída de tensión: Temperatura cable (ºC): 74.58 e(parcial)=15x129728/45.76x400x95=1.12 V.=0.28 % e(total)=0.37% ADMIS (4.5% MAX.) Prot. Térmica: I. Aut./Tet. In.: 250 A. Térmico reg. Int.Reg.: 250 A. Página 5 de 59 Cálculo de la Línea: GYM - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2750 W. - Potencia de cálculo: (Según ITC-BT-44): 1938 W.(Coef. de Simult.: 0.6 ) I=1938/230x0.8=10.53 A. Se eligen conductores Unipolares 2x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 46.29 e(parcial)=2x0.3x1938/50.36x230x2.5=0.04 V.=0.02 % e(total)=0.39% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: EMERG. - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 100 W. - Potencia de cálculo: (Según ITC-BT-44): 100x1.8=180 W. I=180/230x1=0.78 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.08 e(parcial)=2x20x180/51.5x230x1.5=0.41 V.=0.18 % e(total)=0.56% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. GYM - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 500 W. - Potencia de cálculo: (Según ITC-BT-44): 500x1.8=900 W. Página 6 de 59 I=900/230x1=3.91 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 42.04 e(parcial)=2x20x900/51.14x230x1.5=2.04 V.=0.89 % e(total)=1.27% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: T.C. GYM - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 25 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x25x2000/50.05x230x2.5=3.47 V.=1.51 % e(total)=1.9% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: F/C GYM - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 150 W. - Potencia de cálculo: 150 W. I=150/230x0.8=0.82 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.05 e(parcial)=2x10x150/51.51x230x2.5=0.1 V.=0.04 % e(total)=0.43% ADMIS (6.5% MAX.) Página 7 de 59 Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: BAR - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 24200 W. - Potencia de cálculo: (Según ITC-BT-44): 18284 W.(Coef. de Simult.: 0.7 ) I=18284/1,732x400x0.8=32.99 A. Se eligen conductores Unipolares 4x10+TTx10mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 44 A. según ITC-BT-19 Diámetro exterior tubo: 32 mm. Caída de tensión: Temperatura cable (ºC): 56.86 e(parcial)=10x18284/48.54x400x10=0.94 V.=0.24 % e(total)=0.61% ADMIS (4.5% MAX.) Protección Termica en Principio de Línea I. Mag. Tetrapolar Int. 40 A. SUBCUADRO BAR DEMANDA DE POTENCIAS - Potencia total instalada: EMERG AL. ESTAR I AL. ESTAR II EMERG AL. COMEDOR I AL. COMEDOR II EMERG AL. COCINA AL. BARRA F/C BAR COMEDOR EXTRACTOR TC. DESPACHO BAR CAFETERA BOTELLEROS T.C. COCINA I T.C. COCINA II T.C. COCINA III PLANCHA/FREID TOTAL.... 200 W 300 W 300 W 200 W 300 W 300 W 200 W 300 W 300 W 800 W 1000 W 2000 W 5000 W 2000 W 2000 W 3000 W 3000 W 3000 W 24200 W - Potencia Instalada Alumbrado (W): 2400 - Potencia Instalada Fuerza (W): 21800 Página 8 de 59 Cálculo de la Línea: - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 800 W. - Potencia de cálculo: (Según ITC-BT-44): 864 W.(Coef. de Simult.: 0.6 ) I=864/1,732x400x0.8=1.56 A. Se eligen conductores Unipolares 4x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 40.17 e(parcial)=0.3x864/51.49x400x2.5=0.01 V.=0 % e(total)=0.61% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 10 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 200 W. - Potencia de cálculo: (Según ITC-BT-44): 200x1.8=360 W. I=360/230x1=1.57 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.17 e(parcial)=2x8x360/51.49x230x2.5=0.19 V.=0.08 % e(total)=0.69% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. ESTAR I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. Página 9 de 59 I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.37 e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 % e(total)=0.73% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. ESTAR II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.37 e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 % e(total)=0.73% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 800 W. - Potencia de cálculo: (Según ITC-BT-44): 864 W.(Coef. de Simult.: 0.6 ) I=864/1,732x400x0.8=1.56 A. Se eligen conductores Unipolares 4x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 40.17 e(parcial)=0.3x864/51.49x400x2.5=0.01 V.=0 % e(total)=0.61% ADMIS (4.5% MAX.) Página 10 de 59 Prot. Térmica: I. Mag. Tetrapolar Int. 10 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 200 W. - Potencia de cálculo: (Según ITC-BT-44): 200x1.8=360 W. I=360/230x1=1.57 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.17 e(parcial)=2x8x360/51.49x230x2.5=0.19 V.=0.08 % e(total)=0.69% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. COMEDOR I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.37 e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 % e(total)=0.73% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. COMEDOR II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra Página 11 de 59 - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.37 e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 % e(total)=0.73% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 800 W. - Potencia de cálculo: (Según ITC-BT-44): 864 W.(Coef. de Simult.: 0.6 ) I=864/1,732x400x0.8=1.56 A. Se eligen conductores Unipolares 4x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 40.17 e(parcial)=0.3x864/51.49x400x2.5=0.01 V.=0 % e(total)=0.61% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 10 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 200 W. - Potencia de cálculo: (Según ITC-BT-44): 200x1.8=360 W. I=360/230x1=1.57 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K Página 12 de 59 I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.17 e(parcial)=2x8x360/51.49x230x2.5=0.19 V.=0.08 % e(total)=0.69% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. COCINA - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.37 e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 % e(total)=0.73% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. BARRA - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.37 e(parcial)=2x8x540/51.45x230x2.5=0.29 V.=0.13 % e(total)=0.73% ADMIS (4.5% MAX.) Prot. Térmica: Página 13 de 59 I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 10800 W. - Potencia de cálculo: 10800 W.(Coef. de Simult.: 1 ) I=10800/1,732x400x0.8=19.49 A. Se eligen conductores Unipolares 4x4mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 27 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 55.63 e(parcial)=0.3x10800/48.75x400x4=0.04 V.