FICHA DETECTOR DE FLUJO U-BOLT IRON MAN UL-FM

Anuncio
IM60011 Waterrflow De
etector
2018 Editio
on
U‐Bolt Vaane Type Waterflow
W
Detector
MODEL: IIM6001‐50//65/80/100
0/125/150//200
FLOW SENSITIVITY RANGE:
R
4 ‐ 10
1 GPM(15‐‐38LPM)
CONTACTT RATING: 8A@250VAC
C,3A@24VD
DC,2.5A@30
0VDC
WORKING
G PRESSUREE: 450PSI
WORKING
G TEMPEREETURE: 0℃ TO 49℃
COMPATIBLE PIPE: STEEL PIPE, SCHEDULE
S
110~40
MAXIMUM SURGE:1
18FPS(5.5M/S)
GENERALL INFOMATIION
Waterflow
w detectorrs are mounted to waater
filled pipes in sprinkkler systemss. It is usedd on
steel pip
pe,schedulees 10 through 40, ssizes
50mm th
hru 200mm (2” thru 8””). See Tab le 1
for detectors sizes.
Waterflow
w in the pipe deflects a vane, whhich
triggers a switch usually
u
afte
er a speciffied
delay period. All waaterflow de
etectos havve a
pneumattically conttrolled mecchanical deelay
mechanissm. Delays reset if the
e flow of waater
stops beffore the enttire delay has
h elapsed.. All
switches are actuatte when th
he water fflow
rate is 100gallons peer minute or
o greater, but
will not actuate iff the rate is less t han
4gallons per minutee. This instaallation mannual
covers th
he followingg waterflow
w detectors for
sprinkler. It can bee mounted in verticall or
horizontaal position and suitab
ble for inddoor
and outdoor wet pip
pe.
Nom
minal Pipe Size
S
Model
DN500
2”
IM6001‐5 0
DN655
2
2.5”
IM6001‐6 5
DN800
3”
IM6001‐8 0
DN1000
4”
IM6001‐1000
DN1225
5”
IM6001‐1225
DN1550
6”
IM6001‐1550
DN2000
8”
IM6001‐2000
Table 1: DETECTOR
D
SIZE
S
Corrosion
n Protection
n
Fusion Bo
onded Epoxxy Coated In
nterior
and
d Exterior or Enamel Sppray Paint, Interior
I
and
d Exterior.
Installation
NO
OTE: Do not leave coverr off for an extended
perriod of time.
1. These de
evices mayy be mou
unted on
horrizontal or vertical
v
pipee. On horizo
ontal pipe
the
ey shall be installed onn the top siide of the
pip
pe where th
hey will bee accessible
e. Be sure
the
ere is adeq
quate clearaance for in
nstallation
and
d remova
al.See Figg.1 for mounting
dim
mensions.
2. The
T device should nott be installed within
15ccm of a fittting which cchange the direction
of the
t waterflo
ow or withiin 60cm of a valve or
draain
3. Drain the system andd drill a ho
ole in the
Shanghai Iron Man Firre Fighting Eq
quipment Co. ,ltd
Room 716, 7F, No.100
0, Xiuyan Road
d, Shanghai 2201315, China
www.firefightingtool.com
IM60011 Waterrflow De
etector
2018 Editio
on
pipe. And
d be sure th
he hole is pe
erpendiculaar to
center off the pipe,ass show in Fiig.2. If the hhole
is off cen
nter, the vaane will bin
nd against the
inside waall of the pip
pe. Use a ho
ole saw
in a slow
w speed drrill to cut a hole of the
proper diiameter, as show in Tab
ble 2.
4. Removve burrs an
nd sharp edges from the
hole. Clean and rem
move all scaale and foreeign
matter ffrom the in
nside of th
he pipe foor a
distance equal to the pipe diam
meter on eitther
side of th
he hole. Cleaan the outside of the
pipe to rremove dirtt,metal chip
ps, and cuttting
lubricant.
