2017 Electrical Insulation Conference (EIC), Baltimore, MD, USA, 11 - 14 June 2017 Review of Field Acceptance Hipot & PD Testing of Medium Voltage Underground Cables Ali Naderian Jahromi, SM IEEE METSCO Energy Solutions Inc. potential, in any form, to XLPE cables as it is detrimental to the insulation and to cable life due to possible trapped space charges. The other disadvantage of DC Hipot is that it is blind to certain types of defects including voids. Another disadvantage of DC Hipot is that it is not possible to do PD measurement. Moreover, the DC stress distribution is sensitive to temperature. Abstract—There are some well-defined guides and standards regarding factory testing of medium voltage shielded cables in laboratories provided by IEEE, IEC, ANSI/ICEA, and CSA. These guides cover AC withstand and PD testing of XLPE and EPR cables and accessories, such as 50/60Hz AC Hipot and PD tests which are routinely conducted on every reel of cable produced at the factory. All terminations, splices, and separable connectors are tested with more or less the same test method using different test levels and timing. On the other hand, there are utilities that have been performing 50/60Hz AC Hipot for several decays for commissioning new cables. In the past 15 years, several other Hipot systems including Very Low Frequency (VLF), Variable Near Power Frequency (VNPF), and Damped AC (DAC) have been developed and promoted by test manufacturers and test companies worldwide. DAC is a withstand test which is described by IEEE Std 400.4. Appendix A lists test voltages not yet acceptable standard values due to the lack of experience [17]. Dissipation factor measurements are also used to assess cable condition. There is, however, limited literature and guidance available to clarify the requirements of onsite Hipot & PD testing. IEEE 400.2 has recommendations regarding VLF Hipot testing. IEEE 400.3 provides a general guide for onsite PD testing of underground cables, but does not cover specifics such as the Hipot level, timing, acceptable PD levels, PDIV, and PDEV for each different voltage class. It is critical that owners and test crew understand the different available options for AC Hipot and PD testing of new and aged underground cables. This paper reviews and compares available literature and guides related to offline Hipot and PD testing including both VLF and 50/60 Hz AC for Polymeric Cables. The objective is to help end users, asset managers, consultants, and service companies to choose the correct test method, parameters and procedures. Keywords—AC Hipot, VLF Hipot, Underground Cables, PDIV, PDEV. Partial The field Hipot test has been around for 50 years yet there are challenges and uncertainties involved in today’s testing practices. Although different Hipot test methods are available and introduced by IEEE 400.2 and IEEE 400.3 for field testing, no comprehensive guides are available which provide details on performing and interpreting the results of Hipot and PD tests, especially PD inception voltage (PDIV) and PD extinction (PDEV). This paper reviews available guides for performing offline AC Hipot and PD tests for commissioning of underground cables. It also provides recommendations with regards to test parameters based on industry practice and expertise of the author. Discharge, I. INTRODUCTION Standards such as IEEE, IEC, ANSI/ICEA, and CSA recommend high voltage withstand tests to manufacturers of polymeric cables to be done in the factory [1-4]. There are several other IEEE and IEC standards that cover AC withstand testing of the cable accessories including terminations, separable connectors, and splices [5-8]. The onsite high voltage withstand test is often called the Hipot test by contractors, utilities, and test crews. The goal of Hipot testing is to find any weak insulation point of the underground cable circuit including the termination, cable, and splices. The ability of the AC withstand tests to find installation problems will reduce the premature failure rate which has historically occurred in new stations. The data provided by the partial discharge (PD) test will also serve as a