=0.01 % e(total)=0.62% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 20 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: F/C BAR COMEDOR - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 800 W. - Potencia de cálculo: 800 W. I=800/230x0.8=4.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 41.29 e(parcial)=2x15x800/51.28x230x2.5=0.81 V.=0.35 % e(total)=0.97% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: EXTRACTOR - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1000 W. - Potencia de cálculo: 1000 W. Página 14 de 59 I=1000/1,732x400x0.8=1.8 A. Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.29 e(parcial)=10x1000/51.46x400x2.5=0.19 V.=0.05 % e(total)=0.66% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: TC. DESPACHO BAR - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x20x2000/50.05x230x2.5=2.78 V.=1.21 % e(total)=1.82% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: CAFETERA - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 5 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 5000 W. - Potencia de cálculo: 5000 W. I=5000/1,732x400x0.8=9.02 A. Se eligen conductores Unipolares 4x4+TTx4mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 24 A. según ITC-BT-19 Diámetro exterior tubo: 25 mm. Caída de tensión: Temperatura cable (ºC): 44.24 e(parcial)=5x5000/50.73x400x4=0.31 V.=0.08 % e(total)=0.69% ADMIS (6.5% MAX.) Página 15 de 59 Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: BOTELLEROS - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/1,732x400x0.8=3.61 A. Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 41.14 e(parcial)=10x2000/51.3x400x2.5=0.39 V.=0.1 % e(total)=0.71% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 11000 W. - Potencia de cálculo: 7700 W.(Coef. de Simult.: 0.7 ) I=7700/1,732x400x0.8=13.89 A. Se eligen conductores Unipolares 4x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 53.13 e(parcial)=0.3x7700/49.17x400x2.5=0.05 V.=0.01 % e(total)=0.62% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: T.C. COCINA I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. Página 16 de 59 - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 % e(total)=1.22% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: T.C. COCINA II - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 3000 W. - Potencia de cálculo: 3000 W. I=3000/1,732x400x0.8=5.41 A. Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.57 e(parcial)=10x3000/51.04x400x2.5=0.59 V.=0.15 % e(total)=0.76% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: T.C. COCINA III - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 3000 W. - Potencia de cálculo: 3000 W. I=3000/1,732x400x0.8=5.41 A. Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.57 e(parcial)=10x3000/51.04x400x2.5=0.59 V.=0.15 % Página 17 de 59 e(total)=0.76% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: PLANCHA/FREID - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 3000 W. - Potencia de cálculo: 3000 W. I=3000/1,732x400x0.8=5.41 A. Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.57 e(parcial)=8x3000/51.04x400x2.5=0.47 V.=0.12 % e(total)=0.73% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. CALCULO DE EMBARRADO BAR Datos - Metal: Cu - Estado pletinas: desnudas - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 45 - Ancho (mm): 15 - Espesor (mm): 3 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.112, 0.084, 0.022, 0.003 - I. admisible del embarrado (A): 170 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =4.57² · 25² /(60 · 10 · 0.022 · 1) = 989.437 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 32.99 A Iadm = 170 A Página 18 de 59 c) Comprobación por solicitación térmica en cortocircuito Ipcc = 4.57 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 45 · 1 / (1000 · √0.5) = 10.44 kA Cálculo de la Línea: AL. GEN P_BA - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2050 W. - Potencia de cálculo: (Según ITC-BT-44): 1830 W.(Coef. de Simult.: 0.6 ) I=1830/1,732x400x0.8=3.3 A. Se eligen conductores Unipolares 4x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 40.74 e(parcial)=0.3x1830/51.38x400x2.5=0.01 V.=0 % e(total)=0.37% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: F/C Z. COMUN - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 800 W. - Potencia de cálculo: 800 W. I=800/230x0.8=4.35 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 41.29 e(parcial)=2x20x800/51.28x230x2.5=1.09 V.=0.47 % e(total)=0.84% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. Página 19 de 59 - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 250 W. - Potencia de cálculo: (Según ITC-BT-44): 250x1.8=450 W. I=450/230x1=1.96 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.51 e(parcial)=2x15x450/51.42x230x1.5=0.76 V.=0.33 % e(total)=0.7% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: BAÑOS GYM - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 25 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 250 W. - Potencia de cálculo: (Según ITC-BT-44): 250x1.8=450 W. I=450/230x1=1.96 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.51 e(parcial)=2x25x450/51.42x230x1.5=1.27 V.=0.55 % e(total)=0.92% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: BAÑOS GRAL. - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 350 W. - Potencia de cálculo: (Según ITC-BT-44): 350x1.8=630 W. I=630/230x1=2.74 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K Página 20 de 59 I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.51 e(parcial)=2x10x630/51.42x230x2.5=0.43 V.=0.19 % e(total)=0.56% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: VESTIBL Z. COMUNES - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x20x720/51.27x230x1.5=1.63 V.=0.71 % e(total)=1.08% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: SALA CALDERAS - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 25 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 87600 W. - Potencia de cálculo: (Según ITC-BT-44): 88880 W.(Coef. de Simult.: 1 ) I=88880/1,732x400x0.8=160.36 A. Se eligen conductores Unipolares 4x95+TTx50mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 180 A. según ITC-BT-19 Diámetro exterior tubo: 75 mm. Caída de tensión: Temperatura cable (ºC): 63.81 e(parcial)=25x88880/47.41x400x95=1.23 V.