energies Article Energy Performance Comparison of a Chiller Plant Using the Conventional Staging and the Co-Design Approach in the Early Design Phase of Hotel Buildings Yamile Díaz Torres 1 , Paride Gullo 2, * , Hernán Hernández Herrera 3 , Migdalia Torres del Toro 4 , Roy Reyes Calvo 5 , Jorge Iván Silva Ortega 6 and Julio Gómez Sarduy 5 1 2 3 4 5 6 * Citation: Díaz Torres, Y.; Gullo, P.; Hernández Herrera, H.; Torres del Toro, M.; Reyes Calvo, R.; Silva Ortega, J.I.; Gómez Sarduy, J. Energy Performance Comparison of a Chiller Plant Using the Conventional Staging and the Co-Design Approach in the Early Design Phase of Hotel Instituto Superior Politécnico de Tecnologías e Ciências (ISPTEC), Departamento de Engenharias e Tecnologias, Ave Luanda Sul, Luanda P.O. Box 583, Angola Department of Mechanical and Electrical Engineering, University of Southern Denmark (SDU), 6400 Sønderborg, Denmark Faculty of Engineering, Universidad Simón Bolivar, Barranquilla 080005, Colombia Instituto Superior Politécnico Alvorecer da Juventude (ISPAJ), Departamento de Engenharias e Ciências Exactas, Urbanição Nova Vida, Rua 45. Kilamba Kiaxi, Luanda P.O. Box 583, Angola Studies Center for Energy and Environment, Universidad Carlos Rafael Rodríguez, Cienfuegos 55100, Cuba Department of Energy, Universidad de la Costa, Barranquilla 080005, Colombia Correspondence: parigul@sdu.dk; Tel.: +45-65507314 Abstract: As part of the design process of a chiller plant, one of the final stages is the energy testing of the system in relation to future operating conditions. Recent studies have suggested establishing robust solutions, but a conservative approach still prevails at this stage. However, the results of some recent studies suggest the application of a new co-design (control–design) approach. The present research involves a comparative analysis between the use of conventional staging and the codesign approach in the design phase of a chiller plant. This paper analyzes the energy consumption estimations of six different chiller plant combinations for a Cuban hotel. For the conservative approach using on/off traditional staging, the results suggest that the best option would be the adoption of a chiller plant featuring a symmetrical configuration. However, the outcomes related to the co-design approach suggest that the best option would be an asymmetrical configuration. The energy savings results were equal to 24.8% and the resulting coefficient of performance (COP) was 59.7% greater than that of the symmetrical configuration. This research lays firm foundations for the correct choice and design of a suitable chiller plant configuration for a selected hotel, allowing for significant energy savings in the tourism sector. Buildings. Energies 2023, 16, 3782. https://doi.org/10.3390/ en16093782 Keywords: chiller plant; co-design; traditional staging; optimal chiller loading; optimal chiller sequencing Academic Editor: Rafik Belarbi Received: 28 February 2023 Revised: 13 April 2023 Accepted: 26 April 2023 Published: 28 April 2023 Copyright: © 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// 1. Introduction Selecting all of a chiller plant’s parameters involves considering the system’s cooling capacity and its configuration. Fang et al. [1] demonstrated that poor design of a plant causes a significant deviation in the efficiency of each element in the system from its optimum point of operation. According to ASHRAE [2], the sequential procedure suggests that a chiller plant design should involve the evaluation of the total cooling load demand of a building, which needs to be increased by an extra load for safety reasons, and, finally, the selection of the other features, i.e., the type of chiller, the number of chillers, the cooling load distribution, and the hydraulic arrangement. Several studies and recommendations related to these steps were summarized by Diaz et al. [3], and the overall procedure is shown in Figure 1. creativecommons.org/licenses/by/ 4.0/). Energies 2023, 16, 3782. https://doi.org/10.3390/en16093782 https://www.mdpi.com/journal/energies Energies 2023, 16, x FOR PEER REVIEW Energies 2023, 16, 3782 2 of 24 2 of 23 recommendations related to these steps were summarized by Diaz et al. [3], and the overall procedure is shown in Figure 1. Cooling load demand analysis under deterministic approach Cooling Peak load demand value Safety Factor, Unmet hours According international and /or local standars Total cooling capacity Redundancy Depend of type facility requirements CHILLER PLANT CONFIGURATION Type of chiller According technical advantanges, building requirements, budged, space, among others technical and economic criteria Number of units (N+1) According engineering recommendation , budged Cooling distribution among chillers Symetrical, Assimetrical, mixed According standards or engineering recommendation Hidraulic arragement Pararell,Serie,Mixed According standards or engineering recommendation Figure 1. A traditional methodology for designing the primary circuit of centralized chiller/heat Figure 1. A traditional methodology for designing the primary circuit of centralized chiller/heat pump plants [3]. pump plants [3]. Over time, time, the traditional chiller Over the traditional chiller plant plant design design methodology methodology has has been been improved. improved. Taylor [4] recommended adding the estimation of the energy consumption according to Taylor [4] recommended adding the estimation of the energy consumption according to the the critical operating conditions of the building to the traditional methodologies for critical operating conditions of the building to the traditional methodologies for selecting selecting lowest lifeAncycle cost. An importantinimprovement this traditional the lowestthe life cycle cost. important improvement this traditionalinmethodology was methodology was its conversion into an iterative process, where the uncertainty analysis its conversion into an iterative process, where the uncertainty analysis of cooling loads of cooling loads was with energy performance, considering an and/or energy, was incorporated withincorporated energy performance, considering an energy, economic, economic, and/or life cycle cost approach called robust design. This methodology allows life cycle cost approach called robust design. This methodology allows for selecting the for selecting the chiller that meets the technical requirements of the facility chiller that meets the technical requirements of the facility and simultaneously offersand the simultaneously offers best empirically performancedetermined from several empirically determined where chiller best performance fromthe several chiller plant combinations, plant combinations, whereare certain design (e.g., number of certain design parameters modified (e.g.,parameters the numberare of modified chillers and the the distribution chillers and the distribution of cooling capacity). cooling capacity). etal. al.[5][5]determined determined capacity number of cooling units using an Cheng et thethe capacity andand number of cooling units using an unceruncertainty procedure to determine the cooling load demand profile and the Markov tainty procedure to determine the cooling load demand profile and the Markov method to method an to energy perform an energy the different proposedThis configurations. This perform analysis of theanalysis differentof proposed configurations. analysis involved analysis involved preventive maintenance reliability. Using a similar preventive maintenance and reliability. Usingand a similar methodology, Yang etmethodology, al. [6] defined the optimal chiller plant byplant modifying the chiller type and the and Yang et al. [6] defined theconfiguration optimal chiller configuration by modifying thenumber chiller type size of the chillers. compares results with thethe application of the the application traditional and the number andFigure size of1the chillers. the Figure 1 compares results with design methodology. Themethodology. chiller plant savings wereplant equal to 26%were of theequal life cycle. of the traditional design The chiller savings to 26% of the Despite the undeniable improvements presented in the previous studies, there are still life cycle. aspects that need to be addressed to obtain a more decisive result in the selection of chiller Despite the undeniable improvements presented in the previous studies, there are plants. This is especially case due totothe fact that these coolingresult systems, once installed still aspects that need to the be addressed obtain a more decisive in the selection of in buildings, automatic control systems, which for systems, increasingonce the chiller plants.usually This isincorporate especially the case due to the fact that theseallow cooling overall efficiency by synchronizing the coolingautomatic load of thecontrol chillerssystems, with the which coolingallow demand. installed in buildings, usually incorporate for In this case, it is possible that this system would incorporate another design scenario, very increasing the overall efficiency by synchronizing the cooling load of the chillers with the different from the In onethis considered both traditional robust design methodologies. cooling demand. case, it isinpossible that thisand system would incorporate another As the most suitable configuration for a certain building is being evaluated, the design scenario, very different from the one considered in both traditional and robust premise is that chiller plants usually comprise N + 1 units. As the energy performance design methodologies. analysis is carried out fromconfiguration the design stage, rules are used in different As the most suitable for asimple certainstaging building is being evaluated, the simulation software and research analyses. A common practice in chiller plant design is premise is that chiller plants usually comprise N+1 units. As the energy performance to consider the