ABB INSTRUCTION MANUAL Product Rated Power Voltage Ratio No. of Phase Voltage Variation Vector Group Customer ABB ref. Serial No. : : : : : : : : : Power Transformer 176.25 MVA 220/23 kV Three Phase + 10% to -10% on HV side YNd11 ISABEL, CHILE 13156 C1222 Prepared by Approved by Srutiranjan Sahu Ajay Sheth This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA, VADODARA, GUJARAT, INDIA Page - 1 of 2 ABB CONTENTS PART No. TITLE PAGES TITLE SHEET, CONTENTS 2 SECTION – I 1 SAFETY INSTRUCTIONS 10 SECTION – II 2 TEST RESULTS OF TRANSFORMER 1 3 TECHNICAL DATA OF TRANSFORMER AND COMPONENTS, GENERAL DESCRIPTION OF TRANSFORMER 15 4 TRANSFORMER DRAWING, LEAFLETS AND CATALOGUES 447 SECTION – III 5 DISMANTLING AND TRANSPORT 16 6 MONITORING OF DRY-GAS FILLING OF TRANSFORMERS DURING SHIPMENT & STORAGE 4 7 RECEIVING INSPECTION AND ARRIVAL ON SITE 8 8 UNLOADING, MOVING, STORING TRANSFORMER AND PRECOMMISSIONING CHECKS. 5 9 TRANSFORMER ASSEMBLY INSTRUCTIONS, ERECTION EQUIPMENT/ TOOLS 13 10 OIL-SPECIFICATION, TESTING, PURIFICATION AND STORAGE 14 11 ERECTION AND ASSEMBLY 7 12 ACCEPTANCE TEST AND ENERGISATION 6 13 FIELD TEST RECORD AND FIELD QUALITY PLAN 16 14 TROUBLE SHOOTING 10 15 STORAGE 5 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA, VADODARA, GUJARAT, INDIA Page - 2 of 2 ABB PART –1 SAFETY INSTRUCTIONS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 1 of 10 ABB SAFETY INSTRUCTIONS 1.1 SAFETY RULES FOR WORKING AT LIVE PARTS 1.2 OBSERVE INSTRUCTIONS IN THIS MANUAL FOR ERECTION, OPERATION AND MAINTENANCE 1.3 RESPONSIBILITY OF THE TRANSFORMER USER 1.4 RESPONSIBILITY OF THE PERSONNEL 1.5 PERMISSIBLE OPERATION 1.6 GUARANTEE AND LIABILITY 1.7 STATUTORY AND REGULATORY REQUIREMENT ON AIR CLEARANCES. 1.8 PROTECTION OF TRANSFORMERS 1.8.1 CIRCUIT BREAKERS OF SUFFICIENT CAPACITY ON HV AND LV SIDES 1.8.2 SURGE DIVERTOR 1.9 DO‘S AND DON‘TS FOR POWER TRANSFORMERS 1.9.1 DO‘S FOR POWER TRANSFORMERS 1.9.2 DON‘TS FOR POWER TRANSFORMERS 1.10 PARALLEL OPERATION TABLE T 1.2: COMMON PERMISSIBLE COMBINATIONS FOR PARALLEL OPERATION This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 2 of 10 ABB 1 SAFETY INSTRUCTIONS 1.1 SAFETY RULES FOR WORKING AT LIVE PARTS Working at live parts of electrical equipment must only be done if the following safety rules are carefully observed: Switch off Secure against involuntary re-closing Make sure that equipment is not alive Connect equipment to earth and short-circuit it Close parts that are alive, must be covered or blocked off . 1.2 OBSERVE INSTRUCTIONS IN THIS MANUAL FOR ERECTION , OPERATION AND MAINTENANCE It is of vital importance for safe working conditions and for trouble-free operation of the transformer that all personnel know the basic safety precautions and prescriptions. This manual contains the most important instructions for safe transformer operation and should be stored at the transformer site. All personnel working at the transformer must carefully observe the safety precautions and the instructions in this manual. Further on local and national regulations for the prevention of accidents and for the protection of the environment must be provided and observed. All safety instructions at the transformer must be clearly readable. The following terms are used in the manual to draw your attention to special safety instructions. DANGER! Indicates a serious imminent danger. If the safety instructions given are disregarded, heavy injury or death will be the consequence. WARNING! Indicates a potentially dangerous situation. If the safety instructions given are disregarded, injury or damage to the equipment might be the consequence. CAUTION! Indicates a situation that might become dangerous. If the safety instructions given are disregarded, the transformer or the equipment might be damaged. 1.3 RESPONSIBILITY OF THE TRANSFORMER USER The user is responsible to take care that all personnel working at the transformer fulfill the following requirements: The personnel is skilled in operating high-voltage equipment, especially transformers and has good knowledge of basic rules for safety and prevention of accidents. Authorization for assembling, putting into operation, operating, maintenance and repair works must be clearly stated. All personnel must have read and fully understood the safety instructions stated in this manual and confirmed this by signature. Semi-skilled staff must only work at the transformer if supervised by an experienced skilled person. Observance of the safety regulations is checked in regular intervals. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 3 of 10 ABB 1.4 RESPONSIBILITY OF THE PERSONNEL Before starting to work at the transformer all persons are obligated to observe the following rules: - Observance of basic instructions concerning safety and prevention of accidents Before starting to work, the safety precautions and the warning instructions in this manual must be read and fully understood. This must be confirmed by signature. 1.5 PERMISSIBLE OPERATION The transformer is built according to the latest technology and the generally acknowledged safety rules. It transforms electrical energy. The transformer must only be operated in accordance with the applicable standards and regulations and within the range of the electrical data mentioned in PART 3. “TECHNICAL DATA OF TRANSFORMER AND COMPONENTS”. Any operating conditions exceeding these regulations are not allowed and can result in injury or damage to the equipment. Asea Brown Boveri Ltd. cannot accept any liability arising from improper use of the transformer. Further, improper use forfeits any guarantee agreements. Permissible operation also includes: - Careful observance of all instructions in this manual and - observance of inspection and maintenance intervals 1.6 GUARANTEE AND LIABILITY Our "General terms of sales and delivery” are applicable. They are given to the customer together with the contract. We cannot accept liability and exclude any guarantees for damage to equipment and personnel injury, which is due to the following factors: - Improper use of the transformer. - Improper assembly, commissioning, operating and maintenance of the transformer - Operating the transformer with faulty protective equipment or with protective equipment which is not mounted correctly and not fully functioning. - Non-observance of the instructions in the operating and maintenance manual concerning transport, storage, assembly, commissioning, operating and maintenance of the transformer - Unauthorized constructional alterations of the transformer - Faulty supervision of accessories, which are subject to wear - Faulty repairs - Catastrophes due to external reasons and force majeure This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 4 of 10 ABB 1.7 STATUTORY AND REGULATORY REQUIREMENT ON CLEARANCES IN AIR For the purpose of safety, Electricity Supply Regulation 1987 clause 10 provides for appropriate minimum clearances from exposed live metal to ground level, platform level or other position where men may normally stand for operating, maintenance purpose, where a portable ladder is used. Arrangement shall be such that there is no danger to an authorised person when operating. Where minimum clearances cannot be obtained effective screening must be provided in order to comply with the above, the following instructions and table of minimum clearances “D“ must be worked out. CONDITION –1 When operation / inspection can be effected on ground level minimum clearance‚ D” must be measured vertically. CONDITION-2 Where a platform is provided for this purpose, minimum clearance‚ D” must be measured radially from the nearest edge of platform to the adjacent live conductor. CONDITION-3 Where no platform is fitted and ladder has to be used, an earthed screen must always be fitted in consultation with ABB. TABLE T 1.1 VOLTAGE CLASS GROUND CLEARANCE NOT EXCEEDING k V MIN. ”D‘ METERS 11 2.75 33 3.70 66 4.00 132 4.60 220 5.50 400 8.00 These rules must be taken care particularly in the case of transformer fitted with on load tap change The following standards/ specifications also give necessary details from dispatch to maintenance of transformers and these also must be referred. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 5 of 10 ABB IS 10028- 1985: CODE OF PRACTICE FOR INSTALLATION AND MAINTENANCE OF TRANSFORMERS. IS 1866- 1961: CODE OF PRACTICE FOR MAINTENANCE OF INSULATING OIL BS-CP-1010 : BRITISH STANDARD CODE OF PRACTICE ,GUIDE TO LOADING OF TRANSFORMERS. CBI & P MANUAL SECTION A (1987) FOR THE REGULATORY REQUIREMENTS. 1.8 PROTECTION OF TRANSFORMERS Adequate electrical protection for transformer should be provided to avoid costly breakdowns and the loss of valuable equipment. The risk of commissioning the transformers without ensuring due protection should be avoided. Generally the transformers should be provided with the following protections 1.8.1 CIRCUIT BREAKERS OF SUFFICIENT CAPACITY ON HV AND LV SIDES: The setting of breakers shall be so adjusted that the fault current and duration shall in no case exceed those specified in clause No. 9 of IS 2026. Currents more than these and of longer duration will cause permanent damage to transformers. 1.8.2 SURGE DIVERTORS OF ADEQUATE CAPACITY SHOULD BE PROVIDED TO THE TRANSFORMER TERMINALS TO PROTECT FROM OVER VOLTAGE DAMAGES. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 6 of 10 ABB 1.9 DO‘S AND DON‘TS FOR POWER TRANSFORMERS 1.9.1 DO‘S FOR POWER TRANSFORMERS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Check and thoroughly investigate the transformer whenever any alarm or protection is operated. Check air cell in conservator Attend the Leakages if any on bushings immediately. Examine the bushings for dirt deposits and coats and clean them periodically Check the oil in transformer and OLTC for di-electric strength and moisture content and take suitable action for restoring the quality. Check the oil level in oil cup and ensure air passages are free in the breather. If oil is less make up the oil. Check the oil for acidity and sludge as per IS 1866 If the inspection covers are opened or any gasket joint is to be tightened, then tighten the bolts evenly to avoid uneven pressure. Check and clean the relay and alarm contacts Check the protection circuits periodically Check the pointers of all gauges for their free movement Clean the oil conservator thoroughly before erecting Check the Buchholz relay and readjust the floats and switches etc. Inspect the painting and if necessary retouching should be done. Check the OTI and WTI pockets and replenish the oil if required Remove the air through the vent plug of the diverter switch before you energise the transformer Check the oil level in the divertor switch and if found less top up with fresh oil conforming to specifications. Check the gear box oil level Examine and replace the burnt or worn out contacts as per maintenance schedule Check all bearings and operating mechanism and lubricate them as per schedule Open the equalizing valve between tank and OLTC wherever provided at the time of filling the oil in the tank. Connect gas cylinder appropriately if transformer is to be stored for long, in order to maintain positive pressure. Fill the oil in the transformer at the earliest opportunity at site and follow storage instructions Check the door seals of marshalling box. Change the rubber lining if required. Do make sure that internal pressure in the transformer is zero gauge before opening the manhole cover. Insulating oil and insulation material for windings and connections are inflammable. Watch for fire hazards. Make sure that nothing is kept inside the pockets before authorised person enters inside the main unit. Also remove wrist watches and footwear. There must be protective guard for lamp to be taken inside This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 7 of 10 ABB 29 30 31 32 33 34 35 36 37 38 39 40 41 42 Keep inspection covers open for supply of fresh air when working inside When one person is working inside, second person must be outside for emergency. Use fix spanners and tie them to the wrist of the person or somewhere outside the tank Be careful during connections where bolted joints (jumper connections) are provided, so that nuts, washers etc. are not dropped inside the tank. If it is necessary to weld some lugs or brackets etc., those should be welded to tank stiffeners and strictly under the supervision of ABB representatives. De-energise the unit by circuit breakers and line switches while working on energized unit. Ground the line terminals. Attach the caution tags „DO NOT OPERATE THE SWITCHES“ while working on energized unit. Make sure that the fire-fighting equipments are available at the oil treatment equipment as well as work place and adjacent to the transformer. Transformer tank, control cabinets etc. as well as oil treatment equipment shall be connected with permanent earthing system of the station Check oil level in condensor bushing; ensure proper tightness of top terminal cap of condenser bushings to avoid rainwater entry. Transport transformers only in upright position Use tools with working surfaces hardened so that they will not peel or chip. Equalise the divertor compartment of the OLTC by connecting equalizing pipe between flange joints provided on the tap changer head. Oil drums at site shall be stored in horizontal position with openings horizontal 1.9.2 DON‘TS FOR POWER TRANSFORMERS 1 2 3 4 5 6 7 8 9 10 11 DO-NOT energise without thorough investigation of the transformer whenever any alarm of protection has operated. DO-NOT re-energise the transformer unless the Buchholz gas is analyzed. DO-NOT re-energise the transformer without conducting all precommissioning checks. The results must be comparable with the results at works. DO-NOT handle the off circuit tap switch (if any) when the transformer is energized. DO-NOT energise the transformer unless the off circuit (if any) tap switch handle is in locked position. DO-NOT leaves off circuit tap switch handle unlocked. DO-NOT leave tertiary terminals (if any) unprotected outside the tank, connect them to tertiary lightning arrestors protection scheme when connected to load. DO-NOT allow WTI/OTI temperature to exceed 65 deg. C during dry out of transformers and filter machine temperature beyond 70 deg C DO-NOT parallel transformer which DO-NOT fulfill required conditions as specified in TABLE T 1.2 DO-NOT use low capacity lifting jacks on transformer for jacking DO-NOT move the transformer with bushings mounted This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 8 of 10 ABB 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 DO-NOT overload the transformer other than the specified limits as per IS 6600 DO-NOT changes the settings of WTI and OTI alarm and trip frequently. The settings should be done as per the site condition. DO-NOT leave red pointer behind the black pointer in WTI and OTI DO-NOT leaves any connections loose. DO-NOT meddles with the protection circuits. DO-NOT allow conservator oil level to fall below 1 / 4 level DO-NOT allow oil level fall in the bushings, they must immediately be topped up DO-NOT switches off the heater in the marshalling box except to be periodically cleaned. DO-NOT leave marshalling box doors open, they must be locked DO-NOT allow dirt and deposits on bushings, they should be periodically cleaned. DO-NOT allow unauthorized entry near the transformer. DO-NOT leave ladder unlocked DO-NOT change the sequence of valve opening for taking stand- by pump and motor into circuit DO-NOT switch on water pump(if any) unless oil pump is switched on in case of OFWF cooling DO-NOT allow water pressure more than oil pressure in differential pressure gauge (in case of OFWF cooling) DO-NOT mix the oil. Unless it conforms to the specification mentioned in this manual ( PART 10) DO-NOT allow inferior oil to continue in transformer. The oil should immediately be processed and to be used only when BDV/PPM and other properties conform fully to IS 1866 and oil specification. DO-NOT continue with pink/white silica gel, this should immediately be changed or regenerated. DO-NOT store the transformer for long after reaching site. It must be erected and commissioned immediately. Otherwise follow special precautions. DO-NOT leave secondary terminals of unloaded CT open DO-NOT keep the transformer gas filled at site for a longer period. DO-NOT take any fibrous material as cotton waste inside while repairing Do not stand on cleats and leads DO-NOT weld/braze/solder inside tank DO-NOT weld any thing to tank wall from outside DO-NOT weld anything to conservator vessel with flxi separator rubber bag DO-NOT smoke on or near transformer. DO-NOT use fibrous cleaning materials as it can deteriorate oil when mixed with it. DO-NOT use pipe flanges and valves as lifting or supporting points DO-NOT drop crates containing porcelain parts DO-NOT open the transformer during periods of inclement weather or when condensation is forming on the internal surfaces of the transformer. Never enter a transformer with dirty or wet clothing DO-NOT filter oil of energized transformer This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 9 of 10 ABB 1.10 PARALLEL OPERATION 1.10.1 If it is desired to parallel a transformer, which is not identical in design with ABB transformer, it is preferable to refer the matter to ABB for advice/guidance. 1.10.2 The voltage ratings/ ratios and impedance values at all taps should match for the two transformers, which are to be paralleled. Only certain combinations of vector groups are capable of being paralleled. The table T1.2 below indicates more common permissible combinations 1.10.3 Reference to the connection diagrams of two transformers should indicate the terminals to be paralleled 1.10.4 The reversal of two leads on either side of a three-phase transformer will reverse the polarity changing them in sequence (example: from UVW to VWU or WUV will swing the vector through 120 deg.) 1.10.5 Phase sequence and polarity can be checked by energizing both transformers on the primary side before paralleling and measuring the open circuit voltage appearing across each pair of terminals which will ultimately be paralleled. 