=0.31 % e(total)=0.68% ADMIS (4.5% MAX.) Página 21 de 59 Protección Termica en Principio de Línea I. Aut./Tet. In.: 250 A. Térmico reg. Int.Reg.: 170 A. SUBCUADRO SALA CALDERAS DEMANDA DE POTENCIAS - Potencia total instalada: RESERVA ENFRIADORA VENTILACION CALDERA T.C. S. CALD EMERG A.L. AZOTEA AL. S. CALD AL. EXT I AL. EXT I TOTAL.... 80000 W 3000 W 1000 W 2000 W 200 W 300 W 300 W 400 W 400 W 87600 W - Potencia Instalada Alumbrado (W): 1600 - Potencia Instalada Fuerza (W): 86000 Cálculo de la Línea: RESERVA ENFRIADORA - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 80000 W. - Potencia de cálculo: 80000 W. I=80000/1,732x400x0.8=144.34 A. Se eligen conductores Unipolares 4x70+TTx35mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 149 A. según ITC-BT-19 Diámetro exterior tubo: 63 mm. Caída de tensión: Temperatura cable (ºC): 68.15 e(parcial)=10x80000/46.73x400x70=0.61 V.=0.15 % e(total)=0.83% ADMIS (6.5% MAX.) Prot. Térmica: I. Aut./Tet. In.: 160 A. Térmico reg. Int.Reg.: 147 A. Protección diferencial: Relé y Transfor. Diferencial Sens.: 30 mA. Cálculo de la Línea: LF. GENERAL - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; Página 22 de 59 - Potencia a instalar: 6000 W. - Potencia de cálculo: 3600 W.(Coef. de Simult.: 0.6 ) I=3600/1,732x400x0.8=6.5 A. Se eligen conductores Unipolares 4x6mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 36 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 40.98 e(parcial)=0.3x3600/51.33x400x6=0.01 V.=0 % e(total)=0.68% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: VENTILACION - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 25 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 3000 W. - Potencia de cálculo: 3000 W. I=3000/1,732x400x0.8=5.41 A. Se eligen conductores Unipolares 4x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 18.5 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.57 e(parcial)=25x3000/51.04x400x2.5=1.47 V.=0.37 % e(total)=1.05% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: CALDERA - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1000 W. - Potencia de cálculo: 1000 W. I=1000/230x0.8=5.43 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Página 23 de 59 Caída de tensión: Temperatura cable (ºC): 42.01 e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 % e(total)=0.98% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: T.C. S. CALD - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 5 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/1,732x400x0.8=3.61 A. Se eligen conductores Unipolares 4x6+TTx6mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 32 A. según ITC-BT-19 Diámetro exterior tubo: 25 mm. Caída de tensión: Temperatura cable (ºC): 40.38 e(parcial)=5x2000/51.45x400x6=0.08 V.=0.02 % e(total)=0.7% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 16 A. Cálculo de la Línea: LA. GENERAL - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1600 W. - Potencia de cálculo: (Según ITC-BT-44): 1728 W.(Coef. de Simult.: 0.6 ) I=1728/230x0.8=9.39 A. Se eligen conductores Unipolares 2x1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 49.72 e(parcial)=2x0.3x1728/49.76x230x1.5=0.06 V.=0.03 % e(total)=0.7% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Página 24 de 59 Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 200 W. - Potencia de cálculo: (Según ITC-BT-44): 200x1.8=360 W. I=360/230x1=1.57 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.33 e(parcial)=2x20x360/51.46x230x1.5=0.81 V.=0.35 % e(total)=1.06% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: A.L. AZOTEA - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.73 e(parcial)=2x20x540/51.38x230x1.5=1.22 V.=0.53 % e(total)=1.23% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. S. CALD - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. Página 25 de 59 I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.73 e(parcial)=2x10x540/51.38x230x1.5=0.61 V.=0.26 % e(total)=0.97% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. EXT I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x20x720/51.27x230x1.5=1.63 V.=0.71 % e(total)=1.41% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. EXT I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x20x720/51.27x230x1.5=1.63 V.=0.71 % Página 26 de 59 e(total)=1.41% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. CALCULO DE EMBARRADO SALA CALDERAS Datos - Metal: Cu - Estado pletinas: desnudas - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 120 - Ancho (mm): 40 - Espesor (mm): 3 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.8, 1.6, 0.06, 0.009 - I. admisible del embarrado (A): 420 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =7.43² · 25² /(60 · 10 · 0.06 · 1) = 957.283 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 160.36 A Iadm = 420 A c) Comprobación por solicitación térmica en cortocircuito Ipcc = 7.43 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 120 · 1 / (1000 · √0.5) = 27.83 kA Cálculo de la Línea: MEDICO - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 5700 W. - Potencia de cálculo: (Según ITC-BT-44): 4662 W.(Coef. de Simult.: 0.7 ) I=4662/230x0.8=25.34 A. Se eligen conductores Unipolares 2x6+TTx6mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 36 A. según ITC-BT-19 Diámetro exterior tubo: 25 mm. Página 27 de 59 Caída de tensión: Temperatura cable (ºC): 54.86 e(parcial)=2x10x4662/48.88x230x6=1.38 V.=0.6 % e(total)=0.97% ADMIS (4.5% MAX.) Protección Termica en Principio de Línea I. Mag. Bipolar Int. 30 A. SUBCUADRO MEDICO DEMANDA DE POTENCIAS - Potencia total instalada: AL. COMUN AL. CONSULTAS AL. ENFER - CURAS EMERG TC. MEDIC II TC. MEDIC I TC. RESTO TOTAL.... 300 W 350 W 350 W 200 W 1500 W 1500 W 1500 W 5700 W - Potencia Instalada Alumbrado (W): 1200 - Potencia Instalada Fuerza (W): 4500 Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1200 W. - Potencia de cálculo: (Según ITC-BT-44): 2160 W.(Coef. de Simult.: 1 ) I=2160/230x0.8=11.74 A. Se eligen conductores Unipolares 2x1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 55.19 e(parcial)=2x0.3x2160/48.82x230x1.5=0.08 V.=0.03 % e(total)=1% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: AL. COMUN - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra Página 28 de 59 - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.73 e(parcial)=2x15x540/51.38x230x1.5=0.91 V.