5. Roll th
he vane so
o that it maay be inserrted
into the hole; do no
ot bend or crease it. SSeat
the gaskeet against the saddle and
a mount the
detector into the pip
pe. Insert th
he vane so tthat
the
e arrow on
o the sadddle points in the
dire
ection of the waterrflow. The bushing
sho
ould fit insid
de the hole in the pipe.
6. Install th
he U‐bolt and tighten nuts
alte
ernately to ensure a uuniform seaal(see the
Tab
ble 2 for torque values)).
7. The
T vane must
m
not ruub the inside of the
pip
pe or bind in any wayy. If the vaane binds,
rem
move the detector
d
annd correct the
t cause
beffore proceeding.
8. Ensure thatt the directtion of arro
ow on the
sad
ddle point should be consistent with the
dire
ection of the waterflow
w.See Fig.3.
Notes: Remove
e burrs from
m edge of hole. Clean
outt scale and foreign maatter from in
nside wall
of pipe
p
Fig.1 Mounting dimensions
Fig.2 Mounting hole location
Table 2 Main dimensions
Pippe Wall thickness
Nominaal Pipe
Sizze
No
ominal Pipe
e
Size OD.
Scheduule10
Scchedule40
mm
DN50
DN65
DN80
DN100
DN125
DN150
DN200
mm
m
60.3
7
73
88.9
11
14.3
14
41.3
16
68.3
21
19.1
mm
2.77
3.05
3.05
3.05
3.40
3.40
3.76
mm
m
3.9
91
5.1
16
5.4
49
6.0
02
6.5
55
7.1
11
8.1
18
inch
2”
2.5”
3”
4”
5”
6”
8”
inch
2.375
5
2.875
5
3.500
0
4.500
0
5.563
3
6.625
5
8.625
5
inch
00.109
0.12
0.12
1.12
00.134
00.134
00.148
Shanghai Iron Man Firre Fighting Eq
quipment Co. ,ltd
Room 716, 7F, No.100
0, Xiuyan Road
d, Shanghai 2201315, China
inch
0.154
0.203
0.216
0.237
0.258
0.280
0.322
L
H
mm
84
92
104
133
160
187
240
m
mm
1188
2200
2220
2245
2272
2298
3350
mm
U‐bolt
Nuts
Torque
nm
32+2
2
40‐50
51+2
2
70‐95
Hole
e
Size
www.firefightingtool.com
IM60011 Waterrflow De
etector
2018 Editio
on
Fig.3 Assembly diagram
2. A ground screw is provided with all
waterflow de
etectors. W
When grou
unding is
req
quired, clam
mp wire withh
screw in ho
ole locatedd between
n conduit
enttrance holess. See Fig.5
Fig.5 Ground screw
3. If a secon
nd conduitt entry is required,
rem
move the kn
nockout pluug: Place sccrewdriver
at inside
i
edge of
kno
ockouts, not in the cennter.
Wiring
1.All mod
del have two
o SPDT swittches,one can
be used to operatee a central station, w
while
the other contact iss used to operate
o
a loocal
audible o
or visual ann
nunciator. Switch
S
contaacts
COM and NO are closed when
w
waterr is
flowing aand open when it is no
ot. Connect the
switches,, as shown in
i Fig.4, dep
pending on the
applicatio
on.
Rettard Adjustment
The
e delay can be adjustedd by rotating the
retard adjustm
ment knob ffrom 0 to max
m setting.
To adjust the
settting, turn th
he adjustmeent knob clockwise
to increase
i
the
e delay, couunterclockw
wise to
deccrease it. Th
he time
dellay should be
b set at thee minimum required
to prevent
p
falsse alarms.
Ma
aintenance
Inspect detecttors monthl y. If leak are
e found,
rep
place the de
etector.
Fig.4 Electric connection
Shanghai Iron Man Firre Fighting Eq
quipment Co. ,ltd
Room 716, 7F, No.100
0, Xiuyan Road
d, Shanghai 2201315, China
www.firefightingtool.com