Subido por rafael alejandro corpus martinez

i-COMM A

Anuncio
i-COMM™ ii / i-COMM™ CONTROLLER INSTRUCTIONS
Pub. No. i-COMM_A FEBRUARY 2016
1
i-COMM™ CONTROLLER
i-COMM ii DIGITAL CONTROLLER SPECIFICATIONS
!
DANGER
When working with electrical or electronic controls, make sure
that the power source has been locked out and tagged according
to OSHA regulations and approved local electrical codes.
!
WA R N I N G
Make sure to barricade the door opening on both sides to prevent
unauthorized use until the door has been completely installed.
NOTICE
DO NOT configure devices such as Motion Sensors, Photoeyes or
Floor Loops to Toggle Mode. Setting these devices to Toggle may
cause the door to close unexpectedly.
NOTICE
The power MUST be OFF and the door on the close limit switch
when plugging in the Downloader Chip.
NOTICE
When connecting i-COMM to other control systems, isolation
relays (Dry Contacts) should be used.
NOTICE TO USER
Our mission is to “Improve Industrial Safety, Security and
Productivity Worldwide Through Quality and Innovation.”
1. If any procedures for the installation or operation have
been left out or are not complete, contact RITE-HITE
DOORS, INC. Technical Support at 1-563-589-2722.
2. The use of a handheld device is no longer required, an
SD card can be used to down load programs.
3. This i-COMM II controller is used on the following door
models: FasTrax, FasTraxFR, FasTrax FR LD,
FasTraxCL, Fastrax XL, FasTrax LD, LiteSpeed,
SplitSecond, Defender, Barrier Glider.
4. Terminals will accept wire sizes from 12 - 22 AWG.
5. 8 Digital Inputs. (24VDC; 10 mA)
6. 3 Relay Outputs. (24VAC/DC; 1 AMP)
7. 6 DC Outputs. (24VDC; 0.5 AMP MAX)
REMOVAL AND INSTALLATION
1.
Change controller with door in the close position.
2.
Make sure you have all the parts before beginning.
3.
Unplug the J4 supply harness.
4.
Remove wires from the input and output terminals.
5.
Remove the board by squeezing the white plastic
supports, and remove supports from bracket.
6.
Install new board, by snapping onto supports.
7.
Plug in the J4 connector.
8.
Insert wires into terminals, based on markings, labels on
the wires as well as the electrical wiring diagram included
with the door.
2
!
DANGER
A qualified electrician should install the wiring in accordance with
local and national electrical codes.
Use lockout and tagout procedures to avoid injury.
NOTICE
Do not drill holes on top of control box to run conduit, as dust
particles and moisture may cause damage to electrical
components. The safest location is at the bottom. Failure to do so
will void warranty.
NOTICE
Damage or debris may fall into electrical components causing failure
or severe equipment damage, when drilling holes in the box.
DO NOT turn control box upside down or go too deeply into the box.
FCC COMPLIANCE
NOTE: This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is
operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to
correct the interference at his own expense.
NOTE: Changes or modifications not expressly approved by the
party responsible for compliance could void the user's authority to
operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesirable operation.
LOCKOUT/TAGOUT PROCEDURES
The Occupational Safety and Health Administration requires that, in
addition to posting safety warnings and barricading the work area, the
power supply has been locked in the OFF position or disconnected. It is
mandatory that an approved lockout device is utilized. An example of a
lockout device is illustrated. The proper lockout procedure requires that
the person responsible for the repairs is the only person who has the
ability to remove the lockout device.
In addition to the lockout device, it is also a requirement to tag the power
control in a manner that will clearly note that repairs are under way and
state who is responsible for the
lockout condition. Tagout devices have
to be constructed and printed so that
exposure to weather conditions or wet
and damp locations will not cause the
tag to deteriorate or become
unreadable.
RITE-HITE Corporation does not
recommend any particular lockout
device, but recommends the utilization
of an OSHA approved device (refer to
OSHA regulation 1910.147). RITEHITE Corporation also recommends
the review and implementation of an
entire safety program for the Control of
Hazardous Energy (Lockout/Tagout).
These regulations are available
through OSHA publication 3120.
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM CONTROLLER (=> 6/20/12)
THE FOLLOWING PAGES ARE FOR i-COMM ii:
ALL 7100, FASTRAX, FASTRAXCL, FASTRAXFR, FASTRAX LD, FASTRAX FRLD,
FASTRAX XL, LITESPEED, SPLITSECOND AFTER 6/20/12.
Pub. No. i-COMM_A FEBRUARY 2016
3
4
I
H
G
F
E
D
C
B
A
N
O
M
P
L
N
O
P
Q
R
A
B
C
D
E
F
G
H
I
J
K
L
M
J
K
Q
R
Component key:
Power LED
Contrast Button
Up Button
Enter Button
Back Button
Down Button
LED Input’s X0 - X15
Encoder Terminals
Input Terminals
DC Terminals
OV Terminals
J4 Connector
Output LED’s K0-K2
& Y0-Y5
Display
Battery (CR2032 3V)
SD Card
Solid State Outputs
Relay Outputs
i-COMM™ CONTROLLER
i-COMM ii LAYOUT
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
RITE-HITE DOORS NOTES PAGE
This page intentional left blank.
Pub. No. i-COMM_A FEBRUARY 2016
5
i-COMM™ CONTROLLER
i-COMM ii SETUP INSTRUCTIONS
MUST complete before operating door.
Operation of the door is not possible when using the
menu system.
To adjust CLOSE position:
3.
Using up button, scroll to “Close Pos. Adjust”.
4.
Press enter button to view parameter value. This
parameter will show a coded value on the left and
relative change in inches on the right. When
entering this parameter the value will always start at
0.0”.
ENCODER SETUP INSTRUCTIONS
1. Verify wiring to encoder is properly terminated.
2.
Place curtain in the closed (or open) position. If
open, curtain should be 1’-2’ below the lintel.
3.
Power up the door and press enter button on the icomm, should state “MAIN MENU - ENCODER
FOLDER”.
4.
Press enter should state “Open Distance”.
5.
Press enter to view parameter value (measured in
feet), should be O.D.H. - (two) 2’. Change the value
using the up or down buttons, round down if
required, press enter.
6.
Press up button, should state “Motor Drive Side”,
press enter and select “Right Drive” or “Left
Drive”, press enter.
7.
Press up button, should state “Set Close Pos.”
(use if curtain is closed) or go to “Set Open Pos.”
(use if curtain is open) and press enter button,
should state “Set Close (or Open) Pos.) and toggle
between RESET ALL LIMITS and Push Up to
Start”, press Up button.
8.
Press the green flashing Open/Reset button on the
front of the control box. Door should run open, time
out and close. Proceed to “Open and Close Position
Adjustment”.
Change values using the up or down buttons.
To bring the curtain closer to the floor, adjust this
value so that it is less than zero. (i.e. To close the
door 4” more, the value for “Close Pos. Adjust” will
be -4.0”) Moving this parameter in the positive
direction raises the curtain relative to the floor.
Changing this value will not affect the open position.
Note: If you leave this parameter and return to it, its value
will again be zero. Any changes made before
leaving the parameter will still be effective. For
example: If you lowered the door 4.0”, leave the
parameter and return, the parameter will display
0.0”. Even though the display shows 0.0” the -4.0”
change has been recorded.
TIP: At any point in the menu mode, press the back
button until screen states “Door Faulted - Service
Required”. This will cause the controller to
automatically accept all the changes made and exit
the system.
5.
Changes are not saved until the menu mode is
exited. Turning power off while in the menu mode
will cancel all changes.
Open and Close Position Adjustment
6.
Test operation of door and continue adjustment.
To adjust the OPEN position:
7.
Press green Open/Reset button.
1.
Using up button, scroll to “Open Pos. Adjust”.
2.
Press enter button to view parameter value. This
parameter will show a coded value on the left and
the opening height in inches on the right. This value
will always be less than the door opening height.
a. The door should begin to open, be ready to
shutdown the door if it begins to move in the wrong
direction. If motor phase is changed, start over at
step #2.
b. If rotation is correct proceed to the instructions for
adjusting the “Open and Close positions”.
Change the value using the up and down buttons.
To bring the open position down (closer to the floor)
adjust this value to be less than the current value.
To open the door more relative to the floor, adjust
this parameter in a positive direction. (i.e. To open
the door 4” more, and the current value is 72.0”.
Change the value for “Open Pos. Adjust” to be
76.0”). Changing this value will not affect the close
position.
6
8.
Press the back (left button) to exit system.
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM ii SETUP INSTRUCTIONS
OPTION
Open Distance
Motor Drive Side
Set Close Pos
Set Open Pos
Open Pos Adjust
Close Pos Adjust
Apr Open Pos
Encoder Startup
Encoder Read
Encoder Velocity
Open Time Limit
Photoeye Blocked
Photoeye Failure
DESCRIPTION
Use this option to set the overall opening distance of the door (in feet). For example, for an 8’ tall
FasTrax. This option should be set to “7” [178]. This measurement is used for initial position setup
only. For small adjustments of the open and close position, use “Close Position Adjust” or “Open
Position Adjust”
Use this option to select which side the motor is located: “Right Drive” or “Left Drive”
Use this option for initial position setup. Manually place door in the close position and select this
option. Alternatively “Set Open Pos.” can be used if it is more convenient to place the door in the
open position. NOTE: This option approximately sets the open and close positions. For additional
adjustment of the open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option for initial position setup. Manually place door in the open position and select this
option. Alternatively “Set Close Pos.” can be used if it is more convenient to place the door in the
closed position.NOTE: This option approximately sets the open and close positions. For additional
adjustment of the open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option to make small adjustment to the open position. The number displayed is the
measurement between the open and closed position. For example if this option was set to 100”
[2540] the door would open 100” [2540] from the closed position. It is recommended to adjust the
closed position of the door first, before adjusting the open position.
Use this option to make small adjustment to the closed position. The number displayed is the
relative displacement of the closed position. For example, if this option was set to -1.0”[-25] the door
would close approximately 1.0” [25] more. If this option was set to 2.0” [51] the door would close 2.0”
[51] less.
Use this option to adjust the approach open position. This option is a measurement in inches from
the open position. For example, if this option was set to 24.0” [610] the door would slow down 24.0”
[610] from the open position.
The controller is waiting for valid data from the encoder. It the controller does not receive a
response at startup, this will remain on the screen indefinitely. If this does not clear with 5 seconds,
please check all encoder wiring.
The controller is unable to read valid data from the encoder. Check all wiring and M12 cable
connections. Ensure that the shield on the encoder cable is connected to ground, and that the
control box is grounded. The error requires the power to be cycled to reset.
The controller has received a signal from the encoder that the door is moving faster than allowed.
This can occur if the encoder is not properly attached to the shaft (check set screws on encoder
collar and sprockets), bad electrical connection to the i-COMM, or improper grounding. The error
requires the power to be cycled to reset.
Door tried to run, but did not reach the open or close position within 8 seconds.
Non-Drive PE’s must have green light on, drive PE’s must have orange & yellow lights on. Check for
alignment & power to each.
To perform photoeye test, output YDC2 must go off on every cycle open. If it does not the output
may have failed. Move the wire in the YDC2 output terminal to YDC1 or YDC0 and change the value
of this output to 17 - Off during run open
i-COMM TROUBLESHOOTING
ISSUE
Dim Display
No Power
Garbled Text
at the
Door Travels
Past Stop Point
RESOLUTION
Adjust contrast dial.
