Subido por Juan Leon

1.5.3. Baterias BPS

Anuncio
Adjust viewing area to see up to column V
Make entries in yellow highlighted cells
Fill out the battery calculation section for each booster power supply needed. You will have to keep track of each battery
size calculated, then at the end, enter the number of booster power supplies using the particular size battery. In most cases,
12V6A5 batteries can be used. Each BPS will require 1 pair of batteries.
Step 5a - Detailed booster bower supply battery calculations
This is for supervisory current from devices such as remote annunciators
and sounder bases connected to signal circuits that have been
configured as AUX outputs (not supervised) and will stay powered if loss
of AC (battery backed up).
Supervisory (AUX1, AUX2, AUX3, AUX4)
Note: Only add auxiliary current if aux output stays on after AC power failure.
Circuit
Aux 1
Aux 2
Aux 3
Aux 4
Current (mA)
1
1 3000m
A max
1 per ckt
Remaining annunciator supervisory load not assigned to panel =
1
Number of ckts set to AUX:
4
x 35 =
140
Total sounder base supervisory load =
Total AUX current (if switch SW2-7 is off):
144 mA (A)
Total 260-CO detector supervisory load =
Total sup. cur. is limited to 6 amps for EBPS6A, 8 amps for EBPS10A.
200 mA AUX
This is the dedicated 200mA AUX output that is typically
used for low current devices, such as 4 wire smokes, that do
require battery backup.
Current (mA)
0
Total 200 mA AUX current:
0 mA (B)
Rated base BPS supervisory current:
Total supervisory current (A+B+C):
Hours of standby supervisory time:
Supervisory mAH required (DxE):
Alarm (NAC1, NAC2, NAC3, NAC4)
Circuit
NAC 1 / Aux 1
NAC 2 / Aux 2
NAC 3 / Aux3
NAC 4 / Aux 4
70
214
24
5136
mA (C)
mA (D)
Hrs (E)
mAH (F)
Enter battery time required
This is for signal loads as well as alarm currents for devices such as remote
annunciators and sounder bases .
Use Vdc, RMS current ratings of devices.
Current (mA)
2200
3000m
2200 A max
2200 per ckt
2200
Total NAC / Aux alarm current:
0 mA
0 mA
0 mA
8800
Rated base BPS alarm current:
270
Total alarm current (D+G+H):
9284
Minutes of alarm time:
5
Hours of alarm (K/60): 0,0833333
Alarm mAH required (JxL): 773,66667
Remaining signal load (dc) not assigned to panel =
Remaining annunciator alarm load not assigned to panel =
mA (G)
Total sounder base alarm load =
Total 260-CO detector alarm load =
mA (H)
mA (J)
Min (K)
Enter battery time required
Hr (L)
mAH (M)
mA
0 mA
0 mA
0 mA
Total battery mAH required (M+F): 5909,6667 mAH (N)
Preliminary Total battery AH required (N/1000): 5,9096667 AH (O)
Final Battery AH Required (Ox1.2):
7,0916 AH (P)
Enter the number of booster power supplies below requiring the calculated battery size. Total
12 volt, 7.2 amp hour
12 volt, 10 amp hour
12 volt, 18 amp hour
12 volt, 26 amp hour
Use:
Use:
Use:
Use:
Part #
12V6A5
12V10A
12V17A
12V24A
Use:
Use:
BC-2
BC-1
Total
Batts
# of BPS
x2=
x2=
x2=
x2=
0
0
0
0
The size and number of booster power supplies
should be selected on the Signals sheet first.
Qty
18AH battery cabinet
26AH battery cabinet
0 Batteries larger than 12V10A require BC-1 or BC-2.
0 Batteries larger than 12V17A require BC-1.
2 batteries per
cabinet
Descargar