progressive according to the cooling the size analysis is carried out from startup the design stage, simple staging load rulesdemand are usedand in different of the chillers. Huang et al. [7] and Li et al. [8] recommended the startup of the chiller involving the highest cooling capacity first. Figure 2 illustrates the cooling load-based chiller sequencings of chiller on/off staging suggested by Sun et al. [9] and Huang et al. [7]. simulation software and research analyses. A common practice in chiller plant design is to consider the progressive startup according to the cooling load demand and the size of Energies 2023, 16,the 3782chillers. Huang et al. [7] and Li et al. [8] recommended the startup of the chiller 3 of 23 involving the highest cooling capacity first. Figure 2 illustrates the cooling load-based chiller sequencings of chiller on/off staging suggested by Sun et al. [9] and Huang et al. [7]. Figure 2 shows the2 energy consumption forecasting of the i-th chiller the j-th hour Figure shows the energy consumption forecasting of the i-th in chiller in the j-th hour using the PLR-COP curve of chiller generalmodels chiller models according to acapacity. fixed capacity. using the PLR-COP curve of general according to a fixed Figure 2. CoolingFigure load-based chiller sequencing representation of the traditional principle of principle of chiller 2. Cooling load-based chiller sequencing representation of the traditional chiller on/off staging. Reprinted/adapted with permission from Ref [9]. on/off staging. Reprinted/adapted with permission from Ref. [9]. Energyprediction consumption prediction is an important phase in chiller design, which Energy consumption is an important phase in chiller plant design,plant which involves the technical characteristics of the chiller and operating involves considering theconsidering technical characteristics of the chiller and operating factors suchfactors such as theof characteristics of the and thevariation thermal load variation predict the interaction as the characteristics the facility and thefacility thermal load to predict thetointeraction of the chiller plant. Designers must adapt the chilled-water system to the of the chiller plant. Designers must adapt the chilled-water system to the cooling loadcooling load variations over time. However, this is when the following questions arise: variations over time. However, this is when the following questions arise: Would it beWould it be possible for a chiller plant which was designed under the traditional staging principle to possible for a chiller plant which was designed under the traditional staging principle to be able to operate efficiently when incorporating an automatic control system? Should its be able to operate efficiently when incorporating an automatic control system? Should its staging involve considering another principle? staging involve considering another principle? Despite the major improvements in design methodologies presented by [5–8,10–13], Despite thewhere majordifferent improvements in design methodologies presented [5–8,10–13], parameters were optimized and these optimalby chiller plant configurations where different were parameters were optimized and these optimal chiller plant configurations then finally tested under traditional staging, it is likely that in the exploitation phase, were then finally tested under traditional staging, it isforecasts likely that in thein exploitation phase,This is why these configurations cannot meet the defined the initial study. these configurations cannotdesign meet of thethe forecasts defined in be theguaranteed, initial study. This is why an optimal chiller plant must considering thean impact of the optimal design automatic of the chiller plant must tobebeguaranteed, considering the impact of the control methods used in the future. In this research area, a gap that persists is that there is not enough research in the automatic control methods to be used in the future. literature to identifying the impact theenough initial design stage chiller plants In this research area,dedicated a gap that persists is that there isofnot research inof the on the [14,15].stage Recent studiesplants call foron extending the literature dedicated tosubsequent identifyingexploration the impactof ofthe thesystems initial design of chiller concept centralized and air (HVAC) the subsequent design exploration ofofthe systems heating, [14,15]. ventilation, Recent studies callconditioning for extending the systems to include possible interaction with the automatic control system, which usually design concept of centralized heating, ventilation, and air conditioning (HVAC) systems increases efficiency in later phases. Garcia [16]control defined this novelty named co-design, as to include possible interaction with the automatic system, whichapproach, usually increases a conceptual design process that uses dynamic systems as a variable to achieve optimal efficiency in later phases. Garcia [16] defined this novelty approach, named co-design, as results. Rampazzo [17] described the optimized operation of a chiller plant as a nonlinear a conceptual design process that uses dynamic systems as a variable to achieve optimal combinatorial mathematical problem, restricted to continuous and discrete variables, being results. Rampazzo [17] described the optimized operation of aHowever, chiller plant as a nonlinear a challenge for standard optimization methods. few researchers have presented combinatorial mathematical problem, restricted to continuous and discrete variables, et al. [15] studies using the co-design concept in the design of HVAC systems. Bhattacharya being a challenge for standard optimization methods. However, few ofresearchers carried out Bayesian optimization using black box models the chillers.have They optimized presented studies using thesystem co-design concept in and the the design of load HVAC systems. the size of the (cooling capacity) cooling chiller sequencing. They Bhattacharya etalso al. [15] carriedanout Bayesian optimization usingetblack boxused models of the included economic analysis. Masburah al. [18] a deep reinforcement chillers. They optimized the sizetoofprovide the system (cooling capacity) and the cooling learning language different control architectures to the HVACload systems during the simulation process inan the design phase. Here, this study cooling storage chiller sequencing. They also included economic analysis. Masburah et focuses al. [18] on used a system capacitylanguage and charging and discharging deep reinforcement learning to provide differentstrategies. control architectures to the In previous research, Diaz in et the al. [19,20] a new methodology for the design HVAC systems during the simulation process designproposed phase. Here, this study focuses of chiller plants for hotel facilities. This methodology integrated different procedures that on cooling storage system capacity and charging and discharging strategies. consisted of multiple statistical analyses of cooling demands [20] to obtain load patterns In previous research, Diaz et al. [19,20] proposed a new methodology for the design allowed obtaining individual chiller cooling capacities and then a mathematical proof chiller plantsthat for hotel facilities. This methodology integrated different procedures that cedure to create multiple chiller plant combinations, modifying several design variables and also considering compliance with technical standards. Subsequently, they presented an energy simulation procedure [19] carried out using the solution of a mathematical opti- Energies 2023, 16, 3782 4 of 23 mization problem of optimal chiller loading (OCL) and optimal chiller sequencing (OCS) analyses to establish an effective operating strategy. The final selection allowed designers to choose the system that best adapted to the variations in the thermal demands of the installation, working under an optimized mode, which would imply the implementation of an automatic control system for the HVAC system. However, the comparison of the effectiveness of this methodology was only based on the comparison of its results and the plant configuration selected according to the technical standard (a symmetrical chiller plant), and no comparative analysis was presented to validate its contribution with respect to the traditional methodologies currently used. Thangavelu et al. [21] showed that chiller plants can reduce their energy consumption by up to 40% in medium-capacity plants and by up to 20% in small-capacity plants by employing these techniques. This means a significant reduction in the environmental impact associated with electricity generation and considerable economic benefits. OCL is a method that optimizes the total distribution of cooling loads in regulated time intervals through several periods subjected to optimization constraints. OCS defines the conditions in which the chillers should operate or not, according to the cooling demand. Therefore, it adjusts the number of chillers in operation to the fluctuation of the cooling load, maximizing the plant’s efficiency. An efficient chiller plant must be designed based on the theoretical operating conditions that largely coincide with the future exploitation conditions in a building. However, there are still design standards and methodologies that include traditional sequencing staging in the energy assessment of chiller plants. Automatic control systems usually fit these systems; however, the savings achieved would likely be limited by errors during the initial design. This research contributes to chiller plant design in buildings. Considering that this process is carried out according to the technical standards and procedures outlined in Figure 1, the use of optimization techniques contributes to a better design of the plant and ensures that it operates under an efficient operating regime. The main objective is to demonstrate, through the energy comparison of two design trends, the impact that both have on the selection of the most suitable configuration for future operating conditions. This paper aims to verify the impact on the design of a chiller plant configuration of the use of a traditional sequencing staging approach or the use of co-design methodology, using the OCL and OCS in the energy performance forecasts study. These outcomes can serve as an inflexion point in the design philosophy of chiller plants. This paper is structured as follows: The methodology is described in Section 2, while the results are presented and discussed in Section 3. Finally, the conclusions are summarized in Section 4. 