Verify Power Supply LED is Green, if not unplug J4 connector on i-COMM. If LED remains Red,
check DC voltage on V+ & V-, should be 24-26 VDC. If LED turns Green, unhook wires from iCOMM to find which wire is shorting the board.
If CUI or LED Count down display or Preannounce is present unplug the J46 and/or J48 connector, if
text clears up check CUI or LED wiring. text maybe garbled due to trying to display two faults
same time.
If your door travels past the open or close position when setting up the encoder, try “setting the
opposite position”. This is especially helpful on the SplitSecond model.
Pub. No. i-COMM_A FEBRUARY 2016
7
i-COMM™ CONTROLLER
i-COMM ii PROGRAMMING FOLDERS
Use the Enter, Up, Down, Back buttons on the i-Comm to
navigate through the folders. To exit system, use back
button until “Door Faulted” appears.
ENCODER FOLDER
See Folder Layout Chart to change / view settings.
* MUST perform encoder setup for door operation.
GENERAL FOLDER
See General Layout Chart to change / view settings.
Use to setup Clock, Maintenance cycles
VIEW FOLDER
See View Layout Chart to change / view settings.
Use to view cycle count, fault history, door information.
I/O SETUP FOLDER
See I/O Setup Layout Chart to change / view settings.
Use to setup Input and Output functions
TIMER FOLDER
See Timer Layout Chart to change / view settings.
Use to change reclose or preannounce timer.
LOAD / SAVE FOLDER
See Load / Save Layout Chart to change / view settings.
See Legal information.
Use for programming.
INVERTER FOLDER
See Inverter Layout Chart to change / view settings.
Use to change door speeds, torque settings.
i-COMM ii PROCEDURES
PROCEDURE FOR ADJUSTING RECLOSE TIMER:
1. Press ENTER button.
2. Use UP button to scroll to TIMER FOLDER, press enter,
should display “Set Close Timer”.
3. Press ENTER button.
4. To increase reclose time, press UP button.
5. To decrease reclose time, press DOWN button.
6. Press BACK button when complete.
PROCEDURE FOR DOWNLOADING A PROGRAM:
PROCEDURE FOR CHECKING FAULT HISTORY:
1. Press ENTER button.
2. Use UP button to scroll to VIEW FOLDER, press enter,
should display “Fault History”.
3. Press ENTER button, should display the last fault / flash
the date / time it occurred.
4. This displays the last 20 faults.
5. Press BACK when complete.
1. Turn off power to the door and insert SD card into socket.
2. Turn on power and press ENTER button.
3. Use UP button to scroll to “LOAD / SAVE Folder”, press
enter, scroll to “Copy from SD” and press ENTER button.
4. Press the UP button when prompted.
5. If “Choose file....” displays, choose the correct file and
press ENTER to start update.
6. After the i-COMM reboots, remove SD card and operate door.
PROCEDURE FOR SETTING CLOCK:
1. Press ENTER button.
2. Use UP button to scroll to GENERAL FOLDER, press
enter, should display “Clock”.
3. Press ENTER button, should display M/D/Y and time.
4. Press UP, set year - press enter, set month - press enter,
set day - press enter, set hour - press enter, set minute press enter.
5. Press BACK when complete.
PROCEDURE FOR SETTING MAINTENANCE:
1. Press ENTER button.
2. Use UP button to scroll to GENERAL FOLDER, press
enter, press UP to scroll to “Maint. Months” or Cycles”.
3. Press ENTER button, should display number of months or
number of cycles.
4. Press BACK when complete.
Note: When setting Maintenance timer, Open / Reset button will
flash slow when set time / cycles have expired and
display Maintenance Required.
To reset Maintenance light, press ENTER button, scroll to
General Folder, press ENTER button, scroll to Reset
Maintenance, press ENTER, then UP to start, then green
Open Button. This will reset flashing Open / Reset button.
8
Pub. No. i-COMM_A FEBRUARY 2016
Watchdog Timer
Normal Power Up
Breakaway
Open Time Limit
Menu Interrupt
Limit Failure
Emergency Stop
Close Time Limit
Limit Pulse Time
Obstruction
System Clk Read
Unknown State
PRO System
Photoeye Failure
Encoder Read
Encoder Velocity
Encoder Connection
VFD Trip # xxx
VFD Comm. Loss
Program Inverter
Check Rev. Edge
Refeed Curtain
Encoder-No Power
LZR Test Failed
VFD Torque Relay
Rev. Edge Count
Door Locked
Curtain Jam
Counterweight
Counterweight
Low Velocity
Low Velocity
Curtain Jam
Door Overtravel
Blank
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
255
i-COMM DISPLAY FAULT
ERROR DESCRIPTION
0
1
2
FAULT
CODE #
Pub. No. i-COMM_A FEBRUARY 2016
Inverter is not programmed for proper door operation
i-COMM ii has detected a reversing edge continuity error
i-COMM ii has detected a curtain refeed error
i-COMM ii has detected no power to encoder error
i-COMM ii has detected an LZR test error
VFD Relay failed to change state
i-COMM has detected reversing edge was activated (CE only)
i-COMM has detected that the door CUI is locked
Curtain is moving slower than expected while closing
i-COMM ii has detected a counterweight closing error
i-COMM ii has detected a counterweight opening error
i-COMM ii has detected a low velocity close error
i-COMM ii has detected a low velocity open error
Curtain is moving slower than expected while opening
i-COMM ii has detected a door overtravel error
No Fault
i-COMM ii has detected a bad encoder read
i-COMM ii has detected a velocity error
i-COMM ii has detected a connection error
Inverter is in fault. xxx Indicates the active inverter fault
i-COMM ii has lost communication with inverter
System clock failed
State unknown
Pro inverter fault (8000, 8000XL)
Indicates problem with reversing photoeye's (FSTX Series, LTSPD or SPLT)
Run close time limit exceeded
Trakline limit problem. Second close limit pulse not detected.
Door has detected obstruction and reversed 3 times
Indicates the board watchdog timer has reset
Indicates loss of power
Door is in breakaway mode: FasTrax - chain hoist; 8000CL/XL - sideframe door;
8000/CL/XL overload relay
Run open time limit exceeded
i-COMM menu interrupted
Limit switch has failed
E-Stop button pushed or overload relay tripped (8900) or Inverter relay failure
(8600) or chain hoist switch open (FasTrax)
FAULT REASON
PROPOSED ACTION REQUIRED
Service Required
Service Required
Service Required
Push Open/Reset
Check
Connection
Service Required
Jog to Close
Jog to Close
Service Required
Jog to Close
Service Required
Jog to Close
Door Locked
Service Required
Service Required
Service Required
Service Required
Service Required
Service Required
Service Required
None
Indicates inverter (VFD) is not properly programmed. Re-program inverter.
Check reversing edge wires for continuity or if shorted.
LiteSpeed header Slack Sensor photoeye has tripped - curtain has reversed 5 times
i-COMM board has detected no power to the encoder. Check wiring connections
Check wiring of LZR or perform "Teach In" per BEA User's Guide
Check torque setting and check VFD relay
Cycle power and reset
Press and hold the Red button on CUI for 15 seconds to unlock
Check for drive system obstruction or high wind load
Check counterweight photoeyes and verify counterweight travels freely in the tube
Check counterweight photoeyes and verify counterweight travels freely in the tube
Wind or pressure on curtain has caused FSTX XL door to close slower than normal
Wind or pressure on curtain has caused FSTX XL door to open slower than normal
Check for drive system obstruction or high wind load
FSTX XL curtain has traveled past the curtain sensing photoeyes
None
Rev. 2/12/2016
i-COMM board did not read encoder status. Check wiring connections.
i-COMM board detected improper speed or wrong direction. Check wiring connections
i-COMM board did not read connection to encoder. Check wiring connections
i-COMM board displaying inverter (VFD) fault. Check manual for inverter faults
i-COMM board has lost communication with inverter (VFD). Check wiring connections
Service Required Door did not reach close limit within 8 seconds
Service Required Check limit switch
Inspect & Reset Door tried to close 3 times but sensed friction or an obstruction, reversed, stayed open and
faulted
Service Required Clock has elapsed, check and/or replace battery
Service Required Cycle power and reset
Check Inverter Check inverter for fault codes
Jog to Close
Reversing photoeye's did not pass test
Service Required i-COMM board requires replacement
Push Open/Reset Power to the door was lost, press Open/Reset button to operate door
Reset/Jog Door If need be - press Open/Reset to "Jog" door. Reset breakaway mechanism. Press Open/Reset
button to operate door.
Service Required Door did not reach open limit within 8 seconds
Push Open/Reset The i-COMM menu was accessed. Press Open/Reset button to operate door.
Service Required Door did not read limit switch or two switches activated simutaneously
Push Open/Reset E-Stop button was activated or is defective. Check 8900 overload relay, check chain hoist
switch on FasTrax series model doors. Press Open/Reset button to operate door.
ACTION
REQUIRED
i-COMM™ CONTROLLER
i-COMM ii FAULT DISPLAY MESSAGES
9
i-COMM™ CONTROLLER
i-COMM ii FOLDER LAYOUT
*NUMBER IS NOT SHOWN IN i-COMM MENU*
FOLDER
#
0
1
2
3
4
Encoder
5
Folder
6
7
8
9
10
11
NAME
Open Distance
Motor Drive Side
Set Close Position
Set Open Position
Close Position Adjust
Open Position Adjust
Partial Open Pos.
Encoder Position
Encoder Baud
Approach Open Pos.
Approach Close Pos.
Set Open PB Function
12 Set Loop Function
I/O
Setup
Folder
Timer
Folder
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
I - Zone System
Output Def. YK0
Output Def. YK1
Output Def. YK2
Output Def. YDC0
Output Def. YDC1
Output Def. YDC2
Output Def. YDC3
Output Def. YDC4
Output Def. YDC5
Output Def. YDC6
Output Def. YDC7
Input Define X0
Input Define X1
Input Define X2
Input Define X3
Input Define X4
Input Define X5
Input Define X6
Input Define X7
Open Alarm Time
VALID VALUES
3 - 24
Right Drive / Left Drive
Press UP to Start
Press UP to Start
+/- 100.0
0 - 990.00
0 - Open Pos. Height
0-01FFFF
433 kbps
999.0
999.0
Auto Close Mode; Toggle
& Auto Close, Reset/Jog
only; Toggle Mode
Auto Close Mode,
Reverse / Hold Open
Enabled / Disabled
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 33 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 17 (See Table)
0 - 255
34 Input Define X10
35 Input Define X11
36 I - Zone Cut - Out
0 - 30
0 - 66
0 - 48
37 Set Close Timer
0 - 255 / Toggle Mode
38 Preannounce Close
39 Preannounce Open
40 Autocycle Time
0 - 255
0 - 255
0 - 254 / Disabled
DESCRIPTION
Used to Set Opening distance for door
Used to select motor drive side.
Use for initial setup of close position
Use for initial setup of open position
Use to adjust close position.
Use to adjust door open position
Use to adjust door partial open position
Current encoder position
Used to select encoder data rate
Used to select Approach Open Position
Used to select Approach Close Position
Use to select the function of the Open/Reset button.
DEFAULT
Varies
Right
433 KBPS
Varies
Varies
Auto Close
Mode
Auto Close
Mode
Disabled
Use to Enable / Disable the I-Zone system.