=0.4 % e(total)=1.4% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. CONSULTAS - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 350 W. - Potencia de cálculo: (Según ITC-BT-44): 350x1.8=630 W. I=630/230x1=2.74 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41 e(parcial)=2x10x630/51.33x230x1.5=0.71 V.=0.31 % e(total)=1.31% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. ENFER - CURAS - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 350 W. - Potencia de cálculo: (Según ITC-BT-44): 350x1.8=630 W. I=630/230x1=2.74 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Página 29 de 59 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41 e(parcial)=2x10x630/51.33x230x1.5=0.71 V.=0.31 % e(total)=1.31% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 200 W. - Potencia de cálculo: (Según ITC-BT-44): 200x1.8=360 W. I=360/230x1=1.57 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.33 e(parcial)=2x15x360/51.46x230x1.5=0.61 V.=0.26 % e(total)=1.27% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 4500 W. - Potencia de cálculo: 4500 W.(Coef. de Simult.: 1 ) I=4500/230x0.8=24.46 A. Se eligen conductores Unipolares 2x4mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 31 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 58.67 e(parcial)=2x0.3x4500/48.24x230x4=0.06 V.=0.03 % e(total)=1% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 25 A. Protección diferencial: Página 30 de 59 Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: TC. MEDIC II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=1.44% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC. MEDIC I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=1.44% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC. RESTO - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Página 31 de 59 Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=1.44% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. CALCULO DE EMBARRADO MEDICO Datos - Metal: Cu - Estado pletinas: desnudas - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 30 - Ancho (mm): 15 - Espesor (mm): 2 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.075, 0.0562, 0.01, 0.001 - I. admisible del embarrado (A): 140 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =3.38² · 25² /(60 · 10 · 0.01 · 1) = 1191.4 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 25.34 A Iadm = 140 A c) Comprobación por solicitación térmica en cortocircuito Ipcc = 3.38 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 30 · 1 / (1000 · √0.5) = 6.96 kA Cálculo de la Línea: PODOLOGO - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 6850 W. - Potencia de cálculo: (Según ITC-BT-44): 5271 W.(Coef. de Simult.: 0.7 ) Página 32 de 59 I=5271/230x0.8=28.65 A. Se eligen conductores Unipolares 2x10+TTx10mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 50 A. según ITC-BT-19 Diámetro exterior tubo: 25 mm. Caída de tensión: Temperatura cable (ºC): 49.85 e(parcial)=2x20x5271/49.74x230x10=1.84 V.=0.8 % e(total)=1.17% ADMIS (4.5% MAX.) Protección Termica en Principio de Línea I. Mag. Bipolar Int. 40 A. SUBCUADRO PODOLOGO DEMANDA DE POTENCIAS - Potencia total instalada: AL. COMUN AL. CONSULTAS EMERG TC. LAVAND TC. CONSULT TC. RESTO TOTAL.... 300 W 350 W 200 W 3000 W 1500 W 1500 W 6850 W - Potencia Instalada Alumbrado (W): 850 - Potencia Instalada Fuerza (W): 6000 Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 850 W. - Potencia de cálculo: (Según ITC-BT-44): 1530 W.(Coef. de Simult.: 1 ) I=1530/230x0.8=8.32 A. Se eligen conductores Unipolares 2x1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 47.62 e(parcial)=2x0.3x1530/50.13x230x1.5=0.05 V.=0.02 % e(total)=1.19% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Página 33 de 59 Cálculo de la Línea: AL. COMUN - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 300 W. - Potencia de cálculo: (Según ITC-BT-44): 300x1.8=540 W. I=540/230x1=2.35 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.73 e(parcial)=2x15x540/51.38x230x1.5=0.91 V.=0.4 % e(total)=1.59% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AL. CONSULTAS - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 350 W. - Potencia de cálculo: (Según ITC-BT-44): 350x1.8=630 W. I=630/230x1=2.74 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41 e(parcial)=2x10x630/51.33x230x1.5=0.71 V.=0.31 % e(total)=1.5% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 200 W. - Potencia de cálculo: (Según ITC-BT-44): 200x1.8=360 W. Página 34 de 59 I=360/230x1=1.57 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.33 e(parcial)=2x15x360/51.46x230x1.5=0.61 V.=0.26 % e(total)=1.46% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 6000 W. - Potencia de cálculo: 6000 W.(Coef. de Simult.: 1 ) I=6000/230x0.8=32.61 A. Se eligen conductores Unipolares 2x6mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 40 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 59.94 e(parcial)=2x0.3x6000/48.04x230x6=0.05 V.=0.02 % e(total)=1.19% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 40 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: TC. LAVAND - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 3000 W. - Potencia de cálculo: 3000 W. I=3000/230x0.8=16.3 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 58.08 e(parcial)=2x10x3000/48.34x230x2.5=2.16 V.=0.94 % Página 35 de 59 e(total)=2.13% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 20 A. Cálculo de la Línea: TC. CONSULT - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=1.64% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC. RESTO - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=1.64% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. CALCULO DE EMBARRADO PODOLOGO Datos - Metal: Cu - Estado pletinas: desnudas Página 36 de 59 - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 24 - Ancho (mm): 12 - Espesor (mm): 2 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.048, 0.0288, 0.008, 0.0008 - I. admisible del embarrado (A): 110 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =2.99² · 25² /(60 · 10 · 0.008 · 1) = 1165.256 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 28.65 A Iadm = 110 A c) Comprobación por solicitación térmica en cortocircuito Ipcc = 2.99 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 24 · 1 / (1000 · √0.5) = 5.57 kA Cálculo de la Línea: 1ª PLANTA - Tensión de servicio: 400 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 23050 W. - Potencia de cálculo: (Según ITC-BT-44): 18683 W.