1.10.6 IS: 2026 and IS:10561 can also be referred. TABLE T 1.2 COMMON PERMISSIBLE COMBINATIONS FOR PARALLEL OPERATION TRANSFORMER (TWO) HV/LV TRANSFORMER (ONE) HV/LV DELTA/ STAR STAR/ DELTA DELTA/ DELTA STAR/ STAR DELTA/STAR YES YES NO NO STAR/DELTA YES YES NO NO DELTA/DELTA NO NO YES YES STAR/STAR NO NO YES YES This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 10 of 10 ABB PART 2 TEST RESULTS OF TRANSFORMER This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 1 of 1 ABB PART 3 Ø TECHNICAL DATA OF TRANSFORMER Ø TECHNICAL DATA OF COMPONENTS Ø GENERAL DESCRIPTION OF TRANSFORMER Ø PROTECTIVE AND SUPERVISORY INSTRUMENTS Ø SPECIFIC INSTRUCTIONS FOR TRANSFORMER INSTALLATION This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 1 of 12 ABB 3.0 TECHNICAL DATA OF TRANSFORMER AND COMPONENTS 3.1 TECHNICAL DATA OF TRANSFORMER 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.1.7 3.1.8 3.1.9 3.1.10 3.1.11 3.1.12 3.1.13 3.1.14 3.1.15 3.1.16 3.1.17 3.1.18 3.1.19 3.2 RATED POWER POWER DEFINITION VOLTAGE RATIO VOLTAGES AND CURRENTS VECTOR GROUP IMPEDANCE VOLTAGES NO LOAD CURRENT MAX. DURATION OF SHORT-CIRCUITS INSULATION LEVEL NO-LOAD LOSS LOAD LOSS TOTAL LOSSES RATED FREQUENCY POWER OF FANS TEMPERATURE RISE AND AMBIENT TEMPERATURE ADJUSTMENT OF TEMPERATURE INDICATORS FOR TEMPERATURE SOUND LEVEL DIMENSIONS WEIGHTS TECHNICAL DATA OF COMPONENTS 3.2.1 OLTC 3.2.2 COOLING EQUIPMENT 3.2.2.1 RADIATORS 3.2.2.2 FANS 3.2.2.3 PUMPS (NOT APPLICABLE) 3.2.3 BUSHINGS: TERMINAL ARRANGEMENT 3.2.4 CURRENT TRANSFORMERS 3.3 GENERAL DESCRIPTION OF TRANSFORMER 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 CORE WINDINGS TANK AND COVER CONSERVATOR AIR CELL This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 2 of 12 ABB 3.4 PROTECTIVE AND SUPERVISORY COMPONENTS 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6 3.4.7 3.4.8 3.4.9 3.4.10 3.5 BUCHHOLZ RELAY DEHYDRATING BREATHER PRESSURE RELIEF DEVICE OIL TEMPERATURE INDICATOR: DIAL TYPE WINDING TEMPERATURE INDICATOR: DIAL TYPE OIL LEVEL INDICATOR 3.4.6.1 MAGNETIC TYPE 3.4.6.2 PRISMATIC TYPE VALVES AIR RELEASE PLUG CT TERMINAL BOX EARTHING ARRANGEMENT 3.4.10.1 CORE EARTHING 3.4.10.2 TANK TO TANK -COVER EARTHING 3.4.10.3 EARTHING OF TANK SPECIFIC INSTRUCTIONS FOR TRANSFORMER INSTALLATION This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 3 of 12 ABB 3.0 TECHNICAL DATA OF TRANSFORMER AND COMPONENTS 3.1 TECHNICAL DATA OF TRANSFORMER 3.1.1 RATED POWER MVA: 141/176.25 (ONAN/ONAF) 3.1.2 POWER DEFINITION: According to IEC-60076, Constant Power at all tapings of OLTC. 3.1.3 RATED RATIO: 220/23 kV Taps on Neutral end of 220 kV side for HV variation Voltage variation is +10% to -10 % Number of steps: 16, Number of Position: 17. 3.1.4 VOLTAGES AND CURRENTS (OLTC Tap no.9) Cooling Stage Voltage System Voltage level in kV Rating in MVA Line Current in Amp ONAN HV 220 141 370.04 ONAF LV 23 141 3539.51 HV 220 176.25 462.55 LV 23 176.25 4424.39 Please refer to Rating Plate ABB Drawing no. 2XYN294001C1222 voltage and currents of All other taps. 3.1.5 VECTOR GROUP HV/LV WINDING: YNd11 as per IEC:60076, however refer Rating & diagram plate for more details 3.1.6 IMPEDANCE VOLTAGES: HV - LV – 19% minimum @ 176.25MVA Base @ Principle tap-9, lowest & highest tap (For more details refer rating plate and test report) All impedances are at 75°C 3.1.7 NO-LOAD CURRENT : Refer Test Report 3.1.8 MAX. DURATION OF SHORT-CIRCUITS (THERMAL): 2 Seconds Maximum 3.1.9 INSULATION LEVEL: TESTING VOLTAGE HV LV HV-N Ur (Nominal Rated) kV 220 23 -- AC (Power Frequency) kVrms 460 50 230 LI (Lightning Impulse) kVP 1050 145 550 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 4 of 12 ABB 3.1.10 NO LOAD LOSS : 67 kW (Max.) at 1.0 x Un (100% rated voltage) 3.1.11 LOAD LOSS : 627 kW (Max.) at 125 MVA base, at 75°C and OLTC tap no.9 3.1.12 TOTAL LOSSES : 704 kW (Max.) at 120 MVA base and OLTC tap no.9 (Including losses consumed by cooling fans) Please refer test report for Impedance and Losses at extreme taps. 3.1.13 RATED FREQUENCY: 50 Hz 3.1.14 POWER OF FANS : 10 kW (Max.) Total Loss (No load loss + Load loss + Auxiliary loss) : 704 kW 3.1.15TEMPERATURE RISE AND AMBIENT TEMPERATURE IN DEG. 40°C max Maximum permissible oil temperature rise : 60 °C Maximum permissible average winding temperature rise : 65 °C 3.1.16 ADJUSTMENT OF TEMPERATURE INDICATORS FOR TEMPERATURE Please refer test report and instrument leaflets 3.1.17 SOUND PRESSURE LEVEL: 64dBA 3.1.18 DIMENSIONS: For details refer General Arrangement Drawing 2XYN460001C1222 Estimated Length Breadth Height Overall in mm 16307 8652 8294 Transport in mm 8212 3056 4116 3.1.19 WEIGHT (kg): Core & Windings Assy.(Active part) 78700 approx. Tank & Fittings 64505 approx. Total Weight of Oil in transformer 40375 approx. Total Weight of Transformer with Oil 183580 approx. Transport Weight (Dry Air Filled) 98000 approx. Total volume of oil in transformer in litre 47500 approx. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 5 of 12 ABB 3.2 TECHNICAL DATA OF COMPONENTS 3.2.1.1 ON LOAD TAP CHANGER Taps are provided on neutral end of 220 kV side for HV variation to keep LV voltage constant Make: ABB SWEDEN make Type: UCGDN Rated Current: 600 A, Step Voltage: 1587.76 V (phase voltage) Variation: +10% to -10 % Number of steps: 16, Number of positions: 17 OLTC Control Supply: 110 V DC 3.2.1.2 MOTOR DRIVE: BUL2 Drive Mechanism, ABB SWEDEN Make [Please Refer Catalogue for Full Details] 3.2.2 COOLING EQUIPMENT The transformer is having mixed cooling ONAN/ONAF by means of radiators, and fans. The radiators are separately mounted through header of the transformer tank by means of butterfly valves and pipes as shown in general assembly drawing 2XYN460001C1222. Fans are mounted on radiators. Interlock device is provided in cooling system work to facilitate automatic switching in of the standby fans, in case the running fan fails. one fan in each group is provided as standby. 3.2.3 BUSHINGS : TERMINAL ARRANGEMENT HV Line: Rated Voltage: 362 kV, Rated Current: 2500 A Lightning Impulse: 1175 kVp, Power Frequency (Dry): 560 kVrms Creepage distance :9120 Make: ABB SECOM Termination: Oil to Air OIP bushing HV Neutral: Rated Voltage: 170 kV, Rated Current: 1250 A Lightning Impulse: 750 kVP, Power Frequency : 325 kVrms Creepage distance :5504 Make: ABB SECOM Termination: Oil to Air RIP bushing This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 6 of 12 ABB LV Line : Rated Voltage: 36 kV, Rated Current: 8000 A Lightning Impulse: 170 kVP, Power Frequency (Dry&Wet): 70 kVrms Creepage distance: 900 mm Make: COMEM Termination: Cable Box 3.2.4 CURRENT TRANSFORMERS SUITABLE FOR FREQUENCY 50 Hz Current transformers for local winding temperature indicator are provided on HV & LV terminals as shown in rating and diagram plate. The secondary winding of the current transformers are connected to a terminal box. Current transformer terminals from terminal box are wired to Marshalling box. WTI CT terminals wired upto winding temperature indicator mounted in marshalling box. The secondary windings of current transformers are connected. The connections between terminals are made by links which also can be arranged to short circuit and earth the current transformer when disconnected. Refer Rating & Diagram plate drawing 2XYN294001C1222 for CT details. 3.3 GENERAL DESCRIPTION OF TRANSFORMER 3.3.1 CORE The magnetic core is of three limbed construction. Each limb being mitred with top and bottom yokes. The laminations are made from non Ageing Cold Rolled Grain Oriented Silicon alloy steel. The insulation of lamination is of carlite type. The core has stepped cross section. The yokes are clamped by means of end frames and yoke bolts of special construction and limbs are clamped by means of special resiglass tape over clamping plates. For lifting the core with winding, adequate provision has been made. The yoke bolts, end frames, clamp plates and core steel are insulated from each other to withstand test voltage of 2.0 kV rms at 50 Hz. for one minute. 3.3.2 WINDINGS Windings are arranged in concentric formation arranged as below LV (23 kV) WINDING : HELICAL(H1) WINDING HV (132 kV) WINDING : DISC (D) WINDING TAP WINDING : LAYER & LOOP LAYER WINDING The paper covered copper strips, paper covered & netting tap CTCE conductors are used for making windings. Windings are compressed adequately before assembly and remain in position by means of special clamping structure. The active part is processed using modern sophisticated vapor phase drying oven. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 7 of 12 3.3.3 TANK AND COVER ABB The tank and cover are welded mild steel conventional type construction, cleaned on inside and outside to remove scale before painting. The cover is of bolted construction and remains bolted at the joint between cover and tank. Adequate number of inspection covers is provided. To make joints oil tight, nitrile rubber gaskets are used. The tank and cover are provided with all fittings and accessories as per the General Assembly drawing. 3.3.4 CONSERVATOR As the temperature of oil increases or decreases during operation there is corresponding rise or fall in volume. To account for this an expansion vessel – CONSERVATOR- is connected to the transformer tank. The conservator is mounted on the cover of the transformer. The conservator has got capacity between minimum to maximum oil level about 7.5% of the total oil in transformer. The conservator is mounted with magnetic oil level gauge which has a low oil level alarm. The dial indicates empty, ¼, at 30 DEG. C, ¾ and full oil level. The terminals for low oil level alarm and high oil level alarm switches are wired upto marshalling box. Please refer MOLG catalogue for more details. Also prismatic oil level gauges are provided on the other end of the conservator. The conservator is provided with FLEXI separator rubber bag. The conservator is filled with oil to level appropriate to the filling temperature and in the remaining portion is Air cell which is connected to atmosphere through a breather. If the volume of oil in the transformer increases the conservator breathes out air and if the volume of oil in the conservator reduces, the conservator breathes in air. As the breathing is through air cell, no moisture comes in contact with the oil thus preventing contamination of oil. A valve also used for air filling air cell before filling oil in conservator at a pressure 0.035 kg/sq cm. The pipe connecting the transformer tank with conservator projects above the lowest point in the conservator such that the portion below acts as a sump where the impurities in the conservator collect. A valve is fitted at the lowest point of the conservator for draining and sampling of oil. On the feed pipe reed type (Earthquake resistance) Buchholz relay is mounted. Between conservator and buchholz relay, an isolating valve is provided. 3.3.5 AIR CELL It is a flexible separator fitted inside the conservator. Oil being out of the air cell, the separator is in direct contact with the atmosphere. This type of mounting makes it possible to compensate for the oil volume displacements due temperature variations and ensures: an efficient barrier between oil and air a protection against water vapour the suppression of any gas bubbles formation in the oil Air cell is made from coated fabric with external coating resistant to transformer oil and inner coating resistant to ozone and weathering. Air cell is made from nylon fabric coated with nitrile rubber. In the event it becomes necessary to replace or test the air cell for leaks the following method is recommended. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 8 of 12 ABB - De-energise the transformer Isolate the conservator by closing relevant valve Drain the oil from the conservator by closing relevant valves Install pressure gauge appropriately Pressurise the air cell by dry nitrogen /air to maximum pressure of 1.5 psi(~1.03kgf/sqcm) and seal. Check the pressure after 6 hours If leaks are found , air cell to be repaired by patching or replaced by new air cell For taking out the air cell from the conservator, remove the air cell flange and loops from hooks provided on inside of the conservator top. Collapse the air-cell slowly and fold, remove it from conservator very carefully. In the event air cell is not available immediately, conservator may be used as a conventional conservator for short period till air cell is replaced. 3.4 PROTECTIVE AND SUPERVISORY COMPONENTS 3.4.1 BUCHHOLZ RELAY The transformer is fitted with reed type buchholz relay. It is fitted in the pipe from conservator to tank and is provided with two sets of micro contacts. The device comprises of a cast iron housing containing the hinged floats, one in upper part and the other in lower part. Each float is fitted with a micro switch, leads of which are connected to a terminal box for external connections. An arrow is cast on the housing to indicate the direction of the conservator. The operation of buchholz relay should be tested before installation by injecting air at the lower cock (test cock). After the inspection and tests, any air which may have accumulated in the gas chamber must be released at the upper pet cock to ensure that the chamber is full of oil. The top most points are piped to the main pipe on which the buchholz relay is mounted so that the gases liberated in the transformer are diverted to the buchholz relay without being trapped anywhere. Please refer to the leaflet on buchholz relay. From the petcock, if any gas is collected in the buchholz relay, can be drawn off for testing. BUCHHOLZ RELAY (Gas Operated Relay) : COMEM Make, 80 NB size Steady oil flow for trip : 90-160 cm/sec Gas volume for alarm : 200 TO 300 CC Operating instructions : For more details refer catalogue Operating instructions : For more details refer catalogue 3.4.2 SILICA GEL BREATHER The conservator is connected to the atmosphere through a dehydrating silica gel filled breather to make sure that the air in the conservator is dry. For general description of the apparatus please refer to the leaflet. 1) For main conservator : silica gel breather Manufacturer : YOGYA Model no. _ : DTO 9 Refer catalogue for more details This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 9 of 12 ABB 2) For OLTC conservator : Orange Color Silicagel Manufacturer : DTO 4 3.4.3 PRESSURE RELIEF VALVE In case of severe fault in the transformer, the internal pressure may build up to a very high level which may result in an explosion of tank. To avoid such a contingency two number pressure relief valves are fitted on the transformer. It is spring loaded and has contacts for tripping the transformer. Please refer to the catalogue for details. To take away the discharge piping arrangement is also provided. COMEM Make pressure relief device 3.4.4 OIL TEMPERATURE INDICATOR: DIAL TYPE Oil temperature indicator is a distance thermometer operating on the principle of liquid expansion. It provides local indication of the top oil temperature at the marshalling box. The connection between the thermometer bulb and the dial indicator is made by flexible steel capillary tube .The bulb is enclosed in a pocket and the pocket is fixed on the transformer at the hottest oil region. The pocket has to be filled with transformer oil. The oil temperature indicator is provided with a maximum pointer and two micro switches one for alarm and other for trip. Switches are suitable for 240 V AC OR DC. The micro switches are adjustable to make contact between 50 and 120o C and have fixed differential of 5o C. The temperature for alarm and trip contact settings shall be as under: Alarm = 100 deg. C, Trip = 105 deg.C (At an ambient temperature of 40deg. C). In addition to local oil temperature indication, provision is available for repeat oil temperature indication at RTCC panel by using a potentiometer in the local OTI and sending 4-20 mA signals to RTCC panel. MAKE: COMEM with alarm & trip contacts 3.4.5 WINDING TEMPERATURE INDICATOR: DIAL TYPE One number WTI is provided for monitoring temperature of winding under running condition. This indicator operates on the principle of liquid expansion. It provides local indication at the marshalling box of hot spot temperature of winding. The winding hot spot to top oil temperature differential is simulated by means of a heater coil fitted around the operating bellows. A current proportional to the load current is fed to the heater coil from a current transformer fitted on V phase of HV & LV as shown in the diagram plate. The bulb is connected by capillary tubing to the local indicator. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 10 of 12 ABB The indicator is fitted with maximum pointer and four micro switches. One is used for alarm and second is used for trip and third & fourth for cooler control. All the switches are adjustable on their individual scales over the entire working range of the instrument. All micro switches are suitable for 240V AC or DC. For details please refer to catalogue on WTI. The WTI pocket has to be filled with transformer oil. The temperature for alarm and trip contact settings for WTI shall be as under: 1] Alarm 105oC 2] Trip 110oC 3] Fans “ON“ for ONAF-70oC At max. Ambient temperature of 40oC MAKE: COMEM with alarm, trip & fan control contacts. 3.4.6 OIL LEVEL INDICATOR 3.4.6.1 MAGNETIC TYPE: For main tank conservator:SUKRUT make, with low oil level and high oil level alarm contacts on one flat side of the conservator. 3.4.6.2 PRISMATIC TYPE: ABB Make on the other flat side of the conservator 3.4.7 VALVES Both end flanged globe valves Butterfly valves Globe valves Ball Valve Gun metal Gate valves : OLTC suction, OLTC conservator drain, Oil surge relay isolating, Air cell equalizing. : Radiator isolating. : Top & bottom oil sampling. : Sludge removal valve. : Main tank drain, Main conservator top filter, Main conservator drain & filling, conservator shut off, top & bottom filter. For exact location of all the valves, refer general assembly drawing and valve schedule plate drawing 3.4.8 AIR RELEASE PLUGS: Two nos. each on the main tank cover & conservator. 