0
User configurable relay
20
User configurable relay
20
User configurable relay
3
User configurable DC output
29
User configurable DC output
29
Internal - not available DC output
20
Internal - not available DC output
20
Internal - not available DC output
2
User configurable DC output
20
Internal - not available DC output
20
Internal - not available DC output
8
User configurable input
7
User configurable input
2
User configurable input
2
User configurable input
4
User configurable input
3
User configurable input
2
User configurable input
2
User configurable input
0
Open Alarm Time in minutes. Requires at least one output
to be configured to function 25, menu is hidden if not.
24
Torque
60
Unused
42
I-Zone cut out height
Use to select induction loop input function
Close Timer in seconds. Set to Toggle Mode to
disable automatic closing.
Preannounce to close timer in seconds
Preannounce to open timer in seconds
Autocycle Time in minutes
6
2
Disabled
Disabled*
* No Auto Re-close on Defender model.
10
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM ii FOLDER LAYOUT
*NUMBER IS NOT SHOWN IN i-COMM MENU*
FOLDER
General
Folder
View
Folder
Load /
Save
Folder
# NAME
41 Clock
VALID VALUES
-
DESCRIPTION
42
43
44
45
46
47
48
49
50
51
52
53
English, Espanol, Portuguese
Enabled / Disabled
Disabled, CE, Canada Opt
Enabled / Disabled
xx
208/220/230/400/460/575
0 - 999
Enabled/Disabled
xx
Displays current time and date. To set: press UP, scroll to year - press
Enter; scroll to month - press Enter; scroll to day - press Enter; scroll to
hour - press Enter; scroll to minute - press Enter
57 Reset to Default
-
Set LCD display language
Use to change access mode.
Use to enable reversing edge.
Used to enable specification packages.
Used to enable remote LCD
Consult Engineering. Special Applications only
Reverse Delay
Consult Engineering. Special Applications only
Voltage of door
Square footage of door. Width x Height
Enables non-powered open for LiteSpeed
Number of months before maintenance indicator
goes off. Note: Once changed user must initiate
“Reset Maintenance” Procedure.
Number of cycles before maintenance indicator
goes off. Note: Once changed user must initiate
“Reset Maintenance” Procedure.
Resets Maintenance Counters and Timers. Press
Up to initiate the reset
Used to adjust the speed threshold for the
counterweight sensor
Resets all settings back to factory defaults
58
59
60
61
62
63
0 - 99999999
-
Displays
Displays
Displays
Displays
Displays
Displays
64 Copy from SD
Press UP to Start Copy
65 Copy to SD Card
Press UP to Start Copy
66 Legal info to SD
Press UP to Start Copy
67 Bootloader Upgrade
Press UP to Start Copy
68 Export Settings
Press UP to Start Copy
69 Import Settings
Press UP to Start Copy
Use to upgrade i-COMM II program. Correct .BIN file must
be saved so SD Card. Note Card must be SD - 2GB or
SDHC - 4,8,16 or 32 GB.
Use to copy i-COMM II program to SD Card in .BIN
format.
Use to display legal information about program.
Legal.txt will be saved to SD card.
Used to upgrade bootloader. CAUTION: DO NOT
INTERRUPT THIS PROCESS
Use to save i-COMM II settings to SD Card in .BIN
format.
Use to copy i-COMM II settings to SD Card in .BIN
format.
Language
PassCode
Rev. Edge Option
Spec. Package
Compact User Interface
Partial Open
Reverse Delay
AB Inverter Delay
Voltage
Square Feet
Non-Powered Open
Maintenance Months
54 Maintenance Cycles
0 - 100000
55 Reset Maintenance
-
56 Speed Threshold
0-100%
70
Display Cycle Count
Fault History
Display Model #
Display RHC #
Display Serial #
Firmware Revision
CT SK MODBUS, AB PF40
MODBUS, CT SK NO
MODBUS, AP PF NO
MODBUS, No Inverter
Program Inverter
Press UP to Start Copy
Open Speed
0 - 70 Hz
Close Speed
0 - 70 Hz
Approach Speed
0 - 70 Hz
Accel Time
0 - 10.0 s
Accel Time 2
0 - 10.0 s
Decel Time
0 - 10.0 s
Torque Reverse Level 0 - 100 %
DC Brake Time
0 - 10.0 s
DC Brake Level
0 - 100 %
current Cycle Count
fault log. Use Up and Down to scroll
door model number
RHC number
door serial number
current program revisions
Used to set inverter type
Inverter Type
Inverter
Folder
71
72
73
74
75
76
77
78
79
80
Use to program inverter.
Open Speed
Close Speed
Approach Open Speed
Acceleration Rate
Acceleration Rate 2
Deceleration Rate
Torque Reversing Level
Injection Braking Time
DC Injection Braking Level
DEFAULT
English
Disabled
Disabled
Disabled
0%*
460
0
Disabled
6
100000
CT SK
MODBUS
Varies
Varies
Varies
Varies
Varies
Varies
Varies
Varies
Varies
Last Rev: 7.20.15
48 - Reverse delay should be set to 40% for 8900 TrakLine doors with counterweight.
Pub. No. i-COMM_A FEBRUARY 2016
11
i-COMM™ CONTROLLER
i-COMM ii INPUT / OUTPUT VALUES
TYPE
INPUT
OUTPUT
NUMBER
FUNCTION
0
Interlock In
1
2
3
Stop N.C.
Activation
Toggle
4
5
Close
Sequential Activation
6
7
8
Reverse
Stop N.O.
Manual Open
9
10
11
Auto / Manual
Partial Open Activation
Partial Open Toggle
12
Toggle w/ Auto Close
13
14
15
16
17
18
19
20
Hand / Auto Mode
Disabled
Reverse N.C.
Clean
E-Stop N.C.
Seq. Activation 2
LZR in N.C.
Preannounce to Open
21
Interlock Override
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Interlock
Interlock N.C.
Preannounce
Open
Open N.C.
Fault
Ready
Activation
Run Open
Run Close
Run
At Limits
I-Zone Alarm
Door Open 30 sec.
Door Open 60 sec.
Door Open 120 sec.
Sequential Activation
Run Open N.C.
Run Close N.C.
Run Close N.C.
Disabled
Flash 3.1 Hz
Flash 1.6 Hz
Partial Timer
Reverse / Activation
Door Open Alarm
Interlock Pass-Thru
27
28
29
30
31
32
33
34
35
36
DESCRIPTION
Interlock Input - When Input is set to this function door will not open until
input is ON. Valid only for inputs X3, X4, and X5.
Stops the door when input is OFF
Opens the door when input is ON, w/ Auto close.
Open and Closes the door when ON. Door will not automatically close
when opened by a toggle input.
Closes the door when input is ON
Activates door and blocks sequential activation output from triggering
opposite door. Use only for sequential interlocks.
Reverses the door when input is ON.
Stops the door when input is ON.
Opens the door when input is ON. This input will open from a stop
condition, unlike activation. Do not connect motion sensors or other
automatic devices to a manual open input
When input is ON reclose timer is disabled.
Opens the door to the partial open position when ON
Toggle open/close door to and from partial open position.
See function #3 above
Open and Closes the door when ON. Door will automatically close when
opened by this type of toggle input.
When input is ON reclose timer is disabled and hold-to-run close is enabled.
Input disabled
Reverses the door when input is OFF.
Opens door to "Cleaning" position when on.
Places door in fault when OFF.
Consult Engineering
Reverses the door when off and monitors the input for fault
Opens the door after the set amount of time in the Preann. to Open timer.
Immediate reversal / activation if the door is not closed.
Opens the door and overrides any standard interlock configuration
ON when door is closed.
OFF when door is closed.
ON during preannounce to close, and stays on until the door is closed
ON when door is open.
OFF when door is open.
ON during fault.
ON when not in fault.
ON during activation.
ON during run open.
ON during run close.
ON during run open or close.
ON when door is open or closed.
ON during I-Zone alarm
ON when door is open for more than 30 seconds.
ON when door is open for more than 60 seconds.
ON when door is open for more than 120 seconds.
ON to activate opposite door. Use for sequential interlock.
OFF during run open.
OFF during run close.
OFF during run open or close.
Always OFF
Flashes at 3.125 Hz.
Flashes at 1.5625 Hz.
Consult Engineering
ON when any reverse command or activation signal is on.
ON when door has been opened for time set in "Open Alrm Time"
ON when door is able to be opened (Interlock Input is not preventing door
from opening)
Interlock Pass-Thru N.C. OFF when door is able to be opened (Interlock Input is not preventing
door from opening)
Preannounce & Close
ON during preannounce to close, and while closing. Note this output will turn
on while door is closed from Toggle or Close command or re-close timer.
Photoeye Test
ON when emitters are on, OFF to test photoeyes
Encoder Bit 9
Consult Engineering
Encoder Bit 10
Consult Engineering
Encoder Bit 11
Consult Engineering
Encoder Bit 12
Consult Engineering
Preannounce to Open
ON during the set preannounce to open time.
Preannounce to Close ON only during preannounce to close. OFF during run close.
Preannounce & Flash
Flashes at 3.1 Hz during preannounce to close. OFF during run close.
Last updated: 2.09.16
12
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM ii LOGIC CHART - FASTRAX/LD/CL/FR/FRLD
R
FasTrax Encoder
i-COMM II Quick Reference
OUTPUT TABLE
INPUT TABLE
Relay Output
Function
Input
Function
X0
Open PB
YK0
Interlock Out
X1
Stop PB
YK1
Programmable
YK2
Programmable
X2,X3,X6,X7
Activation Command
X4
Close PB
X5
Toggle Command
DC Output
Function
X8*,X9*
IZone Sensors (R & L)
YDC0
X10*
18" Photoeye Input
YDC1
Photoeye Test
X11*
54" Photoeye Input
*YDC2
Photoeye Test
X12
Open/Reset PB
*YDC3
X13
Induction Loop Input
*YDC4
X14*
Fault Input
YDC5
X15*
Input Power
*YDC6
* Not shown in I/O menu and not programmable
*YDC7
On when door Open
Open/Reset PB Light
I-Zone Alarm
Preannounce to Close
NPO Contactor
Disabled
Encoder Adjustment Descriptions
(Refer to i-COMM and Owners Manuals for additional detail)
Open Distance
Set Close
Position
Set Open
Position
Close Position
Adjust
Open Position
Adjust
Motor Drive
Side
Use this option to set the overall opening distance of the door (in feet). This
measurement is used for initial position setup only. For small adjustments of the
open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option for initial position setup. Manually place door in the close position
and select this option. Alternatively “Set Open Pos.” can be used if it is more
convenient to place the door in the open position.
Use this option for initial position setup. Manually place door in the open position
and select this option. Alternatively “Set Close Pos.” can be used if it is more
convenient to place the door in the closed position.
Use this option to make small adjustment to the closed position. The number
displayed is the relative displacement of the closed position.
Use this option to make small adjustment to the open position. The number
displayed is the measurement between the open and closed position.
Use this option to change the encoder rotation direction. For a motor mounted on
the right side of the drive tube, select "Right Drive". For a motor mounted on the left
side of the drive tube, select "Left Drive".
Timer Adjustment
1. Press [ENTER], Controller will stop and fault door.
2. Press [UP] or [DOWN] until the timer folder is displayed.
3. Press [ENTER], to enter the timer folder.
4. Using [UP] & [DOWN] keys select desired timer.
5. Press [ENTER] to view the current timer value.
6. Use [UP] or [DOWN] keys set the desired value.
7. Press [ENTER] to save the value and return to
the timer folder.