(Coef. de Simult.: 0.7 ) I=18683/1,732x400x0.8=33.71 A. Se eligen conductores Unipolares 4x10+TTx10mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 44 A. según ITC-BT-19 Diámetro exterior tubo: 32 mm. Caída de tensión: Temperatura cable (ºC): 57.61 e(parcial)=10x18683/48.42x400x10=0.96 V.=0.24 % e(total)=0.61% ADMIS (4.5% MAX.) Protección Termica en Principio de Línea I. Mag. Tetrapolar Int. 40 A. Protección Térmica en Final de Línea I. Mag. Tetrapolar Int. 40 A. Protección diferencial en Principio de Línea Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Página 37 de 59 SUBCUADRO 1ª PLANTA DEMANDA DE POTENCIAS - Potencia total instalada: BIBLIO I BIBLIO II BIBLIO III BAÑOS/COMUN EMERG TC BIBL I TC BIBL I TC BIBL I TC DESP BIB AULA EMERG SALA I SALA II SALA III SALA IV TC SALA I TC SALA II TC SALA III TC SALA IV TOTAL.... 400 W 400 W 400 W 350 W 250 W 1000 W 1000 W 1000 W 1500 W 6900 W 250 W 400 W 400 W 400 W 400 W 2000 W 2000 W 2000 W 2000 W 23050 W - Potencia Instalada Alumbrado (W): 4550 - Potencia Instalada Fuerza (W): 18500 Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1800 W. - Potencia de cálculo: (Según ITC-BT-44): 2592 W.(Coef. de Simult.: 0.8 ) I=2592/230x0.8=14.09 A. Se eligen conductores Unipolares 2x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 51.25 e(parcial)=2x0.3x2592/49.49x230x2.5=0.05 V.=0.02 % e(total)=0.63% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Página 38 de 59 Cálculo de la Línea: BIBLIO I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.17% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: BIBLIO II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.17% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: BIBLIO III - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. Página 39 de 59 I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.17% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: BAÑOS/COMUN - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 350 W. - Potencia de cálculo: (Según ITC-BT-44): 350x1.8=630 W. I=630/230x1=2.74 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 40.51 e(parcial)=2x8x630/51.42x230x2.5=0.34 V.=0.15 % e(total)=0.78% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 250 W. - Potencia de cálculo: (Según ITC-BT-44): 250x1.8=450 W. I=450/230x1=1.96 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.51 e(parcial)=2x10x450/51.42x230x1.5=0.51 V.=0.22 % Página 40 de 59 e(total)=0.86% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 4500 W. - Potencia de cálculo: 2700 W.(Coef. de Simult.: 0.6 ) I=2700/230x0.8=14.67 A. Se eligen conductores Unipolares 2x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 52.21 e(parcial)=2x0.3x2700/49.33x230x2.5=0.06 V.=0.02 % e(total)=0.64% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: TC BIBL I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1000 W. - Potencia de cálculo: 1000 W. I=1000/230x0.8=5.43 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.01 e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 % e(total)=0.93% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC BIBL I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra Página 41 de 59 - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1000 W. - Potencia de cálculo: 1000 W. I=1000/230x0.8=5.43 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.01 e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 % e(total)=0.93% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC BIBL I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1000 W. - Potencia de cálculo: 1000 W. I=1000/230x0.8=5.43 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 42.01 e(parcial)=2x10x1000/51.14x230x2.5=0.68 V.=0.3 % e(total)=0.93% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC DESP BIB - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Página 42 de 59 Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=1.08% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: AULA - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 20 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 6900 W. - Potencia de cálculo: (Según ITC-BT-44): 5334 W.(Coef. de Simult.: 0.7 ) I=5334/230x0.8=28.99 A. Se eligen conductores Unipolares 2x6+TTx6mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 36 A. según ITC-BT-19 Diámetro exterior tubo: 25 mm. Caída de tensión: Temperatura cable (ºC): 59.45 e(parcial)=2x20x5334/48.11x230x6=3.21 V.=1.4 % e(total)=2.01% ADMIS (4.5% MAX.) Protección Termica en Principio de Línea I. Mag. Bipolar Int. 30 A. SUBCUADRO AULA DEMANDA DE POTENCIAS - Potencia total instalada: EMERG AULA II AULA I TC I TC II TC III RACK TOTAL.... 100 W 400 W 400 W 1500 W 1500 W 1500 W 1500 W 6900 W - Potencia Instalada Alumbrado (W): 900 - Potencia Instalada Fuerza (W): 6000 Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared Página 43 de 59 - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 900 W. - Potencia de cálculo: (Según ITC-BT-44): 1620 W.(Coef. de Simult.: 1 ) I=1620/230x0.8=8.8 A. Se eligen conductores Unipolares 2x1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 16.5 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 48.54 e(parcial)=2x0.3x1620/49.97x230x1.5=0.06 V.=0.02 % e(total)=2.03% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 100 W. - Potencia de cálculo: (Según ITC-BT-44): 100x1.8=180 W. I=180/230x1=0.78 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 40.08 e(parcial)=2x8x180/51.5x230x1.5=0.16 V.=0.07 % e(total)=2.1% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AULA II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K Página 44 de 59 I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x10x720/51.27x230x1.5=0.81 V.=0.35 % e(total)=2.39% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: AULA I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 8 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x8x720/51.27x230x1.5=0.65 V.=0.28 % e(total)=2.32% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 6000 W. - Potencia de cálculo: 3600 W.(Coef. de Simult.: 0.6 ) I=3600/230x0.8=19.57 A. Se eligen conductores Unipolares 2x2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 23 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 61.71 e(parcial)=2x0.3x3600/47.75x230x2.5=0.08 V.