3.4.9 CT TERMINAL BOX: On HV, LV & Neutral terminal turrets as shown in general assembly drawing. If these boxes are removed for any purpose, those should be fitted in position properly. 3.4.10 EARTHING ARRANGEMENT: ABB practice of earthing arrangement is indicated as per drawing no. 1ZYN932342. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 11 of 12 ABB 3.4.10.1 CORE EARTHING: Connecting leads from core and end frame are being terminated at the top of the cover. By connecting to the tank cover, core and end frame get earthed. Insulation resistance between the leads from core and end frames or between lead from core and earth point can be checked by 500V meggar. Leads from end frames are brought out for proper earthing of end frames. 3.4.10.2 EARTHING OF TANK: Two numbers stainless steel earthing pads are provided on the diagonally opposite sides of the tank for connection to the station earth by M.S. flat of size 50 x 6 mm. Please refer G.A. drawing no. for further details. 3.4.10.3 OTHER EARTHING POINTS Earthing points are also provided on turrets for HV bushings, pipe work-tank, cover to supports etc. 3.5 PLEASE REFER PART MARKING AND CABLE WIRING DRAWINGS 2XYN467957C1222 & 2XYN468958C1222 FOR FINAL ASSEMBLY AT SITE 3.6 Marshalling box & Cooler Control Box Tank mounted Marshalling box and cooler control box is provided for transformer. Control accessories are provided in cooler control box, where as Oil & Winding are mounted on marshalling box. All wirings from transformer accessories are also terminated to M.box . This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB INDIA LTD. MANEJA, VADODARA, GUJARAT, INDIA PAGE - 12 of 12 ABB PART 4 OUTLINE DRAWING, PLATES & CIRCUIT DIAGRAMS OF TRANSFORMER LEAFLETS AND CATALOGUES This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 1 of 3 ABB 4.1 LIST OF CUSTOMER DRAWINGS Sr. No. 1 2 3 4 6 7 8 9 10 11 12 13 14 15 DESCRIPTION General Arrangement HV Line OIP Bushing HV-N RIP Bushing LV Bushing Rating and Diagram Plate-English Rating and Diagram Plate-Spanish Valve Schedule Plate Foundation Plan Transport Outline Arrangement Cable Box drawing Schematic of Marshalling Box Schematic of OLTC & RTCC General Arrangement M.BOx General Arrangement of RTCC 4.2 LIST OF REFERENCE DRAWINGS Sr.No. Description DRAWING NUMBER REV INDEX 2XYN460001C1222 2XYN275001C1222 2XYN275002C1222 2XYN275003C1222 2XYN294001C1222 2XYN294002C1222 2XYN460036C1222 2XYN460003C1222 2XYN460011C1222 2XYN460015C1222 2XYN464032C1222 2XYN464034C1222 2XYN464033C1222 2XYN464036C1222 F B B B D A B E A C C C C C Drawing Number Rev Index 1 Part Marking 2XYN467957C1222 B 2 Cable Wiring 2XYN468958C1222 A 3 Earthing Arrangement 1ZYN932342 A This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 2 of 3 ABB 4.3 LIST OF LEAFLETS AND CATALOGUES/O&M MANUALS Sr.No. Component Make 1 WTI & OTI COMEM 2 Buchholz Relay COMEM 3 Pressure Relief Device COMEM 4 Magnetic Oil Level Gauge-Main Tank SUKRUT 5 Magnetic Oil Level Gauge-OLTC SUKRUT 6 Cooling Fan Ziehl Abegg 7 OLTC ABB, SWEDEN 8 Bushings ABB & COMEM 9 Silica gel breather YOGYA 10 Automatic Voltage Regulator A-EBERLE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LTD. MANEJA, VADODARA, GUJARAT, INDIA. Page 3 of 3 1 2 3 4 3527 B 22 $ 22 $ 3200 C TERMINAL NOMENCLATURE TERMINALS H1, H2, H3 X1, X2, X3 H0 B 500 2324 Jack 3800 5000 C 2950 TOP VIEW H0 X2 X1 X3 357 94 H1 PHASE-EARTH 1950 290 1150 H2 85 $ CG OF MAIN TANK DURING ASSESMBLY 7079 ELECTRICAL CLEARANCES IN AIR AS PER IEC (mm) B SIGNAL BOX OF PNT FIRE SYSTEM MOUNTING PROVISION E E 7947 - HV U and W phase height 2079.5 3529 6225 E NOTE: 1. DIMENSIONS EXCEPT RAIL GAUGE AND MINIMUM AIR CLEARANCES HAVE A TOLERANCE OF # 5%. 2. WEIGHTS HAVE A TOLERANCE OF # 5%. 3. ALL BOUGHT-OUT ITEMS SHALL RETAIN THE SAME PAINT SHADE AS SUPPLIED BY OEM. 4. PAINT SHADE : RAL7035 5. THERE CAN BE A MINOR CHANGIS REGARDING THE LOCATION OF FITTINGS. THOSE CHANGES WILL BE INCORPORATED IN AS-BUILT DRAWING. 6.APPROX. TRANSFORMER MASS (EXCLUDING FREE STANDING COOLER BANK) = 148500 KG 7.APPROX COOLER BANK MASS (EACH) = 17540 KG PHASE-PHASE 2650 290 - 2447 Jack A 8652 Overall width 1550 8294 -HV V phase height / overall max height 5854 - HVN bushing height 3200 39 850 - LV and HVN bushing position 785 12 RUNS OF XLPE 630SQ MM 60 850 B 8 4502 - LV busbar height 3527 675 A HV LV HVN 7 LEFT SIDE 830 HV LV HVN 6 HV SIDE RIGHT SIDE D 5 B H3 D 85 $ CHECK FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION MARSHALLING BOX F 16307 Overall length B BOX E LV SIDE D C B No. 28.02.20 AS BUILT RA APR 24.01.20 NIFPS PROVISION ADDED RA APR 24.10.19 MASSES UPDATED 12.10.19 19.09.19 SEISMIC INPUTS INCORPORATED SLK COMMENTS INCORPORATED SLK DATE PROJECT APR RA REMARKS APR APR DRN CKED TITLE: SOLAR PV PLANT AT SANTA ISABEL CHI CLIENT:- E APPROXIMATE MASSES CORE AND WINDING PART 78,700 kg TANK & FITTINGS 64,505 kg OIL MASS (TOTAL) 40,375 kg OIL QUANTITY (TOTAL) 47,500 litre TOTAL TRANSFORMER 183,580 kg SHIPPING MASS (MAIN UNIT-DRY AIR FILLED) CONSULTANT:- EPC CONTRACTOR IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. D 98,000 kg DRAWING TITLE: DRAWING NO GENERAL ARRANGEMENT 176.25MVA, 220/23kV TRANSFORMER C ALL DIMENSIONS ARE IN MM UNLESS STATED OTHERWISE. CHECKED APPROVED DATE 2 3 4 5 6 7 : 2XYN460001C1222 DRAWN 1 :- STERLING & WILSON SOLAR LIMITED SLK APR TKG 09.09.2019 8 SHEET NO PAPER SIZE REV NO. NTS 1 OF 2 A2 F 1 2 3 4 5 6 7 8 LIST OF FITTINGS PART NO. A 1 40 46 9 45 25 E 7 33 B 24 23 4 LIFTING HOOKS 4 TANK EARTHING PADS 2 JACKING PADS 7 AIR RELEASE PLUG ON TRANSFORMER 10 11 1 ** 13 B 14 15 28 16 17 18 19 20 21 8 B 35 22 48 2 16 C 23 SCALE 0.015 B 44 5 34 4 3 B 27 24 26 49 25 B 50 26 27 28 29 19 30 31 11 13 E 20 31 41 ** 36 38 52 33 47 34 35 10 36 37 D 37 43 38 39 40 41 42 43 44 45 46 47 48 14 49 B E 17 15 29 42 51 30 6 50 E E 18 VALVE POSITION INDICATING PLATE 5 9 51 52 53 1 4 2 EARTHING LINK TOP COVER TO TANK 2 HV LINE BUSHINGS 3 HV NEUTRAL BUSHING 1 LV LINE BUSHINGS 3 *** ** ACCESS FOR CORE TO TANK EARTHING 1 SILICAGEL BREATHER FOR OLTC CONSERVATOR 1 TOP FILTER VALVE DN50 1 TOP SAMPLING VALVE DN15 1 BOTTOM SAMPLING VALVE DN15 1 MAIN CONSERVATOR WITH AIR CELL 1 BUCHHOLZ RELAY ISOLATING VALVES DN80 2 MAIN CONSERVATOR DRAIN VALVE DN50 1 RADIATORS WITH LIFT, AIR RELEASE AND DRAIN PLUG 23+1 RADIATOR ISOLATING BUTTERFLY VALVES DN80 46+2 ON LOAD TAP CHANGER WITH DRIVE MECHANISM BOX 1 THERMOMETER POCKET ON COVER 1 COOLING FANS WITH IP54 TERMINAL BOX 1 250MM DIAL SIZE MOLG WITH LOLA CONTACT FOR MAIN CONSERVATOR 1 PRESSURE RELIEF DEVICE 2 DETACHABLE LADDER 1 BUCHHOLZ RELAY DOUBLE FLOAT, DN80 1 ** & RTD 6 AIRCELL INSTRUCTION PLATE 1 SILICA GEL BREATHER FOR MAIN CONSERVATOR 1 EXPANSION BELLOW (DN80) 1 OLTC CONSERVATOR D 1 CT TERMINAL BOX 1-SET SLUDGE REMOVAL VALVE DN32 1 CONSERVATOR TO AIRCELL EQUILIZING VALVE DN25 1 DUMMY FOR PNRV BOX FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION 6 OLTC CONSERVATOR DRAIN VALVE DN25 1 OLTC SUCTION VALVE DN25 1 OSR ISOLATING VALVE DN25 1 PRISMATIC OIL LEVEL GAUGE FOR MAIN CONSERVATOR 1 SET PRISMATIC OIL LEVEL GAUGE FOR OLTC CONSERVATOR DRAIN VALVE FOR FIRE FIGHTING SYSTEM CHECK 1 VALVES FOR NITROGEN INJECTION SYSTEM DN25 1 SET DN200, BUTTERFLY TYPE 2 SET CABLE BOX WITH BUSBAR AND POST INSULATORS 1 SET DGA SERVERON TM1 NIFPS DETECTOR PROVISION AS BUILT 28.02.20 E D NIFPS PROVISION ADDED 12.10.19 SEISMIC INPUTS INCORPORATED SLK B No. PROJECT APR RA COMMENTS INCORPORATED 19.09.19 DATE APR RA MASSES UPDATED 24.10.19 C APR RA 24.01.20 APR SLK REMARKS DRN APR CKED TITLE: SOLAR PV PLANT AT SANTA ISABEL CHI CLIENT:- 1 17 (PROVISION FOR RPRR) F 1 FREESTANDING COOLER BANK WITH TOP AND BOTTOM HEADERS AND ISOLATING VALVES 50NB VALVE C 10+2 MARSHALLING BOX BATH FOR OTI, WTI B 1 BOTTOM FILTER CUM DRAIN VALVE DN50 *** A 2 1 8 21 ABB MONOGRAM PLATE RATING AND DIAGRAM PLATE 6 22 QUANTITY 2 3 53 DESCRIPTION E CONSULTANT:- 1 EPC CONTRACTOR :- STERLING & WILSON SOLAR LIMITED IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. SCALE 0.015 DRAWING TITLE: GENERAL ARRANGEMENT 176.25MVA, 220/23kV TRANSFORMER DRAWING NO DRAWN CHECKED APPROVED DATE 1 2 3 4 5 6 7 : 2XYN460001C1222 SLK APR TKG 09.09.2019 8 SHEET NO PAPER SIZE REV NO. NTS 2 OF 2 A2 F Rated Voltage Phase to-earth Voltage Dry Lightning Impulse 1,2/50µs Wet Switching Impulse Wet Power frequence AC Routine test 1min dry 50Hz Rated Current Creepage Distance 850 kV N/A kV 560 kV 2500 A D2 Threaded hole M8 for pulling wire 825 kg D2 (mm) 60 60 60 60 D9 D3 D9 Cond.area (mm)(mm2) 45 45 600 R492 Additional joint on request 50 48 330 480 $ Position of Test tap Prepared 2017-07-18 Balaji.G.R 2017-07-20 Natalia Gutman 2017-07-20 Approved by Revision A-A H 8 mounting holes 2 3 N1=6 N1=4 N1=Number of holes M12, equipped with thread insert with screw lock, depth 20, for cable lugs. Responsible department Balaji.G.R Modified by 90 $ Position of oil sample valve R8 R30 430 45 C 170 *) WITH PILOT HOLE D=5 Current (A) IEC IEEE 1600 1360 Lower draw rod END SHIELD 1033 5 LOWER DRAW ROD WITH N1=4 OR N1=6 UPPER DRAW ROD End of cable 60 2"-12UN 96 EPOXY INSULATED INSULATED WITH3 mm PRESSBOARD D3 (mm) O *) 40 B 25 A1 Cu Cu/Ag Cu/Sn Cu/Ag Cu Upper draw rod H1 min260 LF170 056-E LF170 056-D Max. Rated H2 Current (A) (mm) 125 2500 125 4000 125 4000 4000 125 3000 125 5000 125 3311 60 COLOUR AIR INSULATOR BROWN PGCO/BK Take over department Title GOE 1175-850-2500-0.3 Used in product GOE 1175-850-2500-0.3 Drawing display updated 4 58 INNER TERMINAL Outer terminal 39 DRAW ROD SYSTEM LF170 059 LF170 057 A Threaded hole M8 for pulling wire 65 28 1175 kV 350 073-A 073-B 073-G 073-L 073-BA 073-AA END-SHIELD LF170 046U LF170 046UP 305 Outer terminal 265 195 335 209 kV Ordering Data: LF170 LF170 LF170 LF170 LF170 LF170 Earthed layer 362 kV H2 Mass OUTER TERMINAL Earthing hole M12 6 INNER TERMINAL / OUTER TERMINALDRAW ROD SYSTEM / OUTER TERMINAL D2 9120 mm BUSHING 1ZSC902362-AAA 2470 3311 60 485 1035 5 The information contained in this document has to kept strictly confidential. Any unautorized use, reproduction, distribution or disclosure to third parties are strictly forbidden. ABB reservs all rights regarding Intellectual Property Rights. © Copyright 2013 ABB. All rights reserved. 5 H2 Bushing Data: B 4 511 A C 3 2 140 This document is issued by means aofcomputerized system. The digitally stored original is ctronically ele approved. The approved document has a date entered in the `Approved'-field. A manual signature is not required. 1 5 Language 82 Order Sheet no. Document no. No. Shts. 2751369-315 6 1 (1) D 1 2 3 FOUNDATION DETAILS FOR COMPLETE A 4 5 6 7 8 3800 TRANSFORMER ASSEMBLY 1900 A LV SIDE 1600 EARTHING POINT FOR NEUTRAL EARTHING POINT FOR MAIN TANK D 3465-Anchor point 2324- Jacking 765 1433 B C D 1433 INSTALLATION CENTER OF GRAVITY OF MAIN TRANSFORMER UNIT 785 1183 25 50 94 1238- Jacking 357 C 1238- Jacking B INSTALLATION CENTER OF GRAVITY OF SINGLE RADIATOR BANK B 2566-Anchor point 2447- Jacking 3965 1785 Jacking load on each pad 49MT SEE DETAIL A 1635 1530 2447-Jacking D EARTHING POINT FOR MAIN TANK 150150 CHECK 2324-Jacking FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION 5000 3800 E 450 HV SIDE COMMENTS INCORPORATED 17.01.20 D B B C B COMMENTS INCORPORATED 19.09.19 No. DATE PROJECT Base plate of cooler bank structure (Part of transformer supply) SLK CABLE BOX FOUNDATION REMOVED & ANCHOR POINTS INCREASED 04.10.19 APR RA FOUNDATION DRAWING UPDATED BASED ON SEISMIC INPUTS 14.10.19 REMARKS APR RA APR SLK APR DRN CKED TITLE: SOLAR PV PLANT AT SANTA ISABE CLIENT:- E 450 E BOX D 5518 ORMER. D 3985 150150 D 1600 1900 CONSULTANT:- C D NOTE : 1. The level of loading surface should be adjusted with # 3 mm. FOUNDATION FOR COOLER BANK 2. The level of loading surface should be formed within one foundation. WEIGHT ON EACH BLOCK 113344 N (approx.) 3. Earthing terminal for transformer groundiing available on tank. 4. Approx. Transformer mass (excluding free standing cooler bank) = 148500 kg TRANSFORMER BASE AND 5. Approx Cooler bank mass (each) = 17540 kg ERTHING TERMINAL LOCATION 176.25MVA, 220/23kV TRANSFORMER 6. Anchor box design and provision required to ensure Seismic proper condition anchoring (Civil under scope). 2XYN460003C1222 7. One single Monolithic block is recommended for transformer foundation. and cooler bank SLK 8. Overall dimensions and weights have tolerence of # 5% APR 9. Refer 2XYN931510C1222 for Seismic report. TKG **TRANSFORMER SHOULD BE ANCHORED TO AVOID OVERTURING DURING SEISMI EPC CONTRACTOR :- STERLING & WILSON SOLAR LIMITED IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. DRAWING TITLE: DRAWING NO : DRAWN CHECKED NTS NO PAPER A2 SIZE APPROVED DATE 1 2 3 4 5 6 7 09.09.2019 8 1 OF 3 SHEET REV NO. E 1 2 3 4 5 6 7 8 D FOUNDATION DETAILS FOR MAIN TRANSFORMER UNIT A A 2- STOPPERS (400X100X50; ST52-3 (NOT IN ABB SCOPE OF SUPPLY) EMBED STEEL PLATE AS PER CIVIL DESIGN; MATERIAL: St 52-3 (NOT IN ABB SCOPE OF SUPPLY) B B C C D D CHECK A 14 Base of transformer tank All shear wedges BOX FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION E D COMMENTS INCORPORATED 17.01.20 14.10.19 a.Total 3 anchor bolts of M48 per Achor point (No in ABB Scope of supply). b. Maximum Traction Force per Anchor point is 526446 N. c. Maximum Shear Force per Anchor point is 329997 N. SOLAR PV PLANT AT C 04.10.19 B 19.09.19 No. DATE PROJECT SLK CABLE BOX FOUNDATION REMOVED & ANCHOR POINTS INCREASED COMMENTS INCORPORATED REMARKS APR RA FOUNDATION DRAWING UPDATED BASED ON SEISMIC INPUTS APR RA APR SLK APR DRN CKED TITLE: SANTA ISABE CLIENT:- 100 E CONSULTANT:- 20 250 E EPC CONTRACTOR :- STERLING & WILSON SOLAR LIMITED 150 DRILL HOLES 150 600 IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. n 52 FOR ANCHOR BOLTS M48. (ANCHOR BOLTS NOT IN ABB SCOPE OF SUPPLY) DETAIL A SCALE 0.084 DRAWING TITLE: DRAWING NO TRANSFORMER BASE AND ERTHING TERMINAL LOCATION 176.25MVA, 220/23kV TRANSFORMER DRAWN : 2XYN460003C1222 SLK APR APPROVED TKG DATE 09.09.2019 SHEET NTS NO 2 OF 3 **TRANSFORMER SHOULD BE ANCHORED TO AVOID OVERTURING DURING SEISM CHECKED 1 2 3 4 5 6 7 8 PAPER REV A2 SIZE NO. E 1 2 3 4 5 6 7 8 FOUNDATION DETAILS FOR SINGLE DRADIATOR BANK 3800- ANCHOR POINT A 1900 175 E A 1 MM GAP REQUIRED BETWEEN STOPPERS & BASE PLATE A8 All shear wedges 175 175 E 175 2- STOPPERS (100x100x30; ST52-3) 8 mm weldment (NOT IN ABB SCOPE OF SUPPLY) B B 3200- ANCHOR POINT 1600 ANCHOR BOX PROJECTION C E HOLES D C n 28 FOR 4 ANCHOR BOLTS OF M24. a.Total 4 anchor bolts of M24 per Achor point (Not in ABB Scope of supply). INSTALLATION CENTER OF GRAVITY b. Maximum Traction Force per Anchor point is 65165 Newton. OF SINGLE RADIATOR BANK c. Maximum Shear Force per Anchor point is 30112 Newton. D CHECK BOX FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION E D C B COMMENTS INCORPORATED 17.01.20 FOUNDATION DRAWING UPDATED BASED ON SEISMIC INPUTS 14.10.19 CABLE BOX FOUNDATION REMOVED & ANCHOR POINTS INCREASED 04.10.19 COMMENTS INCORPORATED 19.09.19 No. DATE PROJECT REMARKS RA APR SLK RA APR APR SLK APR DRN CKED TITLE: SOLAR PV PLANT AT SANTA ISABE CLIENT:- E E CONSULTANT:- EPC CONTRACTOR :- STERLING & WILSON SOLAR LIMITED 175 IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. DRAWING TITLE: DRAWING NO TRANSFORMER BASE AND ERTHING TERMINAL LOCATION 176.25MVA, 220/23kV TRANSFORMER 2XYN460003C1222 : SLK DRAWN APR CHECKED SHEET NTS NO 3 OF 3 **RADIATOR BANK SHOULD BE ANCHORED TO AVOID OVERTURING DURING SEISMICTKGEVENT.** PAPER A2 SIZE APPROVED DATE 1 2 3 4 5 6 7 09.09.2019 8 REV NO. E 1 2 3 4 5 6 7 8 Transport Center of gravity 2159 2169 A A 100 4116 - Overall height Transport Center of gravity B 1) 1) B 1) 1) 1) Impact recorders 1663 Jacking Pad Jacking Pad C C 2913 5818 - Base length 2866 - Base width 1528 D CHECK 100 3056 - Overall width D BOX FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION No. DATE PROJECT REMARKS CKED DRN TITLE: SOLAR PV PLANT AT SANTA ISABEL CHI CLIENT:- E E CONSULTANT:- 4604 EPC 8212 - Overall length CONTRACTOR IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. Note: 1. Transport mass (dry air filled) = 98,000 kg. 2. The transformer shall be dispatched with dry air at positive pressure. 3. The transformer tank is fitted with a pressure regulating device and pressure gauge for monitoring internal air pressure during transit. 4. Total 8 latching points provided on four sides of tank marked by 1). 3. Transport weight & dimensions have a tolerance of # 5%. 4. Impact recorders (on returnable basis) are provided on transformer during transport. 7. Total 4 numbers of lifting hooks with capacity 40tons each. 8. SFRA bushings are to be mounted during transport. DRAWING TITLE: DRAWING NO TRANSPORT DETAILS 176.25MVA, 220/23kV TRANSFORMER 3 4 5 6 7 2XYN460011C1222 SLK CHECKED APR TKG 10.09.2019 DATE 2 : DRAWN APPROVED 1 :- STERLING & WILSON SOLAR LIMITED 8 SHEET NO PAPER SIZE REV NO. NTS 1 OF 1 A2 A 1 2 3 4 5 6 7 8 5 GLAND PLATE DETAIL 1 4 3 2 1780 650 650 126 8 228 422 228 422 228 A 157 175 175 175 1188 175 175 A B B SEE DETAILA Holes scribed indicating cable knockots through gland plate. Drilling to be done at site as per cable dimension. cable support Supported from tank C C 1660 175P*5 875 = SCALE 0.042 1058 M12 NUT ,BOLT & WASHER ASSEEMBLY(MATERIAL STAINLESS STEEL) FOR CABLE FIXING WITH BUSBAR BASED ON CABLE TERMINATION KIT. 794 GLAD PLATE FROM CABLE FIXING HOLE LV BUSHING D D CHECK BOX FOR INFORMATION FOR AS-BUILT APPROVAL ONLY FABRICATION X DETAIL A SCALE 0.200 7 Typical section showing the termination of cables 12 runs of 1 core x 630sq.mm XLPE cable (not in ABB scope of supply) CLEARANCE IN AIR FILLED CABLE BOX Ph to Ph. 350 6 ITEM NO. E LV CABLE BOX 3 FLEXIBLE CONNECTOR 4 5 110 10 6 7 SCALE 0.200 NAME 1 2 180 8 9 10 Ph. to Earth LV DISCONNECTING CHAMBER BUS BAR SUPPORT INSULATOR GLAND PLATE (UNDRILLED) INSPECTION COVER FOR CABLE BOX INSPECTION COVER FOR DC CHAMBER LOUVERS M12 NUT ,BOLT & WASHER ASSEMBLY C B No. SLK RA 18/10/2019CUSTOMER COMMENTS INCORPORATED 18/10/2019CUSTOMER COMMENTS INCORPORATED RA SLK DATE PROJECT DRN CLIENT:- E 1 1 3 CONSULTANT:- 3 6 1 EPC CONTRACTOR IMPERIA, A-25, MOHAN CO-OPERATIVE INDUSTRIAL ESTATE, MATHURA ROAD, NEAR SARITA VIHAR METRO STATION, DELHI 110044 E-mail : delhi.solarsterlingwilson.com. Website : www.sterlingandwilson.com. 2 2 2 :- STERLING & WILSON SOLAR LIMITED DRAWING 36 SETS TITLE: LV CABLE BOX ASSEMBLY NOTE: DRAWING NO : 1. GLAND PLATE TO BE DRILLED AT SITE BY CUSTOMER AS PER REQUIREMENT. 