8. Press [BACK] until "Door Faulted" is displayed.
9. Reset Door.
Preannounce Timer is the amount of time the
Preannounce to close output will be on before door closes.
Close Timer is the amount of time the door will remain
open before the preannounce to close timer activates
Autocycle Time is the amount of time between each
automatic cycle of the door (disabled by default).
53850610-1
Pub. No. i-COMM_A FEBRUARY 2016
13
i-COMM™ CONTROLLER
i-COMM ii LOGIC CHART - FASTRAX XL
14
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM ii LOGIC CHART - LITESPEED
TM
LiteSpeed Encoder
i-COMM II Quick Reference
OUTPUT TABLE
INPUT TABLE
Relay Output
Function
Input
Function
X0
Open PB
YK0
Interlock Out
X1
Stop PB
YK1
Programmable
YK2
Programmable
X2,X3,X6,X7
Activation Command
X4
Close PB
X5
Toggle Command
DC Output
Function
X8*,X9*
IZone Sensors (R & L)
YDC0
X10*
18" Photoeye Input
YDC1
Photoeye Test
X11*
Header Photoeye Input
*YDC2
Photoeye Test
X12
Open/Reset PB
*YDC3
X13
Induction Loop Input
*YDC4
On when door Open
Open/Reset PB Light
I-Zone Alarm
X14*
Fault Input
YDC5
X15*
Input Power
YDC6
Disabled
*YDC7
Disabled
* Not shown in I/O menu and not programmable
Preannounce to Close
Encoder Adjustment Descriptions
(Refer to i-COMM and Owners Manuals for additional detail)
Open Distance
Set Close
Position
Set Open
Position
Close Position
Adjust
Open Position
Adjust
Motor Drive
Side
Use this option to set the overall opening distance of the door (in feet). This
measurement is used for initial position setup only. For small adjustments of the
open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option for initial position setup. Manually place door in the close position
and select this option. Alternatively “Set Open Pos.” can be used if it is more
convenient to place the door in the open position.
Use this option for initial position setup. Manually place door in the open position
and select this option. Alternatively “Set Close Pos.” can be used if it is more
convenient to place the door in the closed position.
Use this option to make small adjustment to the closed position. The number
displayed is the relative displacement of the closed position.
Use this option to make small adjustment to the open position. The number
displayed is the measurement between the open and closed position.
Use this option to change the encoder rotation direction. For a motor mounted on
the right side of the drive tube, select "Right Drive". For a motor mounted on the left
side of the drive tube, select "Left Drive".
Timer Adjustment
1. Press [ENTER], Controller will stop and fault door.
2. Press [UP] or [DOWN] until the timer folder is displayed.
3. Press [ENTER], to enter the timer folder.
4. Using [UP] & [DOWN] keys select desired timer.
5. Press [ENTER] to view the current timer value.
6. Use [UP] or [DOWN] keys set the desired value.
7. Press [ENTER] to save the value and return to
the timer folder.
8. Press [BACK] until "Door Faulted" is displayed.
9. Reset Door.
Preannounce Timer is the amount of time the
Preannounce to close output will be on before door closes.
Close Timer is the amount of time the door will remain
open before the preannounce to close timer activates
Autocycle Time is the amount of time between each
automatic cycle of the door (disabled by default).
53850677-1
Pub. No. i-COMM_A FEBRUARY 2016
15
i-COMM™ CONTROLLER
i-COMM ii LOGIC CHART - SPLITSECOND
TM
SplitSecond Series
i-COMMII Quick Reference
OUTPUT TABLE
INPUT TABLE
Input
Function
X0
Open PB
X1
Stop PB
X2
Relay Output
Torque Reverse
X3,X6,X7
Function
YK0
YK1
Interlock Out
Programmable
YK2
Programmable
Activation Command
X4
X5
Close PB
Toggle Command
Unused
X8*
36" Photoeye
X9*
DC Output
YDC0
Photoeye Test
*YDC2
Photoeye Test
*YDC3
X11*
54" Photoeye Input
*YDC4
X12
Open/Reset PB
YDC5
X13
Induction Loop Input
*YDC6
X14*
Fault Input
On when door Open
YDC1
18" Photoeye Input
X10*
Function
*YDC7
Open/Reset PB Light
I-Zone Alarm
Preannounce to Close
NPO Contactor
Disabled
X15*
Input Power
* Not shown in I/O menu and not programmable
Encoder Adjustment Descriptions
(Refer to i-COMM II and Owners Manuals for additional detail)
Close Position
Adjust
Use this option to set the overall opening distance of the door (in feet). This
measurement is used for initial position setup only. For small adjustments of the
open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option for initial position setup. Manually place door in the close position
and select this option. Alternatively “Set Open Pos.” can be used if it is more
convenient to place the door in the open position.
Use this option for initial position setup. Manually place door in the open position
and select this option. Alternatively “Set Close Pos.” can be used if it is more
convenient to place the door in the closed position.
Use this option to make small adjustment to the closed position. The number
displayed is the relative displacement of the closed position.
Open Position
Adjust
Use this option to make small adjustment to the open position. The number
displayed is the measurement between the open and closed position.
Open Distance
Set Close
Position
Set Open
Position
Motor Drive
Side
Not used on SPLIT SECOND DOOR.
Timer Adjustment
1. Press [ENTER], Controller will stop and fault door.
2. Press [UP] or [DOWN] until the timer folder is displayed.
3. Press [ENTER], to enter the timer folder.
4. Using [UP] & [DOWN] keys select desired timer.
5. Press [ENTER] to view the current timer value.
6. Use [UP] or [DOWN] keys set the desired value.
7. Press [ENTER] to save the value and return to
the timer folder.
8. Press [BACK] until "Door Faulted" is displayed.
9. Reset Door.
Preannounce Timer is the amount of time the
Preannounce to close output will be on before door closes.
Close Timer is the amount of time the door will remain
open before the preannounce to close timer activates
Autocycle Time is the amount of time between each
automatic cycle of the door (disabled by default).
53850616-1
16
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM ii LOGIC CHART - BARRIER GLIDER 7100
‡
$#44+'4).+&'4
6/
KÄ%1//++.1)+%6#$.'
0#/'
+0276(70%6+10
Func.
X0
X1
X2
X3
X4
X5
X6
X7
X8
X9
X10
X11
X12
X13
X14
X15
2
2
4
3
2
2
0#/'
Open Limit Switch
Close Limit Switch
User Input (Activation) (4)
User Input (Activation) (4)
User Input (Close) (4)
User Input (Toggle) (4)
User Input (Activation) (4)
User Input (Activation) (4)
Unused
Unused
Torque Reverse
Unused
Open/Reset Switch (1)
Induction Loop Activation(1)
Fault Input
Power Indicator
176276(70%6+10
Func.
YK0
YK1
YK2
YDC0
YDC1
YDC2
YDC3
YDC4
YDC5
YDC6
YDC7
0
20
20
3
20
2
User Out (Interlock) (4)
User Out (Disabled) (4)
User Out (Disabled) (4)
User Out (Door open) (4)
User Out (Disabled) (4)
Unused
Dedicated (Fault Ind.)
Unused
User Out (Preannounce) (1)
Unused
Dedicated (Spare)
56#6'6#$.'
O
ø
1
X
X
X
X
X
X
X
X
X
X
X
X
1
1
C
Ro Rc
1
ø
X
X
X
X
X
X
X
X
X
X
X
X
1
1
1
1
X
X
X
X
X
X
X
X
X
X
X
X
1
1
1
1
X
X
X
X
X
X
X
X
X
X
X
X
1
1
%1//'065
Off when door opened.
Off when door closed.
On to open door (4)
On to open door (4)
On to close door (4)
On to toggle open or close (4)
On to open door (4)
On to open door (4)
Unused
Unused
Off to reverse door.
Unused
On to reset from fault (1)
On to open door (1)
On to run door
On to run door
56#6'6#$.'
O
C
Ro Rc
ø
X
X
1
X
X
X
X
X
X
X
1
X
X
ø
X
X
X
X
ø
X
X
ø
X
X
ø
X
X
X
X
ø
X
X
ø
X
X
ø
X
X
X
X
X
X
X
%1//'065
On when door closed (4)
User selectable output (4)
User selectable output (4)
On when door open (4)
User selectable output (4)
Unused
PB light output
Unused
Preannounce to close (1)
Unused
Spare output
6KOGT#FLWUVOGPV
1. Press [ENTER], Controller will stop and fault door.
2. Press [UP] or [DOWN] until the timer folder is
displayed.
3. Press [ENTER], to enter the timer folder.
4. Using [UP] & [DOWN] keys select desired timer.
5. Press [ENTER] to view the current timer value.
6. Use [UP] or [DOWN] keys set the desired value.
7. Press [ENTER] to save the value and return to
the timer folder.
8. Press [BACK] until "Door Faulted" is displayed.
9. Reset Door.
Preannounce Timer is the amount of time the
Preannounce to close output will be on before door closes.
Close Timer is the amount of time the door will remain
open before the preannounce to close timer activates
Autocycle Time is the amount of time between each
automatic cycle of the door (disabled by default).
-';
11RGP5VCVG
%%NQUGF5VCVG
4Q4WPPKPI1RGP
4E4WPPKPI%NQUG
“1((
10
:/C[DG10QT1((
NOTES:
(1) Device operation can be changed
through menu. Consult i-COMM manual for
additional details.
(4) Default setting shown in table &
comments. Consult i-COMM manual for
additional details.
53850651-1
Pub. No. i-COMM_A FEBRUARY 2016
17
i-COMM™ CONTROLLER
i-COMM ii LOGIC CHART - DEFENDER
Input Table
Input
Input Function
Comments
XO
Close Command
On to close door
X1
Stop Command N.C.
Off to stop door
X2,X3,X6,X7
Activation Command
On to open door
X4
Stop Command N.C.
Off to stop door
X5
Toggle Command
On to toggle open or close
X8
Not Used
Not Used
X9,X10,X11
Not Used
Not Used
X12
Open/Reset Switch
X13
Induction Loop Activation
On to reset fromfault.
On to open door
X14
Fault Input
Must be on for door to run.
Note(s)
1
1
2
2
Encoder Adjustment Descriptions
(Refer to i-COMM and SplitSecond Manuals for additional detail)
Open Distance
Use this option to set the overall opening distance of the door (in feet). For example, for an
8ft tall Defender. This option should be set to “8”. This measurement is used for initial
position setup only. For small adjustments of the open and close position, use “Close
Position Adjust” or “Open Position Adjust”
Set Open Pos.
Use this option for initial position setup. Manually place door in the open position and select
this option. Alternatively “Set Close Pos.” can be used if it is more convenient to place the
door in the closed position. NOTE: This option approximately sets the open and close
positions. For additional adjustment of the open and close position, use “Close Position
Adjust” or “Open Position Adjust”
Set Close Pos.
Use this option for initial position setup. Manually place door in the close position and select
this option. Alternatively “Set Open Pos.” can be used if it is more convenient to place the
door in the open position. NOTE: This option approximately sets the open and close
positions. For additional adjustment of the open and close position, use “Close Position
Adjust” or “Open Position Adjust”
Open Pos. Adjust
Use this option to make small adjustment to the open position. The number displayed is the
measurement between the open and closed position. For example if this option was set to
100” the door would open 100 inches from the closed position. It is recommended to adjust
the closed position of the door first, before adjusting the open position.
