2019 International Conference on Intelligent Green Building and Smart Grid (IGBSG2019), 6-9 Sept., Yichang China Analysis of Brazilian blackout on March 21st,2018 and revelations to security for Hunan Grid Yongyan Liu State Grid Hunan Electrical Power Company Limited Research Institute Changsha, China 467634341@qq.com Abstract—Brazil ±800kV Xingu convertor station’s technical defects lead to chain reaction in Brazil that a Brazilian nationwide blackout accident happened on March 21st, 2018. This blackout severely impact the north and northeast of Brazil including 14 states. In this paper, the general situation of Brazilian power grid is introduced. And the occurrence and propagation of the blackout are retrospected. Furthermore, the main reason of the blackouts are analyzed in this article. According to the Brazilian blackout, Qishao DC is evaluated from the relay protection, configuration of security and stability equipment and strategy analysis of power plants’ primary frequency regulation. Combined with the reality of Hunan power grid, this paper sum up experience and lessons of Brazilian blackout. Keywords—Brazil power grid, blackout, defense line of power grid, accident analysis I. INTRODUCTION At the moment of local time in Brazil, March 21, 2018 at 15:48, a power outage happens in Brazil which lead to the north and northeast of Brazil grid are separated from the main grid. Fourteen states of northern and northeastern Brazil have widespread blackout and loss load about 21735MW which count 27 percent of National Integrated System(SIN). Fourteen states in the north and northeast of Brazil were severely affected, with 2,049 cities accounting for 93% (2,204 cities in total). The south, south-east and midwest of Brazil have been affected, including Sao Paulo, Rio DE janeiro, Minas, Barana, Santa catarina, Goias, Mato grosso, South mato grosso and the federal autonomous region, a total of nine states. The blackout caused huge economic loss and serious social impact. At the same time, some problems of Brazilian power grid are exposed. This paper briefly introduces the general situation of the Brazilian power grid and analyzes the development process and main reasons of the blackout. At the end, this paper analyzes and concludes the experience and lessons of the Brazil blackout which can be used as reference for the operation and development of Hunan power grid. II. POWER GRID OVERVIEW A. The overview of Brazilian power grid and the review of historical blackout The power grid of Brazil is divided into northwest power grid, north power grid, midwest power grid and southeast power grid. The southeast power grid of Brazil, including economic centers like Rio DE janeiro and Sao Paulo, is the load center of Brazilian power grid, and its load accounts for more than 50% of the whole power grid. Brazil's National Integrated System(SIN) includes: the Itaipu hydropower station-Sao Paulo's delivery project; the Tucurui power plant delivery project, which connects the northern and northeastern power grids, and the north-south grid interconnection system. Brazil has suffered several large-scale power outages in the last decade. At 22:13 on November 10, 2009, the power transmission line of the Itaipu hydroelectric power plant in Brazil has fault trip, resulting in power failure in four major cities in the southeast, including Sao Paulo, Rio DE Janeiro and other continents [1]. At 0:8 on February 4, 2011, the malfunction of relay underreaching protection of circuit breaker which installed between the circuit and the bus of the fault substation luizgonzaga-sobradinho lead to the northeast power grid separated from the north power grid and the national power grid of Brazil, and the isolated operation of the northeast power grid [2]. At 15:50 on September 13, 2016, due to the fault tripping of 600kV Madeira I dc project's two poles successively, the National Integrated Systems’s power failure occurred within a small scope, and the power grid was basically restored to normal at 18:31 of the same day [3]. B. Belo Monte phase I 800kV HVDC project Belo Monte Hydropower Station, which located in the north of Brazil with installed capacity of 11000MW, transmits power to Estreito converter station, which located in the south of Brazil through Xingu converter station and 800kV dc line of Belo Monte phase I, with rated power of 4000MW. At the same time, the northern and northeastern parts of