OVF 5.7-21 Rev. 2
Dated: 09/27/2019
CERTIFICATE OF COMPLIANCE
Certifies that the following products:
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
8
PCS
SERIAL NUMBERS: 2310038-001 THRU 2310038-008
TECNOVAL, LLC
A 115 - (L-2)
N/A
10/03/2023
Manufactured for buyer:
Purchase Order #:
Customer Part / Rev #:
Customer PO Date:
Were manufactured in accordance with contractual terms and the following standards and
specifications:
•
OMNI PN#
3907-00C-996153B-G
________________________
Geo George
Quality Manager
Page 1 of 1
4520 Chandler Road, Muskogee, OK – 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-001
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2650
PSI
17 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
2:35:00 PM
11/08/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:00:00 AM
11/09/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/09/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-002
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2675
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:00:00 PM
11/08/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:00:00 AM
11/09/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/09/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-003
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2675
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:10:00 PM
11/08/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:10:00 AM
11/09/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/09/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-004
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2700
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:15:00 PM
11/08/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:15:00 AM
11/09/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/09/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-005
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2675
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:25:00 PM
11/08/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:25:00 AM
11/09/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/09/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-006
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2690
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:30:00 PM
11/08/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:30:00 AM
11/09/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/09/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-007
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
150 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2700
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:35:00 PM
11/09/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:35:00 AM
11/10/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/10/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105
OVF 5.7-49 Rev. 2
Dated:010/02/2018
ESD PRESSURE TEST
DESCRIPTION:
WORK
3907-00C-996153B-G
ASSEMBLY #
2310038-008
ORDER #
MODEL EX HYDRAULIC CONTROLLER WITH MANUAL PUMP & COVER
HPILOT 500-1500 PSI (SET 1,400 PSI), LPILOT 50-450 PSI (SET 200 PSI),
MOUNT: HORIZONTAL, HX-30, MOP: 3,000 PSI, SET PRESSURE: 2,700 PSI
OPTIONS: EXTERNAL GAUGE, HI/LOW PILOT SYSTEM, NO LIMIT SWITCH ASSY
SYSTEM HAZARDOUS AREA CERTIFICATION: CL1 DIV2 UL/CSA
SOLENOID: NONE, RESERVOIR: 0.5 GAL, PUMP: MANUAL 0.55 CUIN DISP,
FILL KIT # 3907-0000-00A (INCLUDED)
WORK INSTRUCTION#
OWI-A400-5.7
UNIT DATA
RATED WORKING PRESSURE
3,000 PSI
MANUAL
YES
PILOT 1
N/A PSI
PILOT 2
N/A PSI
N/A
SOLENOID
PILOT 3
N/A PSI
PILOT 4
N/A PSI
FILTERED HI-TEK HVI/AW 032 HYDRAULIC OIL
TESTING FLUID
UNIT SETUP
ACCUMULATOR CHARGE PRESSURE
1,800 PSI
KICK DOWN SETTING
N/A PSI
HIGH PRESSURE RELIEF SETTING
N/A PSI
REGULATOR SETTING
160 PSI
PRESSURE TEST
TEST
PRESSURE HOLD
START
HOLD
PRESSURE
2700
PSI
2700
PSI
16 HOURS
PRESSURE HOLD END
TEST 1
TEST 2
PASS / FAIL
PASS / FAIL
MANUAL
PASS
PASS
SOLENOID
N/A
N/A
PILOT
N/A
N/A
TEST TYPE
TECHNICIAN SIGNATURE: J. Settlemyre
TIME
TEST RESULTS
3:30:00 PM
11/09/2023
NO VISIBLE SIGNS OF LEAKAGE OR OTHER RELEVANT INDICATIONS UNDER
THE TEST PRESSURE DURING EACH HOLDING PERIOD
7:30:00 AM
11/10/2023
FUNCTIONAL TEST
PRESSURE THE UNIT UP TO THE RATED WORKING PRESSURE FOR EACH
TEST. ALLOW PRESSURE TO STABILIZE BEFORE EACH TEST.
DATE: 11/10/2023
4520 CHANDLER ROAD, MUSKOGEE, OK - 74403
Tel: 918-687-6100 Fax: 918-687-6105