Close Pos. Adjust
Use this option to make small adjustment to the closed position. The number displayed is
the relative displacement of the closed position. For example, if this option was set to -1.0”
the door would closed approximately 1.0 inch more. If this option was set to 2.0” the door
would close 2.0 inches less.
NOTES:
(1) Default setting shown in table & comments. Record
any changes on space provided. Consult i-COMM
manual for additional details.
(2) Device operation can be changed through menu.
Consult i-COMM manual for additional details.
Ä
18
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM TO i-COMMii UPGRADE EMERSON INVERTER
Pub. No. i-COMM_A FEBRUARY 2016
19
i-COMM™ CONTROLLER
i-COMM TO i-COMMii UPGRADE EMERSON INVERTER
20
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM TO i-COMMii UPGRADE AB INVERTER
Pub. No. i-COMM_A FEBRUARY 2016
21
i-COMM™ CONTROLLER
i-COMM TO i-COMMii UPGRADE AB INVERTER
22
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM TO i-COMMii UPGRADE WIRE HARNESS
Pub. No. i-COMM_A FEBRUARY 2016
23
i-COMM™ CONTROLLER
i-COMM CONTROLLER (< 6/20/12)
THE FOLLOWING PAGES ARE FOR i-COMM 1:
ALL 7100, 8000, 8000CL, 8000XL, 8600, 8910, 8920, 8920PL
FASTRAX, FASTRAXCL, FASTRAXFR, SPLITSECOND PRIOR TO 6/20/12.
24
Pub. No. i-COMM_A FEBRUARY 2016
Pub. No. i-COMM_A FEBRUARY 2016
Input Terminals
Encoder Terminals
Up Key
Enter Key
Display Contrast Potentiometer
(Lighter / Darker)
Green Input
Terminal LED’s
Down Key
Battery Jumper
Power LED
J1 Programming Port
Clock Battery
LCD
Display
JP1 Jumper
JP2 Jumper
Induction
Loop
JP3
Jumper
Output
Terminals
Red
Output
Terminal
LED's
i-COMM™ CONTROLLER
ENCODER - i-COMM LAYOUT
25
i-COMM™ CONTROLLER
i-COMM SETUP INSTRUCTIONS
ENCODER SETUP INSTRUCTIONS
1.
Change values using the up or down arrows.
Verify wiring to encoder is properly terminated.
To bring the curtain closer to the floor, adjust this
value so that it is less than zero. (i.e. To close the
door 4” more, the value for “Close Pos. Adjust” will
be -4.0”) Moving this parameter in the positive
direction raises the curtain relative to the floor.
Changing this value will not affect the open position.
Note: right-hand drive doors require a wire to be
terminated in the ‘DC’ terminal, while left-hand drive
doors do not. If motor phase is changed during this
setup, please restart this procedure.
2.
Move curtain to closed position.
3.
Power up door and press enter button to enter
“MAIN MENU”.
4.
Using down arrow, scroll to “Open Distance”.
5.
Press enter button to view parameter value
(measured in feet), should be O.D.H. - (two) 2’.
Change the value using the up or down arrow keys,
round down if required, then press enter to return to
“MAIN MENU”.
6.
Scroll using down arrow to item “Set Close Pos.”.
7.
Press enter button to view parameter. The controller
will display the following message “RESET ALL
LIMITS” … “Press Up to Start”. Pressing the up
arrow key will reset all of the limits, and reboot the
controller.
NOTE: DO NOT use this menu item to make
adjustment to the limits; this is only for initial
setup.
8.
Press green Open/Reset button.
Note: If you leave this parameter and return to it, its value
will again be zero. Any changes made before
leaving the parameter will still be effective. For
example: If you lowered the door 4.0”, leave the
parameter and return, the parameter will display
0.0”. Even though the display shows 0.0” the -4.0”
change has been recorded.
4.
When parameter is changed press enter button for
three (3) seconds to return to the “MAIN MENU”.
5.
Test operation of door and continue adjustment.
TIP:
To adjust the OPEN position:
1.
Power up door and press enter button to enter
“MAIN MENU”.
2.
Using up arrow key, scroll to “Open Pos. Adjust”.
3.
Press enter button to view parameter value. This
parameter will show a coded value on the left and
the opening height in inches on the right. This value
will always be less than the door opening height.
a. The door should begin to open, be ready to
shutdown the door if it begins to move in the wrong
direction. If motor phase is changed, start over at
step #2.
Change the value using the up and down arrow
keys.
b. If rotation is correct proceed to the instructions for
adjusting the “Open and Close positions”.
To bring the open position down (closer to the floor)
adjust this value to be less than the current value.
To open the door more relative to the floor, adjust
this parameter in a positive direction. (i.e. To open
the door 4” more, and the current value is 72.0”.
Change the value for “Open Pos. Adjust” to be
76.0”). Changing this value will not affect the close
position.
Open and Close Position Adjustment
To adjust CLOSE position:
1.
Power up door and press enter button to enter
“MAIN MENU”.
2.
Scroll using up arrow to the item “Close Pos.
Adjust”.
3.
Press enter button to view parameter value. This
parameter will show a coded value on the left and
relative change in inches on the right. When
entering this parameter the value will always start at
0.0”.
26
At any point in the menu mode, Pressing and
holding the enter button for at least 2 seconds will
cause the controller to automatically accept all the
changes made and exit the menu system.
4.
When parameter is changed press enter button for
three (3) seconds to return to the “MAIN MENU”.
5.
Test operation of the door, and continue adjustment.
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM SETUP INSTRUCTIONS
OPTION
Open Distance
Set Open Pos
Set Close Pos
Open Pos Adjust
Close Pos Adjust
Apr Open Pos
Encoder Startup
Encoder Read
Encoder Velocity
DESCRIPTION
Use this option to set the overall opening distance of the door (in feet). For example, for an 8’ tall
FasTrax. This option should be set to “7” [178]. This measurement is used for initial position setup
only. For small adjustments of the open and close position, use “Close Position Adjust” or “Open
Position Adjust”
Use this option for initial position setup. Manually place door in the open position and select this
option. Alternatively “Set Close Pos.” can be used if it is more convenient to place the door in the
closed position. NOTE: This option approximately sets the open and close positions. For additional
adjustment of the open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option for initial position setup. Manually place door in the close position and select this
option. Alternatively “Set Open Pos.” can be used if it is more convenient to place the door in the
open position. NOTE: This option approximately sets the open and close positions. For additional
adjustment of the open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option to make small adjustment to the open position. The number displayed is the
measurement between the open and closed position. For example if this option was set to 100”
[2540] the door would open 100 inches from the closed position. It is recommended to adjust the
closed position of the door first, before adjusting the open position.
Use this option to make small adjustment to the closed position. The number displayed is the
relative displacement of the closed position. For example, if this option was set to -1.0”[-25] the door
would close approximately 1.0” [25] more. If this option was set to 2.0” [51] the door would close 2.0”
[51] less.
Use this option to adjust the approach open position. This option is a measurement in inches from
the open position. For example, if this option was set to 24.0” [610] the door would slow down 24.0”
[610] from the open position.
The controller is waiting for valid data from the encoder. It the controller does not receive a
response at startup, this will remain on the screen indefinitely. If this does not clear with 5 seconds,
please check all encoder wiring.
The controller is unable to read valid data from the encoder. Check all wiring. Ensure that the
shield on the encoder cable is connected to ground, and that the control box is grounded. The error
requires the power to be cycled to reset.
The controller has received a signal from the encoder that the door is moving faster than allowed.
This can occur if the encoder is not properly attached to the shaft, bad electrical connection to the iCOMM, or improper grounding. The error requires the power to be cycled to reset.
Pub. No. i-COMM_A FEBRUARY 2016
27
28
Input Terminals
Up Key
Power LED
J1 Programming Port
Down Key
LCD
Display
Green Input
Enter Key
Terminal LED’s
Display Contrast Potentiometer
(Lighter / Darker)
JP1 Jumper
JP3
Jumper
Output
Terminals
Red
Output
Terminal
LED's
JP2 Jumper
Induction
Loop
i-COMM™ CONTROLLER
NON-ENCODER i-COMM DIGITAL CONTROLLER DETAIL
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM DISPLAY MESSAGES
LCD DISPLAY MESSAGES:
TOP DISPLAY BOTTOM DISPLAY REASON / FAULT MESSAGES
ACTION REQUIRED
Door Faulted
Push Open/Reset*
Service Required*
Service Required*
Push Open/Reset*
Reset / Jog Door*
Reset / Jog Door*
Push Open/Reset*
Service Required*
Push Open/Reset*
Service Required*
Service Required*
Inspect & Reset*
Service Required*
Service Required*
Service Required*
Check Inverter*
None*
None*
Jog To Close*
Normal Power Up
Watchdog Timer
Reset From Sleep
Low Voltage
Breakaway
Breakaway
Emergency Stop
Open Time Limit
Menu Interrupt
Limit Pulse Fail
Limit Failure
Obstruction
Unknown
System Clock read
Unknown State
Pro System
Jog to Open Pos
Jog to Close Pos
Photoeye Failure
Indicates Loss of Power
Indicates the boards watchdog timer has reset
Indicates the controller was awaken from sleep mode
Drop in voltage caused controller to restart
Door is in breakaway mode
FasTrax - Chainfall; 8000/CL/XL - Sideframe door; 8000/CL/XL Overload Relay
E-Stop pushed, Overload Relay (8900), Inverter (8600)
Run open time limit exceeded
Menu Interrupted
Trakline limit problem (8910/20/PL only)
Limit switch has failed
Door has detected obstruction and reversed 3 times
Unknown fault
System clock failed
State unknown
Pro Inverter Fault
Displays when jogging open
Displays when jogging close
Indicates problem with photoeye system (FasTrax only)
* Displays on Screen during jog only
DOOR IS OPENING
Door is Opening
Door is Open
Stand Clear
Closing in xx.xs
Activation On
Waiting for cmd.
Photoeye Blocked
I-Zone Detection
Stand Clear
DOOR IS OPEN
When not in preannounce to close
When in preannounce to close
Displays closing time in seconds
Indicates activation on (overrides timer display)
Indicates door is waiting for manual close cmd.
Photoeye is blocked (overrides timer display)
I-Zone active (overrides timer display)
DOOR IS CLOSING
Door Closing
Door Closed
Door Closed
Cycles: xxxxxx
Interlock Active
Door Stopped
Push Open/Close
None
DOOR IS CLOSED
Displays cycle count
Door is interlocked and cannot be opened
DOOR IS STOPPED
DC
Controller
Input
BASIC INPUT WIRING
Relay Coil
DC OUTPUT WIRING
Pub. No. i-COMM_A FEBRUARY 2016
None
Perform Interlocking
Open/Close Door
X_
(+24VDC)
DC
None
None
None
Device Holding Open
Close Door
Remove Obstruction
Remove Detection
YDC_
Try this if YDC0, YDC1 or YDC2 outputs have failed:
1. Move the YDC2 wire to terminal K3.
2.
Place a jumper from K3N to 0V.
3.
Change value of output YK3 to function needed.
Try this if K0 open output relay has failed:
1. Move the wire from open command to terminal K3.
2.
Place a jumper from K3N to AC.
3.
Change value of output YK3 to 8 - on during run
open.
Try this if K1 close output relay has failed:
1. Move the wire from close command to terminal K3.
2.
Place a jumper from K3N to AC.
3.
Change value of output YK3 to 9 - on during run
close.