Brazil, the northern and southern parts, and the northeastern and southeastern parts of Brazil each are connected by 500kV ac liaison line. In order to meet the requirements of power delivery of Belo Monte Hydropower Station, ANEEL of Brazil hopes that the first-phase HVDC project (800kV) of Belo Monte will be put into operation in advance. After the negotiation with the project company, ANEEL has proposed a phased bus-bar operation plan for Xingu converter station. The main wiring diagram of Xingu converter station is shown in Fig.1. XXX-X-XXXX-XXXX-X/XX/$XX.00 ©20XX IEEE 422 on July 10,2020 at 04:21:25 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: City, University of London. Downloaded 2019 International Conference on Intelligent Green Building and Smart Grid (IGBSG2019), 6-9 Sept., Yichang China Manaus Macapá Jurupari SE Xingu B F SA F F Section switch 9522 A Belo Monte UHE Belo Monte Tucurui UHE Tucurui Imperatriz Marabá Sistema NE Colinas Sistema NE Interligação Norte-Sul Estreito Sistema S/SE-CO Fig. 1. Main wiring diagram of Xingu converter station The phased bus-bar operation plan are as follows. Stage 1: 500kV B bus operates without circuit breaker to ensure the debugging and operation of bipolar DC. Stage2: 500kV A bus with circuit breaker is put into operation, and 500kV B bus is shut down and relevant equipment is installed. Stage 3: 500kV B bus operates with circuit breaker. Before the blackout, Xingu converter station ac bus-bar is in the second stage of the construction process. The 500kV A bus adopts the operation mode with circuit breaker, and the over current protection’s preset value of section switch 9522 is set to 4000A. III. THE OVERVIEW OF BLACKOUT AND THE ANALYSIS OF CAUSES A. The process of the accident According to the accident investigation report issued by Brazilian Power Grid Dispatching Center (ONS) on June 4, 2018, the development process of the blackout is as follows. 1) The over-current protection of the section switch act which lead to a DC bipolar block of Belo Monte first-phase HVDC project. Before 15:48 p.m., the transmission power of the DC line was increased to 4000MW while the current was 4400A. The section switch of A bus operate correctly because of the over-load protection. As a result, the converter station’s 500kV bus voltage drops and the Belo Monte first-phase HVDC bipolar was blocked. 2) The security device did not operate in time, and the power system splitting into isolated grid. After the DC line bipolar blocking, the power flow transfer to the AC line due to the failure of SEP that the hydropower units of the Belo Monte Hydropower Station were not removed in time. As a result, the important links connecting the north, northeast and south jumped off in about three seconds after the accident. And the northern power grid and northeastern power are Split from the southern main grid. About 15:48:06,The Brazilian grid forms three main isolated grids: the northern grids, the northeastern grids and the southern grids(including the southeastern and central grids). 3) Each isolated network operates independently. The isolated networks in the East and northeast collapsed. B. Analysis of Accident Causes 1) The reason of the over-current protection action of the Xingu converter station’s section switch and the bipolar block of Belo Monte first-phase HVDC is the error of the over-current protection’s set value of the section switch 9522. The ONS stated in its subsequent statement that it was not clear to them that the over-current protection’s set value of the section switch 9522 was 4000A. Therefore, they gave instructions that DC should operate at rated power of 4000MW before the accident. As a result, the AC current reaches 4400A which was exceeding the set value of 9522 over-current protection. 2) Because the SEP does not consider the extreme situation of voltage loss of both 500 kV AC buses and the voltage loss of single bus during single bus operation transition period. 