2XYN460015C1222 2. CABLE BOX IS SUITABLE FOR 12 RUNS x 1 CORE x 630sq. mm XLPE CABLE PER PHASE. LINE CURRENT : 4424A DRAWN SHEET NO AND TOLERANCES SHALL BE AS PER GENERAL ARRANGEMENT DRAWING.RA REQUIRED CROSS SECTION AREA FOR BUSBAR: 34003.SQDIMENSIONS MM CHECKED APR PAPER SIZE GIVEN CROSS SECTION AREA FOR BUSBAR: 4000 SQ4.MMFOR OTHER DIMENSIONS, REFER GENERAL ARRANGEMENT DRAWING. APPROVED TKG 5. ALL HARDWARE EXCEPT CABLE FIXING ARE IN ABB SCOPE OF SUPPLY REV NO. BUSBAR CROSS SECTION CALCULATION DATE 1 2 3 4 5 6 7 CKED SOLAR PV PLANT AT SANTA ISABEL CHI 320 QTY. REMARKS TITLE: 17.10.2019 8 NTS 1 OF 1 A2 C A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 SRS CKED AS AS FOR FABRICATION DRN AKP INFORMATION ONLY REMARKS Revised as built Revised as per customer comment FOR APPROVAL 06.03.20 19.09.19 AS-BUILT CHECK BOX R2 R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE TKG AS AKP REV NO. PAPER SIZE R2 A3 1 OF 31 NTS No. PROJECT TITLE: CLIENT:- CONSULTANT:- DRAWN 09.09.2019 SHEET NO FOR 176.25MVA TRANSFORMER SCHEMATIC OF COOLER CONTROL STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464032C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 AS AS FOR FABRICATION CKED INFORMATION ONLY DRN AKP SRS FOR APPROVAL Revised Revised as built AS-BUILT CHECK BOX 19.09.2019 06.03.2020 SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS R1 DATE TKG AS AKP REV NO. PAPER SIZE R2 A3 1 OF 2 NTS R2 No. PROJECT TITLE: CLIENT:- CONSULTANT:- DRAWN 09.09.2019 SHEET NO FOR 176.25MVA TRANSFORMER GENERAL ARRANGEMENT OF M.BOX STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464033C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 AS-BUILT CHECK BOX DATE R2 06.03.2020 R1 19.09.2019 No. FOR APPROVAL Revised INFORMATION ONLY REMARKS Revised as built TKG AS AKP CKED AS AS FOR FABRICATION SRS AKP REV NO. PAPER SIZE R2 A3 2 OF 2 NTS DRN SOLAR PV PLANT AT SANTA ISABEL CHILE PROJECT TITLE: CLIENT:- CONSULTANT:- DRAWN 09.09.2019 SHEET NO FOR 176.25MVA TRANSFORMER GENERAL ARRANGEMENT OF M.BOX STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464033C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 4 5 6 7 8 9 SCHEMATIC OF OLTC & DIGITAL RTCC 3 10 11 INFORMATION ONLY FOR FABRICATION Ajay Ajay FOR APPROVAL SRS AS-BUILT CHECK BOX AKP AS AKP REV NO. PAPER SIZE R2 A3 1 OF 12 CKED Revised as built DRN Revised as per customer comment SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS R2 06.03.2020 DATE R1 19.09.2019 No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED Ajay Ajay FOR FABRICATION 06.03.2020 INFORMATION ONLY 19.09.2019 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 2 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED Ajay Ajay FOR FABRICATION 06.03.2020 INFORMATION ONLY 19.09.2019 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 4 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 FOR APPROVAL INFORMATION ONLY FOR FABRICATION Ajay Ajay AS-BUILT CHECK BOX AKP SRS AS AKP REV NO. PAPER SIZE R2 A3 3 OF 12 CKED Revised as per customer comment Revised as built DRN 19.09.2019 06.03.2020 SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS R1 DATE R2 No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED Ajay Ajay FOR FABRICATION 06.03.2020 INFORMATION ONLY 19.09.2019 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 5 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED AJAY AJAY FOR FABRICATION 18.01.2020 INFORMATION ONLY 19.09.2019 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 6 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A AKP SRS AJAY AJAY FOR FABRICATION Revised INFORMATION ONLY Revised as per customer comment FOR APPROVAL 06.03.2020 AS-BUILT CHECK BOX DATE 19.09.2019 TKG AS AKP SHEET NO R2 A3 7 OF 12 NTS PAPER SIZE CKED R2 DRN R1 REMARKS No. SOLAR PV PLANT AT SANTA ISABEL CHILE PROJECT TITLE: CLIENT:- CONSULTANT:- STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: DRAWN 09.09.2019 REV NO. FOR 176.25MVA TRANSFORMER SCHEMATIC OF OLTC & DIGITAL RTCC CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED G A 11 B 10 B 9 C 8 C 7 D 6 D 5 E 4 E 3 F 2 F G H 1 A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP AKP CKED AJAY AJAY FOR FABRICATION 06.03.2020 INFORMATION ONLY 19.09.2019 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 8 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 AVR 5 6 7 8 9 10 11 SRS AJAY AJAY FOR FABRICATION AKP INFORMATION ONLY Revised as built FOR APPROVAL Revised as per customer comment AS-BUILT CHECK BOX 06.03.2020 AS AKP REV NO. SHEET NO R2 A3 9 OF 12 CKED DATE 19.09.2019 DRN R2 REMARKS No. R1 SOLAR PV PLANT AT SANTA ISABEL CHILE PROJECT TITLE: CLIENT:- CONSULTANT:- TKG NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: DRAWN 09.09.2019 PAPER SIZE FOR 176.25MVA TRANSFORMER CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED 1 2 - + OLTC Upper Limit Reached - + 3 67 4 - OLTC in Local mode 3 + 5 69 6 7 70 71 9 10 5 11 12 - 72 76 77 14 79 15 80 13 - + - + 16 81 7 M.BOX Failure of Normal source & Transfer to standby supply fail. - + Standby supply fail + 6 Supply changeover fail - + Fan group-2 Fail - + Fan Group-1 Fail - + Cooler Control Supply Fail REG-D + 75 BINARY INPUT OLTC Control supply fail 190V..250 AC/DC - 8 - + (common) 4 74 - + LTC in Remote Auto mode - + OLTC in Remote Manual mode - + 68 A + OLTC Lower Limit Reached B -X1 66 Tap changer motor Trip 2 - Common 82 Common Thermal overload trip 78 OLTC in SCADA mode 73 C D E F G H 1 65 Tap Change incomplete 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED AJAY AJAY FOR FABRICATION 06.03.2020 INFORMATION ONLY 19.09.2019 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 10 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 DRN AKP SRS CKED AJ AY AJ AY FOR FABRICATION R ev is ed as b uilt INFORMATION ONLY R ev is ed as p er customer comment FOR APPROVAL 06.03.2020 AS-BUILT CHECK BOX 19.09.2019 SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS R2 DATE R1 No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 11 OF 12 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS SCHEMATIC OF OLTC & DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED AVR A Revised as built DRN AKP SRS CKED AJAY AJAY FOR FABRICATION Revised as per customer comment INFORMATION ONLY 06.03.2020 FOR APPROVAL DATE 19.09.2019 AS-BUILT CHECK BOX R2 REMARKS No. R1 SOLAR PV PLANT AT SANTA ISABEL CHILE PROJECT TITLE: CLIENT:- CONSULTANT:- STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: DRAWN 09.09.2019 TKG AS AKP 12 OF 12 NTS SHEET NO R2 A3 REV NO. PAPER SIZE FOR 176.25MVA TRANSFORMER SCHEMATIC OF OLTC & DIGITAL RTCC CHECKED 2XYN464034C1222 DRAWING NO : DATE APPROVED G A 11 B 10 B 9 C 8 C 7 D 6 D 5 E 4 E 3 F G H 2 F 1 A B C D E F G H 1 3 4 5 6 7 8 9 10 GENERAL ARRANGEMENT OF DIGITAL RTCC PANEL 2 11 06.03.20 REMARKS Revised as per customer comment Revised as built DRN AKP SRS CKED Ajay Ajay FOR FABRICATION 19.09.19 INFORMATION ONLY R2 FOR APPROVAL R1 DATE AS-BUILT CHECK BOX No. SOLAR PV PLANT AT SANTA ISABEL CHILE PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 1 OF 4 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS GENERAL ARRANGEMENT OF DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464036C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED Ajay Ajay FOR FABRICATION 06.03.20 INFORMATION ONLY 19.09.19 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 2 OF 4 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS GENERAL ARRANGEMENT OF DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464036C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 2 3 4 5 6 7 8 9 10 11 Revised as per customer comment Revised as built DRN AKP SRS CKED Ajay Ajay FOR FABRICATION 06.03.20 INFORMATION ONLY 19.09.19 FOR APPROVAL R2 AS-BUILT CHECK BOX R1 DATE SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP PAPER SIZE R2 A3 3 OF 4 REV NO. SHEET NO FOR 176.25MVA TRANSFORMER DRAWN 09.09.2019 NTS GENERAL ARRANGEMENT OF DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: CHECKED 2XYN464036C1222 DRAWING NO : DATE APPROVED A B C D E F G H 1 Right Side view GASKET PROFILE 2 3 4 Front view (DOOR OPEN) 5 Left Side view 6 Front view (DOOR CLOSED) 3D VIEW FOR REFERENCE NOTE: 1. MATERIAL: MIN. 2.5 mm THICK CRCA SHEET. 2. Paint shade (external) : RAL 7035 outside and glossy white inside as per powder coating (1ZYN206004) Paint thickness (internal & external) : 60 micron minimum 3. Undrilled gland plate and double compression cable glands suitable For following sizes shall be provided at the bottom. (a) 1100 volts grade PVC insulated Stranded 2.5 mm2 copper cable with armour : 4. Gland shall be dust proof, screw on and double compression type and made of brass. The gland shall have provision for securing armour of the cable separately and shall be provided with earthing tag. The gland shall conform to BS:6121 and shall be nickel plated 5. Degree of Ingress Protection shall be IP-31. 6. Weight of RTCC is appx. 250 Kg. 7. Size & quantity of gland is subject to change in final stage. 8. EARTHING TERMINALTwo Nos. earthing bosses are provided with tapped hole of size M10.Two plain washers and a bolt of size M10X20 is provided with each earthing boss. 9. The gland shall project at least 25 mm above gland plate to prevent entry of moisture in cable crutch, gland plate shall have provision for some future glands to be provided later. 9 10 10.All doors, removable covers and plates shall be gasketed all around with neoprene gaskets.Ventilation louvers if provided shall have screens and filters. The screens shall be made of either brass or GI wire mesh with a graduation of 1 mm or less.applicable for indoor control cubical. 11.Doors shall be gasketted all around with suitably profiled neoprne gaskets. The gaskets shall be tested in accordance with approved quality plan, IS: 1149 and IS: 3400. 12. EARTHING TERMINALTwo earthing terminals suitable for connection to 75 x 12 mm galvanised steel flat shall also be provided 8 13. All gasketed surfaces shall be smooth straight and reinforced if necessary to minimize distortion to make a tight seal. 14. Ventilating Louvers, if provided, shall have screen and filters. The screen shall be fine wire mesh of brass. 15. Component & its arrangement is subject to change in final stage. 7 11 AS-BUILT CHECK BOX FOR APPROVAL INFORMATION ONLY FOR FABRICATION Ajay Ajay CKED AKP SRS DRN Revised as per customer comment Revised as built SOLAR PV PLANT AT SANTA ISABEL CHILE REMARKS R1 19.09.19 DATE R2 06.03.20 No. PROJECT TITLE: CLIENT:- CONSULTANT:- TKG AS AKP REV NO. SHEET NO R2 A3 4 OF 4 NTS GENERAL ARRANGEMENT OF DIGITAL RTCC STERLING & WILSON SOLAR LIMITED EPC CONTRACTOR :- DRAWING TITLE: DRAWN 09.09.2019 PAPER SIZE FOR 176.25MVA TRANSFORMER CHECKED 2XYN464036C1222 DRAWING NO : DATE APPROVED 1 2 3 4 5 102 101 103 6 7 8 216 217 104 A A 563 564 236 228 229 501 B B 321 502 We reserve all rights in this nt docume and in the information contained therein.ction, Reprodu use or disclosure to third parties express without authority C is strictly forbidden. ABB 570 571 C 572 230 573 574 503504 SR. NO. 231 1 Main & OLTC conservator HV Loose Turrets LV Loose DC CHAMBER LV cable box 2 238 101 102, 103, 104 105 106 1 3 1 1 Buchholtz Relay Pipe HV&LV Air Vent Pipe OLTC OSR PIPE Conservator Equalizer Pipe Main Conservator Breather Pipe OLTC Conservator Breather Pipe OLTC Suction Pipe Cooler pipe line Cooler pipe reducer PRD pipe loose 201 TO 206 207 TO 212 213 TO 215 216, 217 218 TO 221 222 TO 224 228 TO 235 236 237,238 6 6 3 2 4 3 3 8 4 2 H Support HEADER ASSEMBLY INCLINED SUPPORT HORIZONTAL SUPPORT PIPE SUPPORT 1 PIPE SUPPORT 2 CROSS ANGLE TIE HORIZONTAL ANGLE TIE Cross radiator tie long Cooler pipe support with c clamp 301 TO 302 303 304 TO 307 308 TO 309 310 TO 313 314 TO 317 318 319 320 321 2 1 4 2 4 4 8 2 8 2 sets Main Conservator Supports Expansion Bellow Support-1 Expansion Bellow Support-2 OLTC Bevel Gear Support OLTC Suction Pipe Support Ladder with anti-climb door Radiator Ties (1ZYN934020) 501, 502 503 504 505 511 TO 513 529 536 537 TO 560 561 562 563,564 565,566,567 568,569 570 2 4+4 4+4 1 3 1 40 24 1 4 2 3 2 12 601 to 605 606 607 608 5 1 3 3 PIPE WORK 237 3 225 TO 227 COOLER BANK (2 SET ;HV & LV SIDE) D 4 SUPPORTS 601 233 PART NO. QUANTITY MAIN COMPONENT 106 105 DESCRIPTION 232 E FAN BRACKET WITH 2NOS U-BOLTS EACH E 604 reviewProduction COPPER FLATS & FLEXIBLE 5 602 605 603 Based on Neutral flat with joint Neutral flexible Cable box bus bar Cable box flexible Reg. 1ZXX469152 engineering Design Inspection engineering review engineering review Cable tie horizontal Cross cable tie Expansion Bellow Support-1&2 Cable support cable box support Header cable tray support Prepared 235 234 568 565 566 567 2 SETFO Approved Take -- APR 569 Mass 3 4 ALL THE DIMENSION 5 ARE IN MM UNLESS Part number added Rev Ind OTHERWISE SPECIFIED. Revision 6 RA Appd 24/01/20 Date B over Part Marking department 9808298721 kg E Scale 0.020 Language en Order Document 7 D department 13156 ABB INDIA LIMITED 2XYN468957C1222 Revision B 1 Responsible RA Title No. C No. 8 Page 1 Total 2 1 2 3 4 5 6 307 7 8 317 313 316 A A 306 218 312 308 211 212 303 210 219 220 B 207 B 209 208 305 221 304 315 We reserve all rights in this nt docume and in the information contained therein.ction, Reprodu use or disclosure to third parties express without authority C is strictly forbidden. ABB 314 309 301 222 C 311 310 302 SCALE C 0.040 319 223 201 202 204 203 205 206 D D 224 225 226 E E E 227 214 318 reviewProduction 213 320 SCALE Based 0.040 on Reg. 1ZXX469152 engineering Design Inspection engineering review engineering review 215 Prepared Responsible RA SETFO Approved Take -- APR Mass B 1 2 3 4 ALL THE DIMENSION 5 ARE IN MM UNLESS Part number added Rev Ind OTHERWISE SPECIFIED. Revision 6 RA Appd 24/01/20 Date Part Marking department 9808298721 kg Order Document 7 0.031 department 13156 ABB INDIA LIMITED 2XYN468957C1222 Revision B over Scale Title No. No. 8 Language en Page 2 Total 2 1 2 3 4 5 6 307 7 8 317 313 316 A A 306 218 312 308 211 212 303 210 219 220 B 207 B 209 208 305 221 304 315 We reserve all rights in this nt docume and in the information contained therein.ction, Reprodu use or disclosure to third parties express without authority C is strictly forbidden. ABB 314 309 301 222 C 311 310 302 SCALE C 0.040 319 223 201 202 204 203 205 206 D D 224 225 226 E E E 227 214 318 reviewProduction 213 SCALE Based 0.040 on Reg. 1ZXX469152 engineering Design Inspection engineering review engineering review 215 Prepared Responsible RA SETFO Approved Take -- APR Mass 1 2 3 4 ALL THE DIMENSION 5 ARE IN MM UNLESS Rev Ind OTHERWISE SPECIFIED. Revision 6 Appd Date Part Marking department 9808298721 kg Order Document 7 0.031 department 13156 ABB INDIA LIMITED 2XYN468957C1222 Revision A over Scale Title No. No. 8 Language en Page 2 Total 2 1 2 3 4 5 6 7 8 A B B We reserve all rights in ntthis and docume in the information contained therein. ction,Reprodu use or disclosure to third parties without express authority C is strictly forbidden. ABB A C C D D CABLE SCHEDULE S. No. Main MOLG 3 Oil surge relay Fans 5 OLTC PRESSURE RELAY 6 7 1 1 1 11 12 14 Pressure relief device (PRD) 2 2 6 core 1 Buchholtz relay 1 1 415V AC 3-Ph 4W supply to DM box Current transformer (CT) 1 1 b) H0 1 - 1 - 2 c)X1(WTI) 3 1 1ZBA217004-AV D=10 ;L=173 Based Part ID on No. Prepared Responsible Approved Take Revision Mass APR Rev 1 2 3 4 5 Ind Revision 6 Appd Date ABB A INDIA 7 over - - - - - 15 10 10 15 15 - E - - - - 4 core 15 - 2 core15 - 2 core 15 2 core 15 Material XYN468958_CABLE_WIRING RA 15 - 1ZBA135003-X Cable Supp100 Dimension Reg. - 240 - 1 Unit Item Quantity - 15 2 core a) H2 E 4 core 1 1 220AC SUPPLY TO DGA 8 review 1 20 15 1 review Production engineering 1 12 DGA engineering Design review 1 12 PRV OLTC 7 engineering 1 OLTC Magnetic oil level gauge 1 (MOLG) 1 4 Inspection Cable details (Armoured cable) Cables/ Total Total component Qty. 2.5 mm2 4.0 mm2 Qty. (m) Qty. (m) Description 1 2 E Component ID Description 0.1 Mass Rem Scale Title Cable wiring 0.030 department department en Order 13156 LIMITED 2XYN468958C1222 Document No. 8 Page 1 Total 1 ⊆≡♥〉 ∂±≈〉 ⊆≡♥∂←∂°± ⇒↓↓≈〉 ⇒⊆⇒∫ ñ⌠⊄〉 ⊕∅∇∫⇒⇔ ⌠ ⊕∅∇∫∉ ⊕∅∇ ⇒⊆⇒∫ ⇒⊆⇒∫ ⇒⊆⇒∫ ⇒⊆⇒∫ ⇒⊆⇒∫ ⊕∅∇∫⊕ ⊕⇑⇒∫⇐ ⌡ ⌡ ñ⌠∩〉 〉ñ〉⌡〉 ⊄ ∩ √↔≡″ ∈♠±↔∂↔ƒ ∉↑↔ √⇔ ⇔∂″≡±←∂°± ⊇±∂↔ ⇑←≡≈ °± ⊆≡÷ ∇° ∉↑≡↓↑≡≈ ⊆≡←↓°±←∂≥≡ ≈≡↓↑↔″≡±↔ ⇑〉♠↑≥∂ °•± ⊄∉⊄⇔ ⇒↓↓↑°♥≡≈ ⊄×≡ °♥≡↑ ≈≡↓↑↔″≡±↔ ⇒∫ ⇐⇒⊂⊂〉 ∉⇒√∇ ∪⇒⊂⋅∨⊆ ⊂⊄∨∨ ⊂⊄⊇⇔ ∨⇒⊆⊄⋅√∇¬ ⊄∨⊆√∇⇒ ∨⇒⊆⊄⋅√∇¬ ⇐⇒⇑∨ 〉 ⇐⇒⊂⊂ ⋅∨∩〉⊂⇐⊆∨∪ 〉 ⇐⇒⊂⊂ ⋅∨∩〉⊂⇐⊆∨∪ ⇒∫ ⋅∨∩〉∇⊇⊄ ⇒∫ ∉⇒√∇ ∪⇒⊂⋅∨⊆ ⇒∫ ⋅∨∩〉∇⊇⊄ ∇√⊄⊆√∨⊆⊇⇑⇑∨⊆ ∠∫⊆√∇¬ ⇐∠∉∉∨⊆ ⊂⊄⊆√∉ ↔≡↑∂≥ √⇔ ⇔≡←…↑∂↓↔∂°± ⊄∂↔≥≡ ←← ⊗×÷ℜ ⊆≡″〉 ⊂…≥≡ ∨⇒⊆⊄⋅√∇¬ ⇒⊂⊂∨⇑∅ ±÷♠÷≡ 〉⊂≡×↑ ⊆≡♥∂←∂°± ⇔↔≡ ≡± ⊄°↔≥ ″←← ⊗×÷ℜ ∠↑≈≡↑ ∉÷≡ ⊂⊄⇒∇⇔⇒⊆⇔ ⇒ ⇔°…♠″≡±↔ ∇°〉 ⇒←≡ ⇑↑°♦± ⇑°♥≡↑∂ ↔≈〉 …°±↔〉 ⊕∅∇ ∫ INSTRUCTION MANUAL Oil Temperature Indicator type “OTI / eOTI” Winding Temperature Indicator type “WTI / eWTI” 5COW423700 – REV_E I II CONTENTS 1. SAFETY...................................................................................................................... 1 1.1 Safety instructions....................................................................................................... 1 1.2 Specified applications ................................................................................................. 1 1.3 Safety notes on the equipment operation ................................................................... 1 2. DRAWING .................................................................................................................. 2 2.1 OTI/WTI/eOTI/eWTI .................................................................................................... 2 2.2 Bulbs ........................................................................................................................... 4 3. OPERATING PRINCIPLE .......................................................................................... 5 3.1 Oil temperature indicator (OTI) – Oil temperature indicator with digital and analog output (eOTI) .................................................................................................................... 