29
i-COMM™ CONTROLLER
i-COMM MENU
Operation of the door is not possible when using the menu system.
1.
To enter the menu press the ENTER key, the Controller will stop and fault the door.
2.
Use the arrow keys (Up and Down) to navigate through the choices
3.
When the desired item is selected press enter to view the value or setting.
4.
Use the arrow keys to change the value if needed. Once editing is completed press ENTER to return to the main menu.
5.
When settings are completed, scroll to the "Exit" option in the main menu and press ENTER.
6.
Changes are not saved until the menu mode is exited. Turning power off while in the menu mode will cancel all changes.
Display Cycle Count Read-Only Displays current cycle count for the door. [All models]
Set Close Timer
Read/Write Displays and sets current close timer. This time plus the Preannounce Timer will be the
amount of time the door will stay open. Setting the Close Timer to 0 will place the door in
toggle mode. In toggle mode the reclose timer will be disabled.
(Valid Range: 1-255 seconds, with 0=Toggle Mode) [All models]
Set Preannounce
Read/Write Displays and sets Preannounce to close timer. This time plus the Close Timer will be the
amount of time the door will stay open. (Valid Range: 0-255 seconds) [All models]
Encoder Position* Read-Only Displays position of encoder. [FasTrax/FR/CL, SplitSecond]
Open Pos Adjust* Read/Write Use to change the open position for encoder. [FasTrax/FR/CL, SplitSecond]
Close Pos Adjust* Read/Write Use to change the close position for encoder. [FasTrax/FR/CL, SplitSecond]
Display Model #
Read-Only Displays door model. [All models]
Set Loop Func.
Read-Write Valid Choices are:
Auto Close Mode - Loop board will open and reverse door. (Note: Door will not close in
Toggle Mode is enabled (Close Timer = 0))
Rev./Hold Open - Loop board will only reverse door. Loop will not open door from fully
closed position. [All models]
Set Open PB Func Read-Write Valid Choices are:
Auto Close Mode" - Push button will open and reverse door. (Note: Door will not close is
Toggle Mode is enabled (Close Timer = 0))
Toggle Mode - Places the Open/Reset button in Toggle. Push the Open/Reset once to open
the door and again to close. Note reclose is disabled when door has been opened via Toggle.
Reset/Jog Only - Open/Reset button will only reset and jog the door. If pressed while door is
traveling close, door will reverse to open. (If Reset Only is required without opening door
please consult applications or Rite-Hite Door Technical Support) [All models]
I-Zone System
Read-Write Use to Enable/Disable I-Zone System. [Valid for FasTrax, Trakline and Protecdor series doors]
Output Definition
Read-Write Use to change functions of outputs where allowed. (YK2 Relay K2), YK3 (Relay K3), YDC0,
(see chart) (Note: Outputs which are not changeable will display "Not Adjustable") YDC1, YDC2, YDC3
Input Define
Read-Write Use to change functions of inputs where allowed. X2, X3, X5, X6, X7
(Note: Inputs which are not changeable will display "Not Adjustable")
Language
Read-Write Use to change language of the menus. Select Additional Languages (i.e., Portuguese,
Spanish) [All models]
Fault History
Read-Only Displays Last five faults as codes. Use arrows to provide a detailed description of each fault code
displayed. See details instructions on Page 7.
Partial Config
Read-Write Consult Technical Support (=/> Version 2.2.5)
Reverse Delay
Read-Write Consult Technical Support - FasTrax only (=/> Version 2.2.5) (0)
AB Inverter Delay Read-Write Consult Technical Support - FasTrax only (=/> Version 2.2.5) (075) use if does not fully close
Set Open Pos
Read/Write Use to set the open position for encoder, initial setup only. [FasTrax/FR/CL, SplitSecond]
Set Close Pos
Read/Write Use to set the close position for encoder, initial setup only. [FasTrax/FR/CL, SplitSecond]
Open Distance
Read/Write Use to set the door opening distance for encoder, initial setup only. [FasTrax/FR/CL, SplitSecond]
Open Alrm Time
RW - #25 Use to set time alarm on when door open [All models]
Clock
Read/Write Displays date and time. [FasTrax/FR/CL, SplitSecond]
Passcode*
Read/Write Consult Customer Service [All models}
CE Option
Read/Write Use to shut-off light curtain. [European - FasTrax only]
X10 PE Cut-Out*
Read/Write Use to shut-off lower PE when door closing. [FasTrax/CL/FR only]
X11 PE Cut-Out*
Read/Write Use to shut-off upper PE when door closing. [FasTrax/CL/FR only]
I-Zone Cut-Out
Read/Write Use to shut-off I-Zone when door closing. [FasTrax/CL/FR only]
Copy from Loader Write-Only Copies program from loader to i-COMM. Use up arrow to start copy process.
See details instructions on Page 7.
Copy to Loader
Read-Only Copies program in i-COMM to loader. Use up arrow to start copy process.
See details instructions on Page 7.
Exit [Enter]
Read-Only Use to exit menu system and save changes. [All models]
* - Not on doors prior to 8/13/2010
30
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
i-COMM PROCEDURE INSTRUCTIONS
PROCEDURE FOR USING DOWNLOADER CHIP:
PROCEDURE FOR CHANGING OPEN BUTTON OPERATION:
1. Turn power off.
1. Press ENTER key.
2. Plug in downloader chip.
2. Use UP / DOWN keys to scroll to “Set Open PB Func”.
3. Turn power on.
3. Press ENTER key.
4. Press ENTER.
4. Choose between “Auto Close Mode”, “Toggle Mode” or
Reset/Jog Only”.
5. Scroll to “Copy From Loader”.
5. Press ENTER when complete.
6. Press ENTER and UP key to start copy process.
6. Scroll to EXIT.
7. When complete, turn power off and remove loader.
7. Press ENTER, operate door.
8. Restore power and operate door.
The following describes what the fault codes convert to:
PROCEDURE FOR ADJUSTING RECLOSE TIMER:
Description
1. Press ENTER key.
2. Use UP key to scroll to “Set Close Timer”.
3. Press ENTER key.
4. To increase reclose time, press UP key.
5. To decrease reclose time, press DOWN key.
6. Press ENTER when complete.
7. Scroll to EXIT.
8. Press ENTER to save changes.
PROCEDURE FOR CHECKING FAULT HISTORY:
Code
#define FaultNone
0
#define FaultPowerUp
1
#define FaultBreakaway
2
#define FaultRunOpenTimer
3
#define FaultMenuInt
4
#define FaultLimitSwitch
5
#define FaultEstop
6
#define FaultRunCloseTimer
7
#define FaultLimitPulseFail
8
1. Press ENTER key.
#define FaultObstruction
9
2. Use UP / DOWN keys to scroll to “Fault History”.
#define FaultTimerRead
0A
3. Press ENTER key.
#define FaultStateOB
0B
4. This displays the last 5 faults in numerical code.
#define FaultPROSystem
0C
5. For a detailed view, press the UP key to scroll through the
fault codes.
#define FaultPhotoeye
0D
6. Press ENTER when complete.
7. Scroll to EXIT.
8. Press ENTER, operate door.
#define FaultEncoderRead
0E
#define FaultEncoderVelocity
0F
#define FaultEncoderNC
10
CONNECTOR
CONNECTOR TABLE
J3
J4
J5
PIN #
1
2
3
4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
This table shows the function of each of the connectors on the i-COMM controller. The voltages listed for each pin
assume that either the input or output is activated.
FLASHING LAMP OUT
I-ZONE ALARM OUT
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE CO
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
UNUSED OUTPUT
I-ZONE ALARM OUT
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE COM
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
Pub. No. i-COMM_A FEBRUARY 2016
FLASHING LAMP OUT
UNUSED
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE COM
INVERTER OUT 2(K1)
INVERTER OUT 1 (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
FLASHING LAMP OUT
UNUSED
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
UNUSED
UNUSED
OPEN/CLOSE COM
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
FLASHING LAMP OUT
UNUSED
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE COM
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
31
i-COMM™ CONTROLLER
NON-ENCODER i-COMM BOARD
1. If any procedures for the installation or operation have been left out or are not complete, contact RITE-HITE DOORS, INC.
Technical Support at 1-563-589-2722.
2. The use of a handheld device is no longer required, a downloader will be sent to download the new program.
3. This controller is used on the following door models:
FasTrax, FasTraxFR, FasTraxCL, SplitSecond, 7100, 7514, 8000, 8000CL, 8000XL, 8600, 8910, 8920, 8920PL.
4. Terminals will accept wire sizes from 12 - 22 AWG.
5. 15 Digital Inputs. (24VDC; 10 mA)
6. 5 Relay Outputs. (24VAC/DC; 1 AMP)
7. 4 DC Outputs. (24VDC; 0.5 AMP MAX)
REMOVAL AND INSTALLATION
1.
Change controller with door in the close position.
2.
Make sure you have all the parts before beginning.
3.
Unplug the J3 push button harness.
4.
Unplug the J4 power supply harness.
5.
Unplug the J5 induction loop harness if applicable.
6.
Remove wires from the input and output terminals.
7.
Remove the board by cutting the white plastic supports, and remove supports from bracket.
8.
Install new board, by screwing supports into mounting bracket.
9.
10.
32
Plug in the J3, J4 and J5 connectors.
Insert wires into terminals, based on markings, labels on the wires as well as the electrical wiring diagram included with the
door.
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
INPUT / OUTPUT SETTING FUNCTIONS
Default Value for Output (Factory Configuration)
YK2
YK3
YDC0 YDC1 YDC2 YDC3
Model:
X0
X1
Default Value for Input (Factory Configuration)
X2
X3
X4
X5
X6
X7
FasTrax/FR
n/a
0
2
20
n/a
n/a
n/a
n/a
2
2
n/a
3
2
2
FasTraxCL
n/a
0
2
20
n/a
n/a
n/a
2
2
2
2
3
2
2
SplitSecond
n/a
0
2
20
n/a
20
n/a
n/a
2
2
n/a
3
2
2
Protecdor/CL
n/a
0
2
20
20
20
n/a
n/a
2
2
n/a
3
2
2
Protecdor/CL PRO
n/a
0
2
20
20
n/a
n/a
n/a
n/a
2
n/a
3
2
2
Protecdor XL
n/a
0
2
20
20
20
n/a
n/a
2
2
n/a
3
2
2
Protecdor XL PRO
n/a
0
2
20
20
n/a
n/a
n/a
n/a
2
n/a
3
2
2
Trakline
20
0
2
20
20
20
n/a
n/a
n/a
2
n/a
3
2
2
Iso-Tek
n/a
0
2
20
20
20
n/a
n/a
n/a
2
n/a
3
2
2
Barrier Glider
20
0
2
20
20
n/a
n/a
n/a
n/a
2
n/a
3
2
2
Barrier Fold
n/a
0
2
20
20
20
n/a
n/a
n/a
2
n/a
3
2
2
n/a = Not available for change
Valid Values for Output Settings
Value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Valid Values for Output Settings
Function
Value
On when door closed (Interlock Out)
On when door Not Closed
On during preannounce to close
On when door full open
On when door not full open
On when door faulted
On when door not faulted
On when activation command
On during run Open
On during run Close
On during run (Open or Close)
On when door on limit (open or close)
On when I-Zone alarm
On when door open for 30 seconds
On when door open for 60 seconds
On when door open for 120 seconds
On during sequential activation
On when not running open
On when not running close
On when not running (open or close)
Output Disabled
21
22
23
24
25
26
27
28
29
Function
Flash 3Hz (=/> Version 2.2.5)
Flash 2Hz (=/> Version 2.2.5)
Partial Timer
Act rev I-Zone Pass
Door Open Alarm
Interlock Out N.O.