2. Materials and Methods 2.1. Methodology To meet the thermal demand of a chiller plant, regardless of the selected approach, the following steps need to be taken: 1. 2. 3. Calculation of the cooling load demand of the building. Implementation of accurate energy models of the HVAC systems for simulation purposes. Implementation of chiller plant sequencing algorithm and energy performance evaluation. 2.2. Cooling Load Demand of Building In this work, the thermal load of the investigated facility, i.e., a Cuban hotel, was calculated using the deterministic method suggested by [22]. The time base for the input data and thermal properties of the building was established by using the interface TRNBuild of TRaNsient SYstems Simulation software (TRNSYS 16) [23]. Energies 2023, 16, 3782 5 of 23 Using TRNSYS 16, heat load profiles (ki) representing a 24 h scenario were obtained. In addition, the different implemented thermal demand profiles, which represented 24 h heat load scenarios (ki), suggested the use of the following steps: 1. 2. 3. 4. Consideration in the simulation of activity levels in public areas and the activity patterns of hotels near the case study, which have in common the type of hotel, total capacity, and type of tourism. Consideration of the variation in the occupancy levels in each thermal zone with the aid of the historical occupancy levels in similar hotels. Establishment of energy efficiency measures in the thermal zones related to the rooms’ areas according to the suggestions of Yang et al. [6]. Establishment of the concept of a partially loaded room for thermal zones belonging to the rooms. This measure included comfort conditions in unoccupied rooms, considering a set point of 25 ◦ C, which ensured high indoor air quality levels in tropical-climate hotels. The sensible and latent heat portions were considered following the ASHRAE 55 recommendations [24]. The heat gained from the electrical equipment rated was calculated by considering its electrical power, duty factor, load factor, and efficiency. The heat fractions by convection and radiation were set at 0.7 and 0.3, respectively, and at 0.6 and 0.4 for artificial lighting [23]. Finally, a database was built, in which, for each ki, the thermal demand values (CLi) for each time interval (i) were reflected. 2.3. Implementation of Accurate Simulation Models of Air-Cooled Chiller Unit The mathematical models were based on the generalized least-squares method and the use of black box methodology for the implementation and selection presented by [25]. In this study, a multiple linear regression model was carefully chosen for enhanced simulation. . The cooling capacity (Qchi ) (Equation (1)) is a function of the subsequent independent variables. Tcair,in , Tchw,s , and Tcair are defined in Annex 1. x0 , x1 , and x2 represent the regression coefficient of the mathematical model. Qchi (kW) = xo + x1 Tcair,in + x2 Tch w,s xj ∈ Q,j = [0, 1, 2], Tcair,in f(Tamb) (1) To calculate the power input of the i-th chiller (Pch,i), it was decided that the independent variables were those that could be operationally modified, leading to Equation (2). aj ∈ Q,i = [0, 1, 2], Tcair,in , Tch w,r ∈ Q Pchi (kW) = ao + a1 Tch w,r + a2 Tcair (2) in which Tch w,o represents the chilled-water return temperature, which is given by Equation (3): Tchw,r (o C) = Cli + Tchw,s mi Cp (3) The statistical indices used for evaluating the error calculation of the model were the correlation coefficient (R2 ) (Equation (4)) and the mean of the absolute error (MAE) (Equation (5)). R2 is equal to the ratio of SCE (i.e., measure of the variability of the regression model) and SCT (corresponding to the measure of the variability of Y without considering the effect of the explanatory variables X). R2 = SCE , SCT 0 ≤ R2 ≤ 1 (4) The mean of the absolute error is the average absolute value of the residuals and shows the average error in the response prediction using the fitted model. _ N MAE = ∑ i=1 xi − x N i (5) The mean of the absolute error is the average absolute value of the residuals and shows the average error in the response prediction using the fitted model. N MAE = Energies 2023, 16, 3782 xi − xi i =1 6 (5) of 23 N The development of the regression model was based on White’s test for homoscedasThe development of the regression was on White’s test forautocorrelahomoscedasticity [26]. The Breusch–Godfrey test [27]model allowed forbased checking the residual ticity [26]. The Breusch–Godfrey test [27] allowed for checking the residual autocorrelation tion nonappearance in the selected mathematical model. In addition, the Jarque–Bera test nonappearance in to theanalyze selected mathematical model. In addition, the Jarque–Bera testof[28] [28] was employed normality. Compliance with the classical assumptions a was employed to analyze normality. Compliance with the classical assumptions of a reregression model guaranteed that the estimators obtained by the least-squares method gression modelconsistent, guaranteed that the estimators obtained by the least-squares method were were unbiased, and efficient. unbiased, consistent, and efficient. As an initial state in the analysis, the chiller plant was assumed to be a decoupled Asi.e., ancomposed initial stateofinn the analysis, the chiller plant assumed to 3). be The a decoupled system, air-cooled chillers arranged inwas parallel (Figure energy system, i.e., composed of n air-cooled chillers arranged in parallel (Figure 3). The energy analysis was only applied to the primary circuit (section of chillers). analysis was only applied to the primary circuit (section of chillers). Tchw,s Tchw,s Tcair,in Chiller (n) Cooling capacity black box model (Qchi) Tchw,r ṁn Tchw,s Tchw,s Tcair,in Chiller (2) Cooling capacity black box model (Qchi) Tcair,in Chiller (1) Cooling capacity black box model (Qchi) Tchw,r ṁ2 Building cooling load (Cli) Tchw,r ṁ1 Tchw,r Figure3.3.The Thegeneral generalframework frameworkofofthe thedecoupled decoupledchiller chillerplant. plant. Figure Thewater waterchiller chillerplant plantshould should be be composed composed of The of(n (n++1) 1)chillers. chillers.Many Manyauthors authors[6,9,29–31] [6,9,29– have recommended that in the case of a plant with different chiller capacities, the oneone with 31] have recommended that in the case of a plant with different chiller capacities, the the highest cooling capacity should be switched on first. Therefore, in the scenario involvwith the highest cooling capacity should be switched on first. Therefore, in the scenario ing the traditional principle of chiller on/off staging, the chillers werewere activated in order involving the traditional principle of chiller on/off staging, the chillers activated in from the highest to the lowest capacity (Equation (6)): order from the highest to the lowest capacity (Equation (6)): Qch22 ((kW ) ) ≥) ≥Qch ) ≥· ·· Qch Qch Qch kW) ≥ Qch 1 (kW n (kW 1 (kW n (kW ) (6) (6) 2.3.1. Approach Using the Traditional Principle of Chiller On/Off Staging 2.3.1. Approach the Traditional Principle of in Chiller On/Off To answerUsing how many chillers were working a certain timeStaging interval (i) depended on answer how many were(CL working in a certain time interval depended the To thermal demand of thechillers installation ) and the cooling capacity of each(i)chiller Qchn,i i oninthe thermal demand of the installation (CL i ) and the cooling capacity of each chiller each time interval (i). Therefore, Equation (7) gives the total operating chillers. Qchn,i in each time interval (i). Therefore, Equation (7) gives the total operating chillers. Nc= f(CLi ; Qchi ) (7) Nc = f (CL i ; Qch i ) (7) The cooling load capacity of the water chiller plant as well as the electrical power The cooling load capacity of the water chiller plant as well as the electrical power required are in function of the variables shown in Equations (8) and (9), respectively. required are in function of the variables shown in Equations (8) and (9), respectively. Qch Qch Tcair,in ; Tch Tch) = n,i = f f((Tc air, in ; w,s n, i w, s Pch Pch ; Qch Tcair,in Qch n,i = ff(Tc n,i n, i = air,;in n, i ) ) (8) (8) (9) (9) The total cooling load supplied by the chiller plant, composed of n chillers, as well as the total electrical energy consumption are given by Equations (10) and (11), respectively. QchN,i ≤ PchN,i ≤ n ∑ Qchn,i n ∈ N∀, n ≥ 2 (10) ∑ (Pchn,i ) n ∈ N∀, n ≥ 2 (11) k=1 n k=1 Energies 2023, 16, 3782 7 of 23 Equation (12) describes the cooling load that the plant delivers to the building as constrained according to the thermal demand of the building. This also influences the total number of chillers in operation, whose constraint is shown in Equation (13). CLi ≤ Nc = Nc = n − 1 Nc = n n ∑ Qchn,i n ∈ N∀, n ≥ 2 (12) k=1 if(Cli − Qchi ) ≤ 0 if(Cli − Qchi ) > 0 then Ch1,i sj = 1(on) .. . Chn,i sj = 0(off) Ch1,i sj = 1(on) .. then . Chn,i sj = 0(off) Sj ∈ {0; 1} (13) The chilled-water supply temperature range is set according to Equation (14): Tchw,s (o C) ∈ N, Tchw,s = 7 . . . 