=0.03 % e(total)=2.04% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 20 A. Página 45 de 59 Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: TC I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=2.49% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=2.49% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC III - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. Página 46 de 59 I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=2.49% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: RACK - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1500 W. - Potencia de cálculo: 1500 W. I=1500/230x0.8=8.15 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 44.52 e(parcial)=2x10x1500/50.68x230x2.5=1.03 V.=0.45 % e(total)=2.49% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. CALCULO DE EMBARRADO AULA Datos - Metal: Cu - Estado pletinas: desnudas - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 24 - Ancho (mm): 12 - Espesor (mm): 2 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.048, 0.0288, 0.008, 0.0008 - I. admisible del embarrado (A): 110 Página 47 de 59 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =1.65² · 25² /(60 · 10 · 0.008 · 1) = 355.465 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 28.99 A Iadm = 110 A c) Comprobación por solicitación térmica en cortocircuito Ipcc = 1.65 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 24 · 1 / (1000 · √0.5) = 5.57 kA Cálculo de la Línea: - Tensión de servicio: 400 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 1850 W. - Potencia de cálculo: (Según ITC-BT-44): 3330 W.(Coef. de Simult.: 1 ) I=3330/1,732x400x0.8=6.01 A. Se eligen conductores Unipolares 4x1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 44.81 e(parcial)=0.3x3330/50.63x400x1.5=0.03 V.=0.01 % e(total)=0.62% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Tetrapolar Int. 10 A. Protección diferencial: Inter. Dif. Tetrapolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: EMERG - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 250 W. - Potencia de cálculo: (Según ITC-BT-44): 250x1.8=450 W. I=450/230x1=1.96 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Página 48 de 59 Caída de tensión: Temperatura cable (ºC): 40.51 e(parcial)=2x15x450/51.42x230x1.5=0.76 V.=0.33 % e(total)=0.95% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: SALA I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.15% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: SALA II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.15% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Página 49 de 59 Cálculo de la Línea: SALA III - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.15% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: SALA IV - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 15 m; Cos ϕ: 1; Xu(mΩ/m): 0; - Potencia a instalar: 400 W. - Potencia de cálculo: (Según ITC-BT-44): 400x1.8=720 W. I=720/230x1=3.13 A. Se eligen conductores Unipolares 2x1.5+TTx1.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 15 A. según ITC-BT-19 Diámetro exterior tubo: 16 mm. Caída de tensión: Temperatura cable (ºC): 41.31 e(parcial)=2x15x720/51.27x230x1.5=1.22 V.=0.53 % e(total)=1.15% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 10 A. Cálculo de la Línea: - Tensión de servicio: 230 V. - Canalización: C-Unip.o Mult.sobre Pared - Longitud: 0.3 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 8000 W. - Potencia de cálculo: 4800 W.(Coef. de Simult.: 0.6 ) Página 50 de 59 I=4800/230x0.8=26.09 A. Se eligen conductores Unipolares 2x4mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 31 A. según ITC-BT-19 Caída de tensión: Temperatura cable (ºC): 61.24 e(parcial)=2x0.3x4800/47.82x230x4=0.07 V.=0.03 % e(total)=0.64% ADMIS (4.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 30 A. Protección diferencial: Inter. Dif. Bipolar Int.: 40 A. Sens. Int.: 30 mA. Cálculo de la Línea: TC SALA I - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 % e(total)=1.24% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC SALA II - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 % e(total)=1.24% ADMIS (6.5% MAX.) Página 51 de 59 Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC SALA III - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 % e(total)=1.24% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. Cálculo de la Línea: TC SALA IV - Tensión de servicio: 230 V. - Canalización: B1-Unip.Tubos Superf.o Emp.Obra - Longitud: 10 m; Cos ϕ: 0.8; Xu(mΩ/m): 0; - Potencia a instalar: 2000 W. - Potencia de cálculo: 2000 W. I=2000/230x0.8=10.87 A. Se eligen conductores Unipolares 2x2.5+TTx2.5mm²Cu Nivel Aislamiento, Aislamiento: 450/750 V, PVC. Desig. UNE: H07V-K I.ad. a 40°C (Fc=1) 21 A. según ITC-BT-19 Diámetro exterior tubo: 20 mm. Caída de tensión: Temperatura cable (ºC): 48.04 e(parcial)=2x10x2000/50.05x230x2.5=1.39 V.=0.6 % e(total)=1.24% ADMIS (6.5% MAX.) Prot. Térmica: I. Mag. Bipolar Int. 16 A. CALCULO DE EMBARRADO 1ª PLANTA Datos - Metal: Cu - Estado pletinas: desnudas - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 Página 52 de 59 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 45 - Ancho (mm): 15 - Espesor (mm): 3 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.112, 0.084, 0.022, 0.003 - I. admisible del embarrado (A): 170 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =4.57² · 25² /(60 · 10 · 0.022 · 1) = 989.437 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 33.71 A Iadm = 170 A c) Comprobación por solicitación térmica en cortocircuito Ipcc = 4.57 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 45 · 1 / (1000 · √0.5) = 10.44 kA CALCULO DE EMBARRADO CUADRO GENERAL DE MANDO Y PROTECCION Datos - Metal: Cu - Estado pletinas: desnudas - nº pletinas por fase: 1 - Separación entre pletinas, d(cm): 10 - Separación entre apoyos, L(cm): 25 - Tiempo duración c.c. (s): 0.5 Pletina adoptada - Sección (mm²): 100 - Ancho (mm): 20 - Espesor (mm): 5 - Wx, Ix, Wy, Iy (cm3,cm4) : 0.333, 0.333, 0.083, 0.0208 - I. admisible del embarrado (A): 290 a) Cálculo electrodinámico σmax = Ipcc² · L² / ( 60 · d · Wy · n) =9.5² · 25² /(60 · 10 · 0.083 · 1) = 1131.527 <= 1200 kg/cm² Cu b) Cálculo térmico, por intensidad admisible Ical = 234.06 A Iadm = 290 A Página 53 de 59 c) Comprobación por solicitación térmica en cortocircuito Ipcc = 9.5 kA Icccs = Kc · S / ( 1000 · √tcc) = 164 · 100 · 1 / (1000 · √0.5) = 23.19 kA Los resultados obtenidos se reflejan en las siguientes tablas: Cuadro General de Mando y Protección Denominación ACOMETIDA LINEA GENERAL ALIMENT. DERIVACION IND. GYM EMERG. AL. GYM T.C. GYM F/C GYM BAR AL. GEN P_BA F/C Z. COMUN EMERG BAÑOS GYM BAÑOS GRAL. VESTIBL Z. COMUNES SALA CALDERAS MEDICO PODOLOGO 1ª PLANTA P.Cálculo (W) 162160 162160 129728 1938 180 900 2000 150 18284 1830 800 450 450 630 720 88880 4662 5271 18683 Dist.Cálc (m) Sección (mm²) I.Cálculo (A) 20 10 15 0.3 20 20 25 10 10 0.3 20 15 25 10 20 25 10 20 10 3x185/95Al 4x240+TTx120Cu 4x95+TTx50Cu 2x2.