Interlock Out N.C.
Preannounce and Close
Photoeye Test
Valid Values for Input Settings:
*Value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Function
Description
Interlock In
Allows door to open (Only Available for inputs X2, X3 & X5)
(Note: Interlocking is disabled if no inputs are defined as interlock)
Stop
Stops door (Normally-Closed)
Activation
Opens Door
Toggle
Opens/Closes Door
Close
Closes door
Sequential Act.
Opens Door
Reverse
Reverses or Holds open door
Stop
Stops door (Normally-Open)
Manual Open
Opens door (used for open-close-stop, normal activation will not resume from stop)
Auto/Man
Places Door in Toggle Mode when input is on.
Partial Open Activation (8000/CL/XL/8900) (=/> Version 2.2.5)
Partial Open Toggle
(8000/CL/XL/8900) (=/> Version 2.2.5)
Toggle / Auto
Toggle with Automatic close (=/> Version 2.2.5)
Hand / Auto
Consult Customer Service
Disable
Disables Input
Reverse N.C.
Reverses or Holds open door using normally close contacts
Clean
* Value number may or may not appear on display.
Pub. No. i-COMM_A FEBRUARY 2016
33
i-COMM™ CONTROLLER
FASTRAX/FR/CL LOGIC TABLE
®
FasTrax
Encoder
i-COMM Quick Reference
Input Table
Input
XO
X1
X2
X3,X6,X7
X4
X5
X8,X9
Input Function
Open PB
Stop PB
Torque Reverse
Activation Command
Close PB
Toggle Command
IZone Sensors (Right & Left)
X10
18" Photoeye Input
X11
54" Photoeye Input
X12
X13
X14
Open/Reset Switch
Induction Loop Activation
Fault Input
Comments
On to open door
On to stop door
Off to reverse door
On to open door
On to close door
On to toggle open or close
Not Available on FasTraxCL
Must be on for door to close.
Off when blocked.
Must be on for door to close.
Off when blocked.
On to reset from fault.
On to open door
Must be on for door to run.
Note(s)
1
1
1
1
1
2
2
Encoder Adjustment Descriptions
(Refer to i-COMM and Owners Manuals for additional detail)
Open Distance
Set Open
Position
Set Close
Position
Open Position
Adjust
Close Position
Adjust
Use this option to set the overall opening distance of the door (in feet). For example,
for an 9 foot tall FasTrax, this option should be set to “8” (to allow room for fine
adjustment). This measurement is used for initial position setup only. For small
adjustments of the open and close position, use “Close Position Adjust” or “Open
Position Adjust”
Use this option for initial position setup. Manually place door in the open position
and select this option. Alternatively “Set Close Pos.” can be used if it is more
convenient to place the door in the closed position. NOTE: This option
approximately sets the open and close positions. For additional adjustment of the
open and close position, use “Close Position Adjust” or “Open Position Adjust”
Use this option for initial position setup. Manually place door in the close position
and select this option. Alternatively “Set Open Pos.” can be used if it is more
convenient to place the door in the open position. NOTE: This option approximately
sets the open and close positions. For additional adjustment of the open and close
position, use “Close Position Adjust” or “Open Position Adjust”
Use this option to make small adjustment to the open position. The number
displayed is the measurement between the open and closed position. For example if
this option was set to 100” the door would open 100 inches from the closed position.
It is recommended to adjust the closed position of the door first, before adjusting the
open position.
Use this option to make small adjustment to the closed position. The number
displayed is the relative displacement of the closed position. For example, if this
option was set to -1.0” the door would closed approximately 1.0 inch more. If this
option was set to 2.0” the door would close 2.0 inches less.
Timer Adjustment
1. PRESS [ENTER], Controller will stop and fault door.
2. Press [UP] until desired timer is displayed, display will
read "Set Close Timer" or "Set Preannounce".
3. Press [ENTER], Display will show current timer value.
4. Using [UP] & [DOWN] keys select desired time.
5. Press [ENTER] to return to Main Menu.
6. Press [DOWN] until exit is displayed.
7. Press [ENTER] to save values.
8. Reset Door.
Preannounce Timer is the amount of time the
Preannounce to close output will be on before door
closes.
Close Timer is the amount of time the door will remain
open before the preannounce to close timer activates
NOTES:
(1) Default setting shown in table & comments. Record
any changes on space provided. Consult i-COMM
manual for additional details.
(2) Device operation can be changed through menu.
Consult i-COMM manual for additional details.
53850564-1
34
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
RITE-HITE DOORS NOTES PAGE
This page intentional left blank.
Pub. No. i-COMM_A FEBRUARY 2016
35
i-COMM™ CONTROLLER
SPLITSECOND REFERENCE CHART
TM
SplitSecond Series
i-COMM Quick Reference
Input Table
Input
XO
X1
X2
X3,X6,X7
Input Function
Manual Open Command
Stop Command N/O
Torque Reverse
Activation Command
X4
X5
Comments
On to open door
On to stop door
Off to reverse door
On to open door
Close Command
Toggle Command
X8
Not Used
X9,X10,X11
Photoeye Input
X12
X13
X14
Open/Reset Switch
Induction Loop Activation
Fault Input
Note(s)
1
On to close door
On to toggle open or close
1
Not Used
All must be on for door to close. Off
when blocked.
On to reset fromfault.
On to open door
Must be on for door to run.
2
2
Encoder Adjustment Descriptions
(Refer to i-COMM and SplitSecond Manuals for additional detail)
Open Distance
Use this option to set the overall opening distance of the door (in feet). For example, for an
8ft wide SplitSecond. This option should be set to “8”. This measurement is used for initial
position setup only. For small adjustments of the open and close position, use “Close
Position Adjust” or “Open Position Adjust”
Set Open Pos.
Use this option for initial position setup. Manually place door in the open position and select
this option. Alternatively “Set Close Pos.” can be used if it is more convenient to place the
door in the closed position. NOTE: This option approximately sets the open and close
positions. For additional adjustment of the open and close position, use “Close Position
Adjust” or “Open Position Adjust”
Set Close Pos.
Use this option for initial position setup. Manually place door in the close position and select
this option. Alternatively “Set Open Pos.” can be used if it is more convenient to place the
door in the open position. NOTE: This option approximately sets the open and close
positions. For additional adjustment of the open and close position, use “Close Position
Adjust” or “Open Position Adjust”
Open Pos. Adjust
Use this option to make small adjustment to the open position. The number displayed is the
measurement between the open and closed position. For example if this option was set to
100” the door would open 100 inches from the closed position. It is recommended to adjust
the closed position of the door first, before adjusting the open position.
Close Pos. Adjust
Use this option to make small adjustment to the closed position. The number displayed is
the relative displacement of the closed position. For example, if this option was set to -1.0”
the door would closed approximately 1.0 inch more. If this option was set to 2.0” the door
would close 2.0 inches less.
Timer Adjustment
1. PRESS [ENTER], Controller will stop and fault door.
2. Press [UP] until desired timer is displayed, display will
read "Set Close Timer" or "Set Preannounce".
3. Press [ENTER], Display will show current timer value.
4. Using [UP] & [DOWN] keys select desired time.
5. Press [ENTER] to return to Main Menu.
6. Press [DOWN] until exit is displayed.
7. Press [ENTER] to save values.
8. Reset Door.
Preannounce Timer is the amount of time the
Preannounce to close output will be on before door
closes.
Close Timer is the amount of time the door will remain
open before the preannounce to close timer activates
NOTES:
(1) Default setting shown in table & comments. Record
any changes on space provided. Consult i-COMM
manual for additional details.
(2) Device operation can be changed through menu.
Consult i-COMM manual for additional details.
53850563-1
36
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
PROTECDOR/CL/XL LOGIC TABLE
Pub. No. i-COMM_A FEBRUARY 2016
37
38
AAA
AAA
AAA
AAA
AAA
6KOGT#FLWUVOGPV
AAA
AAA
AAA
AAA
AAA
“AAA
1RGP&QQT
%NQUG&QQT
7UGT1WV 7UGT1WV +PVGTNQEM 0QPÄ&GFKECVGF
0QPÄ&GFKECVGF
7UGT1WV 2TGCPPQWPEG 7UGT1WV 7UGT1WV 7UGT1WV (CWNV (NCUJKPI2WUJÄDWVVQP
0QPÄ&GFKECVGF
176276(70%6+10
1RGP.KOKV5YKVEJ
%NQUG.KOKV5YKVEJ
7UGT+PRWV #EVKXCVKQP 7UGT+PRWV #EVKXCVKQP 0QPÄ&GFKECVGF
6QIING%QOOCPF #EVKXCVKQP%QOOCPFÄ1RGP #EVKXCVKQP%QOOCPFÄ1RGP 0QPÄ&GFKECVGF
0QPÄ&GFKECVGF
4GXGTUG
0QPÄ&GFKECVGF
1RGP4GUGV5YKVEJ +PFWEVKQP.QQR#EVKXCVKQP 0QPÄ&GFKECVGF
+0276(70%6+10
%
“
:
:
:
:
:
:
:
:
:
:
:
:
4Q
:
:
:
:
:
:
:
:
:
:
:
:
4E
:
:
:
:
:
:
:
:
:
:
:
:
1
“
“
:
“
“
“
:
:
:
:
“
“
%
“
“
:
“
“
“
:
:
:
“
“
4E
“
:
“
“
“
:
:
:
“
“
1PYJGPFQQTKUQRGPKPI
1PYJGPFQQTKUENQUKPI
7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 0QPÄ&GFKECVGF
0QPÄ&GFKECVGF
7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 1PYJGPKPHCWNV
0QPÄ&GFKECVGF
%1//'065
1HHYJGPFQQTQRGPGF
1HHYJGPFQQTENQUGF
1PVQQRGPFQQT 1PVQQRGPFQQT 0QPÄ&GFKECVGF
1PVQVQIINGQRGPQTENQUG 1PVQQRGPFQQT 1PVQQRGPFQQT 0QPÄ&GFKECVGF
0QPÄ&GFKECVGF
1HHVQTGXGTUGFQQT
0QPÄ&GFKECVGF
1PVQTGUGVHTQOHCWNV 1PVQQRGPFQQT 0QPÄ&GFKECVGF
%1//'065
Ä
016'5
&GXKEGQRGTCVKQPECPDGEJCPIGFVJTQWIJOGPW
%QPUWNVKÄ%1//OCPWCNHQTCFFKVKQPCNFGVCKNU
&GHCWNVUGVVKPIUJQYPKPVCDNG EQOOGPVU4GEQTF
CP[EJCPIGUQPURCEGRTQXKFGF%QPUWNVKÄ%1//
OCPWCNHQTCFFKVKQPCNFGVCKNU
-';
11RGP5VCVG
“1((
%%NQUGF5VCVG
10
4Q4WPPKPI1RGP :/C[DG10QT1((
4E4WPPKPI%NQUG
4Q
“
:
“
“
“
“
:
:
:
“
“
56#6'6#$.'
1
“
:
:
:
:
:
:
:
:
:
:
:
:
56#6'6#$.'