5 3.2 Winding Temperature Indicator (WTI) – Winding Temperature Indicator with digital and analog output (eWTI) ................................................................................................. 5 3.3 Outputs ....................................................................................................................... 6 3.4 Technical features....................................................................................................... 6 3.5 Tests ........................................................................................................................... 7 4. INSTALLATION.......................................................................................................... 8 4.1 Flange connection....................................................................................................... 8 4.1 Elastic Suspension (optional) ...................................................................................... 8 5. ELECTRICAL CONNECTION .................................................................................... 9 5.1 Wiring diagrams .......................................................................................................... 9 5.1.1 OTI – eOTI (2 , 4 contacts) ................................................................................... 9 5.1.2 WTI – eWTI (2 , 4 contacts) ................................................................................. 9 5.1.3 Pt100 .................................................................................................................... 9 5.2 Micro switches and PT100 (optional) ........................................................................ 10 5.2.1 Setting ................................................................................................................. 10 5.3 ΔT calibration for thermal Image (WTI / eWTI).......................................................... 11 5.4 eOTI/eWTI adding terminals ..................................................................................... 11 6. OPERATION AND MAINTANENCE ........................................................................ 12 6.1 Operation and maintenance...................................................................................... 12 6.2 Storage ..................................................................................................................... 12 APPENDIX A: MODBUS COMMUNICATION................................................................... 13 A1: MODBUS register ..................................................................................................... 13 A1.1 MODBUS address ............................................................................................... 14 APPENDIX B: I2-∆T CURVES .......................................................................................... 15 B1: Example: how to utilize the curve ............................................................................. 15 B2: Nominal CT current: 1 A ........................................................................................... 16 B3: Nominal CT current: 1.5 A ........................................................................................ 17 B4: Nominal CT current: 2 A ........................................................................................... 18 B5: Nominal CT current: 4 A ........................................................................................... 19 B6: Nominal CT current: 5 A ........................................................................................... 20 1. SAFETY 1.1 Safety instructions Make sure that any personnel installing and operating the thermometers: - Are technically qualified and competent. - Fully comply with these assembling instructions. Improper operations or misuse could cause danger to: · Life and limb. · To the equipment and other assets of the operator. · To the equipment proper, function. Safety instructions in this manual are shown in three different forms to emphasize important information. WARNING This information indicates particular danger to life and health. Disregarding such a warning can lead to serious or fatal injury. CAUTION This information indicates particular danger to equipment and/or other property of the user. Serious or fatal injury cannot be excluded. NOTE This note gives important and specific information concerning the equipment. 1.2 Specified applications The thermometer is used for oil-insulated transformers to measure the temperature of transformer oil (OTI) or the windings temperature (WTI) using the thermal image principle. It is important to observe the limit values indicated on the nameplate and in the manual before commissioning the device. 1.3 Safety notes on the equipment operation Electrical installation is subject to the relevant national safety rules. It is mandatory to connect the grounding cable because of safety reason. CAUTION Installation, electrical connection and fitting the device have to be carried out by qualified personnel and only in accordance to this instruction manual. It is responsibility of the user to make sure that the device is used for specified application only. For safety matters, please avoid any unauthorized and improperly works. WARNING All relevant fire regulation must be strictly observed. 1 2. DRAWING 2.1 OTI/WTI/eOTI/eWTI The dimensions of the following drawings are valid for the devices (with connection flange) - OTI: oil temperature indicator WTI: winding temperature indicator eOTI: oil temperature indicator with digital and analogue output eWTI: winding temperature indicator with digital and analogue output 2 Fig. 1 3 2.2 Bulbs Fig. 2 Fig. 3 4 3. OPERATING PRINCIPLE 3.1 Oil temperature indicator (OTI) – Oil temperature indicator with digital and analog output (eOTI) These devices are designed to measure the temperature of the insulating oil inside of power transformer tanks. It’s possible to fit up to 5 change-over micro switches suitable to control cooling equipment’s and protection circuits of transformer (alarm and trip). The bulb of thermometer detects the transformer oil temperature variations generating a contraction or expansion of the capillary connected to the pointer shaft. The adjustable switching system connected to the pointer shaft provide the desired alarm/trip signals. The electronic version of this kind of device, reading the signal from a PT100, give like available: - Analogue output 4-20 mA - Modbus RTU communication (optional) 3.2 Winding Temperature Indicator (WTI) – Winding Temperature Indicator with digital and analog output (eWTI) The winding is a “high temperature” component in oil transformers, subjected to fast temperature changes. Thus, an indirect system is used to measure the winding temperature because it is dangerous to place a sensor close to the winding. This method is called Thermal Image principle. This instrument is designed to measure the temperature of winding by using a special bulb surrounded by a heating resistance through which passes a current proportional to the winding current under certain load and temperature conditions. It’s possible to adjust the heating system by using a potentiometer placed on the instrument dial. As indicated for OTI, this special bulb detects the temperature variations generating a contraction or expansion of the capillary connected to the pointer shaft. The adjustable switching system connected to the pointer shaft provide the desired alarm/trip signals. It is possible to fit up to four change-over micro switches suitable to control cooling equipment and protection circuits of transformer (alarm and trip). The electronic version of this kind of device, reading the signal from a PT100, give like available: - Analogue output 4-20 mA Modbus RTU communication (optional) Pt 100 (optional) 5 3.3 Outputs STANDARD CONFIGURATION STANDARD (OTI) STANDARD (WTI) OPTIONS (eOTI-eWTI) PT100 MICRO-SWITCHES 1 up to 4 x change over contact MICRO-SWITCHES 1 up to 4 x change over contact ANALOG OUTPUT 4-20 mA (Maximum resistance: 450 Ohm) COMMUNICATION PORT RS-485 Modbus communication – Appendix A PT 100 port Max 2 x OTI / WTI (1 Optional x eOTI / eWTI) Table 1 3.4 Technical features Standard connection flange Material Color Dial Ambient temperature Degree of protection Vibration damping Ventilation valve Cable gland Wires Micro switches, PT100 features Insulation 4 holes Ø 7 mm, holes wheelbase Ø 175 mm All the external part are resistant to transformer oils, salt fog and UV rays ** White RAL 9002** Tempered glass / Polycarbonate -40°C to 80 °C IP65 in accordance with EN60529 Optional anti-vibration supports available N°2 to prevent the formation of condensation Up to 3 x M25x1.5 Max 2.5mm2 – advised 4x1mm2 o 6x1mm2 shielded twisted pair cable 2000 V 50 Hz between terminals and earth for a 60 s time 1000 V 50 Hz between terminal in open position Outputs (OTI/WTI) Max 2 Pt100 Electronic board features (eOTI – eWTI) Supply voltage (electronic 24 V dc ±10% polarized devices) Power consumption 0,5 W Analog input (electronic devices) 1 x Pt100 1 x 4..20 mA insulated (dielectric strength between electronic card and analogical output:2kV) Analog output (electronic devices) Accuracy : 1.5 % of full scale Maximum resistance: 450 Ω 1 x Pt100 (optional) Distance for analogical output Max 30 m / 98 ft (for different demands contact COMEM) Serial RS485 Modbus RTU (for more information contact COMEM Digital output assistance dept.) Distance for digital output Max 30 m / 98ft (for different demands contact COMEM) Available temperature range* WTI / eWTI range 0 / +150°C, 0 / +160°C, 0 / +180°C OTI / eOTI range -20 / +130°C, -20 / +140°C, 0 / +120°C, 0 / +150°C, 0 / +160°C * For specific range please contact Comem ** For critical environmental conditions please contact Comem 6 Table 2 Voltage 125 VAC 250 VAC 30 VDC 50 VDC 75 VDC 125 VDC 250 VDC Micro switches making and breaking capacity Standard Micro switches High-performances micro switches Resistive Load Inductive Load Resistive Load Inductive Load 5A 5A 10 A 10 A 5A 5A 10 A 10 A 5A 5A 10 A 10 A 1A 1A 3A 2.5 A 0.75 A 0.25 A 1A 0.5 A 0.5 A 0.1 A 0.5 A 0.1 A 0.25 A 0.1 A 0.25 A 0.1 A Table 3 3.5 Tests Description Measuring tolerance test and commutation tolerance test Measuring tolerance test and commutation tolerance test Leakage test IP degree Vibration test REFERENCE STANDARD EN50216-11 JB6302 – JB8450 EN50216-11 EN 60259 EN 60721-3-4 class 4M4 CEI EN 60068-3-3 (class 0, level II) Seismic test Climatic test Dry heat test (60°C 50%RH) Dry heat test (40°C 93% RH) Damp heat, steady state Cold test Damp heat, steady state Damp heat cyclic EMC Fast transient/burst immunity test Immunity to Conducted disturbances Electrostatic discharge Surge immunity test Magnetic field immunity test Immunity test EN 60068-2-2 cl.6 EN 60068-2-2 cl.6 EN60668-2-78 cl7 and 9 EN 60068-2-1 cl.6 EN60668-2-78 cl7 and 9 IEC 60068-2-30 IEC 61 000-4-4 IEC 61 000-4-6 IEC 61 000-4-2 IEC 61 000-4-5 IEC 61 000-4-3 IEC 61 000-6-2 IEC 61 000-6-4 (EN 55022) EN61000-4-8 IEC 61 000-3-2 IEC 61 000-3-3 EN 61000-4-11 Emission standard Power-frequency magnetic field Harmonic current emission Voltage fluctuations and flicker Micro-interruption and voltage variations Table 4 7 4. INSTALLATION CAUTION The operating and the installation requirements described in this manual must be strictly following. If not, the device can be damaged or a malfunction can occur. 4.1 Flange connection The standard solution is with a flange connection. Arrange the transformer with a dedicated place following the scheme in the figure 4. The connection can be done in two alternative way: - threaded pin - screws Fig. 4 4.1 Elastic Suspension (optional) In case of high vibration withstand demand, the elastic suspension connection is available. The actions that have to be followed are: 1. Unscrew the upper rigid locking M14 screw located on the top of the thermometer (Fig. 5) Fig. 5 8 2. Assembly the elastic suspension on the top of the thermometer with a M14 screw that let install the instrument in the plant (Fig.6-7) Fig. 6 Fig. 7 5. ELECTRICAL CONNECTION CAUTION Qualified and skilled personnel trained in the applicable health and safety regulations of the relevant country should only perform electrical connections. WARNING Dangerous electrical voltages! It is imperative to deactivate the power supply during wiring of the device. CAUTION During the terminal box assembly, use caution not to damage the OR gasket (Fig.15/C). If this occurs, it must be substituted. If you do not use all the cable glands, pay attention to close the free cable gland with a plug with gasket. 5.1 Wiring diagrams 5.1.1 OTI – eOTI (2 , 4 contacts) 5.1.2 WTI – eWTI (2 , 4 contacts) 5.1.3 Pt100 9 5.2 Micro switches and PT100 (optional) 1. Removing of the terminal box cover: by unscrewing the four stainless steel captive screws. 2. Cables layout: the numerations 1, 2, 3, 4, 5 indicate the micro switches progress: red, blue, green, yellow, white pointer. 3. On the terminal board is written the cables layout for the different micro switches utilizing the abbreviations: · · · C = common NO = normally open NC = normally closed 4. Connect the micro switches terminals and the earth terminal. 5. If the thermometer is equipped with the PT 100 probe, follow the label about how to connect it 6. Re-position the terminal box cover. 5.2.1 Setting To set the micro switches, follow the instructions: 1. Remove the locking ring (unscrew the eight M4 captive screws). 2. Remove the glass or polycarbonate lens. 3. Stop the micro switches setting dial (small black dial) with two fingers and slide the fractioned micro switches setting pointers until they are located at the desired temperature. Note that to reduce errors you have to slide the pointers towards higher temperature value. 4. Replace the glass or polycarbonate lens taking care that the max. temperature indicating pointer is located on the right side of the temperature indicating pointer and that the lens itself correctly positioned over the sealing O-ring. 5. Lock the lens with the locking ring. CAUTION During the glass/polycarbonate lens removal, use caution not to damage the OR gasket. If this occurs, it must be replaced. If you do not use all the cable glands, pay attention to close the free cable gland with a plug with gasket. 10 5.3 ΔT calibration for thermal Image (WTI / eWTI) Within the instrument’s terminal board there are, as well as earth and micro switches connection terminals, the terminals T-T and the terminals A-A. To calibrate the instruments, follow the steps: 1. Remove the jumper A-A. 2. Insert the ammeter probes in terminals A-A. 3. Connect the terminals T-T to the current transformer. Be sure to use the right Current Transformer (CT) by checking that the CT nominal current of CT is the one printed on the dial. 4. Regulate the current based on the curve I - ∆T (see Appendix A) rotating the potentiometer until the read current on the ammeter corresponds to the value in the curve. 5. Remove the ammeter probes. 6. Replace jumper A-A. 7. Wait few minutes to allow a stabilization of Tw. 8. Check the exactitude of Tw. CAUTION Some holes in the capillary bulb allow the oil flow and so the heat exchange providing a fast and accurate measurement. The bulb must be inserted in a proper thermowell filled with transformer oil.The oil will rise from the thermowell to the bulb holes covering the resistance. 5.4 eOTI/eWTI adding terminals Terminal numbers SUPPLY VOLTAGE 24 V DC ANALOG OUTPUT (4-20 mA) COMMUNICATION PORT RS-485 (MODBUS communication) Optional Pt100 1(-) – 2(+) 6(+) – 7(-) 3(A+) – 4(B-) Table 5 ABb 11 6. OPERATION AND MAINTANENCE 6.1 Operation and maintenance No particular maintenance is required. Only periodical inspections (typical interval 6 months) to verify precision, functions and electrical connections. In case of working test effected with thermostatic bath, please note that WTI bulb MUST NOT be immersed in water. The heating resistance surrounds the WTI bulb and water may cause serious damages to the heating system. The calibration test must be done with oil or hot air only. When the instrument is equipped with polycarbonate lens, cleaning must be done with care in order to avoid scraps on the surface. Use water and soap only. NOTE Comem advices to disconnect the eOTI/eWTI during the electrical transformer routine test 6.2 Storage The devices can be handled without any tools. Handle the device with care. The thermometers must be stored in the original packing and in a dry place with temperature in the range -10÷40°C (14÷104 °F). Upon receiving the device, please check: · The outer surface of the packaging to ensure that it is intact · That there are no breakages If damages are found, please contact COMEM and provide the information from the shipping list and the serial number. 