FALLA EN BORNES DE BAJA TENSION NODO: BusTCM TENSION

Anuncio
FALLA EN SISTEMA DC
NODO: VARIOS
NOTA:
TENSION: 600V
FALLA EN SISTEMA DC
NODO: VARIOS
SECUENCIA DE DISPAROS
TENSION: 100V
FALLA EN BORNES DEL CONTROLADOR EOLICO
SECUENCIA DE DISPAROS
NODO: 11
TIPO DE FALLA
t 1(s)
t 2(s)
BREAKER ID
TIPO DE FALLA
t 1(s)
t 2(s)
BREAKER ID
CORRIENTE Max DC
Icc = 10A
24
N/A
S280 CPPV#4.0
24
N/A
S280 CPPV#1.0
24
N/A
S280 CPPV#4.1
CORRIENTE Max DC
Icc = 10A
24
N/A
S280 CPPV#1.1
CORRIENTE Max DC
Icc = 20A
22.5
N/A
S280 CPPV#4.2
22.5
N/A
S280 CPPV#1.2
22.5
N/A
S280 CPPV#4.3
CORRIENTE Max DC
Icc = 20A
22.5
N/A
S280 CPPV#1.3
VER CURVA SISTEMA DC1
NOTA:
VER CURVA SISTEMA DC2
Se cumple de igual forma para CPPV#1, CPPV#2 y CPPV#3
Generador Eólico 1
2 kW
PFV CCPV#4
PFV CCPV#4.1
PFV CCPV#1
TENSION: 208V
SECUENCIA DE DISPAROS
t 1(s)
TIPO DE FALLA
TRIFASICA
Icc = 358 A
t 2(s)
BREAKER ID
<10xE-3
N/A
S203 GE3.1
10xE-3
11,9xE-3
S203 GE3
VER CURVA GGEN EOLICOS
Se cumple de igual forma para los tres generadores eólicos
Generador Eólico 2
2 kW
PFV CCPV#1.1
PFV CCPV#2
U2
100 MVAsc
Generador Eólico 3
2 kW
PFV CCPV#2.1
PFV CCPV#3
PFV CCPV#3.1
Fusible Dual
Ndc1
Ndc2
Ndc4
Ndc5
Ndc7
Ndc8
Ndc14
3#2 AL Trafo MT
3-1/C 2
Ndc13
FALLA EN ENTRADA A UG_AC
NODO: ENT CPPV#1 TENSION: 120V
2#10 USE-1
2#10 USE-2
dcF1
2#10 USE-3
dcF2
3#8 GE
3-1/C 8
2#10 USE-4
dcF3
2#10 USE-5
dcF4
2#10 USE-6
dcF5
S280 CCPV#4.1
S280 CCPV#1.0
S280 CCPV#2.0
Bus GE1
Ndc6
3#8 GE3
3-1/C 8
2#10 USE-8
dcF9
S280 CCPV#2.1
MONOFASICA
Icc = 1.5kA
S203 GE3
S280 CCPV#3.0
Bus GE3
S280 CCPV#3.1
Bus GE2
Ndc9
TIPO DE FALLA
dcF8
S203 GE2
S280 CCPV#1.1
Ndc3
2#10 USE-9
dcF6
S203 GE1
S280 CCPV#4.0
3#8 GE2
3-1/C 8
Ndc12
FALLA EN BORNES DE BAJA TENSION
NODO:
SECUENCIA DE DISPAROS
t 1(s)
BREAKER ID
10xE-3
N/A
S203 CPPV1.1
16xE-3
478xE-3
XT1-C TCM
16xE-3
640xE-3
XT1-C TRAFO
S280 CCPV#4.2
S280 CCPV#1.2
S280 CCPV#1 DPS
S280 CCPV#2.2
S280 CCPV#2 DPS
TENSION: 208V
SECUENCIA DE DISPAROS
t 1(s)
TIPO DE FALLA
t 2(s)
16xE-3
TRIFASICA
Icc = 2.37kA
N13
Bus2
3#2 Trafo
3-1/C 2
VER CURVA ENTRADA UG-AC
Se cumple de igual forma para S203 UG1.1/ IUG2.1/ IUG3.1
NOTA:
XT1-C Trafo
S280 CCPV#4 DPS
BusTCM
Trafo
30 kVA
t 2(s)
BREAKER ID
N/A
XT1-C TCM
16xE-3
N/A
XT1-C TRAFO
84.3xE-3
169xE-3
FUSIBLE DUAL
VER CURVA FUSIBLE-TOTALIZADOR BT
XT1-C DPS
S280 CCPV#3.2
S280 CCPV#3 DPS
DPS
3#8 GE1.1
3-1/C 8
3#2 TCM
3-1/C 2
3#8 GE3.1
3-1/C 8
3#8 GE2.1
3-1/C 8
2#10 USE PV1
2#10 USE PV2
TABLERO TCM
2#10 USE PV3
2#8 USE INV
XT1-C TCM