13 (14) The “on” and “off” interval status to be analyzed is defined with the variable sj. Equation (15) defines the constraint denoted to the minimum range between the activation and deactivation time of a chiller to avoid too many on/off cycles. Chang et al. [32] recommended that the minimum time between the activation and deactivation of a chiller needs to be between 30 min and 1 h. In [33], Witkowski gives a similar range. n h i o Sj = f CL(i) (kW)= mx CL(t−1) : CL(t) (15) t ∈ N, t = 1 . . . .24 The constraints of the typical sequencing chiller strategy can be summarized as follows: 1. 2. 3. Step 1: If cooling load CLi ≤ Qch1 , then chiller 1 satisfied the system load (with Qch1 > Qch2 ); Step 2: If Cli > Qch1 , then chiller 1 provided the full cooling load and the remaining thermal demand was provided by chiller 2; Step 3: If Cli ≥ Qch1 + Qch2 + . . . Qchn +, then chillers Ch1 , Ch2 , . . . , Chn were turned on (in which Qch1 > Qch2 > . . . > Qchn ). 2.3.2. Optimal Chiller Loading and Optimal Chiller Sequence Staging Approach: Co-Design of Chiller Plant Approach The chiller energy performance simulation is considered an optimal chiller sequence staging approach [18]. This study combined the four OCS strategies defined, the total cooling load-based sequencing control, and the direct power-based sequencing control. To ensure optimal results and to avoid an incorrect designation of the partial load ratio (PLR) value, as only one chiller can satisfy the thermal needs of the system without the use of two or more units, a strategic baseline was built, as is shown in Figure 4. The chillers were arranged from lowest to highest according to their individual cooling capacity, defined by the variable (Qchi). The sequencing chiller strategy shown in Figure 4 can be summarized as follows: 1. 2. 3. Step 1: If CLi ≤ Qch1,i, then chiller 1 satisfied the system load; Step 2: If Qch1,i < CLi ≤ Qch2,i , then chiller 2 met system load; Step 3: If (Qch1,i + Qch2,i ) ≤ CLi ≤ Qchn−1,i, the OF of chillers 1 and 2 was optimized and derived from the optimal load problem, and the results were quantified. The results were compared with the electrical power consumption of the chiller (n − 1). If (Pch1,i + Pch2,i ) < Pchn−1 , chillers 1 and 2 were turned on. If not, chiller n − 1 turned on; 2.3.2. Optimal Chiller Loading and Optimal Chiller Sequence Staging Approach: CoDesign of Chiller Plant Approach The chiller energy performance simulation is considered an optimal chiller sequence staging approach [18]. This study combined the four OCS strategies defined, the total cooling load-based sequencing control, and the direct power-based sequencing control. 8 ofTo 23 ensure optimal results and to avoid an incorrect designation of the partial load ratio (PLR) value, as only one chiller can satisfy the thermal needs of the system without the use of two or more units, a strategic baseline was built, as is shown in Figure 4. The chillers were 4. Step 4: If CLi ≥ Qch1,i + Qch2,i + . . . Qchn,i, then chillers 1, 2, . . . , n were turned on. arranged from lowest to highest according to their individual cooling capacity, defined by OF was optimized for chillers 1,2, . . . , n. the variable (Qchi). Energies 2023, 16, 3782 Start Building cooling load (CLi) Chillers Black models (Qch); (Pch) Meteorological data typical day (Tamb) Chilled water set point temperature (Tchw,s) N chiller plant composed of n chillers Set Objetive Fuction (OF) and constrains Set baseline for OCS analysis CLi≤ Qch(1) No No Qch(1)< CLi≤ Qch(2) (Qch(1)+Qch(2)) ≥ CLi ≥ Qch(N-1) Yes Yes On Qch(1) On Qch(2) Genetic algorithm fuction Solve OF(Qch(1)+Qch(2)) Quantify: PLRi, ∫(Pchi)dt COPi Quantify: PLRi, ∫(Pchi)dt COPi ∑Pchi[(1)i+(2)i] <∑Pch(n-1)i Yes Yes No On Qch(1)+Qch(2) On Ch(n-1) Quantify PLRi, ∫(Pchi)dt COPi Quantify PLRi, ∫(Pchi)dt COPi Order from min→max [∫(Pchi)dt ] Order from max→min [COPi ] End Figure Figure 4. 4. Baseline Baseline schedule schedule of of OCS OCS strategy strategy [18]. [18]. The sequencing chiller strategy shown in Figurewere 4 can be summarized ason follows: conditions in which the chillers operated defined depending the cooling demand. Therefore, the number of chillers in operation was adjusted according to 1. Step 1: If CLi ≤ Qch1,i, then chiller 1 satisfied the system load; the fluctuation of the thermal demand using an optimization algorithm, which allowed 2. Step 2: If Qch1,i < CLi ≤ Qch2,i, then chiller 2 met system load; minimizing required cooling capacity and energy goal ofand the 3. Step 3: Ifthe (Qch 1,i + Qch 2,i) ≤ CLi ≤ Qchn−1,i, the OF of consumption. chillers 1 and 2The wasmain optimized optimization procedure is to maintain the comfort ofwere the facility with The the results lowest derived from the optimal load problem, and thelevels results quantified. energy consumption of the chiller plant. As an initial stage,ofthe were compared with the electrical power consumption thesystem chiller (chiller (n − 1). plant) If (Pchis 1,i decoupled, in order to analyze only the direct interaction between the chiller plant and the + Pch2,i) < Pchn−1, chillers 1 and 2 were turned on. If not, chiller n − 1 turned on; thermal the 1,i building. The Qch OCLn,i,problem to be1,solved classified as on. a nonlinear 4. Stepdemand 4: If CLiof ≥ Qch + Qch2,i +… then chillers 2,…, niswere turned OF was optimization problem with constraints and a combinatorial optimization problem with optimized for chillers 1,2,…, n. continuous, discrete, and binary variables. The conditions in which the chillers operated were defined depending on the cooling Each analyzed period was solved simultaneously and determined the on/off status, demand. Therefore, the number of chillers in operation was adjusted according to the flucPLRi ; Pchi , and COPi for each chiller. OCS complemented the OCL expressed in the objectuation of the(OF) thermal demand using optimization algorithm, which allowed minimiztive function (Equation (16)), andan the constraints (Equations (17)–(20)) complemented the variable decision PLR (Equation (21)), shown below. Objective function (OF) is as follows: ( minPLR n ∑ j=1 a0 + a1 CLi PLRi + Tchw,s mi Cp ! + a2 Tcair n + Qch,mx − ∑ Qchi,n PLRi j=1 ! + n ∑nj=1 COP !) sj (16) Energies 2023, 16, 3782 9 of 23 OF is subject to the following: CLi (kW) ≤ n ∑ (Qchi ∗PLRi )(kW) n ∈ N∀, n ≥ 2 (17) k=1 Tchw,in (o C) ∈ N, Tchw,in = 7 . . . 13 h i CL(i) (kW)= mx CL(t−1) : CL(t) t ∈ N, t = 1 . . . .24 (18) (19) The value of the PLR variable in Equation (20) determines the on/off status, which is a difference between the individual chiller staging and the strategy shown in Section 2.2. Sj = if if PLR = 0 then Sj = 0(off) Sj ∈ {0; 1} 0 < PLR ≤ 1 then Sj = 1 (on) (20) In OCL and OCS problems, the literature commonly uses the PLR as a decision variable, as can be seen in different papers [34–37]. The theoretical (PLRn,i ) of each chiller is as shown in Equation (21). CLi (21) PLRn,i = Qchi For the OCL solution, a genetic algorithm (GA) was used. GA is a metaheuristic method offering an optimal solution to an optimal combinatorial problem, which has many possibilities for a solution. The variables to be processed were the decision variable (PLRn,i ) of the chiller unit and the arrangement of the chiller working in parallel. After the variables were encoded into chromosomes, the information built 10 into Energies 2023, 16, x FOR PEER REVIEW of the 24 chromosomes was the total PLRs of the units running in parallel. A GA flowchart for OCL problems is presented in Figure 5. Figure5.5.General GeneralGA GAflowchart flowchartfor forOCL OCLproblems. problems. Figure CaseStudy Study 3.3.Case Themethods methodsdescribed describedininthe theprevious previoussubsections subsectionsapplied appliedtotoaahotel hotelbeing beingbuilt builtinin The Cienfuegos (Cuba) and involving three functional areas: rooms, public areas, and service Cienfuegos (Cuba) and involving three functional areas: rooms, public areas, and service areas. The room area has 87 rooms, 45 of which are part of the main building and 42 of areas. The room area has 87 rooms, 45 of which are part of the main building and 42 of which are individual modules and cabins. One of the functional areas includes public areas, such as a lobby designed with natural air ventilation, a gift store, a specialized restaurant, a kitchen, and a nightclub. Finally, the service area, including different office modules, was also considered in the total cooling chiller plant capacity. The main characteris- Energies 2023, 16, 3782 10 of 23 which are individual modules and cabins. One of the functional areas includes public areas, such as a lobby designed with natural air ventilation, a gift store, a specialized restaurant, a kitchen, and a nightclub. Finally, the service area, including different office modules, was also considered in the total cooling chiller plant capacity. The main characteristics of the functional areas are summarized in Table 1. Table 1. Main characteristics of the functional areas of the hotel. Functional Areas Type of Thermal Zone Top floor (East) Top floor (West) Top floor (Intermediate rooms) Low levels (Intermediate rooms) Low levels (Intermediate rooms–east–west corner) Cabins (West corner) Cabins (East corner) Cabins (Intermediate rooms) Thermal Zone ID Type of Thermal Zone 1 2 3 4 Restaurant Cabaret Shops Double office 5 North office 6 7 8 South office Intermediate office Rooms Functional Areas Thermal Zone ID 9 10 11 12 Public areas 13 Service areas 14 15 For the cooling demand analysis of the facility, the thermal properties of the hotel walls were obtained from TRNSYS 16 library [22] and are listed in Table 2. Table 2. Thermal properties of the hotel’s walls. Wall Type Nomenclature Thermal Conductivity (W·m−2 ·K−1 ) Overall Transmittance (W·m−2 ·K−1 ) Outwall O 2.05954 11.40879 Inwall I 2.09029 11.67302 Ground G 3.40909 29.18919 Roof Window R W 3.25960 5.8 26.31854 5400 Material (Thickness (m)) Concrete block (0.15); Cement+clay (0.02); Cement+clay (0.01) Brick (0.15); Cement+clay (0.01); Cement+clay (0.01) Concrete (0.24); Ceramics (0.01); Cement+clay (0.01) Concrete (0.24); Rasilla (0.02) Single crystal (0.008) The detailed composition of each functional area, the thermal properties of their