12 APPENDIX A: MODBUS COMMUNICATION A1: MODBUS register Register address Operation Notes Operation for monitoring 0x2000 0x2001 0x2002 0x2003 0x2004 0x2005 0x2006 0x2007 0x200A R R R R R R R R R Pt100 value Electronic board switched on time (minutes) Electronic board switched on time (days) Max Pt100 value of the current day Min Pt100 value of the current day Daily blackout number Max scale value Min scale value Software version Data logging 0x2100 0x2101 0x2102 0x2103 0x2104 0x2105 R R R R R R Max PT100 value of the day -1 Min PT100 value of the day -1 Max PT100 value of the day -2 Min PT100 value of the day -2 Max PT100 value of the day -3 Min PT100 value of the day -3 0x2134 0x2135 0x2136 0x2137 0x2138 0x2139 R R R R R R Max PT100 value of the day -27 Min PT100 value of the day -27 Max PT100 value of the day -28 Min PT100 value of the day -28 Max PT100 value of the week -5 Min PT100 value of the week -5 0x215C 0x215D 0x215E 0x215F R R R R Max PT100 value of the week -23 Min PT100 value of the week -23 Max PT100 value of the week -24 Min PT100 value of the week -24 ……. ……. Event Log 0x2300 0x2301 R R 0x2303 R 0x2304 … 0x248D 0x248F 0x2490 R Available event (0 … 100) Time Stamp 1 Event type 1: 1= alarm; 2 = trip; 3 = threshold trip; 4 = change date Event 1 value R R R Time Stamp 100 (the oldest) Event Type Event Value 13 Table 6 A1.1 MODBUS address When are installed two or more units, it is necessary to differentiate the MODBUS address changing the dip-switches position The available addresses are · eOTI 80(default) to 95 · eWTI 96(default) to 111 Fig. 9 4 3 2 1 ADDRESS eOTI ADDRESS eWTI OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97 96 Table 7 14 APPENDIX B: I2-∆T CURVES B1: Example: how to utilize the curve Starting data: - DT = 31 °C - CT nominal current = 2A Enter in the graph with the known DT, it is possible to define the I2 (Fig. C) Fig.C I2 = 1.2 A Rotate the potentiometer knob until the ammeter reading is 1.2 A 15 1A B2: Nominal CT current: 1 A Gradient (°C) Stainless steel well 6 15 35 53 Gradient (°C) Brass well 5 14 33 50 Heating current I 2 (A) 0.3 0.5 0.8 1.0 Notes: - Maximum WTI absorption power: 15 VA - Oil temperature set: 50 °C 16 1.5 A B3: Nominal CT current: 1.5 A Gradient (°C) Stainless steel well 7 16 37 55 76 96 Gradient (°C) Brass well 8 17 36 53 73 92 Heating current I2 (A) 0.3 0.5 0.8 1.0 1.2 1.4 Notes: - Maximum WTI absorption power: 25 VA - Oil temperature set: 50°C 17 2A B4: Nominal CT current: 2 A Gradient (°C) Stainless steel well 3 6 16 23 31 44 59 69 Gradient (°C) Brass well 3 6 15 21 28 41 57 66 Heating current I2 (A) 0.4 0.5 0.8 1.0 1.2 1.5 1.8 2.0 Notes: - Maximum WTI absorption power: 20 VA - Oil temperature set: 50°C 18 4A B5: Nominal CT current: 4 A Gradient (°C) Stainless steel well 3 7 13 20 28 38 49 63 Gradient (°C) Brass well 3 7 12 19 27 37 47 60 Heating current I2 (A) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 Notes: - Maximum WTI absorption power: 20 VA - Oil temperature set: 50°C 19 5A B6: Nominal CT current: 5 A Gradient (°C) Stainless steel well 1 3 6 9 14 20 26 34 42 51 Gradient (°C) Brass well 1 2 5 8 12 17 23 30 38 47 Heating current I2 (A) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 Notes: - Maximum WTI absorption power: 20 VA - Oil temperature set: 50°C 20 Strada Regionale 11, Signolo 22 36054 Montebello Vic.No (VI) - Italy Tel. +39 0444 449311 - Fax -39 0444 449352 – 440359 http://www.comem.com e-mail:comem@comem.com 21 WTI-OTI Thermometers WTI-OTI Crucial parameters to be monitored in large distribution transformers and power transformers are Winding and Oil temperature: those give a fundamental understanding about the overall performances of your valuable equipment by avoiding unacceptable thermal degradation and ensuring a longer lifetime. WTI-OTI Accurate and stable measurement through maintenance free thermometers Thermometers are based on Bourdon working principle, which enables a direct and precise conveyance of the temperature rise from the bulb up to the main dial. The adjustable switching system connected to the pointer shaft provides the desired alarm/trip signals. On OTI, the bulb of thermometer detects the transformer oil temperature variations generating a contraction or expansion of the capillary connected to the pointer shaft. On WTI, given that a direct measurement of the winding temperature is not feasible, the device make use of thermal image technology whereas the sensing system comprises a heat sensitive resistive circuit through which passes a current proportional to winding current. A potentiometer placed on the main dial allows to adjust the resistive circuit depending on the transformer parameters. 2 Advantages: • • • • • • Accurate and stable measurement Robust design, no need for re-calibration over the time Customizable mounting flange Easy accessibility to wiring box Compact solution, PT 100 embedded into the sensing system Up to 4 change over micro-switches suitable to control cooling equipment and protection circuits. 3 WTI-OTI Temperature sensing system The devices work with an expansion type sensing system compensated for ambient temperature. We adopt particular cares in components testing in order to ensure a very reliable measurement along the time: - Vacuum test (2x10-3 mbar): to verify the quality of the weldings and the porosity of the material. - Pressure test (up to 280 bar): to verify the welding and the performances of the spring. - Overheating test (up to 20% higher of the scale range for 8 hours): to train the spring and to verify the precision of the spring. Indications for assembly It’s possible to provide the instruments with the following connections: - Rigid locking screw M14 located on the top of thermometer. - Elastic suspension mounted on the top of the thermometer. - Rear flange for tank wall mounting. Tests and inspections The gauges are subjected to insulation test towards earth as follows between circuit and earth, the minimum dielectric withstand strenght is 2kV in accordance to EN - 50216/1. The instruments calibration is carried-out through thermostatic baths controlled by a computer system. 4 Calibration procedure: - a check is carried out to see whether the temperature taken by the instrument under test differs from that taken through the sample sensor by more than the 70% of the maximum allowed instrument reading tolerance value. This test is performed by sequentially plunging thermometer bulb into successive temperature increasing thermostatic baths: 0°C / +20°C / +50°C / +100°C / +125°C. - the instrument is heated until the instrument pointer exceeds by 20% the angular full scale value. - step 1 is repeated, but inversely. Microswitches activation test: The bulb is immersed in a thermostatic bath. The computer changes the temperature inside the bath and by means of suitable sensors verifies the commutation tolerance, the commutation differential, the electrical circuits of each microswitch. At the end of the test a test report is directly printed by the computer. No particular maintenance is required. Only periodical inspections ( typical interval 6 months ) to verify precision, functions and electrical connections. In case of working test effected with thermostatic bath, please note that WTI bulb MUST NOT be immersed in water. The WTI bulb is surrounded by the heating resistance and water may cause serious damages to the heating system. The calibration test must be done with oil or hot air only. When the instrument is equipped with polycarbonate lens, cleaning must be done with care in order to avoid scraps on the surface. Use water and soap only. Winding and Oil Temperature Indicator COMEM Technical Data Standard Tested and qualified in accordance to EN 50216-11 and JB/T 6302-2005 Material Housing All the external pars are resistant to oils, salt fog and UV rays Capillary and Bulb Capillary tube: copper or stainless steel Bulb: bronze or stainless steel Capillary tube protection Copper tube Flexible AISI 304 stainless steel armouring or Rilsan Lens Mokrolon Polycarbonate, Multistrate glass or Tempered Glass Specifications Painting RAL 9002 Ambient temperature -40°C + 70°C Degree of protection IP65 according to EN 60529 Optionally IP 66 Ventilation valve 2, to prevent the formation of condensation Cable gland Up to 3, M25x1,5 Micro Switches Up to 4 Output Measuring range WTI: 0/+150°C, 0/+160°C, 0/+180°C, -50/+150°C OTI: -50/+150°C, -20/+130°C, -20/+140°C, 0/+120°C, 0/+150°C, 0/+160°C Measuring tolerance 1,5% of full scale Repeat accuracy 1% of full scale value Remote output Up to 2x PT 100 5 Overall dimension OTI / WTI OTI Bulbs O.T.I. Bulbs Fig. 1 O.T.I. equipped with PT 100 sensors bulbs Fig. 2/3 Fig. 1 Fig. 2 A 3/4 BSP M27x2 Other 3/4 BSP 1’’ BSP M27x2 M22x1.5 Other A 3/4 BSP M27x2 Other 3/4 BSP 1’’ BSP M27x2 L Min 150mm - Std. 150mm Min 120mm - Std. 150mm L Min 150mm - Std. 150mm Min 120mm - Std. 150mm 6 M22x1.5 Other WTI Bulbs Fig. 1 Fig. 2 A 3/4 BSP M27x2 Other 3/4 BSP 1’’ BSP M27x2 M22x1.5 Other L Min 150mm - Std. 150mm Min 120mm - Std. 150mm Electrical characteristics Micro switches making and breaking capacity Voltage 125 VAC Standard Micro switches High-performances micro switches Resistive Load Inductive Load Resistive Load Inductive Load 5A 5A 10 A 10 A 250 VAC 5A 5A 10 A 10 A 30 VDC 5A 5A 10 A 10 A 50 VDC 1A 1A 3A 2.5 A 75 VDC 0.75 A 0.25 A 1A 0.5 A 125 VDC 0.5 A 0.1 A 0.5 A 0.1 A 250 VDC 0.25 A 0.1 A 0.25 A 0.1 A 7 Order sheet OTI Number of pieces JB/T 6302-2005 EN 50216-11 OTI Standard Rigid locking screw Flange Elastic suspension -50/+150°C -20/+130°C -20/+140°C 0/+120°C 0/+150°C 0/+160°C Fixing Scale Diam. 150 Lens type Makrolon Polycarbonate Makrolon Polycarbonate with resetting pointer Multilayers glass with resetting pointer Tempered glass 1 2 Contacts features 3 4 Standard High performance AISI 304 RILSAN Capillary protection 1 2 4 6 Provided as standard supply. Other pls. specify……………………………………………………………............................................. 1 2 PT 100 Fig. 1 (female) Fig. 2 (male) Fig. 3 (male with well) Bulb type ¾ BSP 1”BSP M27 x2 Other M22X1,5 Bulb thread ………………… No. Cable gland M25x1,5 ………………… Moderate salinity areas acc. to ISO 12944 Environmental protection 8 Other ………………… Off-shore areas acc. to ISO 12944 Order sheet WTI Number of pieces JB/T 6302-2005 EN 50216-11 OTI Standard Rigid locking screw Flange Elastic suspension Fixing 0/+160°C 0/+150°C 0/+180°C -50/+150°C Scale Diam. 150 Makrolon Polycarbonate Lens type Makrolon Polycarbonate with resetting pointer Multilayers glass with resetting pointer 1 Tempered glass 2 Contacts features 3 4 Standard High performance AISI 304 RILSAN Capillary protection 1 2 4 6 Capillary length (mt) Other pls. specify……………………………………………………………............................................. 1 2 Fig. 1 (female) Fig. 2 (male) PT 100 Bulb type ¾ BSP 1”BSP M27 x2 Other M22X1,5 Bulb thread ………………… M25x1,5 No. Cable gland ………………… Other ………………… Moderate salinity areas acc. to ISO 12944 Off-shore areas acc. to ISO 12944 Environmental protection Nominal current from current transformer 1A 1.5A 2A 4A 5A Strada Regionale 11, Signolo 22 36054 Montebello Vicentino (VI) - ITALY Tel. +39 0444 449311 Fax +39 0444 449352 - 440359 E-mail: comem@comem.com www.comem.com Due to technical product updates, the information contained in this catalogue may be subject to change without notice. © Copyright 2015 COMEM. All rights reserved. Ed. 05/2015 Relay BR Index Buchholz relay General information 2 Overall dimensions according to EN 50216-2 and EN 50216-2_A1 6 Gas sampling device 22 Requirement sheet 23 Gas relay General information 24 Overall dimensions 26 Requirement sheet 29 Flow relay General information 30 Overall dimensions 32 Requirement sheet 37 1 Buchholz relay Transformer outages have a considerable economic impact on the operation of a power supply network. Therefore it is the aim to ensure an accurate assessment of the transformer condition. Partial discharges, leakage currents, hot spots and arcing are phenomena that contribute to degradation of oil insulating performances by generating dangerous gas flow inside the transformer tank. BR Internal gas accumulation and oil flow are monitored and kept under control by the Buchholz relay. Thanks to COMEM’s proven expertise, we have developed a reliable Buchholz relay that promptly provide information about internal malfunctioning giving the possibility to eventually stop the system prior its destruction. The Buchholz relay is sited in the pipework between the transformer and its conservator and it is filled with oil during normal transformer operation. When gas is generated in the transformer it rises towards the conservator and collects in the upper chamber of the relay. The oil level drops and the top float triggers alarm switch. Gas shall not freely pass from the relay body and escape into the pipework before the alarm contact has operated. Another important functionality of the Buchholz relay is to operate if oil flow from the transformer tank to the oil conservator. In case the oil flow speed exceed the pre-set value, the the flow vent operates and switch the trip contact. 2 Advantages • • • • • Proven “on the field” reliability No false alarms Robust reed switch design Electrical wiring provided with change-over contacts Additional accessories: Gas sampling device. 3 Buchholz relay (1) (8) (9) Construction The housing consists of an aluminum alloy and it is provided with flanges for the connection of the transformer tank pipe and the oil conservator pipe. The terminals of the reed switches are positioned in the terminal box and the perfect sealing is guaranteed by an OR gasket. The terminal box cover (1) is fixed to the terminal box with 4 unloosable screws. There are two floats (8) with their associated switches encapsulated in glass bulbs. The flow vent (9) has two permanent magnets. 4 Special features Upon request our Buchholz relais are available with 4M6 vibration class in accordance with EN 50216-2 and EN 50216-2_A1, load stress are in compliance to EN60721-3-4 and to C5. Buchholz relais are available with improved corrosion resistance C5 class according to ISO 12944, suitable for offshore environment and high salinity area. Installation guidelines The following table gives guidelines values: Transformer Power MVA Pipe Nominal diameter Volume of oil Tons Up to 5MVA 25 Up to 3,5 From 5 up to 20 MVA 50 From 3,6 up to 14 Over 20 MVA* 80 Over 14,1* Over 20 MVA* 100 Over 14,1* * In agreement with the transformer design Tests Topic Type tests Routine tests Test description Standard Checking of the switching capacity of contacts Vacuum test Impulse withstand test of electrical circuits Calibratione of gas collection scale on relay window to operate alarm contact if required Determination of the minimum oil flow to operate the contact and the time for closing Verification of the absence of reaction of contacts to a flow of oil from conservator to the tank Pressure withstand test Verification of the absence of reaction of contacts to magnetic field Vibration test Short duration power frequency withstand test Oil leakage test Operation test EN EN EN EN EN EN EN EN EN EN EN EN 50216-1 50216-2 50216-1 50216-2 50216-2 50216-2 50216-2 50216-2 50216-1 50216-1 50216-2 50216-2 and EN 50216-2_A1 and and and and and EN EN EN EN EN 50216-2_A1 50216-2_A1 50216-2_A1 50216-2_A1 50216-2_A1 and EN 50216-2_A1 and EN 50216-2_A1 5 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 G1" 1/2 A BG25 Weight 2.1 Kg 6 BR25 Weight 2.9 Kg 7 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 BR50 Weight 4.9 Kg 8 BR80 Weight 5.8 Kg 9 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 BS25 Weight 2.2 Kg 10 BS50 Weight 4.1 Kg 11 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 BS80 Weight 4.3 Kg 12 NF25 Weight 3.0 Kg 13 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 NF50 Weight 4.8 Kg 14 NF80 Weight 5.5 Kg 15 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 C01 Weight 2.2 Kg 16 C1 Weight 2.3 Kg 17 Buchholz relay Overall dimensions according to EN 50216-2 and EN 50216-2_A1 C4 Weight 5.9 Kg 18 Main features General data Material All the external part are resistant to transformer oils, salt fog and UV rays Ambient temperature -40 to 80°C Oil temperature -40 to 115 °C Degree of protection IP65 in accordance with EN60529 Oil flow speed (oil temperature 20°C) 1.00 ± 0.15 m/s 1.50 ± 0.20 m/s 2.00 ± 0.30 m/s Switch electrical data (according to EN 50216-2 and EN 50216-2_A1) Breaking capacity Voltage Current Breaking capacity 220 V d.c. (min. 12V) 2 A for 1000 maneuvers 250 W L/R<40 ms 230 V a.c. (min. 12V) 6 A for 1000 maneuvers 400 VA cosФ>0.5 Dielectric strength of contacts Short duration power frequency withstand voltage 1 min – kV (r.m.s.) Lightning impulse withstand voltage kV (peak) Between circuits and earth 2 5 Across open contacts 1 3 Alarm signalling Gas Volume Buchholz relay type BG25-BR25-NF25-C01-C1 100-200 cm3 NF50-NF80 100-200 cm3 BR50-BR80-C4 150-250 cm3 BS25 170-230 cm3 BS50-BS80 250-300 cm3 19 Buchholz relay Wiring diagrams Diagram type “A” - ALARM CONTACT (terminals 3-4) NO contact 1 2 3 4 - TRIP CONTACT (terminals 1-2) NO contact Alarm circuit Trip circuit Diagram type “L” - ALARM CONTACT (terminals 3-4- C2) change over contact NO contact: terminals 4-C2; NC contact: terminal 3-4 1 2 C1 3 4 C2 - TRIP CONTACT (terminals 1-2-C1) change over contact NO contact: terminals 2-C1; NC contact: terminal 1-2 Alarm circuit Trip circuit Diagram type “P” - ALARM CONTACT (terminals C2-3) NO contact - ALARM CONTACT (terminals C1-4) NO contact 1 2 C1 3 C1 - TRIP CONTACT (terminals 1-2) NO contact Alarm circuit Trip circuit 20 4 Diagram type “G” - ALARM CONTACT (terminals 3-4) NO contact - TRIP CONTACT (terminals C2-2) NO contact C2 2 C1 1 3 4 - TRIP CONTACT (terminals C1-1) NO contact Alarm circuit Trip circuit Diagram type “I” - ALARM CONTACT (terminals 5-6) NO contact - ALARM CONTACT (terminals 7-8) NO contact 1 2 3 4 5 6 7 8 - TRIP CONTACT (terminals 1-2) NO contact - TRIP CONTACT (terminals 3-4) NO contact Alarm circuit Trip circuit Diagram type “V” - ALARM CONTACT (terminals 5-6) NC contact - ALARM CONTACT (terminals 7-8) NC contact 1 2 3 4 5 6 7 8 - TRIP CONTACT (terminals 1-2) NC contact - TRIP CONTACT (terminals 3-4) NC contact Alarm circuit Trip circuit 21 Buchholz relay Gas sampling device Insulating materials within transformers and electrical equipment break down to liberate gases. The distribution of these gases can be related to the type of electrical fault, and the rate of gas generation can indicate the severity of the fault. The identity of the gases being generated by a particular unit can be very useful information in any preventative maintenance program. The collection and analysis of gases in an oil-insulated transformer can indicate the severity of the default. The presence of gas inside an oil filled transformer is always a sign of malfunction and one of the tasks of the Buchholz relay is to signal this presence. Analysis of the evolved gas can often give good indication of the type of malfunction but accessing the Buchholz relay during live operation of the transformer can be hazardous. The gas sampling device has been designed to overcome this problem by siting the unit remote from the Buchholz and in a readily accessible position typically on the side of the transformer. 