Subido por facardosove

ANEXO A Column Assemblies UL 1700

Anuncio
COLUMN ASSEMBLIES
UL 1709 RAPID TEMPERATURE RISE RATINGS
PYROCRETE® 241
The temperature of the fire in which rapid temperature rise
ratings are derived, reaches 2000oF within five minutes of
exposure. The fire temperature is maintained at this level
throughout the rating period. This fire exposure was developed to provide a means to evaluate fire resistive assemblies
intended for use in areas which may develop fire temperatures at a faster rate than assemblies tested under Standard
UL 263. Systems classified in this category are also investigated to determine their ability to retain a degree of fire
resistance when exposed to various environments. Materials are subjected to standardized environmental tests which
include simulated aging, ultraviolet light, salt spray exposure, the cycling effects of water freezing temperatures /
dryness and exposure to air containing carbon dioxide and
sulfur dioxide.
U.L. DESIGN XR-702
U.L. DESIGN XR-701
Tie Wire
PYROCRETE® 241
PYROCRETE 241
Column (W10 x 49)
Column (W10 x 49)
3.4 lbs. Galvanized
Metal Lath
3.4 lbs. Galvanized
Metal Lath
Rating
3/4
1
1-1/2
2
3
4
Rating
Thickness
1/2 in.
(13mm)
11/16 in. (17mm)
15/16 in. (24mm)
1-1/8 in.
(29mm)
1-3/8 in.
(35mm)
1-9/16 in. (40mm)
Thickness
5/8
11/16 in.
7/8 in.
1 in.
1-1/8 in.
1-1/4 in.
1-1/2 in.
3/4
1
1-1/2
2
2-1/2
3
4
(16mm)
(17mm)
(22mm)
(25mm)
(29mm)
(32mm)
(38mm)
BULKHEAD RATINGS
PYROCRETE 241
Steel Spring Washer
RATING
A-30
A-60
H-30
H-60
H-120
16mm
25mm
15mm
23mm
33mm
FIRTO
(5/8 in.)
(1 in.)
(9/16 in.)
(15/16 in.)
(1-1/4 in.)
LPG TANKS fire protected coatings
Steel Pin
Steel Bulkhead
3/4 Galvanized Metal Lath
DET NORSKE VERITAS
14mm
(9/16 in.)
20mm
(13/16 in.)
15mm
(9/16 in.)
21mm
(13/16 in.)
33mm
(1-1/4 in.)
LLOYD'S REGISTER
16mm
(5/18 in.)
25mm
(1 in.)
15mm
(9/16 in.)
23mm
(15/16 in.)
33mm
(1-1/4 in.)
VESSEL WALL
F.M. APPROVED
3.4 lbs Galvanized
Metal Lath Overall
PYROCRETE 241
Thickness--3/8 in. (10mm) Wet
NOTE: Consult Carboline Company for topcoat recommendation.
June 98 Replaces Jan 98
Section AA
Page 10 of 10
Descargar