construction materials, the heat gains deriving from occupation, and the use of equipment were considered (Tables 3 and 4). Table 3. Thermal comfort features of main building rooms and cabins (room area). Thermal Zone ID Number of Rooms Dimensions (m3 ) Wall Type Heat Gains 1 2 3 4 5 6 7 8 3 3 9 18 12 3 3 36 108 108 108 108 108 111.38 111.38 111.38 W(1); O (1); I (2); R(1); W(1); O (1); I (2); R(1); W(1); I (4); W(1); I (3); G (1) W(1); O (1); I (2); G(1); W(1); O (1); I (1); R(1); G(1); W(1); O (1); I (1); R(1); G(1); W(1); I (2); R(1); G(1); Electronic appliances: 1643 W Lighting: 13 W·m−2 People: Max 3 guests (sensible/latent: 65/55 W) Energies 2023, 16, 3782 11 of 23 Table 4. Thermal comfort features of public areas and service area. Thermal Zone ID Number of Rooms Dimensions (m3 ) Wall Type Heat Gains 9 1 951.34 W(2); O (2); R(1); G(1); Electronic appliances: 21,080 W Lighting: 16 W·m−2 Max 58 guests (sensible/latent: 65/55 W) Max 9 employees (sensible/latent: 75/55 W) 10 1 1463 O (2); R(1); G(1) Electronic appliances: 7317.61 W Lighting: 10 W·m−2 Max 500 guests (sensible/latent: 90/160 W) Max 9 employees (sensible/latent: 65/55 W) 11 2 111.38 W(2); O (2); R(1); G(1); Electronic appliances: 700 W Lighting: 13 W·m−2 Max 12 guests (sensible/latent: 65/55 W) Max 3 employees (sensible/latent: 75/55 W) 12 13 14 15 3 1 1 4 47.73 23.4 23.4 23.4 W(1); O (1); I(1); R(1); G(1); W(1); O (1); I(1); R(1); G(1); W(1); O (1); I(1); R(1); G(1); W(1); R(1); G(1); I(2); Electronic appliances: 413 W Lighting: 13 W·m−2 Max 2 employees (sensible/latent: 63/52 W) The hotel design criteria were establishing according to thermal inside comfort Cuban standard NC 217:2002 [38]. Using TRNSYS 16, the standard procedure for thermal demand analysis recommended in ASHRAE Fundamentals [2] was applied, taking into consideration the worst operating conditions scenario at the hotel and other future operating scenarios that reflected the great variation in the nature of activities in the facility. Different cooling profiles suggest the need for energy efficiency measures to mitigate the different occupancy levels of the hotel. In addition, this analysis considered the occupancy and employment patterns of a hotel in operation (from the same hotel chain) based on a previous study [19,22,39,40]. Furthermore, the hotel featuring these partners was characterized by a service disruption between 10:00 am and 4:00 pm (defined as transit hotel classification). The occupied room indicator (Hdo) fluctuated according to the tourist season from low occupancy (Hdo ≤ 10%) to medium occupancy (45% ≤ Hdo ≤ 50%) to high occupancy (75% ≤ Hdo ≤ 90%) to full hotel occupancy (Hdo = 100%). Therefore, several cooling load profiles (ki) in the functional areas, i.e., the rooms, public areas, and service areas, were implemented. In addition, for the ki calculation: (1) (2) (3) The concept of a “partially loaded” room (unoccupied rooms which were kept at 26 ◦ C by an air conditioner) was applied [32]. Different occupancy rates between 10%, 50%, 75%, and 100% for the hotel in the rooms and public areas were considered. The load diversity through occupancy strategies was eliminated using the lowestthermal-demand rooms for occupancy rates of 75% and 50%. Six chiller plants with an arrangement of two air-cooled screw-type water chillers were proposed to be installed in the hotel; see Table 5. The primary circuit was characterized by a constant chilled-water mass flow rate. The installed cooling capacity varied between 538 kW and 589 kW, representing the common practice of a load safety factor between 10% and 20% of the total installed capacity (as recommended in [2]). The plant configurations are presented in Table 5. Energies 2023, 16, 3782 12 of 23 Table 5. Chiller plant configurations. Chiller Plant Configuration * (kW) * (kW) Chiller Cooling Capacity Distribution (%) Total Cooling Capacity (kW) Safety Factor 1 2 3 4 5 6 180.1 198.7 201.6 228.9 271.2 271.2 357.8 357.8 357.8 310.6 271.2 310.6 33/67 36/64 36/64 42/58 50/50 47/53 537.92 556.59 559.82 539.53 542.46 581.85 10.2 14.1 14.7 10.6 11.7 19.2 * Chiller cooling capacity in standard conditions (STD): chilled-water supply/return of 7/12 ◦ C, air temperature at the condenser inlet of 32 ◦ C. Using the manufacturer’s data set of the chillers selected, the mathematical models that represent the Qch and Pch, using Equations (1) and (2), were determined through the least-squares method. The regression coefficients and the quality of the black box models were defined using the software Eviews 12 [41]. The results of the adjustability as well as the quality of the models are shown in Table 6. Table 6. Quality measurement of the selected chiller black box models [41]. t Student Diagnostic Test 10−14 −7.822 × 0.990 Stadígraph p-value White Breusch–Godfrey Jarque–Bera 10.947 0.952 29,046 4.929 × 10−7 4.152 0.125 In the performed tests, the p-value for compliance with the null hypothesis was ≥0.05. It was observed that the selected models fulfilled the established statistical assumptions. The selected models did not fulfil the assumption of the nonexistence of autocorrelation. This is a consequence of the cyclical nature of the data used for their construction. Finally, the fourth assumption, i.e., the null hypothesis that dictated normality in the data, was fulfilled as well. It is emphasized that this is an inviolable requirement of regression. The regression coefficients of each of the investigated chiller plant configurations, as well as the results of the adjustment measurement, are shown in Table 7. It was found that they have a high explanatory percentage with an R2 above 99% and lower values of MAE and AIC. Considering these results and considering that the violation of the third assumption did not invalidate the estimators obtained by the least-squares method, this can establish that the regression coefficients (x0 , x1 , x2 ; a0 , a1 , a2 ) and the chillers’ black box models obtained are unbiased, consistent, and efficient. Table 7. Regression coefficients and fitting measurements of the models. Cooling Capacity Model Chiller Cooling Capacity at STD 180.1 198.7 201.6 228.9 271.2 310.6 357.8 ṁ (kg·s−1 ) 8.67 9.56 9.72 11 13 14.9 17.2 Regression Coefficients Electrical Power Model Fitting Measurements of the Models Regression Coefficients Fitting Measurements of the Models x0 x1 x2 R2 MAE AIC a0 a1 a2 R2 MAE AIC 203.1 221.0 226.0 257.0 302.7 345.3 403.5 −2.30 −2.42 −2.51 −2.87 −3.37 −3.80 −4.55 7.21 7.91 8.07 9.12 10.9 12.4 14.2 99.6 99.7 99.7 99.8 99.6 99.7 99.6 1.08 0.97 1.04 0.93 1.64 1.51 2.15 0.32 0.28 0.29 0.27 0.32 0.27 0.32 19.55 22.93 22.69 24.57 30.15 34.96 39.07 0.84 0.92 0.93 1.18 1.29 1.39 1.68 0.24 0.33 0.37 0.26 0.37 0.53 0.47 99.0 98.8 98.9 98.8 99.0 98.8 99.1 0.60 0.74 0.71 0.96 0.93 1.10 1.18 0.40 0.40 0.39 0.40 0.40 0.41 0.40 4. Results and Discussion The cooling thermal demand of each feasible scenario was calculated according to the elements and design criteria exposed in Section 3. The thermal profiles k1 and k2 are the critical scenarios of the hotel, i.e., the maximum demand and minimum demand, respectively. The other thermal profiles simulate different occupation scenarios and activity Energies 2023, 16, 3782 13 of 23 levels which could occur in the hotel. The eight load profiles of the hotel were generated using TRYNSYS 16 [22]. The time interval for the analysis was 24 h in a typical summer day profile, obtained using METEONORM data [42]. For each thermal zone, a graphical interface was built into the program. For the infiltration gains, a factor of 0.8 was assumed. The convection/radiation fraction of the heat gain due to the use of electronic equipment was 0.3/0.7. The simulation in TRNBuild [22] was carried out using the power level control, while the cooling loads of the building were calculated considering the information above. The results of the demand load values are shown in Table 8. Table 8. Cooling load demand values of the 8 analyzed profile schedules. Time (h) 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 Cooling Load Demand Values Cli (kW) k1 k2 k3 k4 k5 k6 k7 k8 387.74 387.38 347.84 342.10 340.69 339.16 338.36 337.45 383.76 388.71 415.22 436.97 456.91 473.62 483.59 488.26 487.54 476.32 439.19 424.56 418.87 411.23 399.14 401.53 96.04 90.41 84.47 79.59 76.32 73.67 85.59 94.15 105.42 115.99 120.71 147.52 166.02 179.50 187.89 192.69 182.40 171.97 165.65 168.73 158.23 129.84 115.54 105.80 345.74 345.50 308.20 300.86 299.47 299.01 321.25 324.88 339.18 337.89 347.08 388.49 410.54 427.18 425.09 429.24 417.64 402.85 402.86 410.88 406.21 384.29 358.72 360.86 289.30 293.56 255.96 248.02 245.88 245.12 259.69 261.63 273.98 270.96 290.72 325.39 344.90 361.45 357.58 362.48 362.43 349.18 356.05 345.47 340.41 333.80 306.89 309.27 241.30 240.44 203.32 195.66 194.00 193.56 208.61 211.11 223.42 220.60 239.84 274.35 293.54 309.25 304.90 309.00 307.99 293.42 299.13 288.27 283.37 277.40 251.49 254.51 154.79 154.19 117.04 109.07 107.80 105.96 196.54 156.40 150.03 148.47 150.19 239.18 207.44 223.27 220.91 225.00 315.73 224.23 278.36 232.83 227.59 206.63 181.54 183.68 146.45 150.38 112.93 104.52 102.50 100.58 180.10 137.89 132.46 129.14 141.46 227.26 193.01 208.75 204.77 209.61 264.88 215.08 276.51 212.25 206.81 200.85 174.26 176.64 142.45 141.26 104.29 96.36 94.82 93.42 170.42 128.37 125.50 122.38 134.18 223.02 188.45 203.35 199.09 203.13 214.84 200.12 260.79 196.05 190.97 185.45 159.66 162.68 For the comparison of the energy performance of the chiller plants presented in Table 5 with the eight thermal demand profiles calculated in Section 3, Equations (1)–(3) were used by substituting the correlation coefficients listed in Table 7 and setting a fixed temperature setpoint value equal to 7 ◦ C. In addition, the ambient temperature profile corresponding to the same day when the thermal demand was calculated was extracted. Subsequently, the mathematical algorithm described by Equations (12)–(15) was