22 Construction The Comem gas sampling device is manufactured from an aluminium alloy casting with the following fittings: - a tempered glass inspection window with graded markings for volume indication. - a gas sampling valve (2). - a bleed valve (3). - a gas inlet valve for pneumatic testing (5). - a valve for draining oil from the relay (this can be mounted on the right or left hand side of the body (6) or (7). As a routine test all castings are tested by injecting ambient air at 2.5 bar for 2 minutes. A certificate to this effect is supplied with the unit. For the sake of standardisation the device is fitted with the left and right hand valve supports but only one valve. Customer can then choose which side he prefers. - with fittings for outside dia. 10 tubes, code 1RDPG00005 (standard); - with fittings for outside dia. 6 tubes, code 1RDPG00006 (on request); - with fittings for outside dia. 8 tubes, code 1RDPG00007 (on request). PRD Pressure Relief Device Index Pressure Relief Device - LPT General information 2 Overall dimensions according to EN 50216-5/A2 5 Assembling sequence 6 Order sheet 7 Pressure Relief Device - M General information 8 Overall dimensions according to EN 50216-5/A2 12 Assembling sequence 14 Order sheet 15 Pressure Relief Device - T and Q General information 16 Overall dimensions according to EN 50216-5/A2 19 Assembling sequence 22 Order sheet 24 How to select the PRD type for your transformer in 3 simple steps 1st Select size 2nd Select protection type 3rd protection material Depending on volume of oil tank up to 3000 dm 3 up to 9000 dm3 up to 25000 dm3 50 80 125 up to 40000 dm3 125 up to 45000 dm3 200 no protection needed “T” model guard “T” model plastic conveyor duct “M” model aluminium alloy no protection needed “T” model guard “T” model plastic conveyor duct “T” model stainless steel no protection needed “T” model guard “T” model plastic conveyor duct “M” model aluminium alloy conveyor duct with internal spring “LPT” model aluminium alloy no protection needed “T” model guard “T” model metallic 1 Pressure Relief Device - LPT LPT COMEM’s “LPT” pressure relief device is used to control the pressure inside tanks. It is important in cases where an accidental, sudden and uncontrolled increase in pressure creates the danger of explosion. It is designed to discharge pressure in a very short time (a few thousandths of a second). It is widely used in oil-cooled electric transformer metal tanks. Sudden and violent short circuits inside these tanks, in fact, instantly generate an enormous amount of gas which cause a substantial increase in internal pressure. If the pressure cannot be externally discharged there is danger that the transformer could explode and potentially cause harm and damage. This danger can be prevented by installing one or more pressure relief devices. It is always good practice to install these pressure relief devices in places where internal pressure values must not exceed specific safety limits. The external protection with a perfect seal guarantees that no drop of oil is dispersed into the environment Total pressure relief completely opening Operating performance The pressure relief device is totally opened each time the pressure relief device operates at pressure settings between 20 and 175 kPa. If pressure generated inside the tank is much higher than the setting, then the further compressed spring allows the closing disk to create even larger discharge areas when it operates. Nominal operating pressure: the prefixed overpressure value shall be established between the supplier and the purchaser within the standard range of 20 up to 140 kPa, with 10 kPa steps and 175kPa. Tolerances are - 5 kPa to + 7 kPa for 20-90 kPa and ±10 kPa for 100-175 kPa calibration. 2 Construction Our pressure relief device is completely protected against external corrosion and against penetration by foreign bodies between the cover and protective cap. This ensures perfect operating efficiency even for extended periods of time. “LPT” pressure relief device These consist of a flanged body and a corrosion-proof aluminium alloy disk. There are two gaskets in the pressure relief device: a specially-shaped upper gasket and a lip seal. When the pressure relief device is closed, the upper gasket is pressed against the disk. The shape of the gasket creates a perfect seal even if the disk lifts 1-2 mm. The disk also seals against the lip seal gasket as it moves upwards. If, due to internal pressure, the disk rises beyond this amount then the upper seal is no longer maintained while the lip seal remains. When this happens, the surface of the washer condumed by internal pressure is increased in area equal to the total force applied on the spring. This causes the total and instant opening of the pressure relief device which consequently discharges excess pressure to the exterior. When the pressure has been discharged, the disk pushed back by the spring lowers down and closes the valve. As the disk moves downward, it first closes against the side gasket and then against the upper gasket. The latter, because of its special shape, is pressed down 1-2 mm and the disk moves further down breaking the seal on the lip seal gasket. This releases any pressure that may have been trapped between the two gaskets. Now the pressure relief device is ready to work. Routine tests It is necessary to carry out operational tests, with compressed air: • to check the correct functioning of the device at operating pressure values • to check the functioning of the optic signal and of the electric contacts. Installation guidelines Our “LPT” pressure relief device comes in 1 size. The following table gives guideline values: Volume of oil tank: Type of pressure relief device up to 40000 dm LPT 3 We recommend using multiple pressure relief devices when oil volumes exceed these levels. Instant pressure relief device opening implies direct contact between the closing disk and the oil. For this reason, the pressure relief device is equipped with a screw to bleed out that may accumulate during oil tank filling procedures. In order to prevent harm to people or property due to violent jets of hot oil evacuating from the pressure relief device, it is good practice for pressure relief device discharges to be guided towards points that are properly designed to receive the hot oil. Environmental protection is also another important issue which should be pursued by everyone. Our protection duct allows the oil that is evacuated by the pressure relief device to be drained. The system’s perfect hydraulic seal guarantees that no drop of oil is dispersed into the environment, but is, rather, collected through a pipe into a tank (pipe and tank are not supplied). The sealing oil duct is made of die-casted aluminium; a terminal flanged tube made of steel can be also provided if you want to weld the pipeline air necessary. O-ring gaskets have been applied for duct sealing. Detailed assembly instructions are supplied with the equipment. 3 Pressure Relief Device - LPT The switches have the following characteristics: Specifications: Breaking and making capacity (NO and NC contacts) Voltage Uninterrupted current Interrupted current (making capacity) (breaking capacity) 24 VDC to 220 VDC 2A 100 mA L/R<40 ms 230 VAC 2A 2 A cos φ>0.5 Other characteristics: Visual signal that the pressure relief device is open The pressure relief device is equipped with a visual signal that shows if it was opened when it is open. This signal consists of a red knob that protrudes from the central part of the duct when the pressure relief device is opened. Simply press it down in order to make it go back to its normal position and reset the switches. Electrical signalling switch Maximum 3 “pressure relief device open signal” contacts can be mounted upon request. These are fast tripping limit switches with switching contacts contained inside a watertight room IP65. The contacts act together with the visual signal. - The pressure relief device is supplied with a “locking system” which allows the pressure relief device to be blocked during the transformer oil leakage test. The locking system has been tested to withstand max 2 bar pressureand can also be used during the transformer transport. WARNING!: the locking system must be removed before powering-up the transformer. - The pressure relief device is supplied with a M25x1.5 cable gland. - Colour: RAL 9002. Outer surface protection The outer surfaces are protected against weather corrosion. Aluminum alloy components are non-corroding, their surface is protected with a thick layer of paint which offers a high level of protection against atmospheric agents and can resist temperature variations between -40 °C and +100 °C. Standard protection suits moderate salinity areas acc. ISO 12944-5. Special protection for severe climate applications, off-shore, is also available upon request. Contact diagram - FIRST SWITCH (terminals 12-14-11) change-over contact: – 14-11 normally open – 11-12 normally closed - SECOND SWITCH (terminals 22-24-21) change-over contact: – 23-21 normally open – 21-22 normally closed - THIRD SWITCH (terminals 32-34-31) change-over contact: – 34-31 normally open – 31-32 normally closed 4 1st Switch 12 14 2nd Switch 11 22 24 21 3RD Switch 32 34 Ground 31 Overall dimensions according to EN 50216-5/A2 Weight kg 19 5 Pressure Relief Device - LPT Assembling sequence RECOMMENDED TORQUE 8Nm 15 16 14 13 12 17 RECOMMENDED TORQUE 8Nm 10 11 9 8 7 6 5 4 3 2 1 35 M16 Ø170 A-A Ø235 6 18 19 20 Ref. Q.ty 1 1 Code Description 2 1 5GOD041050 Gasket OR 41050 3 1 5GOD008750 Gasket OR 8750 4 1 125x-6 safety valve 5 6 M16 washer (not supplied) 6 6 M16 grower washer (not supplied) 7 6 8 1 9 1 10 4 5v50606060 UNI 5931 M6X60 screw 11 4 5400800861 M6 washer (plain+elastic) 12 1 5GOD041100 Gasket OR 41100 13 1 LPT type oil duct cover 14 1 Visual signal 15 4 5V50605035 UNI 5931 M5x35 screw 16 4 5RG0600050 M5 washers (plain+elastic) 17 1 5GOD004475 Gasket OR 4475 18 1 5COV464600 LPT type flange with pipe for duct 19 4 5V50612030 UNI 5931 M12x30 screw 20 4 5RB0600120 M12 washer Transformer cover M16 nut (not supplied) 5GOD041050 Gasket OR 41050 LPT type oil duct APPLICATION : SUKRUT This indicator is suitable for conservator of oil filled transformer having Aircell (Flexi separator) SCOPE : Indicator continuously reads level of oil inside the conservator and operates a mercury switch when oil level drops down near Empty level mark. OIL LEVEL INDICATOR MODEL: SO-HE-10-ATMS CONSTRUCTION & WORKING : MAIN BODY The indicator has cast aluminium body with built-in flange. To avoid leakage of oil and to avoid entry of contaminated moist air in conservator, a pair of permanent magnets is used for the operation of indicator separated by a metallic wall. A roller type float is used as sensor of level and it is connected to driving magnet through a bevel gear. Float, driving magnet and bevel gear remain in oil inside the conservator. The driven magnet is positioned outside in air in the housing. The driven magnet carries a cam and a pointer. The cam is set to operate the switch near Empty level and the pointer is set to read the level inside the conservator. (see schematic Fig.1) In this model, the dial body can be separated from the base by loosening 6 screws to have access to the switch. This model can be mounted in inclined position only at an angle 150 or 300 as per specific requirement. The buyer is required to provide the mounting flange as per Fig. 2. For this model a float arm suitable for specified diameter of conservator is supplied. It is not possible to supply adjustable length type float arm for this model. The leads from the switch are brought out in a separate terminal box at the bottom of indicator with a removable cover. Terminal box is provided with a hole with 3/4” BSC threads for cable gland. WITH MOUNTING FLANGE SUKRUT SUKRUT UDYOG PUNE, INDIA ROLLER FLOAT WITH FLOAT -ARM TERMINAL BOX WITH COVER FIG. 1 Mounting : To mount the indicator, buyer has to provide mounting pad as per Fig. 2. SCHEMATIC SWITCH OPERATING CAM MERCURY SWITCH METALLIC WALL DIAL DRIVING MAGNET SPECIFICATIONS : Liquid in Tank : Transformer oil. Working : 0 0 Temp. : -30 to 120 Celsius of oil 2 Pressure : 0 to 1 kg/cm Environment : Indoor or Outdoor SWITCH, DIAL & POINTER ASSEMBLY DRIVEN MAGNET POINTER IN AIR GEAR & PINION FLOAT IN LIQUID 0 Travel : 45 max. See Fig. 3 Margin : Leave 100 mm beyond Lower Limit and 150 mm above Higher Limit for Clearance. (See Fig. 3) Switch : Type : Mercury Switch Calibration : Dial size : 250 mm Dia nominal. Unit : Calibration in any unit as per customers requirement is possible. Colour : Black marking on yellow background OR black marking on white background OR any other. 0 Spread : Max 150 (see Fig. 4 view of dial). ROUTINE TESTS : Each indicator is tested for 1. Specified levels. 2. Switch operation 3. HV Test 4. Leakage Test. A combined test certificate is issued for each batch. Float (sensor) and arm : Material : Float - Brass, Float arm - S.S. HOW TO ORDER : We provide a Questionnaire for specifying your requirements. However, a drawing is acceptable giving all specifications. Contact Rating : 5 Amps 240 V AC, 0.5 Amp 240V DC Operation : See wiring diagram (Fig.5) OIL LEVEL INDICATOR MODEL SO HE - 10 - ATMS ORIENTATION OF MOUNTING PAD FOR 300 (Any other Inclination possible) By removing these 6 screws dial body can be separated from base unit. 2 3 4 1 56 7 8 6” NB Pipe TOP 9 10 12 5 22 5 26 Oil Level at Mark ‘EMPTY’ B B 0N 15 1 114 FIG. 2 b 136 Approx 12 Use M10 Bolts x 50 Long with Nuts & Washer - 8 Nos. 110 09.5 Pipe 12 11 13 BOTTOM 075 160 Mounting Pad, Gasket Not Supplied by ‘SUKRUT’ 175 Hardware, Gasket & Cable Gland-Not Supplied by ‘SUKRUT’ Details at ‘B’ PART LIST : Sr.No. 1 2 3 4 5 6 7 Description Housing Base with Flange Gasket (Neoprene) 6 mm thick. Mounting Pad Bracket Lever with Gear Split Pin FIG. 3 FLOAT TRAVEL Material. Cast. Al. Cast Al. Rubber. M.S. Cast Al Brass Brass Sr.No. Description Material. 8 Float Arm (9.5 Pipe) S.S. 9 Bracket for Float S.S. 10 Roller Float Brass 11 Cable Gland (3/4” BSC.) Brass 12 Terminal Box with cover Cast Al. 13 Ring for Glass Cast Al.. Item Nos. 3, 4 & 11 are not supplied by Sukrut FIG. 4 VIEW OF DIAL FIG. 5 WIRING DIAGRAM MERCURY SWITCH OIL LEVEL AT FULL INTERNAL WIRING FULL 150 1 SUKRUT 3/4 2 TERMINALS PUNE INDIA EXTERNAL WIRING 0 35C 1/4 0 45 Max ALARM EMPTY 100 OIL LEVEL AT EMPTY ANY OTHER MARKING IS POSSIBLE SUPPLY Contact Rating : 5 Amps 240 V AC, 0.5 Amp 240 V DC GENERAL NOTES : 1. Indicators of different specifications are not interchangeable. Hence care should be taken while storing Indicators and their Float with Arms with respective Sr. Nos. This indicator can be used for inclined mounting only, at any angle specified by buyer. 2. Float & Indicator, loose or assembled, should be handled carefully as they cannot be repaired if damaged. 3. The complaint of damage or demand for spares should be very specific with respect to Sr. No. of indicator. Lot of correspondence and time can be saved just by informing Sr. No. of concerned Indicator. 4. We continuously review specifications and where appropriate, introduce modifications. We, therefore, reserve the right to change specifications in this catalogue without prior notice. SUKRUT UDYOG 9/1 A, ERANDAWANA, PUNE 411 004. (INDIA) Ph. No. Fax No. E-Mail Website Cat. No. SOHE10 ATMS : +91 20 25441514, 25441726 : +91 20 25440231. : sukrut@pn2.vsnl.net.in : www.sukrutudyog.com 0706 APPLICATION : This indicator is suitable for oil filled Power Transformers & oil filled tanks. SCOPE : Indicator continuously reads level inside the conservator and operates a microswitch when oil level drops near Empty level mark. CONSTRUCTION & WORKING : The indicator has aluminium body with built in flange for mounting. To avoid leakage of oil and to avoid entry of contaminated air into tank, a pair of permanent magnets is used separated by a metallic wall. A float is used as sensor & is connected to driving magnet through a bevel gear. The driven magnet is positioned outside in air in main body which carries a pointer and a cam. The pointer is set to read the oil level and the cam is set to operate the switch near Empty level(See Schematic). Switch resets automatically when level of oil is brought to normal. Contacts of switch are brought outside in terminal box with threaded hole for fixing cable gland. The body of indicator with dial and switch is sealed to avoid entry of moist air. Hence switch is not accessible for resetting or servicing. SUKRUT OIL LEVEL INDICATOR MODEL: SO-6-M MAIN BODY WITH MOUNTING FLANGE SWITCH, DIAL & POINTER ASSEMBLY LABEL WITH SERIAL NO. SPECIFICATIONS : Liquid in tank : Transformer oil & other oils. TERMINAL BOX WITH COVER Working : Temp. -30 to 1000 Cent. of oil. Press : 0 to 1 Kg/Cm2 Environment : Indoor or outdoor. Mounting : To mount the indicator, buyer is required to provide a pad as per Fig. 4. The position can be selected on vertical wall of conservator/tank depending on importance of oil level readings and switching near Empty level. Calibration : Dial Size : 150 mm round (nominal) Unit : Any calibration as per Customer’s requirement is possible. Colour : Black marking on white background or any other combination as required. 0 Spread : Max 300 (See Photograph). FLOAT WITH FLOAT -ARM HOLE FOR CABLE GLAND FIG. 1 SCHEMATIC SWITCH OPERATING CAM MICROSWITCH METALLIC WALL DIAL DRIVING MAGNET GEAR & PINION DRIVEN MAGNET POINTER FIG. 2 FLOAT TRAVEL Switch : Type : Microswitch Contact Rating : See wiring diagram. (Fig. 5) Operation : See wiring diagram (Fig. 5) OIL LEVEL AT FULL MARGIN MIN 65 Float (sensor) and arm : Float & Float - Arm are made of brass. Float - Arm is supplied of fixed Length or adjustable length type as per order. Margin : Leave Min. 65 mm beyond lower & higher limit markings to avoid striking of float to bottom & top of conservator. (See Fig.2) FLOAT IN LIQUID IN AIR MARGIN MIN 65 MAX 45 0 MAX 45 0 OIL LEVEL AT EMPTY ROUTINE TESTS : Each indicator is tested for 1. Specified levels. 