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x10+TTx10Cu 4x2.5Cu 2x2.5+TTx2.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5+TTx2.5Cu 2x1.5+TTx1.5Cu 4x95+TTx50Cu 2x6+TTx6Cu 2x10+TTx10Cu 4x10+TTx10Cu I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 292.58 292.58 234.06 10.53 0.78 3.91 10.87 0.82 32.99 3.3 4.35 1.96 1.96 2.74 3.13 160.36 25.34 28.65 33.71 300 401 268 23 15 15 21 21 44 21 21 15 15 21 15 180 36 50 44 0.4 0.09 0.28 0.02 0.18 0.89 1.51 0.04 0.24 0 0.47 0.33 0.55 0.19 0.71 0.31 0.6 0.8 0.24 0.4 0.09 0.37 0.39 0.56 1.27 1.9 0.43 0.61 0.37 0.84 0.7 0.92 0.56 1.08 0.68 0.97 1.17 0.61 180 200 125 16 16 20 20 32 20 16 16 20 16 75 25 25 32 Cortocircuito Denominación Longitud (m) LINEA GENERAL ALIMENT. 10 DERIVACION IND. 15 GYM 0.3 EMERG. 20 AL. GYM 20 T.C. GYM 25 F/C GYM 10 BAR 10 AL. GEN P_BA 0.3 F/C Z. COMUN 20 EMERG 15 BAÑOS GYM 25 BAÑOS GRAL. 10 VESTIBL Z. COMUNES 20 SALA CALDERAS 25 MEDICO 10 PODOLOGO 20 1ª PLANTA 10 Sección (mm²) IpccI (kA) 4x240+TTx120Cu 4x95+TTx50Cu 2x2.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x10+TTx10Cu 4x2.5Cu 2x2.5+TTx2.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5+TTx2.5Cu 2x1.5+TTx1.5Cu 4x95+TTx50Cu 2x6+TTx6Cu 2x10+TTx10Cu 4x10+TTx10Cu 12 11.39 9.53 8.47 8.47 8.47 8.47 9.53 9.53 8.47 8.47 8.47 8.47 8.47 9.53 9.53 9.53 9.53 P de C (kA) IpccF (A) tmcicc (sg) tficc (sg) Lmáx (m) 50 15 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 5673.62 4747.63 4215.15 299.99 299.99 391.04 861.43 2285.66 4215.15 478.1 391.04 243.33 861.43 299.99 3712.8 1690.96 1495.76 2285.66 36.59 8.19 0.752 374.69 0.33 0.33 0.54 0.11 0.25 0.36 0.19 0.5 0.11 0.33 8.66 0.17 0.59 0.25 Curvas válidas 315 250;B,C 16 10;B,C,D 10;B,C,D 16;B,C,D 16;B,C,D 40;B,C,D 16 16;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 250;B,C 30;B,C,D 40;B,C,D 40;B,C,D Subcuadro BAR Denominación EMERG AL. ESTAR I AL. ESTAR II P.Cálculo (W) 864 360 540 540 864 Dist.Cálc (m) Sección (mm²) 0.3 8 8 8 0.3 4x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x2.5Cu I.Cálculo (A) 1.56 1.57 2.35 2.35 1.56 I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 21 21 21 21 21 0 0.08 0.13 0.13 0 0.61 0.69 0.73 0.73 0.61 Página 54 de 59 20 20 20 EMERG AL. COMEDOR I AL. COMEDOR II EMERG AL. COCINA AL. BARRA F/C BAR COMEDOR EXTRACTOR TC. DESPACHO BAR CAFETERA BOTELLEROS T.C. COCINA I T.C. COCINA II T.C. COCINA III PLANCHA/FREID 360 540 540 864 360 540 540 10800 800 1000 2000 5000 2000 7700 2000 3000 3000 3000 8 8 8 0.3 8 8 8 0.3 15 10 20 5 10 0.3 10 10 10 8 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x4Cu 2x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x4+TTx4Cu 4x2.5+TTx2.5Cu 4x2.5Cu 2x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 1.57 2.35 2.35 1.56 1.57 2.35 2.35 19.49 4.35 1.8 10.87 9.02 3.61 13.89 10.87 5.41 5.41 5.41 21 21 21 21 21 21 21 27 21 18.5 21 24 18.5 21 21 18.5 18.5 18.5 0.08 0.13 0.13 0 0.08 0.13 0.13 0.01 0.35 0.05 1.21 0.08 0.1 0.01 0.6 0.15 0.15 0.12 0.69 0.73 0.73 0.61 0.69 0.73 0.73 0.62 0.97 0.66 1.82 0.69 0.71 0.62 1.22 0.76 0.76 0.73 20 20 20 20 20 20 20 20 20 25 20 20 20 20 20 Cortocircuito Denominación EMERG AL. ESTAR I AL. ESTAR II EMERG AL. COMEDOR I AL. COMEDOR II EMERG AL. COCINA AL. BARRA F/C BAR COMEDOR EXTRACTOR TC. DESPACHO BAR CAFETERA BOTELLEROS T.C. COCINA I T.C. COCINA II T.C. COCINA III PLANCHA/FREID Longitud (m) 0.3 8 8 8 0.3 8 8 8 0.3 8 8 8 0.3 15 10 20 5 10 0.3 10 10 10 8 Sección (mm²) IpccI (kA) 4x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x4Cu 2x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x4+TTx4Cu 4x2.5+TTx2.5Cu 4x2.5Cu 2x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 4x2.5+TTx2.5Cu 4.59 4.32 4.32 4.32 4.59 4.32 4.32 4.32 4.59 4.32 4.32 4.32 4.59 4.42 4.42 4.42 4.42 4.42 4.59 4.32 4.32 4.32 4.32 P de C (kA) IpccF (A) tmcicc (sg) 6 4.5 4.5 4.5 6 4.5 4.5 4.5 6 4.5 4.5 4.5 6 4.5 4.5 4.5 4.5 4.5 6 4.5 4.5 4.5 4.5 2149.9 828.25 828.25 828.25 2149.9 828.25 828.25 828.25 2149.9 828.25 828.25 828.25 2198.9 541.01 723.08 432.16 1344.27 723.08 2149.9 717.65 717.65 717.65 828.25 0.02 0.12 0.12 0.12 0.02 0.12 0.12 0.12 0.02 0.12 0.12 0.12 0.04 0.28 0.16 0.44 0.12 0.16 0.02 0.16 0.16 0.16 0.12 tficc (sg) Lmáx (m) Curvas válidas 10 10;B,C,D 10;B,C,D 10;B,C,D 10 10;B,C,D 10;B,C,D 10;B,C,D 10 10;B,C,D 10;B,C,D 10;B,C,D 20 16;B,C,D 16;B,C,D 16;B,C,D 16;B,C,D 16;B,C,D 16 16;B,C,D 16;B,C,D 16;B,C,D 16;B,C,D Subcuadro SALA CALDERAS Denominación RESERVA ENFRIADORA LF. GENERAL VENTILACION CALDERA T.C. S. CALD LA. GENERAL EMERG A.L. AZOTEA AL. S. CALD AL. EXT I AL. EXT I P.Cálculo (W) 80000 3600 3000 1000 2000 1728 360 540 540 720 720 Dist.Cálc (m) Sección (mm²) 10 0.3 25 10 5 0.3 20 20 10 20 20 4x70+TTx35Cu 4x6Cu 4x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x6+TTx6Cu 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu I.Cálculo (A) 144.34 6.5 5.41 5.43 3.61 9.39 1.57 2.35 2.35 3.13 3.13 I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 149 36 18.5 21 32 16.5 15 15 15 15 15 0.15 0 0.37 0.3 0.02 0.03 0.35 0.53 0.26 0.71 0.71 0.83 0.68 1.05 0.98 0.7 0.7 1.06 1.23 0.97 1.41 1.41 Página 55 de 59 63 20 20 25 16 16 16 16 16 Cortocircuito Denominación Longitud (m) RESERVA ENFRIADORA LF. GENERAL VENTILACION CALDERA T.C. S. CALD LA. GENERAL EMERG A.L. AZOTEA AL. S. CALD AL. EXT I AL. EXT I 10 0.3 25 10 5 0.3 20 20 10 20 20 Sección (mm²) IpccI (kA) 4x70+TTx35Cu 4x6Cu 4x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 4x6+TTx6Cu 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 7.46 7.46 7.16 7.16 7.16 7.46 6.38 6.38 6.38 6.38 6.38 P de C (kA) IpccF (A) tmcicc (sg) 10 10 10 10 10 10 10 10 10 10 10 3315.21 3563.56 384.28 829.35 2122.05 3178.47 292.97 292.97 537.31 292.97 292.97 5.9 0.04 0.56 0.12 0.11 tficc (sg) Lmáx (m) Curvas válidas 160;B,C,D 16 16;B,C,D 16;B,C,D 16;B,C,D 10 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 0.35 0.35 0.1 0.35 0.35 Subcuadro MEDICO Denominación P.Cálculo (W) 2160 540 630 630 360 4500 1500 1500 1500 AL. COMUN AL. CONSULTAS AL. ENFER - CURAS EMERG TC. MEDIC II TC. MEDIC I TC. RESTO Dist.Cálc (m) Sección (mm²) I.Cálculo (A) 0.3 15 10 10 15 0.3 10 10 10 