423 on July 10,2020 at 04:21:25 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: City, University of London. Downloaded 2019 International Conference on Intelligent Green Building and Smart Grid (IGBSG2019), 6-9 Sept., Yichang China a)After the large-scale power transfer from DC line to the AC channel in the Northern Power grid, many lines tripped. After the DC bipolar blocking, the SEP receives the cutoff signal, that cutting six units of Belo Monte Hydropower Station, from Siemens DC control and protection system. However, the SEP was still judged invalid, so the cut-off signal was not sent to the Belo Monte Hydropower Station. As a result, the removal of Belo Monte Hydropower Station’s units is delayed and the accident was further expanded. When the northern power grid is isolated, due to the unbalance between generation and load, the system frequency rises to 71.69Hz (power frequency 60Hz), and the generator unit is cut off by protection. At 15:49:21, the northern isolated network system collapsed, and the frequency fluctuation of the northern system is shown in Fig. 2.The total lost load of the northern power grid is 5750 MW, accounting for 93% of the load before the fault. 3) During the operation of the isolated network, the loss load of the Northern and Northeastern Power Grids is relatively serious. The power system remains stable while the Southern Power Grid’s under-frequency load shedding act. 80 Sao Luiz 70 Manaus 60 f/Hz Macapa Belén 50 18:50:53.333 18:50:45.000 18:50:36.666 18:50:28.333 18:50:20.000 18:50:11.666 18:50:03.333 18:49:55.000 18:49:46.666 18:49:38.333 18:49:30.000 18:49:21.666 18:49:13.333 18:49:05.000 18:48:56.666 18:48:48.333 18:48:40.000 18:48:31.666 18:48:23.333 18:48:15.000 18:48:06.666 18:47:58.333 18:47:50.000 18:47:41.666 18:47:33.333 18:47:25.000 18:47:16.666 18:47:08.333 30 18:47:00.000 40 Time Fig. 2. Frequency Fluctuation in Northern power System b) After the accident, the transfer of power flow resulted in the power system separation of the Northeast Power Grid to the North and South Power Grids from Pres. Dutra Substation, Ribeiro Gonalves Substation and Bom Jesus Da Section switch 9552 trip Lapa Substation. The frequency of isolated network dropped to 57.3Hz, and the frequency fluctuation in Northeast power system is shown in Fig.3. 60Hz 58.5Hz The thermal power plants removed from the power grid 57 Frequency Restored after load shedding Two units of Paulo Afonso Hydropower Plant were cut off successively 52 f/Hz The frequency is less than 58.5Hz and maintains for more than 10s. The relay protection equipment act. 47 Fortaleza 18:48:49.166 18:48:48.333 18:48:47.500 18:48:46.666 18:48:45.833 18:48:45.000 18:48:44.166 18:48:43.333 18:48:42.500 18:48:41.666 18:48:40.833 18:48:40.000 18:48:39.166 18:48:38.333 18:48:37.500 18:48:36.666 18:48:35.833 18:48:35.000 18:48:34.166 18:48:33.333 18:48:32.500 18:48:31.666 18:48:30.833 18:48:30.000 18:48:29.166 18:48:28.333 18:48:27.500 18:48:26.666 18:48:25.833 18:48:25.000 18:48:24.166 18:48:23.333 18:48:22.500 18:48:21.666 18:48:20.000 18:48:19.166 18:48:18.333 18:48:17.500 18:48:16.666 18:48:15.833 18:48:15.000 18:48:14.166 18:48:13.333 18:48:12.500 18:48:11.666 18:48:10.833 18:48:10.000 18:48:09.166 18:48:08.333 18:48:07.500 18:48:06.666 18:48:05.833 18:48:05.000 18:48:04.166 18:48:03.333 18:48:02.500 18:48:01.666 18:48:00.833 18:48:20.833 Recife 42 Time Fig. 3. Frequency fluctuation in Northeast power system 424 on July 10,2020 at 04:21:25 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: City, University of London. Downloaded 2019 International Conference on Intelligent Green Building and Smart Grid (IGBSG2019), 6-9 Sept., Yichang China and maintains for more than 10s. As a result, the relay protection equipment act, and the thermal power plants is removed from the power grid. The system frequency drops sharply, and the Northeast isolated network system collapses. Before isolated network formed in the Northeastern Power grid, under frequency load shedding for 5 rounds with a total load shedding of 1000MW was performed. After the under frequency load shedding operation, the isolated network frequency of northeast power grid was restored to 60Hz, and the system maintained short-term stability. At 15:48:20 and 15:48:25, two units of Paulo Afonso Hydropower Plant were cut off successively because of the relay protection equipment. The isolated network frequency dropped again from about 60 Hz to less than 58.5 Hz. As the Northeast power grid didn’t has further action in under frequency load shedding, the frequency is less than 58.5Hz c)After the accident occurred, the southern power system formed an isolated network at about 15:48:06. At around 15:48:08, the frequency of southern power system dropped to 58.44 Hz (power frequency 60 Hz). After the 3665MW load was removed from the system by under frequency load shedding, the system gradually restored to stability. The frequency fluctuation of the system in the southern power system is shown in Fig.4. 