useful baseline for trending the deterioration of such equipment during service. II. Table 1 shows a summary of high voltage withstand and partial discharge tests recommended by different standards for underground cables [1-4]. Table 2 provides a summary of tests for accessories such as terminations and splices [5-8]. U0 is the cable rated phase-to-ground rms voltage and UC is the cable rated voltage, where UC = 1.73U0. According to both IEEE and IEC standards for factory PD testing, the voltage shall be raised to 20% above the specified partial discharge voltage level. If partial discharge exceeds the limit of 5 pC (IEEE) or 10 pC (IEC), the test voltage shall be lowered to the partial discharge voltage level specified and shall be maintained at this level for at least 1 minute. If partial discharge readings still exceed the limit, the cable accessory does not meet the requirements of this standard. Traditionally, DC Hipot testing has been employed for different types of medium voltage (5kV to 44kV) and high voltage cables (66kV to 230kV) including XLPE, EPR, or oil filled cables. The new industry standards such as ICEA S-94649 and ICEA S-97-682 now warn against applying a DC 978-1-5090-3967-8/17/$31.00 ©2017 IEEE FACTORY ACCEPTANCE TEST 241 determining the economic replacement interval for deteriorated cables. Field diagnostics are performed periodically thereafter during service (maintenance testing) to determine if the cable system remains reliable. Manufacturers typically have an electromagnetically shielded high voltage lab to shield EMI coming from the outside, and an input filter to provide a clean power supply. This helps to minimize the background noise usually to be in the range of 3 pC or less. In order to satisfy the 5pC requirement of the IEEE, the measurement background noise at test voltage has to be 2.5 pC which is usually hard to achieve. In this regard, the IEC requirement of 10pC is more practical. U0 [kV] 2.9 Table 1 Factory high voltage withstand test for cables rated 5kV to 46kV, 100% insulation – 5 minutes ICEA S-94-649 IEC 60502-2 CSA C68.3-97 UC ICEA S-97-682 Rated voltage PD PD 50/60 PD 50/60Hz 50/60Hz [kV] EV Hz AC AC AC Hipot [kV] Hipot Hipot [kV] [kV] [kV] 18 (6U0) 18 10 5 11.5 15 35 (4U0) 14.4 25 52 (3.6U0) 16.2 28 56 (3.5U0) 8.7 A. 50/60Hz AC Hipot The size of the power frequency AC Hipot equipment can be substantially reduced by using the principle of resonance. If the effective capacitance of the cable is resonated with an inductor, the multiplying effect of the resonant circuit, often called the Q factor, allows the use of a smaller test source. In the ideal case of perfect resonance, the test source will only be required to supply energy to balance the true resistive loss in the inductor and cable system. In practical resonant test systems, provision is made for varying both the magnitude of the inductance and the system voltage. IEEE 400-2001 proposed duration of acceptance testing on a new cable system to be 15 minutes but does not specify the waveform type or type of AC test voltage. 20.2 35 69 (3.5U0) 26.6 46 89 (3.3U0) 5pC at AC Hipot Test Level 30 50 56 70 10 pC @ 1.7U0 - 35 35 52 52 56 56 69 69 89 89 Unfortunately, IEEE 400 does not specify any 50/60Hz test voltage or PDEV/PDIV for a given voltage class. Historically, Ontario Hydro has implemented guides to perform power frequency AC Hipot and PD tests [13]. NETA proposed that the user can choose between DC Hipot, AC Hipot, and VLF Hipot to test underground cables. NETA does not differentiate between XLPE, EPR, and PILC cables. NETA does not specify the duration of the tests but it refers to ANSI/ICEA S93-639, and ANSI/ICEA S-94-649 [12]. NETA does not specify the PDEV for 25kV and higher-rated voltage cables. Ontario Hydro’s recommendation is currently used by some utilities in Canada and suggests to use 70% of the factory test levels for field testing [13]. On the other hand, Australian electric utility Ergon Energy refers to IEC 71-1-1993 insulation co-ordination and has proposed to choose AC Hipot test voltage equal to the “standard short duration power frequency withstand voltage” specified by