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x4Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 11.74 2.35 2.74 2.74 1.57 24.46 8.15 8.15 8.15 I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 16.5 15 15 15 15 31 21 21 21 0.03 0.4 0.31 0.31 0.26 0.03 0.45 0.45 0.45 1 1.4 1.31 1.31 1.27 1 1.44 1.44 1.44 16 16 16 16 20 20 20 Cortocircuito Denominación Longitud (m) 0.3 15 10 10 15 0.3 10 10 10 AL. COMUN AL. CONSULTAS AL. ENFER - CURAS EMERG TC. MEDIC II TC. MEDIC I TC. RESTO Sección (mm²) IpccI (kA) 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x4Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 3.4 3.15 3.15 3.15 3.15 3.4 3.3 3.3 3.3 P de C (kA) IpccF (A) tmcicc (sg) 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 1568.2 337.38 457.07 457.07 337.38 1642.75 650.16 650.16 650.16 0.01 0.26 0.14 0.14 0.26 0.08 0.2 0.2 0.2 tficc (sg) Lmáx (m) Curvas válidas 16 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 25 16;B,C,D 16;B,C,D 16;B,C,D Subcuadro PODOLOGO Denominación P.Cálculo (W) 1530 540 630 360 6000 3000 1500 1500 AL. COMUN AL. CONSULTAS EMERG TC. LAVAND TC. CONSULT TC. RESTO Dist.Cálc (m) Sección (mm²) I.Cálculo (A) 0.3 15 10 15 0.3 10 10 10 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x6Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 8.32 2.35 2.74 1.57 32.61 16.3 8.15 8.15 I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 16.5 15 15 15 40 21 21 21 0.02 0.4 0.31 0.26 0.02 0.94 0.45 0.45 1.19 1.59 1.5 1.46 1.19 2.13 1.64 1.64 16 16 16 20 20 20 Cortocircuito Denominación AL. COMUN AL. CONSULTAS EMERG Longitud (m) 0.3 15 10 15 Sección (mm²) 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu IpccI (kA) 3 2.81 2.81 2.81 P de C (kA) IpccF (A) tmcicc (sg) 4.5 4.5 4.5 4.5 1398.77 328.78 441.41 328.78 0.02 0.28 0.15 0.28 tficc (sg) Lmáx (m) Curvas válidas 10 10;B,C,D 10;B,C,D 10;B,C,D Página 56 de 59 TC. LAVAND TC. CONSULT TC. RESTO 0.3 10 10 10 2x6Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 3 2.95 2.95 2.95 4.5 4.5 4.5 4.5 1470.28 621.19 621.19 621.19 0.22 0.21 0.21 0.21 40 20;B,C,D 16;B,C,D 16;B,C,D Subcuadro 1ª PLANTA Denominación P.Cálculo (W) 2592 720 720 720 630 450 2700 1000 1000 1000 1500 5334 3330 450 720 720 720 720 4800 2000 2000 2000 2000 BIBLIO I BIBLIO II BIBLIO III BAÑOS/COMUN EMERG TC BIBL I TC BIBL I TC BIBL I TC DESP BIB AULA EMERG SALA I SALA II SALA III SALA IV TC SALA I TC SALA II TC SALA III TC SALA IV Dist.Cálc (m) Sección (mm²) I.Cálculo (A) 0.3 15 15 15 8 10 0.3 10 10 10 10 20 0.3 15 15 15 15 15 0.3 10 10 10 10 2x2.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5+TTx2.5Cu 2x1.5+TTx1.5Cu 2x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x6+TTx6Cu 4x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x4Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 14.09 3.13 3.13 3.13 2.74 1.96 14.67 5.43 5.43 5.43 8.15 28.99 6.01 1.96 3.13 3.13 3.13 3.13 26.09 10.87 10.87 10.87 10.87 23 15 15 15 21 15 23 21 21 21 21 36 15 15 15 15 15 15 31 21 21 21 21 0.02 0.53 0.53 0.53 0.15 0.22 0.02 0.3 0.3 0.3 0.45 1.4 0.01 0.33 0.53 0.53 0.53 0.53 0.03 0.6 0.6 0.6 0.6 0.63 1.17 1.17 1.17 0.78 0.86 0.64 0.93 0.93 0.93 1.08 2.01 0.62 0.95 1.15 1.15 1.15 1.15 0.64 1.24 1.24 1.24 1.24 16 16 16 20 16 20 20 20 20 25 16 16 16 16 16 20 20 20 20 Cortocircuito Denominación BIBLIO I BIBLIO II BIBLIO III BAÑOS/COMUN EMERG TC BIBL I TC BIBL I TC BIBL I TC DESP BIB AULA EMERG SALA I SALA II SALA III SALA IV TC SALA I TC SALA II TC SALA III TC SALA IV Longitud (m) 0.3 15 15 15 8 10 0.3 10 10 10 10 20 0.3 15 15 15 15 15 0.3 10 10 10 10 Sección (mm²) 2x2.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5+TTx2.5Cu 2x1.5+TTx1.5Cu 2x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x6+TTx6Cu 4x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x4Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu IpccI (kA) 4.59 4.32 4.32 4.32 4.32 4.32 4.59 4.32 4.32 4.32 4.32 4.59 4.59 4.15 4.15 4.15 4.15 4.15 4.59 4.42 4.42 4.42 4.42 P de C (kA) IpccF (A) tmcicc (sg) 6 4.5 4.5 4.5 4.5 4.5 6 4.5 4.5 4.5 4.5 6 6 4.5 4.5 4.5 4.5 4.5 6 4.5 4.5 4.5 4.5 2149.9 358.41 358.41 358.41 828.25 496.52 2149.9 717.65 717.65 717.65 717.65 826.13 2067.93 356.03 356.03 356.03 356.03 356.03 2198.9 723.08 723.08 723.08 723.08 0.02 0.23 0.23 0.23 0.12 0.12 0.02 0.16 0.16 0.16 0.16 0.7 0.01 0.23 0.23 0.23 0.23 0.23 0.04 0.16 0.16 0.16 0.16 tficc (sg) Lmáx (m) Curvas válidas 16 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 16 16;B,C,D 16;B,C,D 16;B,C,D 16;B,C,D 30;B,C,D 10 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 10;B,C,D 30 16;B,C,D 16;B,C,D 16;B,C,D 16;B,C,D Página 57 de 59 Subcuadro AULA Denominación P.Cálculo (W) 1620 180 720 720 3600 1500 1500 1500 1500 EMERG AULA II AULA I TC I TC II TC III RACK Dist.Cálc (m) Sección (mm²) I.Cálculo (A) 0.3 8 10 8 0.3 10 10 10 10 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 8.8 0.78 3.13 3.13 19.57 8.15 8.15 8.15 8.15 I.Adm.. C.T.Parc. C.T.Total Dimensiones(mm) (A) (%) (%) Tubo,Canal,Band. 16.5 15 15 15 23 21 21 21 21 0.02 0.07 0.35 0.28 0.03 0.45 0.45 0.45 0.45 2.03 2.1 2.39 2.32 2.04 2.49 2.49 2.49 2.49 16 16 16 20 20 20 20 Cortocircuito Denominación EMERG AULA II AULA I TC I TC II TC III RACK Longitud (m) 0.3 8 10 8 0.3 10 10 10 10 Sección (mm²) 2x1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x1.5+TTx1.5Cu 2x2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu 2x2.5+TTx2.5Cu IpccI (kA) 1.66 1.6 1.6 1.6 1.66 1.62 1.62 1.62 1.62 P de C (kA) IpccF (A) tmcicc (sg) 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 795.56 400.28 356.03 400.28 807.51 460.99 460.99 460.99 460.99 0.05 0.19 0.23 0.19 0.13 0.39 0.39 0.39 0.39 tficc (sg) Lmáx (m) Curvas válidas 10 10;B,C,D 10;B,C,D 10;B,C,D 20 16;B,C,D 16;B,C,D 16;B,C,D 16;B,C,D Página 58 de 59 CALCULO DE LA PUESTA A TIERRA - La resistividad del terreno es 300 ohmiosxm. - El electrodo en la puesta a tierra del edificio, se constituye con los siguientes elementos: M. conductor de Cu desnudo M. conductor de Acero galvanizado 35 mm² 30 m. 95 mm² Picas verticales de Cobre de Acero recubierto Cu de Acero galvanizado 14 mm 14 mm 1 picas de 2m. 25 mm Con lo que se obtendrá una Resistencia de tierra de 17.65 ohmios. Los conductores de protección, se calcularon adecuadamente y según la ITC-BT-18, en el apartado del cálculo de circuitos. Así mismo cabe señalar que la linea principal de tierra no será inferior a 16 mm² en Cu, y la linea de enlace con tierra, no será inferior a 25 mm² en Cu. Página 59 de 59