INSTALLATION AND MAINTENANCE INSTRUCTIONS 12 Clintonville Rd FDM-1 Dual Monitor Module Specifications Normal Operating Voltage: Maximum Current Draw: Average Operating Current: EOL Resistance: Maximum IDC wiring resistance: Temperature Range: Humidity: Dimensions: Accessories: Northford, CT 06472-1653 (203) 484-7161 15 to 32 VDC 5.7 mA (LED on) 750µA (LED flashing) 47K Ohms 1,500 Ohms 32˚F to 120˚F (0˚C to 49˚C) 10% to 93% Noncondensing 41/2″ H x 4″ W x 11/4″ D (Mounts to a 4″ square by 21/8″ deep box.) SMB500 Electrical Box Before Installing This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules. 3. avoid duplicate addressing of modules on the system. Secure module to electrical box (supplied by installer), as shown in Figure 2A. Figure 1. Removing Rotary Switch Stop: NOTICE: This manual should be left with the owner/user of this equipment. 9 General Description The Dual Monitor Module is intended for use in intelligent, two wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices, or either normally open or normally closed security devices. The module has a single panel controlled red LED. 8 7 6 5 LOOP Compatibility Requirements To ensure proper operation, this module shall be connected to a compatible Notifier system control panel (list available from Notifier). 67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 8 6 4 2 ONES 0 1 2 3 4 0 ADDRESS A78-2318-13 Figure 2A. Module mounting: Mounting Mounts directly to 4” square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8”. Surface mounted electrical boxes (SMB500) are available from Notifier. Figure 2B: Wiring NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only. 1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams. 2. Set the address on the module per job drawings. Note: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1. Note: Monitor module L (using terminals 6 and 7) responds at the address set on the code switches. Monitor module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to N500-75-00 www.PDF-Zoo.com LO OP 0 2 3 0 NS 1 2 3 4 5 67 8 9 10 11 15 1 12 14 3 1 5 4 2 0 6 4 8 7 TE 8 AD 8 9 4 5 6 78 3 9 EN 21 1 S 0 1 0 15 1 1 12 1 6 8 4 3 4 7T ON 2 ES 0 AD DR ES S 6 9 5 6 4 3 2 1 0 SS E DR ES ON A78-2611-19 A78-2610-14 1 I56-1463-02 Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B: TO NEXT TWO INITIATING DEVICE CIRCUITS (L & H), EACH POWER LIMITED TO 230 A @ 12VDC MAX. 47 K EOL RESISTOR ELR-47K DEVICE )—( )+( )+( FROM PANEL OR PREVIOUS DEVICE MONITOR MODULE CONNECT MODULES TO LISTED COMPATIBLE NOTIFIER CONTROL PANELS ONLY H 9 8 7 47 K EOL RESISTOR ELR-47K 6 L ANY NUMBER OF UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME INITIATING DEVICE CIRCUIT. INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS. N500-75-00 )—( www.PDF-Zoo.com 5 LOOP 67 8 9 5 10 11 4 3 12 13 2 1 0 15 14 TENS 8 6 4 2 ONES 0 )—( 1 2 3 0 ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED )+( COMMUNICATION LINE 4 32 VDC MAX. SHIELDED-TWISTED PAIR IS RECOMMENDED ADDRESS MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) RESPONDS AT NEXT HIGHER ADDRESS. A78-2280-39 2 I56-1463-02 Notifier ©2001