implemented using MATLAB 2018 [43]. The on/off schedule of each chiller plant and the PLRi values of each chiller are shown in Figures 6 and 7, respectively. As shown in Figure 6, this operating staging forced the first chiller to always be running, regardless of the thermal demand. The second chiller covered the remaining demand if requested, regardless of the load regime to which it was subjected. Figure 7 describes this type of operation causing at least one of the chillers to work in a critical partial regime. The total energy consumption as well as the average COP of each investigated chiller plant are listed in Table 9. According to the results, there were no significant differences in energy performance between the proposed chiller plant configurations. The highest energy consumption was given by the chiller plant configuration #6, which consumes 5.3% greater than the one offering the minimum consumption of electricity (chiller plant #5). Energies 2023, 16, x FOR PEER REVIEW Energies 2023, 16, 3782 07:00 08:00 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 14 of 24 14 of 23 338.36 Table 9.85.59 321.25 and average 259.69COP values 208.61 196.54 chiller180.10 Energy consumption of the investigated plant options.170.42 337.45 94.15 324.88 261.63 211.11 156.40 137.89 128.37 Chiller Plant Configuration Energy Consumption (kWh) Average COP 383.76 105.42 339.18 273.98 223.42 150.03 132.46 125.50 2.43 388.71 115.99 1 337.89 270.96 14,088.54 220.60 148.47 129.14 122.38 2.35 415.22 120.71 2 347.08 290.72 14,187.96 239.84 150.19 141.46 134.18 3 14,162.84 2.22 436.97 147.52 4 388.49 325.39 14,186.33 274.35 239.18 227.26 223.02 2.68 456.91 166.02 5 410.54 344.90 13,882.52 293.54 207.44 193.01 188.45 2.78 6 14,619.42 2.53 473.62 179.50 427.18 361.45 309.25 223.27 208.75 203.35 483.59 187.89 425.09 357.58 304.90 220.91 204.77 199.09 488.26 192.69 429.24 362.48 309.00 225.00 209.61 203.13 Using the traditional load-based sequencing methodology and without the application 487.54 of optimization 182.40 procedures, 417.64 chiller 362.43 307.99 #5 was 315.73 214.84 plant configuration selected for264.88 the hotel facility, 476.32 being the 171.97 402.85 349.18 293.42 224.23 215.08 200.12 highest-performing. For the energy 402.86 performance 356.05 of the chiller 299.13 plants using the mathematical optimization 439.19 165.65 278.36 276.51 260.79 shown in Equations (16)–(20), the same operating conditions used in the investigated hotel 424.56 168.73 410.88 345.47 288.27 232.83 212.25 196.05 The406.21 principle of 340.41 simultaneously reaching the optimum operating of 418.87 were employed. 158.23 283.37 227.59 206.81 point 190.97 each chiller and the chiller plant was defined using the methodology depicted in Figure 4. 411.23 129.84 384.29 333.80 277.40 206.63 200.85 185.45 For the evaluation of the objective function and the constraints, a genetic algorithm was 399.14 115.54 358.72 306.89 251.49 181.54 174.26 159.66 adjust the control (Table 10). MATLAB Simulink [43] was used162.68 for 401.53 used to105.80 360.86parameters 309.27 254.51 183.68 2018 176.64 carrying out the evaluation. For the comparison of the energy performance of the chiller plants presented in Table 5 with the eight thermal demand profiles calculated in Section 3, Equations (1)–(3) were used by substituting the correlation coefficients listed in Table Population size 150.007 and setting a fixed temperatureSelection setpointoperator value equal to 7 °C. In addition, the ambient temperature profile correuniform stochastic Reproduction: elitism 2.00 sponding to the same day when the thermal demand was calculated was extracted. SubCrossover factor 0.80 sequently, the mathematical algorithm described by Equations (12)–(15) was impleMutation uniform 0.01 mented using MATLAB 2018 [43]. The on/off schedule of each chiller plant and the PLRi Crossover heuristic 1.50 values of each chiller are shown in Figures 6 and 7, respectively. Table 10. GA control parameters. Chiller plant #1 Chiller plant #2 Figure 6. Cont. Energies 2023, 16, x FOR PEER REVIEW Energies 2023, 16, 3782 15 of 24 15 of 23 Chiller plant #3 Chiller plant #4 Chiller plant #5 On Off Chiller plant #6 6. On/off schedule chiller plant options using theon/off traditional on/off approach of chiller FigureFigure 6. On/off schedule of chillerof plant options using the traditional approach of chiller staging. staging. As shown in Figure 6, this operating staging forced the first chiller to always be running, regardless of the thermal demand. The second chiller covered the remaining de- Energies 2023, 16, x FOR PEER REVIEW mand if requested, regardless of the load regime to which it was subjected. Figure 7 de16 of 23 scribes this type of operation causing at least one of the chillers to work in a critical partial regime. Energies 2023, 16, 3782 6 6 5 5 5 4 4 4 3 2 POT 6 POT COP 16 of 24 3 2 2 Ch 357.8 kW 1 0 0.0 0.2 0.4 0.6 0.8 Ch 357.8 kW 1 Ch 180.1 kW 1.0 Chiller plant #1 0.4 0.6 PLR 0.8 0.0 1.0 Chiller plant #2 4 4 4 POT 5 3 Ch 310.6 kW 1 Ch 228.9 kW 0.2 0.4 0.6 PLR Chiller plant #4 0.8 1.0 1.0 3 Ch 310.6 kW 1 Ch 271.2 kW Ch 271.2 kW Ch 271.2 kW 0 0 0.8 2 2 2 0.4 0.6 PLR Chiller plant #3 5 3 0.2 6 5 POT POT 0.2 6 0.0 Ch 201.6 kW 0 0.0 6 1 Ch 357.8 kW 1 Ch 198.7 kW 0 PLR 3 0.0 0.2 0.4 0.6 PLR 0.8 1.0 0 0.0 Chiller plant #5 0.2 0.4 0.6 PLR 0.8 1.0 Chiller plant #6 Figure curvesofofchiller chiller plant configuration Figure 7. 7. COP-PLR COP-PLR curves plant configuration ns. ns. The total proposed procedure allowed identification of the optimal PLRi of each chiller at The energy consumption as well as the average COP of each investigated chiller each demand through the established optimalthere sequence, on/off status, and the plant are listedpoint, in Table 9. According to the results, were the no significant differences number chillers in operation. The on/off schedule andconfigurations. PLI-COP curve diagrams are in energyofperformance between the proposed chiller plant The highest enshown in Figures 8 and 9, respectively. ergy consumption was given by the chiller plant configuration #6, which consumes 5.3% Figure shows markedthe difference between the operation of the chiller greater than8the one aoffering minimum consumption of electricity (chillerplant plantand #5).the cooling demand profile obtained in Table 9, concerning the mode of operation shown in Table Energy consumption average COP of the investigated plant options. Figure9. 6. In this case, it canand be seen how thevalues staging sequencing of chiller the chillers is adjusted to the individual cooling capacity and in correspondence to the specific cooling demand. Chiller Plant Configuration Energy Consumption (kWh) Average COP This mode of operation has a positive influence on the individual efficiency of each chiller 1 14,088.54 and in turn on the overall efficiency of the chiller plant, as shown in Figure 2.43 9. 2 2.35 for a more Figure 9 demonstrates that the strategy14,187.96 designed for the chiller plant allows 3 2.22the largest efficient operating regime (range of the PLR14,162.84 greater than 0.5) for the chiller with 4 14,186.33 2.68 capacity. cooling capacity by sacrificing the efficiency of the chiller with the smallest cooling 5 the energy consumption and 13,882.52 2.78 Table 11 shows average COP values of all the chiller plant options. The results reveal that the best configuration was chiller plant configuration #1 6 14,619.42 2.53 (i.e., an asymmetric chiller plant with a cooling distribution of 33/67% and safety factor of 10.2%). Using the traditional load-based sequencing methodology and without the application of optimization procedures, chiller plant configuration #5 was selected for the hotel facility, being the highest-performing. For the energy performance of the chiller plants using the mathematical optimization shown in Equations (16)–(20), the same operating conditions used in the investigated hotel were employed. The principle of simultaneously reaching the optimum operating point 4. For the evaluation of the objective function and the constraints, a genetic algorithm was used to adjust the control parameters (Table 10). MATLAB Simulink 2018 [43] was used for carrying out the evaluation. Table 10. GA control parameters. Energies 2023, 16, 3782 17 of 23 Population size 150.00 Selection operator uniform stochastic elitism 2.00 Table 11. Reproduction: Energy consumption and average COP values of chiller plant options. Crossover factor 0.80 Chiller Plant Configuration Mutation uniform Energy Consumption (kWh) 0.01 Average COP Chiller plant #1 10,446.251 4.491 Crossover heuristic 1.50 Chiller plant #2 10,681.532 4.312 Chiller plant #3 10,696.964 4.304 The proposed procedure allowed identification of the optimal PLRi of each chiller at Chiller plant #4 10,596.201 4.481 each demand Chiller point, through the established optimal sequence, the on/off status, and the plant #5 11,953.838 3.872 number of chillers operation. The on/off schedule are Chillerinplant #6 11,707.874and PLI-COP curve diagrams 3.991 shown in Figures 8 and 9, respectively. Chiller plant #1 Chiller plant #2 Chiller plant #3 Figure 8. Cont. Energies 2023, 16, x FOR PEER REVIEW Energies 2023, 16, 3782 18 of 24 18 of 23 Chiller plant #4 Chiller plant #5 Chiller plant #6 Figure Figure 8. On/off schedule of chiller plantplant options using thethe optimized chillerstaging. 