C O L U M N A S C E N T R A L E S D A T O S R E S U L T A D O S

Anuncio
COLUMNAS
CENTRALES
PROYECTISTA............................................... : ING. DAVID ADRIAN RUBIO RIVERA
Hoja
1
de
1 _
3
PROYECTO..................................................... : TANQUE SUPERFICIAL DE 3,000 m
FECHA............................................................. : OCTUBRE DEL 2000
DATOS
F'C DEL CONCRETO...................................... :
250.00 (Kg/cm2)
2
MOM. CENTRO
"Y" POR C. ACC................ : 0.00
Fy DEL ACERO DE REFUERZO.................... :
4,200.00 (Kg/cm )
FACTOR DE ESBELTEZ (Kx)......................... : 1.00
Fy DE LOS ESTRIBOS.................................... :
4,200.00 (Kg/cm2)
FACTOR DE ESBELTEZ (Ky)......................... : 1.00
LADO "X" DE LA COLUMNA........................... :
30.00 (cm)
TRABE SUPERIOR IZQUIERDA "X"............... : 4.00
LADO "Y" DE LA COLUMNA........................... :
30.00 (cm)
TRABE SUPERIOR DERECHA "X"................. : 4.00
LONG. LIBRE EN EL SENTIDO "X"................ :
405.00 (cm)
TRABE INFERIOR IZQUIERDA "X"................ : 2.00
LONG. LIBRE EN EL SENTIDO "Y"................ :
405.00 (cm)
TRABE INFERIOR DERECHA "X".................. : 2.00
(Kg-m)
VARRILLA PRINCIPAL No.............................. :
5.00
COLUMNA SUPERIOR "X"............................. : 0.00
CARGA VIVA................................................... :
5,356.00 (Kg)
COLUMNA DISEÑO "X".................................. : 1.00
CARGA MUERTA............................................ :
12,875.00 (Kg)
COLUMNA INFERIOR "X"............................... : 0.00
CARGA ACCIDENTAL.................................... :
1,250.00 (Kg)
TRABE SUPERIOR IZQUIERDA "Y"............... : 4.00
CORTANTE POR CARGA VERT.................... :
50.00 (Kg)
TRABE SUPERIOR DERECHA "Y"................. : 4.00
CORTANTE POR CARGA ACCIDENTAL....... :
0.00 (Kg)
TRABE INFERIOR IZQUIERDA "Y"................ : 2.00
RECUBRIMIENTO (4 cm MIN)........................ :
4.00 (cm)
TRABE INFERIOR DERECHA "Y".................. : 2.00
MOM. SUPERIOR "X" POR C. VERT............ :
245.00 (Kg-m)
COLUMNA SUPERIOR "Y"............................. : 0.00
MOM. INFERIOR "X" POR C. VERT............. :
185.00 (Kg-m)
COLUMNA DISEÑO "Y".................................. : 1.00
"X" POR C. VERT.............. :
0.00 (Kg-m)
COLUMNA INFERIOR "Y"............................... : 0.00
MOM. SUPERIOR "Y" POR C. VERT............ :
140.00 (Kg-m)
As ACEREO PROPUESTO............................. : 8.00
(cm2)
MOM. INFERIOR "Y" POR C. VERT............. :
0.00 (Kg-m)
MODULO DE ELAST. CONCRETO................ : 237,170.80
(Kg/cm2)
MOM. CENTRO
"Y" POR C. VERT.............. :
0.00 (Kg-m)
SUMA CARGAS TOTAL COLUMNAS............ : 315,000.00
(Kg)
MOM. SUPERIOR "X" POR C. ACC.............. :
0.00 (Kg-m)
NUM. DE COLUMNAS EN ESTE PISO.......... : 21.00
MOM. CENTRO
MOM. INFERIOR "X" POR C. ACC............... :
0.00 (Kg-m)
INTEMPERISMO S/N ?................................... : N
MOM. CENTRO
"X" POR C. ACC................ :
0.00 (Kg-m)
CONTRAVENTEO EN "X" S/N?...................... : N
MOM. SUPERIOR "Y" POR C. ACC.............. :
0.00 (Kg-m)
CONTRAVENTEO EN "Y" S/N?...................... : N
MOM. INFERIOR "Y" POR C. ACC............... :
0.00 (Kg-m)
SISMO (M)ODERADO O (E)LEVADO............. : M
RESULTADOS
RELACIÓN ESF. ACT./PERM. : 0.39
LADO "X" DE LA COLUMNA (m)............. :
30.000
LADO "Y" DE LA COLUMNA (m)............. :
30.000
ACERO PRINCIPAL 4 VARRILLAS No. 5 REPARTIDAS EN LAS CUATRO CARAS
ESTRIBOS No. 3 @ 13 cm
HA = 0 cm
HB = 57 cm
ESTRIBOS No. 3 @ 25 cm
HA = 67 cm
HB = 338 cm
ESTRIBOS No. 3 @ 13 cm
HA = 338 cm
HB = 405 cm
FACTOR AMPLIACIÓN SENTIDO "X".... :
1.360
FACTOR AMPLIACIÓN SENTIDO "Y".... :
1.360
NOTA : EL PRIMER ESTRIBO SE COLOCARÁ A NO MÁS DE 6 cm
LOS ESTRIBOS SE ESPACIARÁN A 13 cm EN EL TRASLAPE DE VARILLAS