IEC 71-1 for each voltage class. Table 3 provides a summary of available guides for 50/60Hz AC Hipot test. The test voltages specified by NETA and Ergon Energy are very close to each other and to 100% of the factory acceptance test levels presented in Table 1. Table 2 Factory high voltage withstand test for accessories rated 5kV to 46kV U0 [kV] UC Rated voltage [kV] IEEE 48 Terminations & IEEE 404 joints PD 50/60Hz AC Hipot [kV1min] 2.9 5 18 8.7 15 35 14.4 25 52 16.2 28 - 20.2 35 69 26.6 46 80 5pC at 1.5U0 IEC 60502-4 Both terminations & joints PD 50/60Hz AC Hipot [kV] IEEE 386 Separable connectors PD 50/60 Hz EV AC [kV] Hipot [kV 1min] - 4.5 U0 5 min and 4 U0 -15 min 34 10pC @ 1.7U0 40 50 3pC @ 1.3U0 50 - III. Table 3 Field 50/60Hz AC Hipot test levels for cables rated 5kV to 46kV, 100% insulation Ontario Hydro Ergon EnergyNETA [12] UC U0 [13] Australia [14] Rated voltage [kV] PD EV PD AC AC PD AC [kV] [kV] Hipot Hipot EV Hipot [kV] [kV] [kV]* [kV* 5min] 9 18/28 2.9 5 4.5 20 4 ONSITE HIPOT TEST Although medium voltage cables are carefully tested by the manufacturer, defects such as damage during shipment, storage, incorrect cable installation, and defects in accessories may occur. Field testing of completed circuit installation including joints and terminations prior to being placed in service provides a piece of mind to utilities, asset owners, and others involved in a new installation. The field Hipot and PD test is intended to assure owners that the cable and accessories were not damaged during transportation, handling, and installation and the circuit is ready for energization. Additionally, users find that with time, these cable systems degrade and service failures become troublesome [10]. The desire to reduce or eliminate cable failure has led cable users to perform periodic tests after some time in service. As well, cable users need special diagnostic tests as an aid in 8.7 15 19 14 33 14.4 25 17.5* 24 50 - 35/44 11 52 - 16.2 28 39* 26 - 56 - 20.2 35 48* 33 70 69 - 26.6 46 62* 44 90 89 - * calculated based on 70% factory test levels provided in Table 1 ** calculated based on 95% UC TXU Electric and Gas has implemented 60Hz AC Hipot at 242 3Uo [15]. This utility suggested that 60 Hz testing may be used successfully to determine the condition of cable and accessories, but that the cable is more susceptible to failure than the accessories [15]. - B. VLF Hipot Using very low frequency (VLF) high voltage sources has some advantages for cable testing mainly due to weight and cost reduction. The power requirement of the capacitive load drops by a factor of 500 when comparing the commonly used 0.1Hz with the 50/60Hz AC Hipot test. Two common VLF waveforms are as follows: - - - IEC 60840 provides a guideline for field AC Hipot testing of cables 30kV to 150kV [11] which allows using a NPF power supply with frequency of 20Hz to 300Hz. The field Hipot test level for 46kV class cables is 52kV for 1 hour. Allowable PDEV is 39kV. The suggested Hipot test voltage of 1.7U0 and PDEV of 1.5U0 is in line with the IEC 60502-2 factory test levels. Cosine-rectangular VLF AC voltage waveform Sinusoidal VLF AC voltage waveform IEEE 400.2 is the guide for VLF Hipot testing of medium voltage underground shielded cables [11]. It introduces three testing voltage levels (installation, acceptance, and maintenance). The suggested “acceptance test voltage” is based on the most used practices of 2U0 to 3U0, for cables rated between 5kV and 69kV. The recommended maintenance test level is 75% of the acceptance test level. The IEEE 400.2 recommended minimum testing time for an acceptance VLF withstand test on new cable circuits is 60 minutes. The test time can be reduced to 30 minutes if the monitored characteristic such as voltage, leakage current, and PD remains stable and no failure occurs [11]. A 2006 CIGRE study showed that the VLF withstand test is the most preferred Hipot test method in USA [9]. IV. OFFLINE ACCEPTANCE PD TESTS For acceptance testing of cables, it is very common to do both Hipot and PD tests. IEEE 400.3 is the guide for partial discharge testing of shielded power cable systems in a field