8. On/off schedule of chiller options using optimizedon/off on/offprinciple principle of of chiller staging. Considering that the GA tool provided an approximated result, three runs of the Figure 8 shows a marked between thethe operation theoptimization chiller plantprocedures. and program were carried out difference to verify the results of OCL andof OCS the cooling demand profilewere obtained in Tableusing 9, concerning thestandard mode ofdeviation operation(RSD). shown The results obtained corroborated the relative Table 12 reveals ofitless 1%,how proving the existence of a great fit chillers in the control parameters in Figure 6. In an thisRSD case, canthan be seen the staging sequencing of the is adjusted of the GA. cooling capacity and in correspondence to the specific cooling demand. to the individual This mode of operation has a positive influence on the individual efficiency of each chiller 12. the Results obtained with the and inTable turn on overall efficiency of GA the tool. chiller plant, as shown in Figure 9. Chiller Plant Configuration Test 1 Test 2 Test 3 RSD (%) 1 2 3 4 5 6 10,446.25 10,681.53 10,696.96 10,596.20 11,953.83 11,707.87 10,446.29 10,681.51 10,696.82 10,595.67 11,953.83 11,708.70 10,446.25 10,681.55 10,696.90 10,594.91 11,953.83 11,709.26 0.02 0.02 0.07 0.61 0.00 0.60 of 23 19 of1924 7 7 6 6 6 5 5 5 4 4 4 3 3 3 2 Ch 180.1 kW 1 0 0.0 0.4 0.6 0.8 2 0 0.0 1.0 PLR Chiller plant #1 0.4 0.6 PLR 0.8 Chiller plant #2 6 6 5 5 5 4 4 4 3 3 3 1 0 0.0 0.4 0.6 0.8 PLR Chiller plant #4 Ch 271.2 kW 1 Ch 310.6 kW 0.2 COP 6 2 1.0 0 0.0 0.4 0.6 0.8 PLR Chiller plant #5 0.4 0.6 PLR 2 0.8 1.0 Ch 271.2 kW 1 Ch 271.2 kW 0.2 0.2 Chiller plant #3 7 Ch 228.9 kW Ch 357.8 kW 0 0.0 1.0 7 2 Ch 201.6 kW 1 Ch 357.8 kW 0.2 2 7 COP COP Ch 198.7 kW 1 Ch 357.8 kW 0.2 COP 7 COP COP Energies 2023, 3782PEER REVIEW Energies 2023, 16, 16, x FOR 1.0 0 0.0 Ch 310.6 kW 0.2 0.4 0.6 PLR 0.8 1.0 Chiller plant #6 Figure 9. COP-PLR performance curves of chiller plant options. Figure 9. COP-PLR performance curves of chiller plant options. Figure 9 demonstrates the strategy designed forthe thefollowing: chiller plant allows for a As mentioned above,that the results obtained revealed more efficient operating regime (range of the PLR greater than 0.5) for the chiller with the • The application of the traditional load-based sequencing methodology suggested the largest cooling capacity by sacrificing the efficiency of the chiller with the smallest cooling adoption of chiller plant configuration #5, which showed an energy consumption of capacity. Table 11 shows the energy consumption and average COP values of all the chiller 13,882.52 kWh and an average COP of 2.78. plant options. The results reveal that the best configuration was chiller plant configuration • The implementation of the proposed optimization approaches suggested that the #1 (i.e., an asymmetric chiller plant with a cooling distribution of 33/67% and safety factor best option would be the adoption of chiller plant configuration #1 (asymmetric of 10.2%). configuration, chiller cooling capacity distribution of 33/67%, safety factor of 10.2%), which showed an energy consumption of 10,446.25 kWh and an average COP of 4.44. Table 11. Energy consumption and average COP values of chiller plant options. The proposed optimization procedures led the chillers operating in the investigated Chiller Plant Configuration EnergyofConsumption hotel to energy savings about 24.8% (kWh) and an increment in theAverage averageCOP COP by about Chiller plant #1 10,446.251 4.491 59.7% compared with chiller plant configuration #5 selected by the traditional load-based sequencing methodology. In10,681.532 addition, the results obtained supported the adoption of asymChiller plant #2 4.312 metric configurations rather10,696.964 than symmetric arrangements. In particular, Chiller plant #3 4.304it was observed that chiller plant configuration #5, which featured the best-performing arrangement in the Chiller plant #4 10,596.201 4.481 energy analysis carried out under traditional staging and the cooling distribution recomChiller plant #5 11,953.838 3.872 mended by the Cuban standard NC 220-3:2009 [44] (a requirement 3.991 for building design Chiller plant #6 11,707.874 companies), was actually the one with the worst energy performance after implementing the optimization procedures (Figure 10). However, the main conclusion of this research Considering that the GA tool provided an approximated result, three runs of the prois that the use of the proposed approaches prevents engineers from making an incorrect gram were carried out to verify the results of the OCL and OCS optimization procedures. decision regarding the chiller plant to be installed in a building. It is very important to The results obtained were corroborated using the relative standard deviation (RSD). Table keep in mind that in the design phase, it is not only enough to consider the installation of 12 reveals an RSD of less than 1%, proving the existence of a great fit in the control paramthe most advanced system supported by an efficient control system. It is also necessary to eters of the GA. Energies 2023, 16, 3782 Energy Consumption (kWh) 15,000 14,000 13,000 Conventional staging principle Co-desing principle staging 12,000 11,000 1 2 3 4 5 6 Chillers plant configuration number (#) (a) Coeficient of Performance (COP) bution recommended by the Cuban standard NC 220-3:2009 [44] (a requirement for building design companies), was actually the one with the worst energy performance after implementing the optimization procedures (Figure 10). However, the main conclusion of this research is that the use of the proposed approaches prevents engineers from making an 20 of 23 imincorrect decision regarding the chiller plant to be installed in a building. It is very portant to keep in mind that in the design phase, it is not only enough to consider the installation of the most advanced system supported by an efficient control system. It is analyze the future conditions as close to reality as as possible, that the also necessary to operating analyze the future operating conditions close tosoreality as design possible, so and of the are inofline each other. thatthe theoperation design and theproject operation thewith project are in line with each other. 5.0 4.5 4.0 3.5 Conventional staging principle Co-desing staging principle 3.0 2.5 2.0 1 2 3 4 5 6 Chiller plant configuration number(#) (b) Figure 10. Comparative analysis of the results obtained by different energy simulation approaches. Figure 10. Comparative analysis of the results obtained by different energy simulation approaches. (a) Energy consumption. (b) COP. (a) Energy consumption. (b) COP. Conclusions 5.5.Conclusions Implementing energy-efficient chillers can significantly help in the fight against global warming. To promote the adoption of highly performing chillers for hotel facilities, this research studied the energy impact of the selection of the most appropriate chiller configuration for a Cuban hotel. Six different chiller plant combinations and two different approaches to evaluating their energy performance have been considered. The first methodology was based on the traditional staging approach that relies on the on/off principle, whereas the second procedure used a co-design principle and involved the solution to a mathematical optimization problem. The two selected optimization procedures were optimal chiller loading (OCL) and optimal chiller sequencing (OCS). The energy simulation using the two approaches in the earlier chiller plant design stage for buildings demonstrated the following: As regards the traditional principle of chiller on/off staging, the chiller plant with the best energy performance was the solution, featuring a symmetric configuration, chiller cooling capacity distribution of 50/50%, and a safety factor of 11.7%. As regards the co-design approach with staging using OCL and OCS optimization procedures, the best energy performance was provided by the solution involving an asymmetric configuration, chiller plant #1 (featuring an asymmetric configuration, chiller cooling capacity distribution of 33/67%, and a safety factor of 10.2%), showing an energy consumption of 10,446.25 kWh and an average COP of 4.44. The approach based on mathematical optimization offers a reduction in energy consumption by 24.8% and an increase in COP by 59.7%. Therefore, it can be concluded that both analyzed approaches lead to different results that imply selecting different configurations as optimal. However, in terms of practical issues, it is known that for the case study analyzed, the implementation of an automatic control system for the hotel air conditioning system was proposed. Therefore, the chiller plant that is best adapted to the future operation of the system was chosen through the co-design methodology. An erroneous selection of the chiller plant configuration can result in significant energy consumption, environmental impact, and economic losses. It is also highly recommended that different thermal load profiles are considered due to the diversity of cooling load demand scenarios that hotels face during the exploitation phase, and the energy performance analysis of the proposed chiller plant should be set under this premise. Energies 2023, 16, 3782 21 of 23 However, the present research still has limitations that will be addressed in the future, such as the extension of the energy analysis to the rest of the secondary circuits of the chiller plant. In this way, it will be possible to determine more accurately the impact of the operating strategies on the whole chiller plant system. Another aspect that can enhance the analysis is the establishment of the OCS analysis through other approaches such as chilled-water return temperature-based (T-based) sequencing control or bypass flow-based (F-based) sequencing control, in which, although the energy savings are lower, they do not involve on/off chiller operating regimes, thus preserving the technology better. Author Contributions: Conceptualization, Y.D.T. and P.G.; methodology, M.T.d.T.; software, Y.D.T., R.R.C. and J.G.S.; validation, Y.D.T., P.G. and R.R.C.; formal analysis, M.T.d.T. and H.H.H.; investigation, Y.D.T.; resources, Y.D.T., R.R.C. and J.G.S.; data curation, Y.D.T.; writing—original draft preparation, Y.D.T.; writing—review and editing, P.G., H.H.H. and J.I.S.O.; visualization, P.G.; supervision, P.G., H.H.H. and J.I.S.O.; project administration, H.H.H.; funding acquisition, P.G. and H.H.H. All authors have