INSTALLATION AND MAINTENANCE INSTRUCTIONS
12 Clintonville Rd
FDM-1 Dual Monitor Module
Specifications
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Maximum IDC wiring resistance:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Northford, CT 06472-1653
(203) 484-7161
15 to 32 VDC
5.7 mA (LED on)
750µA (LED flashing)
47K Ohms
1,500 Ohms
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Noncondensing
41/2″ H x 4″ W x 11/4″ D (Mounts to a 4″ square by 21/8″ deep box.)
SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation
guide. Refer to the control panel installation manual for detailed
system information. If the modules will be installed in an existing
operational system, inform the operator and local authority that
the system will be temporarily out of service. Disconnect power to
the control panel before installing the modules.
3.
avoid duplicate addressing of modules on the system.
Secure module to electrical box (supplied by installer), as
shown in Figure 2A.
Figure 1. Removing
Rotary Switch Stop:
NOTICE: This manual should be left with the owner/user of this
equipment.
9
General Description
The Dual Monitor Module is intended for use in intelligent, two
wire systems. It provides two independent 2-wire initiating device
circuits (IDC), at two separate, consecutive addresses. It is capable
of monitoring normally open contact fire alarm and supervisory
devices, or either normally open or normally closed security devices. The module has a single panel controlled red LED.
8
7
6
5
LOOP
Compatibility Requirements
To ensure proper operation, this module shall be connected to a
compatible Notifier system control panel (list available from Notifier).
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
8
6
4
2
ONES
0
1
2
3
4
0
ADDRESS
A78-2318-13
Figure 2A. Module mounting:
Mounting
Mounts directly to 4” square electrical boxes (see Figure 2A). The
box must have a minimum depth of 21/8”. Surface mounted electrical boxes (SMB500) are available from Notifier.
Figure 2B:
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for
power limited wiring only.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Note: Some panels support extended addressing. In order
to set the module above address 99 on compatible systems,
carefully remove the stop on the upper rotary switch with
thumb in the direction shown in Figure 1.
Note: Monitor module L (using terminals 6 and 7) responds at the address set on the code switches. Monitor
module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code
switches are set to 76, module L will respond at address 76
and module H will respond at address 77. Use caution to
N500-75-00
www.PDF-Zoo.com
LO
OP
0
2
3
0
NS 1
2
3
4 5 67
8
9
10
11
15 1 12
14 3
1
5
4
2
0
6
4
8
7
TE
8
AD
8
9
4 5 6 78
3
9
EN 21
1
S 0
1 0
15 1 1 12 1
6 8
4 3
4
7T
ON
2
ES 0
AD
DR
ES
S
6
9
5
6
4
3
2
1
0
SS
E
DR
ES
ON
A78-2611-19
A78-2610-14
1
I56-1463-02
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B:
TO NEXT
TWO INITIATING DEVICE CIRCUITS (L & H),
EACH POWER LIMITED TO 230 A @ 12VDC MAX.
47 K EOL
RESISTOR
ELR-47K
DEVICE
)—(
)+(
)+(
FROM PANEL OR
PREVIOUS DEVICE
MONITOR
MODULE
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
H
9
8
7
47 K EOL
RESISTOR
ELR-47K
6
L
ANY NUMBER OF UL LISTED CONTACT CLOSURE
DEVICES MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR SECURITY
DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
N500-75-00
)—(
www.PDF-Zoo.com
5
LOOP
67 8 9
5
10
11
4
3
12
13
2
1 0 15 14
TENS
8
6
4
2
ONES
0
)—(
1
2
3
0
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
)+(
COMMUNICATION LINE
4
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
ADDRESS
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9)
RESPONDS AT NEXT HIGHER ADDRESS.
A78-2280-39
2
I56-1463-02