60.15522 Brasilia 59.65522 Belo Horizonte Curitiba f/Hz Campo Grande 59.15522 Sao Carlos Florianopolis Campinas 58.65522 18:48:42.500 18:48:41.666 18:48:40.833 18:48:40.000 18:48:39.166 18:48:38.333 18:48:37.500 18:48:36.666 18:48:35.833 18:48:35.000 18:48:34.166 18:48:33.333 18:48:32.500 18:48:31.666 18:48:30.833 18:48:30.000 18:48:29.166 18:48:28.333 18:48:27.500 18:48:26.666 18:48:25.833 18:48:25.000 18:48:24.166 18:48:23.333 18:48:22.500 18:48:21.666 18:48:20.000 18:48:19.166 18:48:18.333 18:48:17.500 18:48:16.666 18:48:15.833 18:48:15.000 18:48:14.166 18:48:13.333 18:48:12.500 18:48:11.666 18:48:10.833 18:48:10.000 18:48:09.166 18:48:08.333 18:48:07.500 18:48:06.666 18:48:05.833 18:48:05.000 18:48:04.166 18:48:03.333 18:48:02.500 58.15522 18:48:20.833 58.44Hz Time Fig. 4. Frequency fluctuations in the southern, southeastern and central Western Power system IV. THE ENLIGHTENMENT OF THE BLACKOUT TO HUNAN POWER GRID Brazil's 3.21 blackout was caused by the incorrect set value of the section switch’s relay protection. The incorrect action of stability control equipment after the blocking of the DC system led to the further expansion of the blackout, which led to the tripping operation of the regional grid tie lines and the power system separation. A. Attention on the coordination of relay protection and operation mode According to the 3.21 Brazilian blackout briefing, the tripping of section switch is not because of the incorrect set value. The real reason is that the Brazilian Power Grid Dispatching Center(ONS) is not clear about the set value of the section switch and the actual wiring, but still issued an order to transmit at the rated power of 4000MW which resulting in the trip of the section switch. As the first defense line of power grid, the relay protection devices, which cooperate with the operation mode, is the key to ensure the safety and stability of the power grid. According to the domestic industry habits, to ensure the relay protection equipment do not work, the set value should take full account of the load level of the line. And the set value is issued or filed by the dispatching department. There is no case that the dispatching department is not clear about the actual set value. Therefore, the blackout in Brazil exposed the problem of information exchange and sharing between the Brazilian power grid dispatching center and converter station. In addition, there is high power transmission on the AC/DC channel in Brazilian power grid. The carrying capacity when DC blocking and stability control equipment did not cutting of the units wasn’t take into consideration. Therefore, when bipolar blockade occurs in Belo Monte first-phase (±800 kV) HVDC transmission project, the AC line trips successively. For Hunan power grid, Qishao DC power transmission has reached a maximum of 4500MW. It is necessary to pay more attention to the safety of the power system when power on DC lines transfer to AC channel after DC block. B. Development of Safety and Stability Device Configuration and Strategies From the development of blackouts, stability control equipment of Xingu converter station did not cut the units of Belo Monte Hydropower Station, which is the root of accident expanding. In the actual fault, the DC control and protection system issued the cut-off instructions, but the stability control equipment decided that the cut-off instructions were invalid for the reason that the stability control equipment did not allocation the action strategy when both 500kV bus lose voltage or single bus, during the transitional period, lose voltage. 425 on July 10,2020 at 04:21:25 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: City, University of London. Downloaded 2019 International Conference on Intelligent Green Building and Smart Grid (IGBSG2019), 6-9 Sept., Yichang China Shaoshan converter station of Hunan power grid is the receiving station of Qishao DC. It is suggested that the configuration and strategy of stability control equipment of Shaoshan converter station should be further improved, especially in special working conditions which may occur during the transition period of construction. And the stability control equipment should be tested before it connect to grid. It should be ensured that the stability control equipment can cut load correctly