read and agreed to the published version of the manuscript. Funding: This research received no external funding. Data Availability Statement: The data presented in this study are available in: [19,20,25]. Conflicts of Interest: The authors declare no conflict of interest. Nomenclatures Annex 1: Nomenclature a0 , a1 , a2 Correlation coefficients of the black box model of electrical power BLR Building load ratio CI Specific consumption index CLi Building cooling load for each interval of time i (kW) Comb Combinations of chiller plant COP Coefficient of performance cp Specific heat at constant pressure of water at 7 ◦ C (kJ/(Kg·K)) GA Genetic algorithm Hdo Occupied room indicator ki Simulation scenario ṁ Chilled-water mass flow (Kg/s) nch Total of chiller selected in each chiller plant OCL Optimal chiller loading OCS Optimal chiller sequencing Pch Power consumption of chiller (kW) PLR Partial load ratio Qch Cooling load for the chiller (kW) Qcl Total cooling load (kW) Qchstd Cooling capacity of the chiller at standard conditions according to manufacturer (kW) Qcho Cooling capacity of the reference chiller (kW) Sj off Stage off threshold Sj on Stage on threshold Tc air,in Condenser air inlet temperature (◦ C) Tc hw,s Chiller water supply temperature (◦ C) Tc hw,r Chiller water return temperature (◦ C) x0 , x1 , x2 Correlation coefficients of the black box model of nominal cooling capacity Subscripts ch Chiller water i ith max Maximum min Minimum c Condenser in Inlet s Supply r Return Energies 2023, 16, 3782 22 of 23 References 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. Fang, X.; Jin, X.; Du, Z.; Wang, Y.; Shi, W. Evaluation of the design of chilled water system based on the optimal operation performance of equipments. Appl. Therm. Eng. 2017, 113, 435–448. [CrossRef] ASHRAE. ASHRAE Fundamentals Handbook; ASHRAE: Peachtree Corners, GA, USA, 2017; ISBN 10: 1939200598. Díaz Torres, Y.; Álvarez Guerra Plasencia, A.; Viego Felipe, P.; Crespo Sanchez, G.; Diaz Gonzalez, M. Chiller plant design. Review of the aspects that involve its efficient design. Ing. Energética 2020, 41, e1711. Taylor, S. Fundamentals of Design and Control of Central Chilled-Water Plans (I-P); Atlanta ASHRAE: Peachtree Corners, GA, USA, 2017; ISBN 978-1-939200-67-9. Cheng, Q.; Wang, S.; Yan, C. Sequential Monte Carlo simulation for robust optimal design of cooling water system with quantified uncertainty and reliability. Energy 2016, 118, 489–501. [CrossRef] Yan, C.; Cheng, Q.; Cai, H. Life-Cycle optimization of a chiller plant with quantified analysis of uncertainty and reliability in commercial buildings. Appl. Sci. 2019, 9, 1548. [CrossRef] Huang, P.; Huang, G.; Augenbroe, G.; Li, S. Optimal configuration of multiple-chiller plants under cooling load uncertainty for different climate effects and building types. Energy Build. 2018, 158, 684–697. [CrossRef] Li, H.; Wang, S.; Xiao, F. Probabilistic optimal design and on-site adaptive commissioning of building air-conditioning systems concerning uncertainties. Energy Procedia 2019, 158, 2725–2730. [CrossRef] Sun, Y.; Wang, S.; Huang, G. Chiller sequencing control with enhanced robustness for energy efficient operation. Energy Build. 2009, 41, 1246–1255. [CrossRef] Gang, W.; Wang, S.; Xiao, F.; Gao, D.-c. Robust optimal design cooling systems considering cooling load uncertainty and equipment reliability. Appl. Energy 2015, 159, 265–275. [CrossRef] Gang, W.; Wang, S.; Yan, C.; Xiao, F. Robust optimal design of building cooling systems concerning uncertainties using mini-max regret theory. Sci. Technol. Built Environ. 2015, 21, 789–799. [CrossRef] Cheng, Q.; Yan, C.; Wang, S. Robust Optimal Design of Chiller Plants Based on Cooling Load Distribution. Energy Procedia 2015, 75, 1354–1359. [CrossRef] Niu, J.; Tian, Z.; Lu, Y.; Zhao, H.; Lan, B. A robust optimization model for designing the building cooling source under cooling load uncertainty. Appl. Energy 2019, 241, 390–403. [CrossRef] Chen, Y.; Yang, C.; Pan, X.; Yan, D. Desing and operation optimization of multi-chiller plants based on energy performance simulation. Energy Build. 2020, 222, 110100. [CrossRef] Bhattacharya, A.; Vasisht, S.; Adetola, V.; Huang, S.; Sharma, H.; Vrabie, D. Control co-design of commercial building chiller plant using Bayesian optimization. Energy Build. 2021, 246, 111077. [CrossRef] Garcia-Sanz, M. Control co-design: An engineering game changer. Adv. Control. Appl. Eng. Ind. Syst. 2019, 1, e18. [CrossRef] Rampazzo, M. A static moving boundary modelling approach for simulation of indirect evaporative free cooling systems. Appl. Energy 2019, 250, 1719–1728. Masburah, R.; Sinha, S.; Lochan, R.; Dey, S.; Zhu, Q. Co-Designing Intelligent Control of Building HVAC and Microgrids. DSD 2021: Euromicro Conference on Digital System Design. 2021. Available online: https://ieeexplore.ieee.org/document/9556332 (accessed on 20 December 2021). Díaz-Torres, Y.; Calvo, R.; Herrera, H.; Gomez, S.; Guerra, M.; Silva, J. Procedure to obtain the optimal distribution cooling capacity of an air-condensed chiller plant for a hotel facility conceptual design. Energy Rep. 2021, 7, 622–637. [CrossRef] Díaz Torres, Y.R.; Hernandez, H.; Torres, M.; Alvarez-Guerra, M.; Gullo, P.; Silva, I. Statistical- mathematical procedure to determine the cooling distribution of a chiller plant. Energy Rep. 2022, 8, 512–526. [CrossRef] Thangavelu, S.R.; Myat, A.; Khambadkone, A. Energy optimization methodology of multi-chiller plant in commercial buildings. Energy 2017, 123, 64–76. [CrossRef] Díaz-Torres, Y.; Valdivia-Noda, Y.; Monteagudo-Yanes, J.P.; Miranda-Torres, Y. Application of building energy simulation in the validation of operational strategies of HVAC systems on a tropical hotel. Ing. Mecánica 2017, 20, 31–38. TRNSYS 16; Solar Energy Laboratory, University of Wisconsin-Madison: Madison, WI, USA, 2006; Volume 5, Mathematical Reference. ASHRAE 55; Thermal Environmental Conditions for Human Occupancy. ASHRAE: Washington, DC, USA, 2010. Díaz-Torres, Y.; Santana-Justiz, M.; Francisco-Pedro, G.J.; Daniel-Álvarez, L.; Miranda-Torres, Y.; Guerra-Plascencia, M.Á. Methodology for the preparation and selection of black box mathematical models for the energy simulation of screw type chillers. Ing. Mecánica 2020, 23, e612. White, H. A heteroskedasticity-consistent covariance matrix estimator and a direct test for heteroskedasticity. Econometrica 1980, 48, 817–838. [CrossRef] Breusch, T.S.; Pagan, A. The Review of Economic Studies. In Econometrics Issue; Oxford University Press: Oxford, UK, 1980; Volume 47, pp. 239–253. Jarque, C.M.; Bera, A.K. A test for normality of observations and regression residuals. Int. Stat. Rev. 1987, 55, 163–172. [CrossRef] Catrini, P.; Piacentino, A.; Cardona, F.; Ciulla, G. Exergoeconomic analysis as support in decision-making for the design and operation of multiple chiller in air conditioning applications. Energy Convers. Manag. 2020, 220, 113051. [CrossRef] Teimourzadeh, H.; Jabari, F.; Mohammadi-Ivatloo, B. An augmented group search optimization algorithm for optimal cooling-load dispatch in multi-chiller plants. Comput. Electr. Eng. 2020, 85, 106434. [CrossRef] Energies 2023, 16, 3782 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 23 of 23 Ho, W.T.; Yu, F.W. Improved model and optimization for the energy performance of chiller syste with diverse component staging. Energy 2021, 217, 119376. [CrossRef] Chang, Y.-C.; Lin, F.-A.; Lin, C.H. Optimal Chillers sequencing by branch and bound method for saving energy. Energy Convers. Manag. 2005, 46, 2158–2172. [CrossRef] Witkoswski, K.; Haering, P.; Seidelt, S.; Pini, N. Role of thermal technologies for enhancing flexibility in multi-energy systems through sector coupling: Technical suitability and expected developments. IET Energy Syst. Integr. 2020, 2, 69–79. [CrossRef] Acerbi, A.; Rampazzo, M.; De Nicolao, G. Na exact algorithm for the optimal chiller loading problem and its application to the OptimalChiller Sequencing Problem. Energies 2020, 13, 6372. [CrossRef] Satué, M.; Arahal, M.; Acedo, L.; Ortega, M. Economic versus energetic model predictive control of a cold production plant with thermal energy storage. Appl. Therm. Eng. 2022, 210, 118309. [CrossRef] Qiu, S.; Zhang, W.; Li, J.; Chen, J.; Li, Z.; Li, Z. A chiller operation strategy based on multiple-objetive optimization. Energy Procedia 2018, 152, 318–323. [CrossRef] Zheng, Z.; Li, J.; Duan, P. Optimal chiller loading by improved artificial fish swarm algorithm for energy saving. Math. Comput. Simul. 2019, 155, 227–243. [CrossRef] Norma Cubana NC 217: 2002; Climatización. Especificaciones de Diseños. Temperaturas en Locales Climatizados. Norma Cubana: Havana, Cuba, 2002. Guerra, M.A.; Cabello, J.; Sousa, V.; Sagastume, A.; Monteagudo, Y.; Lapido, M.; Lara, B. Forescasting and control of the electricity consumption in hotels. In Proceedings of the IX International Conference for Renewable Energy, Energy Saving and Energy Education (CIER 2017); Centro de Estudio de Tecnologias Energeticas Renovables CETER: Havana, Cuba, 2017; p. 1CD-ROM. Valdivia, Y.; Álvarez Guerra, M.; Gómez, J.; Luc, H.; Vandecasteele, C. Sanitary hot water production from heat recovery in hotel buildings in Cuba. Ing. Energética 2019, 40, 234–244. E-View 12 Student Version. Available online: https://www.eviews.com/home.html (accessed on 14 February 2023). METEONORM, 2020. Global Meteorological Database for Engineers, Planners and Education. Available online: www.meteonorm. com/pages/en/meteonorm.php (accessed on 10 July 2022). MATLAB Simulink. 2018. Available online: https://www.mathworks.com/help/simulink/release-notes-R2018a.html (accessed on 14 February 2023). Norma Cubana NC 220-3:2009; Edificaciones-Requisitos de diseño para la eficiencia energética-Parte 3: Sistemas y Equipamiento de Calefacción, Ventilación y Aire Acondicionado. Oficina Nacional de Normalización (NC): Havana, Cuba, 2009. Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.