environment. Hipot and PD testing has been employed more than before in the past 15 years. Colorado Springs Utilities, Oklahoma Gas and Electric, PECO, Xcel Energy, TXU Energy, BC Hydro, Hydro One, and Ontario Power Generation have successfully implemented Hipot and PD testing programs that help them to detect cable defects [15]. However, there are concerns about the difficulty of PD assessment and the accuracy of PD location needs improvement. A. PD Limits IEEE 400.3 proposed a minimum PDIV of 2U0 as an example. Regarding PDEV, the only available recommendation is from Ontario Hydro [13] suggesting PDEV = 0.95UC = 1.65U0. Ontario Hydro’s recommendation for onsite maximum PD is 3pC, and IEEE 400.3 recommends 5pC. These levels of PD are typically very hard to achieve onsite due to the power supply or background noise. Table 4 Acceptance VLF Hipot test for cables rated 5kV to 46kV IEEE 400.2 Utility A NETA UC U0 Rated Sine Sine Sine wave Cosine voltage [kV] wave wave [kVrms] rectangle [kV] [kVrms] [kVrms] Wave [kVrms] 10 (3.4U0) 2.9 5 14 10* 10 8.7 15 21 (2.4U0) 30 20 14.4 25 32 (2.2U0) 45 32* 31 16.2 28 36 (2.2U0) 51 34 34* 20.2 35 44 (2U0) 62 45* 44 26.6 46 57 (2.14Uo) 81 60 55* It has no moving parts and no mechanical systems to maintain. The core can be designed with a distributed gap to reduce the size and weight. It has typically higher Q (~80 to 150) compared to 60Hz variable inductor systems (Q=25 to 50) resulting lower input power. By reducing the test frequency, a larger capacitive load can be tested. 20 B. PD Frequency Most of above standards refer to IEC 60270 as a classic PD measurement protocol, with a center frequency of around 300kHz and a bandwidth of 300kHz (f = 300kHz ± 150kHz). IEC 60270 frequency bandwidth applies to lumped capacitances as per this standard. IEC frequency may not be suitable for long run of cables. Higher frequencies of typically 3MHz to 20 MHz are recently used for field testing. The test frequency shall also be selected by looking at the FFT of the background noise to search for low ambient noise. A proper sensitivity check and calibration is required for any selected PD test frequency. * calculated by extrapolation of adjacent data (lower and higher numbers) C. Variable Frequency Hipot Variable Frequency AC Hipot, or near power frequency (NPF) AC Hipot, has been implemented in the past 10 years due to the progress of power electronics devices. The test setup has a fixed reactor fed by a variable input frequency AC/AC converter with an output frequency between 20Hz and 300Hz. Once the frequency of the input power is tuned to the resonance frequency by an initial frequency sweep, the voltage is raised to Hipot or PD test levels. The test frequency depends on the capacitance (i.e. cable length, insulation material, thickness, etc). The main advantages of NPF power supplies are as follows: C. Background Noise PD background noise can come from different sources: - Input power such as portable generator or power plug - Environment EMI such as corona, working machinery at the site, rain, and damped weather - Testing transformer 243 Table 6 Recommended VLF Sine Hipot & PD acceptance test voltages for polymeric cables Air termination Separable connectors PDEV AC PDEV Rated AC U0 [kV] withstand [kV] voltage withstand 1.5U0 [kV]1.3U0 [kV] [kV] [kV] 30 min 30 min 10 min 10 min 10 (3.4U0) 5* 2.9 5 - Background noise can be permanent or intermittent. It is possible to reduce the power supply noise by using an input isolating transformer as well as a high voltage filter at the transformer output. If the background noise is still high due to the nature of the environment, the PD measurement frequency has to be adjusted. D. Onsite PD localization One of the challenges of onsite PD measurement is localization in the event of PD presence. To fix the problem it is necessary to determine if the PD is in the terminations, or splice, or inside the cable. Most PD equipment is equipped with PD time domain reflection analysis that allows users to estimate the location of the PD and see how far it is from the source. V. 8.7 15 21 (2.4U0) 13 21 11 14.4 25 32 (2.2U0) 22 25 18 16.2 28 36 (2.2U0) 24 28 21 20.2 35 44 (2U0) 30 35 26 26.6 46 57 (2.14Uo) 40 - - *selected equal to Uc RECOMMENDATIONS AND CONCLUSION In the absence of this data, it is proposed to use PDEV of 1.5U0 for air terminated cables and 1.3U0 for separable connector terminations. More systematic research is necessary to improve the proposed test parameters. It is expected that IEEE 400 series standards will improve and cover the existing gaps. The recommendation is based on available reviewed documents and limited experience of the author. Table 5 summarizes the recommendation for field AC Hipot and PD acceptance tests for XLPE and EPR cables. The recommended acceptance level for 50/60Hz AC Hipot testing is 70% of the factory test voltage for 5 minutes. The test voltage must be selected based on the termination type. The recommended minimum PDIV is 2U0 proposed by IEEE 400.1. The recommended PDEV is based on the termination PDEV proposed by IEEE 48 for air-terminated and IEEE 386 for separable connectors which is 1.5U0 and 1.3U0, respectively. 10pC is recommended as a limit with a maximum of 5pC of background noise. In case of NPF variable frequency, the same test voltage can be used (Table 5). If 5pC of background noise is not achievable, it might be possible to select a better PD frequency range to achieve a reasonable PD background. VI. [1] [2] [3] [4] [5] [6] The VLF sinusoidal AC withstand test voltage for air terminated cables is selected based on IEEE 400.2. The test voltage for cables with separable connectors in Table 6 is selected based on the cable line-to-line voltage rating. The proposed 30-minute test time is accepted when the monitored PD and leakage current does not increase during the 30-minute test. Otherwise, the VLF AC Hipot will continue for 60 minutes. Although there are several publications comparing VLF and 50/60Hz PD data, there is not enough information regarding VLF PDEV and PDIV. [7] [8] [9] [10] [11] [12] Table 5 Recommended field AC Hipot &PD acceptance test voltages Air termination Separable connectors PDEV PDEV AC UC AC U0 [kV] [kV] withstand withstand Rated 1.5U0 1.3U0 [kV] [kV] voltage [kV] 5min 5min [kV] 1min 1min 5 2.9 5 12.5 5 [13] [14] 8.7 15 24.5 13 24 11 [15] 14.4 25 36.5 22 28 18 [16] 16.2 28 39.0 24 28 21 20.2 35 48.0 30 35 26 26.6 46 62.0 40 - 35 [17] 244 REFERENCES ANSI/ICEA S-94-649-2013- STANDARD FOR CONCENTRIC NEUTRAL CABLES RATED 5 THROUGH 46 kV. ANSI/ICEA S-97-682-2013- STANDARD FOR UTILITY SHIELDED POWER CABLES RATED 5 THROUGH 46 kV. IEC 60502-2-2005 Power cables with extruded insulation and their accessories for rated voltages from 6 kV up to 30 kV (Um = 36 kV). CSA-C68.3-97 - Shielded and Concentric Neutral Power Cables Rated 5-46 kV. IEEE 48-1996 EEE Standard Test Procedures and Requirements for Alternating-Current Cable Terminations 2.5 kV Through 765 kV. IEEE 404-2006 - IEEE Standard for Extruded and Laminated Dielectric Shielded Cable Joints Rated 2.5 kV to 500 kV. IEEE 386-2006 - IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600 V. IEC 60502-4-2005 Power cables and their accessories for rated voltages from 1 kV up to 30 kV- Part 4: Test requirements on accessories. CIGRE Brochure B1-301, “Experience with withstand testing of cables in the USA”, 2010. IEEE 400- 2012 - Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above. IEEE 400.2-2013 - Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF). ANSI/NETA ATS-2013 Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems . M. T. G. Gillespie, G. B. Murchie, and G. C. Stone, Experience with AC Hipot and Partial Discharge Tests for Commissioning Generating Station Cables and Switchgear, IEEE Power Engineering Review, September 1989. Neil Dwyer, Ergon Energy Reference SP0407R02- Testing of HV Cables. Harry E. Orton, “Partial Discharge Testing of InSitu Power Cable Accessories – An Overview”, Electricity Energy, 2002. IEC 60840- 2011 Power cables with extruded insulation and their accessories for rated voltages above 30 kV up to 150 kV – Test methods and requirements. IEEE 400.4-2015: Guide for Field-Testing of Shielded Power Cable Systems Rated 5 kV and above with Damped Alternating Current Voltage