in normal operation, maintenance operation and transition period. C. Attention on primary frequency regulation Characteristics of Units During the blackout in Brazil, as the receiving end of the Belo Monte first-phase (±800 kV) DC project, the southern power grid’s frequency dropped to 54.88 Hz after the accident. The frequency of the power system recovery takes about 17 seconds. The recovery time of the receiving-end grid’s frequency is closely related to the operating speed of the unit's primary frequency regulation characteristic. Similarly, to ensure that the primary frequency regulation of units in Hunan province can act correctly in time in case of various blocking accidents and holdover frequency stability. Hunan power grid, as the receiving end of Qishao DC, is suggested to strengthen the technical supervision of primary frequency regulation parameters. D. Improving the under-frequency load shedding configuration After expansion of effect of the blackout in Brazil, the strategy of under frequency load shedding is insufficient after the operation of the isolated network in the Northeastern Power grid. As a result, two units in the Paulo Afonso hydropower plant overload trip out because of the over load. And the frequency of the system cannot be restored, which eventually leads to system collapse. From this point of view, the power grid should be equipped with enough sufficient under frequency load shedding. And its configuration should cooperate with the system separation scheme to ensure the security of the system or the isolated network. Fourteen regional power grids in Hunan power grid are equipped with basic I-V load shedding rounds, which divided by equal capacity, with a total load shedding of 7270MW. In addition to the Xiang xi, Huaihua and Zhangjiajie power grids, the other regional power grids are equipped with special three rounds of under frequency load shedding, which divided by equal capacity, with load shedding capacity of about 1620MW. Hunan power grid’s under frequency load shedding configuration uses the average maximum load of each region as the base, and the under frequency load shedding allocates about 40% of the total load. With the development of society and economy, the electrical load of Hunan power grid has reached new heights. The allocation of under frequency load shedding configuration in Hunan power grid should match the electrical load of the grid. It ensures that the load can be effectively reduced under the extremely arduous condition of low frequency. And it also ensures the safety of the power grid, and avoids large-scale blackouts. CONCLUSION In this paper, the background, cause and development process of Brazilian blackout are introduced in detail. And the causes of occurrence and expansion of the accident are analyzed based on the introduction of Brazilian blackout. According to the problems in each link of accident development, the possible operation risks of Hunan power grid are analyzed. Hunan power grid should attach importance to relay protection’s set value management, and carry out safety and stability device configuration and strategy combing to set effective fault response measures. Meanwhile the technical supervision of primary frequency modulation parameters of important units should be carried out, and the underfrequency load shedding configuration of Hunan power grid should be improved. REFERENCES [1] [2] [3] [4] [5] Y. Chen, J. Hong, “Analysis on Causes of Blackout Occurred in Brazilian Power Grid on Nov. 11, 2009 and Lessons Drawn From It to China Southern Power Grid,” Power System Technology, vol. 34, pp.77-82, 2010. J. Zou, X. Zhang, “Summary and revelation of “2009·11·10” and “2011·2·4” blackouts in Brazil Power System,” Electric Power, vol. 44, pp. 19-22, 2011. Y. Liu, “Analysis on and Inspiration of the “9.13” Islanding and Outage of Brazilian Remote Northwest Power Grid,” Proceedings of the CSEE, vol. 38, pp. 3204-3213, 2018. M. Xiang, J. Zuo, X. Xie, C. Li, “Analysis of Holland blackout on March 27th, 2015 and revelations to security for Hunan Grid,” Hunan Electirc power, vol. 36, pp. 31-35, 2016. Y. Tang, G. Bu, J. Yi, “Analysis and Lessons of the Blackout in India Power Grid on July 30 and 31.2012,” Proceedings of the CSEE, vol. 32, pp. 167-174, 2012. 426 on July 10,2020 at 04:21:25 UTC from IEEE Xplore. Restrictions apply. Authorized licensed use limited to: City, University of London. Downloaded