Bus3
Bus4
dcBus1
Bus5
BusTCM
S203 GE1.1
S280 CCPV#1.3
S203 DPSE1.1
S280 CCPV#4.3
S280 CCPV#2.3
S280 CCPV#3.3
S203 GE2.1
S203 GE3.1
S203 DPSE2.1
DPSE1.1
INVRED
S203 DPSE3.1
DPSE2.1
CS1
CE1
CS2
DPSE3.1
CE2
CS3
N11
XT1-B DPS1
CE3
S203 UG2.1
S203 UG1.1
Battery1
Battery2
BusINV
S203 UG3.1
DPS1
Battery3
S280 CPPV#1.5
S280 CPPV#2.5
S280 CCPV#1.4
FALLA EN TG CONECTADO A GENERADOR
NODO:
S280 CCPV#3.4
3#6 IUG#2.1
3#6 IUG#1.1
dcSW2
dcSW1
XT1-B TCM-TG
S280 CPPV#3.5
S280 CCPV#2.4
dcSW3
Open
Conexion
UG-AC1
Bus TG
3#6 IUG#3.1
3-1/C 6
3-1/C 6
3-1/C 6
Open
Open
Conexion a UG-AC#1 DC
Conexion a UG-AC#2 DC
Conexion a UG-AC#3 DC
Conexion UG-AC2
NOTA:
3#2 TCM4
3-1/C 2
TENSION: 208V
SECUENCIA DE DISPAROS
TIPO DE FALLA
t 1(s)
TRIFASICA
Icc = 674A
15xE-3
10,801
XT3-N-TG
1,019
22,793
t 2(s)
XT3-N-Gen.
BREAKER ID
VER CURVA TG MICRORED
3#6 INVRED
3-1/C 6
Conexion UG-AC#2
Conexion
Conexion UG-AC3
Conexion UG-AC#3
UG-AC#1
G. Diesel
37,4 kW
3#6 OUG#1
3-1/C 6
3#6 OUG#3
3-1/C 6
3#6 OUG#2
3-1/C 6
N26
N1
DPS2
XT3-N Gen.
TRMC
XT3-N DPS Gen
DPS GEN
SACEA1 DPS2
SACEA1 UG1.2
SACEA1 UG2.2
SACEA1 UG3.2
3#2 TCM2
3-1/C 2
3#2 Gen.2
3-1/C 2
SACEA1 INVRED
3-1/C 2
3#2 TCM3
TABLERO GENERAL
BusTCM2
TRTG
FALLA EN BORNES DE SALIDA UG-AC
NODO: SAL UG-AC#1 TENSION: 120V
TIPO DE FALLA
MONOFASICA
Icc = 1,465 kA
FALLA EN BUS TG ALIMENTADO DESDE MICRORRED
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
16xE-3
N/A
SACEA1-C UG1.2
16xE-3
N/A
SACEA1-C INVRED
7,112
22,979
SACEA1-C UG2.2
7,112
22,979
SACEA1-C UG3.2
NODO:
BREAKER ID
Bus TG
TENSION: 208V
TIPO DE FALLA
TRIFASICA
Icc = 1.90kA
VER CURVA SALIDA UG-AC
Se cumple de igual forma para UG-AC 1.2 / 2.2 /3.2.
NOTA:
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
15xE-3
N/A
16xE-3
N/A
SACEA1 INVRED
3,043
10,285
SACEA1 UG 1.2
3,043
10,285
SACEA1 UG 2.2
3,043
10,285
SACEA1 UG 3.2
NODO:
NODO:
Bus INV
TENSION: 208V
TIPO DE FALLA
TRIFÁSICA
Icc =1,447 kA
NOTA:
VER CURVA INVERSOR DE RED
TENSION: 208V
TRIFASICA
Icc = 1.52kA
VER CURVA TG - MICRORRED
BusTG
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
10xE-3
N/A
10xE-3
N/A
15xE-3
N/A
XT3-N-TG
16xE-3
N/A
SACEA1 INVRED
BREAKER ID
S203 BTS1
S203 BTS1.1
S203 DPS3
S203 BTS1.1
t 2(s)
NODO:
BREAKER ID
16xE-3
N/A
SACEA1-C INVRED
2,754
9,449
SACEA1-C UG1.2
2,754
9,449
SACEA1-C UG2.2
2,754
9,449
SACEA1-C UG3.2
S201 LO
S201 PR
S201 TA
S201 TM
S201 TT
2#8 IE
3-1/C 8
1#12 LO
3-1/C 12
1#10 PR
3-1/C 10
1#12 TA
3-1/C 12
1#12 TM
3-1/C 12
1#12 TT
3-1/C 12
N4
N5
Luz Obs.