24'55='06'4?%QPVTQNNGTYKNNUVQRCPFHCWNVFQQT
2TGUU=72?WPVKNFGUKTGFVKOGTKUFKURNC[GFFKURNC[YKNN
TGCF5GV%NQUG6KOGTQT5GV2TGCPPQWPEG
2TGUU='06'4?&KURNC[YKNNUJQYEWTTGPVVKOGTXCNWG
7UKPI=72? =&190?MG[UUGNGEVFGUKTGFVKOG
2TGUU='06'4?VQTGVWTPVQ/CKP/GPW
2TGUU=&190?WPVKNGZKVKUFKURNC[GF
2TGUU='06'4?VQUCXGXCNWGU
4GUGV&QQT
2TGCPPQWPEG6KOGTKUVJGCOQWPVQHVKOGVJG
2TGCPPQWPEGVQENQUGQWVRWVYKNNDGQPDGHQTGFQQT
ENQUGU
%NQUG6KOGTKUVJGCOQWPVQHVKOGVJGFQQTYKNNTGOCKP
QRGPDGHQTGVJGRTGCPPQWPEGVQENQUGVKOGTCEVKXCVGU
-
-
-
-
-
-
;&%
;&%
;&%
;&%
,Ä
,Ä
(WPE
0#/'
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
(WPE
0#/'
6/
KÄ%1//.1)+%6#$.'
$#44+'4).+&'4 ‡
i-COMM™ CONTROLLER
BARRIER GLIDER / FOLD LOGIC TABLE
Pub. No. i-COMM_A FEBRUARY 2016
i-COMM™ CONTROLLER
ISO-TEK LOGIC TABLE
+51Ä6'- ‡
6/
KÄ%1//.1)+%6#$.'
0#/'
+0276(70%6+10
(WPE
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
1RGP.KOKV5YKVEJ
%NQUG.KOKV5YKVEJ
AAA 7UGT+PRWV #EVKXCVKQP AAA 7UGT+PRWV #EVKXCVKQP #RRTQCEJ1RGP.KOKV5YKVEJ
AAA 6QIING%QOOCPF AAA #EVKXCVKQP%QOOCPFÄ1RGP AAA #EVKXCVKQP%QOOCPFÄ1RGP 0QPÄ&GFKECVGF
0QPÄ&GFKECVGF
4GXGTUG
0QPÄ&GFKECVGF
1RGP4GUGV5YKVEJ +PFWEVKQP.QQR#EVKXCVKQP 0QPÄ&GFKECVGF
0#/'
176276(70%6+10
(WPE
-
-
-
-
-
-
;&%
;&%
;&%
;&%
,Ä
,Ä
“AAA
AAA
AAA
AAA
AAA
8(&N5RGGFDKV
8(&N5RGGFDKV
$TCMG1WVRWV
7UGT1WV +PVGTNQEM (CWNV
(CWNV
7UGT1WV 2TGCPPQWPEG 7UGT1WV 7UGT1WV 7UGT1WV (CWNV (NCUJKPI2WUJÄDWVVQP
0QPÄ&GFKECVGF
56#6'6#$.'
1 %
“ “
: :
: :
: :
: :
: :
: :
: :
: :
: :
: :
: :
: :
4E
:
:
:
:
:
:
:
:
:
:
:
:
%1//'065
1PYJGPFQQTCEVKXCVGUUYKVEJ
1PYJGPFQQTCEVKXCVGUUYKVEJ
1PVQQRGPFQQT 1PVQQRGPFQQT 1PYJGPFQQTCEVKXCVGUUYKVEJ
1PVQVQIINGQRGPQTENQUG 1PVQQRGPFQQT 1PVQQRGPFQQT 0QPÄ&GFKECVGF
0QPÄ&GFKECVGF
1HHVQTGXGTUGFQQT
0QPÄ&GFKECVGF
1PVQTGUGVHTQOHCWNV 1PVQQRGPFQQT 0QPÄ&GFKECVGF
%1//'065
56#6'6#$.'
1
“
“
“
:
:
:
:
“
“
6KOGT#FLWUVOGPV
24'55='06'4?%QPVTQNNGTYKNNUVQRCPFHCWNVFQQT
2TGUU=72?WPVKNFGUKTGFVKOGTKUFKURNC[GFFKURNC[YKNN
TGCF5GV%NQUG6KOGTQT5GV2TGCPPQWPEG
2TGUU='06'4?&KURNC[YKNNUJQYEWTTGPVVKOGTXCNWG
7UKPI=72? =&190?MG[UUGNGEVFGUKTGFVKOG
2TGUU='06'4?VQTGVWTPVQ/CKP/GPW
2TGUU=&190?WPVKNGZKVKUFKURNC[GF
2TGUU='06'4?VQUCXGXCNWGU
4GUGV&QQT
2TGCPPQWPEG6KOGTKUVJGCOQWPVQHVKOGVJG
2TGCPPQWPEGVQENQUGQWVRWVYKNNDGQPDGHQTGFQQT
ENQUGU
%NQUG6KOGTKUVJGCOQWPVQHVKOGVJGFQQTYKNNTGOCKP
QRGPDGHQTGVJGRTGCPPQWPEGVQENQUGVKOGTCEVKXCVGU
Pub. No. i-COMM_A FEBRUARY 2016
4Q
:
:
:
:
:
:
:
:
:
:
:
:
%
“
“
“
:
:
:
“
“
4Q
:
“
“
“
:
:
:
“
“
4E
“
“
“
:
:
:
“
“
1PYJGPFQQTKUQRGPKPI
1PYJGPFQQTKUENQUKPICPFHCUVQRGP
1PVQGPICIGOQVQTDTCMG
7UGTUGNGEVCDNGQWVRWV 1PYJGPPQHCWNV
1PYJGPPQHCWNV
7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 1PYJGPKPHCWNV
0QPÄ&GFKECVGF
-';
11RGP5VCVG
%%NQUGF5VCVG
4Q4WPPKPI1RGP
4E4WPPKPI%NQUG
“1((
10
:/C[DG10QT1((
016'5
&GXKEGQRGTCVKQPECPDGEJCPIGFVJTQWIJOGPW
%QPUWNVKÄ%1//OCPWCNHQTCFFKVKQPCNFGVCKNU
&GHCWNVUGVVKPIUJQYPKPVCDNG EQOOGPVU4GEQTF
CP[EJCPIGUQPURCEGRTQXKFGF%QPUWNVKÄ%1//
OCPWCNHQTCFFKVKQPCNFGVCKNU
Ä
39
i-COMM™ CONTROLLER
TRAKLINE LOGIC TABLE
64#-.+0'5'4+'5
6/
6/
KÄ%1//.1)+%6#$.'
0#/'
+0276(70%6+10
(WPE
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
1RGP.KOKV5YKVEJ
%NQUG.KOKV5YKVEJ
AAA 7UGT+PRWV #EVKXCVKQP AAA 7UGT+PRWV #EVKXCVKQP 0QPÄ&GFKECVGF
AAA 6QIING%QOOCPF AAA #EVKXCVKQP%QOOCPFÄ1RGP AAA #EVKXCVKQP%QOOCPFÄ1RGP 6/
+Ä<QPG5GPUQT
6/
+Ä<QPG5GPUQT
2JQVQG[GÄ4GXGTUG&QQT
2JQVQG[GÄ4GXGTUG&QQT
1RGP4GUGV5YKVEJ +PFWEVKQP.QQR#EVKXCVKQP (CWNV+PRWV
0#/'
176276(70%6+10
(WPE
-
-
-
-
-
-
;&%
;&%
;&%
;&%
,Ä
,Ä
“AAA
AAA
AAA
AAA
AAA
4WP1RGP
4WP%NQUG
5GPUQT5YKVEJ&KUCDNG
7UGT1WV +PVGTNQEM (CWNV
(CWNV
7UGT1WV 2TGCPPQWPEG 7UGT1WV 7UGT1WV 7UGT1WV 0QPÄ&GFKECVGF
+Ä<QPG#NCTO
56#6'6#$.'
1 %
“ “
: :
: :
: :
: :
: :
: :
: :
: :
: :
: :
: :
: :
4E
:
:
:
:
:
:
:
:
:
%1//'065
1HHYJGPFQQTRCUUGUUYKVEJ
1HHYJGPFQQTRCUUGUUYKVEJ
1PVQQRGPFQQT 1PVQQRGPFQQT 0QPÄ&GFKECVGF
1PVQVQIINGQRGPQTENQUG 1PVQQRGPFQQT 1PVQQRGPFQQT 1HHVQTGXGTUG JQNFQRGP 1HHVQTGXGTUG JQNFQRGP 1HHYJGPRJQVQG[GUDNQEMGF
1HHYJGPRJQVQG[GUDNQEMGF
1PVQTGUGVHTQOHCWNV 1PVQQRGPFQQT /WUVDGQPVQTWPÄ+HQHH
EJGEMGÄUVQRQTQXGTNQCF
56#6'6#$.'
1
“
“
“
:
:
:
:
“
:
6KOGT#FLWUVOGPV
24'55='06'4?%QPVTQNNGTYKNNUVQRCPFHCWNVFQQT
2TGUU=72?WPVKNFGUKTGFVKOGTKUFKURNC[GFFKURNC[YKNN
TGCF5GV%NQUG6KOGTQT5GV2TGCPPQWPEG
2TGUU='06'4?&KURNC[YKNNUJQYEWTTGPVVKOGTXCNWG
7UKPI=72? =&190?MG[UUGNGEVFGUKTGFVKOG
2TGUU='06'4?VQTGVWTPVQ/CKP/GPW
2TGUU=&190?WPVKNGZKVKUFKURNC[GF
2TGUU='06'4?VQUCXGXCNWGU
4GUGV&QQT
2TGCPPQWPEG6KOGTKUVJGCOQWPVQHVKOGVJG
2TGCPPQWPEGVQENQUGQWVRWVYKNNDGQPDGHQTGFQQT
ENQUGU
%NQUG6KOGTKUVJGCOQWPVQHVKOGVJGFQQTYKNNTGOCKP
QRGPDGHQTGVJGRTGCPPQWPEGVQENQUGVKOGTCEVKXCVGU
40
4Q
:
:
:
:
:
:
:
:
:
:
:
:
:
%
“
“
“
:
:
:
“
:
4Q
“
“
“
“
:
:
:
“
:
4E
“
“
“
:
:
:
“
:
%1//'065
1PVQQRGPFQQT
1PVQENQUGFQQT
1PYJGPFQQTQRGPGFCPFFQQTENQUGF
7UGTUGNGEVCDNGQWVRWV 1PYJGPPQVKPHCWNV
1PYJGPPQVKPHCWNV
7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 7UGTUGNGEVCDNGQWVRWV 0QPÄ&GFKECVGF
1PFWTKPI+Ä<QPGCNCTO -';
11RGP5VCVG
%%NQUGF5VCVG
4Q4WPPKPI1RGP
4E4WPPKPI%NQUG
“1((
10
:/C[DG10QT1((
016'5
&GXKEGQRGTCVKQPECPDGEJCPIGFVJTQWIJOGPW
%QPUWNVKÄ%1//OCPWCNHQTCFFKVKQPCNFGVCKNU
1RVKQPCNWUGFQPN[HQT+Ä<QPGUGPUQTU[UVGO
&GHCWNVUGVVKPIUJQYPKPVCDNG EQOOGPVU4GEQTF
CP[EJCPIGUQPURCEGRTQXKFGF%QPUWNVKÄ%1//
OCPWCNHQTCFFKVKQPCNFGVCKNU
Ä
Pub. No. i-COMM_A FEBRUARY 2016
Descargar