Summary of Earthing Design
1
Project Name
2
Site Address
New Project
3
Standard
4
Earthing System Installation(Common, Total,
Individual)
5
System Earthing Method (TN, TT, IT)
6
Resistivity (Ωm)
7
Surface Material(Concrete, Epoxy, Etc)
8
Crushed rock resistivity (Ωm)
4000
9
Thickness of crushed rock surfacing (m)
0.15
10
Bus Impedance(% Z1, % Z2)
11
Bus Impedance(% Z0)
12
Line Impedance(% Z1, % Z2)
13
Line Impedance(% Z0)
14
Length(km)
10
15
Maximum ground fault current (A)
634
16
Fault Current Division Factor Sf
0.6
17
Grid Current (A)
380.4
18
Fault duration (s)
0.15
19
Conductor Material and Size
20
Rod Material, Size, Number
21
Simulation Program
22
Tolerable Touch Voltage - 50 kg person (V)
1687.05
23
Estimated Mesh Voltage by IEEE STD 80 (V)
0
24
Evaluation
Et50 > Em
For Em the Design is OK
25
Grounding resistance Sverak equation, IEEE STD
80 2013(Ω)
0
26
Grid resistance by Tester Rg(Ω)
5
IEEE 80
50
Report
Page 2 of 13
Simplified Analysis Results
No
Symbol
1
-
Earthing System Installation(Common, Total, Individual)
2
-
System Earthing Method (TN, TT, IT)
3
-
Conductor Material and Size
4
-
Rod Material, Size, Number
5
If
Maximum ground fault current (A)
6
IG
Grid Current (A)
0
7
Sf
Fault Current Division Factor Sf
0
8
Cp
System Expanding factor
1.0
9
ρ
Resistivity (Ωm)
50
10
ρs
Crushed rock resistivity (Ωm)
4000
11
hs
Thickness of crushed rock surfacing (m)
0.15
12
tf
Fault duration (s)
0.15
13
h
Depth of ground grid conductors (m)
0.6
14
n
Geometric factor
15
d
Diameter grid conductors (m)
16
D
Spacing between parallel conductors (m)
5
17
LR
Total length of ground rods(m)
0
18
Lx
Maximum length of grid conductors in x direction (m)
0
19
Ly
Maximum length of grid conductors in y direction (m)
0
20
Ta
Ambient Temperature (°C)
32
21
Tm
Fusing temperature Tm (°C)
0
22
Rg
Grounding resistance Sverak equation, IEEE STD 80 2013(Ω)
0
23
EPR
GPR Sverak resistance, IEEE STD 80 2013(V)
0
24
Em
Estimated Mesh Voltage by IEEE STD 80 (V)
0
25
Es
Estimated Step Voltage by IEEE STD 80 (V)
0
26
Et70
Tolerable Touch Voltage - 70 kg person (V)
2283.34
27
Et50
Tolerable Touch Voltage - 50 kg person (V)
1687.05
28
Properties
Value
634
0
0.01
Evaluation Et50 > Em
For Em the Design is OK
29
Es70
Tolerable Step Voltage - 70 kg person (V)
7917.23
30
Es50
Tolerable Step Voltage - 50 kg person (V)
5849.67
31
Evaluation Es50 > Es
For Es the Design is OK
Report
Page 3 of 13
Grid
Report
Page 4 of 13
Grid 3D
Report
Page 5 of 13
Touch Voltage (V)
Report
Page 6 of 13
Step Voltage (V)
Report
Page 7 of 13
Touch Voltage 2D (V)
Report
Page 8 of 13
Step Voltage 2D (V)
Resistivity (Ωm)
Properties
Value
No
Symbol
1
ROMAX
Maximum resistivity (Ωm)
0
2
ROMIN
Minimum resistivity (Ωm)
0
3
ROAVG
Average of resistivity (Ωm)
0
4
ROSTDEV
Standard deviation of resistivity (Ωm)
0
5
ROSTDEVP
Standard deviation of resistivity (%)
0
6
RO70
Resistivity with 70% probability of not being
exceeded (Ωm)
0
7
(ROMAX
+ROMIN)/2
Average of resistivity between maximum and
minimum values (Ωm)
0
8
RO1
Upper layer resistivity (Ωm)
0
9
RO2
Lower layer resistivity (Ωm)
0
10
h
Upper layer thickness (m)
0
Report
Page 9 of 13
Conductors
Name
X1(m)
Y1(m)
X2(m)
Y2(m)
h(m)
R(m)
A(mm²)
1
0.00
0.00
5.00
0.00
0.75
0.004635
67.4
New Conductor
0.00
2.50
5.00
2.50
0.75
0.0049
70
New Conductor
0.00
5.00
5.00
5.00
0.75
0.0049
70
New Conductor
0.00
0.00
0.00
5.00
0.75
0.0049
70
New Conductor
2.50
0.00
2.50
5.00
0.75
0.0049
70
New Conductor
2.50
0.00
2.50
5.00
0.75
0.0049
70
New Conductor
5.00
0.00
5.00
5.00
0.75
0.0049
70
Rods
Name
X(m)
Y(m)
L(m)
h(m)
R(m)
D(mm)
New Rod
0.00
0.00
2.4
0.75
0.007
14
New Rod
5.00
0.00
2.4
0.75
0.007
14
New Rod
0.00
5.00
2.4
0.75
0.007
14
New Rod
5.00
5.00
2.4
0.75
0.007
14
Conductor Selection
Description
Material conductivity (% IACS)
αr factor at 20 °C (1/°C)
K0 at 0 °C(0°C)
Fusing temperature Tm (°C)
Copper, annealed soft-drawn
100
0.00393
234
0
Report
Page 10 of 13
Resistivity at 20 °C ρr (μΩ cm)
1.72
Thermal capacity TCAP [J/(cm3 °C)]
3.42
RMS Current (kA)
2.5
Ambient Temperature (°C)
32
Duration of Current (s)
0.5
Mínimal Cross Section (mm²)
0
Conductor Size Selection (mm²)
0
Report
Page 11 of 13
Grid Profiles
Touch Voltage Profiles
Report
Page 12 of 13
Step Voltage Profiles
Results
No
Symbol
Properties
1
IF
Maximum ground fault current (A)
2
IG
Grid Current (A)
3
β
Remote Current Contribution (%)
60
4
ρ
Resistivity (Ωm)
50
5
ρs
Crushed rock resistivity (Ωm)
6
hs
Thickness of crushed rock surfacing (m)
0.15
Value
634
380.4
4000
7
Cs
Surface layer derating factor
0.772
8
tf
Fault duration (s)
0.15
9
f
System Frequency (Hz)
10
Sf
Fault Current Division Factor Sf
60
0.6
1000
11
Zt
Body Impedance (Ω)
12
Lc
Total length of the conductor (m)
35
13
NR
Total number of rods
4
14
Rg
Grounding grid resistance (Ω)
3.404
Ground Potenctial Rise GPR (V)
1294.94
15
EPR
Report
Page 13 of 13
16
Et70
Tolerable Touch Voltage - 70 kg person (V)
2283.34
17
Et50
Tolerable Touch Voltage - 50 kg person (V)
1687.05
18
Em
Mesh Voltage (V)
374.23
19
Evaluation Et50 > Em
For Em the Design is OK
20
Es70
Tolerable Step Voltage - 70 kg person (V)
7917.23
21
Es50
Tolerable Step Voltage - 50 kg person (V)
5849.67
22
Es
Step Voltage (V)
190.69
23
Evaluation Es50 > Es
For Es the Design is OK
Remarks