1 kVA
Precal.
1 kVA
3#6 BTS
3-1/C 6
N10
TENSION: 208V
TIPO DE FALLA
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
BREAKER ID
N3
S203 BTS1
10xE-3
TRIFASICA
Icc = 647 A
NOTA:
N/A
S203 BTS1
10xE-3
N/A
S203 BTS1.1
15xE-3
11,236
XT3-N-TG
1,078
22,93
NODO:
XT3-N-Gen.
Ilum. Ext.
1 kVA
VER CURVA BTS2
N3
TENSION: 208V
TIPO DE FALLA
BIFASICA
Icc =998 A
t 1(s)
t 2(s)
10xE-3
N/A
S202 IE
15xE-3
N/A
XT3-N-TG
TENSION: 208V
TIPO DE FALLA
BIFASICA
Icc = 528 A
NOTA:
VER CURVA ILUM. EXTERIOR
N8
T. Aux MIC
1 kVA
T. Aux Torre
1 kVA
16xE-3
5,638
42,684
NODO:
N4
TENSION: 208V
TIPO DE FALLA
SACEA1 INVRED
MONOFASICA
Icc =842 A
SACEA1 UG 1.2
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
BREAKER ID
<10xE-3
N/A
S202 IE
0,604
14,886
XT3-N-TG
1,750
35,107
XT3-N-Gen.
FALLA EN PRE-CALENTADOR CONECTADO A LA MICRORED
FALLA EN LUZ DE OBSTRUCCIÓN CONECTADO A LA MICRORED
VER CURVA ILUM. EXTERIOR
N3
T. Aux BTS
1 kVA
Ilum. Ext.2
1 kVA
BREAKER ID
FALLA EN ILUMINACIÓN EXTERIOR CONECTADO AL GENERADOR DIESEL
NODO:
N7
SECUENCIA DE DISPAROS
12,139
NOTA:
N6
N10
FALLA EN ILUMINACION EXTERIOR CONECTADO A LA MICRORED
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
BREAKER ID
10xE-3
N/A
S202 IE
15xE-3
N/A
16xE-3
6,341
37,668
188,992
TENSION: 208V
TIPO DE FALLA
MONOFASICA
Icc = 672 A
N5
TENSION: 208V
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
N/A
15xE-3
N/A
XT3-N-TG
SACEA1 INVRED
16xE-3
N/A
SACEA1 INVRED
SACEA1 UG 1.2
19,.213
74,582
TIPO DE FALLA
MONOFASICA
Icc =1,083 kA
XT3-N-TG
NOTA:
FALLA EN LA LUZ DE OBSTRUCCIÓN CONECTADO AL GENERADOR DIESEL
N4
NODO:
10xE-3
NOTA:
VER CURVA LUZ DE OBSTRUCCIÓN
Se cumple igual para circuitos auxiliares
NODO:
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
BREAKER ID
10xE-3
N/A
S202 IE
15xE-3
10,601
XT3-N-TG
0,992
22,272
XT3-N-Gen.
NOTA:
VER CURVA LUZ DE OBSTRUCCIÓN
Se cumple igual para circuitos auxiliares
G
S202 IE
DPS3
VER CURVA BTS1
FALLA EN RECTIFICADORES BTS CONECTADO AL GENERADOR DIESEL
SECUENCIA DE DISPAROS
t 1(s)
N10
TIPO DE FALLA
NOTA:
FALLA INVERSOR
XT3-N-TG
FALLA EN RECTIFICADORES BTS CONECTADO A LA MICRORED
BREAKER ID
XT3-N-TG
BREAKER ID
S201 PR
SACEA1 UG 1.2
VER CURVA PRE-CALENTADOR
FALLA EN PRE-CALENTADOR CONECTADO AL GENERADOR DIESEL
NODO:
N5
TENSION: 208V
TIPO DE FALLA
MONOFASICA
Icc = 747 A
NOTA:
VER CURVA PRE-CALENTADOR
SECUENCIA DE DISPAROS
t 1(s)
t 2(s)
BREAKER ID
10xE-3
N/A
15xE-3
9,068
XT3-N-TG
0,794
18,465
XT3-N-Gen.
S201 PR