2. Switch operation 3. HV Test 4. Leakage Test. A combined test certificate is issued for each batch. HOW TO ORDER : We provide a Questionnaire for specifying your requirements. However, a drawing is acceptable giving all specifications. FIG. 3 OIL LEVEL INDICATOR MODEL: SO - 6 - M 70 8 HOLES, 12 DIA ON PCD 209.7 12 57 22.5 1/2 SUKRUT 1/4 3/4 5 EMPTY FULL 6 H 4 7 T NG LE 295 RM TA OA FL 0 232 DIA 3 1 2 8 FLOAT SIZE DIA 50 x 75 LG. COVER REMOVED 3/4" B.S.CONDUIT FRONT VIEW Sr. No. Description SIDE VIEW PART LIST Material Qty. Sr. No. Description Material Qty. 1. Crystal Glass 1 5. Lever with Gear Brass 1 2. Float Brass 1 6. Float Arm Brass 1 3. Main Body Cast Al. 1 7. Label with Serial No. Brass 1 4. Limit Stoppers Al. Rod 2 8. Terminals Brass FIG. 4 FIG. FIG. 55 MOUNTING PAD 22.5 SWITCH SWITCH CONTACT CONTACT POSITION POSITION AT NORMAL LEVEL 0 AT MIN. LEVEL MICROSWITCH A 8 STUDS, M 10 EQUALLY SPACED AS SHOWN ON 209.7 P.C.D. Ø 235 Ø 175 Ø 165 HOLE IN TANK A INTERNAL WIRING TERMINAL PLATE LEAKPROOF WELDING JOINT SECTION AT ‘A-A’ MOUNTING PAD & GASKET NOT SUPPLIED BY SUKRUT EXTERNAL WIRING CONTACT RATING 5A 240V AC, 0.25A 240 V DC SWITCH RESETS AUTOMATICALLY WHEN OIL LEVEL IS BROUGHT TO NORMAL GENERAL NOTES : 1. Indicators of different specifications are not interchangeable. Hence care should be taken while storing Indicators and their Float with Arms. This indicator can be used for vertical or inclined mounting as per order. 2. Float & Indicator, loose or assembled, should be handled carefully as they cannot be repaired if damaged. 3. The complaint of damage or demand for spares should be very specific with respect to Sr. No. of indicator. Lot of correspondence and time can be saved just by informing Sr. No. of concerned Indicator. 4. We continuously review specifications and where appropriate, introduce modifications. We, therefore, reserve the right to change specifications in this catalogue without prior notice. SUKRUT UDYOG 9/1 A, ERANDAWANA, PUNE 411 004. (INDIA) Cat. No. S0-6-M-704 PHONE : (020) 25441726, 25441514 FAX : (020) 25440231 E-Mail : sukrut@pn2.vsnl.net.in IN Movement by Perfection The Royal League in ventilation, control and drive technology Product documentation Type FN080-ADL.6N.V7P5 Article number TBD Article number TBD Product documentation Customer ABB India Project 176.25MVA Transformer Chile ZIEHL-ABEGG Contact Kai Rittmann Tel. +49 7940 16 90102 Kai.Rittmann@ziehl-abegg.de ZIEHL-ABEGG Subsidiary India ZIEHL-ABEGG INDIA PVT LTD. Plot No. E-8, Chakan Industrial Area, Phase III, Village Kuruli, Tal. Khed, Chakan, Pune- 410 501, Maharashtra, INDIA Phone +91 21 3567 9679 Fax +91 21 3567 9680 www.ziehl-abegg.in vikas.kundra@ziehl-abegg.com Type FN080-ADL.6N.V7P5 Article number TBD Contents 1. Product specification - Technical data 3 2. Characteristic curve 4 3. Drawing 5 4. Connection diagram 6 5. EU-Declaration of conformity 7 www.ziehl-abegg.com/de 23.09.2019 Movement by Perfection │ Bewegung durch Perfektion 2│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. Article number TBD 1. Product specification - Technical data Article number TBD Type FN080-ADL.6N.V7P5 Designation Axial fan with sickle blades 3~ 380V ±10% D/Y 50Hz P1 860/480W 2,2/1,05A DI=0% 650/490rpm COSY 0,59 70°C 3~ 380V ±10% D/Y 60Hz P1 1,10/0,52kW 2,4/1,05A DI=0% 680/460rpm COSY 0,69 70°C 3~ 440V ±10% D/Y 60Hz P1 1,30/0,64kW 2,6/1,15A DI=0% 740/510rpm COSY 0,65 65°C Pstat=0Pa: 680/530/MIN 700/440W 4,7/3,7m3/s Pstat=0Pa: 730/510/MIN 960/480W 5,1/3,5m3/s Pstat=0Pa: 780/570/MIN 1100/580W 5,4/3,9m3/s Rated values Electrical connection Terminal box K04 9x 0,75 mm2, 50 cm Min. operating temperature °C -40*** Mounting type terminal box Mounted on fan housing Cable quality Li4G4G-J Type of protection IP55 Thermal class THCL155 Connection diagram 1360-108XA Rating plate 1x fixed Fitting position H/Vu/Vo Motor protection thermal contact Quality of bearings ball bearing with long-time lubrication Material Rotor Aluminium Painting rotor 3 coat painted colour rotor RAL 7035 (light grey) Material blades Aluminium Painting impeller 3 coat painted Colour blades RAL 7035 (light grey) Guard grille type ring grill for suction side in stainless steel Other All connecting elements in stainless steel. Other All connecting elements secured with Loctite. Painting housing Bell mouth 3 coat paint Colour housing RAL 7035 (light grey) Painting mot.suspens Motor suspension 3 coat paint colour suspension RAL 7035 (light grey) Weight kg 63,30 ErP Data Efficiency ηstatA: 33,5 % Efficiency grade: Nactual = 40,3 / Ntarget = 40* *ErP 2015 www.ziehl-abegg.com/de 23.09.2019 Movement by Perfection │ Bewegung durch Perfektion 3│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. Article number TBD 2. Characteristic curve www.ziehl-abegg.com/de 23.09.2019 Movement by Perfection │ Bewegung durch Perfektion 4│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. Article number TBD 3. Drawing Dimensions in mm Shown drawing is just to show the dimensions of the fan. www.ziehl-abegg.com/de 23.09.2019 Movement by Perfection │ Bewegung durch Perfektion 5│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. Article number TBD 4. Connection diagram 1360-108XA 3~ motor, 2 speeds (Δ/Y switch over) with thermostatic switch (if built in).Without bridge when using speed change-overswitch. BN BU BK RD GY OG WH GNYE brown blue black red grey orange white green-yellow High speed/D-connection www.ziehl-abegg.com/de 23.09.2019 Low speed/Y-connection Movement by Perfection │ Bewegung durch Perfektion 6│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. Article number TBD 5. EU-Declaration of conformity www.ziehl-abegg.com/de 23.09.2019 Movement by Perfection │ Bewegung durch Perfektion 7│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. Article number TBD The Royal League in ventilation, control and drive technology Intelligent control technology for any application ZIEHL-ABEGG system capabilities: Everything from a single source – perfectly matched for optimal performance Please contact us. We would be pleased to design an individual solution for your requirements. We would like to welcome you on our worldwide exhibitions. Please find our next exhibitions here. www.ziehl-abegg.com/de 23.09.2019 Movement by Perfection │ Bewegung durch Perfektion 8│8 © ZIEHL-ABEGG SE All rights reserved. Confidential and proprietary document, not to be disclosed or used except in accordance with applicable agreements. No disclosure to third parties, if not expressively agreed by ZA SE. 1ZSE 5492-155 en, Rev. 4 On-load tap-changers, type UC User’s manual Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted. Manufacturer’s declaration The manufacturer ABB AB Components SE-771 80 LUDVIKA Sweden Hereby declares that The products On-load tap-changers, type UC with motor-drive mechanisms, types BUE and BUL comply with the following requirements: By design, the machine, considered as a component of a mineral oil filled power transformer, complies with the requirements of • Machinery Directive 89/392/EEC (amended 91/368/EEC and 93/44/EEC) and 93/68/EEC (marking) provided that the installation and the electrical connection are correctly realized by the manufacturer of the transformer (e.g. in compliance with our Installation Instructions) and • EMC Directive 89/336/EEC regarding the intrinsic characteristics to emission and immunity levels and • Low Voltage Directive 73/23/EEC (modified by Directive 93/68/EEC) concerning the built-in motor and apparatus in the control circuits. Certificate of Incorporation: The machines above must not be put into service until the machinery into which they have been incorporated has been declared in conformity with the Machinery Directive. Date 2013-02-15 Signed by ......................................................................... Hans Linder Title Manager Tap-Changers, Local Product Group Unit Components Introduction The UC range of on-load tap-changers manufactured by ABB has been developed over many years to provide maximum reliability. The simple and rugged design gives a service life equal to the service life of the transformer. Minimum maintenance is required for trouble-free operation. The only parts requiring maintenance are contacts that might need replacement during the service, the insulating oil and the motor-drive mechanism. The design allows ready access to all parts, making inspection and maintenance quick and simple. The tap-changers are housed in the transformer tank. The motor-drive mechanism, type BUE or BUL, is attached to the transformer tank and connected to the tap-changer by means of drive-shafts and a bevel gear. The same motor-drive can operate one, two or three units on the same transformer. Those units are then considered as one tap-changer. Safety warnings The following warnings and notes are used in the manual: WARNING WARNING indicates an imminently hazardous situation, which if not avoided will result in death or serious injury. This signal word is to be limited to the most extreme situations. WARNING also indicates a potentially hazardous situation, which if not avoided could result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation, which if not avoided may result in minor or moderate injury. It may also be used to alert of unsafe practices. CAUTION may also indicate property-damage-only hazards. INFO provides additional information to assist in carrying out the work described and to provide trouble-free operation. 4 User's manual UC | 1ZSE 5492-155 en, Rev. 4 Safety precautions WARNING Personnel operating and inspecting the tap-changer must have good knowledge of the apparatus and must be aware of the risks pointed out in this manual. Personnel making electrical connections in the motordrive mechanism have to be certified. WARNING Small amounts of explosive gases might come out from the breathing devices (dehydrating breather or one-way breather). Make sure that no open fire, hot surfaces or sparks occur in the immediate surroundings of the breathing devices. CAUTION After a trip from a supervisory device, an inspection must be made by a specialist. The diverter switch housing must be drained and the diverter switch lifted and carefully investigated before the transformer is reenergized. Operation – – For resetting of the emergency stop, turn the knob clockwise and switch on the motor protective switch. WARNING The handcrank must not be inserted during electrical operation. WARNING If the tap-changer is not in the exact position and the handcrank is pulled out, the motor-drive mechanism will start and go to the exact position if the power supply is on. WARNING If a failure in power supply occurs during operation, the operation will be completed when the power returns. – – The LOCAL/REMOTE switch. In position LOCAL the tapchanger can be operated by the RAISE/LOWER switch. In position LOCAL remote operation is rendered impossible. In position REMOTE the tap-changer is operated from the control room or by a voltage regulator. Local operation is not possible in remote position. – – In case of a failure in power supply for the motor-drive mechanism, it is possible to handcrank the tap-changer. Put the handcrank on the shaft. Make sure it has entered the slot in the shaft. Crank in the desired direction as per the information plate above the shaft. The number of turns for one step is also shown on the rating plate. When the handcrank is inserted all electrical operations are impossible. Continue cranking until the tap-changer in progress indicator shows POSITION for BUE or white colour for BUL. – – The position indicator shows the actual tap-position. – – The draghands show the max. and min. tap-position between which the tap-changer has been operating since last resetting. –– For BUE: The tap-change in progress indicator shows POSITION in service position, RAISE when operating in a raise operation and LOWER when operating in a lower direction. – – For BUL: The tap-change in progress indicator shows RED during operation and WHITE when the tap-changer is in service position. – – Thermostat for extra heater (option). We recommend a setting at +5 °C. – – Hygrostat for extra heater (option). We recommend a setting at approximately 60 %. – – Outlet (option) with earth fault protector. Normally the tap-changer is controlled by a voltage regulator and no manual operation of the tap-changer and the motordrive mechanism is needed. 1ZSE 5492-155 en, Rev. 4 | User's manual UC 5 Maintenance schedule CAUTION To maintain the high reliability of the tap-changer it is important that the rules for maintenance given below are followed. The maintenance schedule given on the rating plate should always be followed. The statement on the rating plate is maintenance after a certain amount of operations or after a certain time, whichever comes first. In addition to that, an annual inspection should be carried out. Maintenance of the tap-changer consists of three steps: –– Inspection to be carried out by the site personnel once a year. – – Overhaul to be carried out by a specialist at intervals stated on the rating plate. Breakdown voltages according to IEC 60156, 1995-07, should be carried out. The test should be performed as soon as possible after sampling in order to do the test at almost the same oil temperature as in the tap-changer. The following values should be fulfilled: Tap-changer 1) Dielectric strength All star point and all BIL 380 kV ≥ 30 kV/2.5 mm Others ≥ 40 kV/2.5 mm 1) Star point is denoted N, the fifth letter in the type designation. The BIL value is the first numerical digit in the type designation on the rating plate. For instance: UCGRN 380/700. In case the dielectric strength of the oil is lower than the values given above, proceed as follows: – – Make sure the sample is analysed immediately after sampling in order to do the test at approximately the same oil temperature as in the tap-changer – – Measure at least five times and take an average. – – Contact replacement to be carried out by a specialist. The possible need for replacement is decided during overhaul. In addition to these three steps, oil samples according to IEC 60422, 2005-10, should be taken at regular intervals of 2-6 years for those tap-changers having a maintenance interval exceeding 7 years. 6 User's manual UC | 1ZSE 5492-155 en, Rev. 4 – – If the values still do not fulfill the requirements, the oil needs to be treated by filtering. For procedure, see the Maintenance guide. A specialist is a service engineer from ABB or an authorized person trained by ABB for maintenance work on UC tapchangers. Inspection Procedure CAUTION WARNING Approval should be given by the site engineer in charge for inspection as well as for operating the tapchanger. Checking of the breather and the oil level must be carried out from ground level since the transformer is energized. It is recommended to inspect the tap-changer once a year. This principally concerns the motor-drive mechanism and refers to a visual inspection inside the BUE/BUL cabinet to check that nothing is loose, and that the heater is functioning. In the motor-drive mechanism a counter registers every tapchange operation. During inspection the counter is read and noted. If possible, motor and counter are to be tested by operating one step and then back. If the tap-changer has its own oil conservator, the breather and the oil level indicator on the oil conservator are to be checked according to the instructions from the transformer manufacturer. The inspection is to be carried out while the transformer is in service. On the conservator the following are to be checked: –– Oil level – – Breather In the motor-drive mechanism the following items are to be checked: – – Motor and counter – – Emergency stop – – Heater – – Earth fault protector for the outlet (option) If the tap-changer is equipped with an oil filter unit, the pressure drop over the filter is to be checked. Required tools The following eq uipment is required for the inspection: – – Set of screwdrivers – – Pen and note pad 1. Checking of the breather WARNING The breathers and the tube from the conservator might contain explosive gases. No open fire, hot surfaces or sparks may be present when removing the breather. Check the breather according to the instructions for the transformer. 2. Checking of the oil level in the conservator The oil level in the conservator should be according to the instructions in the transformer documentation. 3. Checking of the motor and the counter Open the motor-drive cabinet door and turn the selectorswitch to the LOCAL position. Then turn the control switch to the RAISE (LOWER) position. Check that the motor works properly, the position indicator increases (decreases) one step, and the counter advances one step for each operation. Record the counter’s value. The counter shows the number of operations performed by the tap-changer (the overhaul schedule can be determined with the help of this information). Turn the control switch to the LOWER (RAISE) position. Check that the motor also works properly in that direction, the position indicator decreases (increases) one step and the counter advances one step more. Reset the draghands. Read the counter and note the reading. 4. Checking of the emergency stop Press the emergency stop and the protective motor switch shall switch off. Reset the emergency stop by turning the knob clockwise and set the protective motorswitch to ON. 1ZSE 5492-155 en, Rev. 4 | User's manual UC 7 5. Checking of the earth fault protector (option) If the motor-drive mechanism is equipped with an outlet, the earth fault protector should be tested by pressing the test knob on the outlet on BUE or on the separate earth fault protector on BUL. 6. Checking of the heater WARNING Before starting any work inside the motor-drive mechanism the auxiliary power must be switched off. N. B. The motor, contactors and heating element may be energized from separate sources. 8. Trip or alarm from supervisory devices A tap-changer might be equipped with several different supervisory devices, such as pressure relay, oil flow relay and pressure relief device. Every tap-changer will be equipped with at least one of these devices. Even two or all of these might be installed. The pressure relay and/or the oil flow relay will trip the transformer in case their set points are reached. The pressure relief device might be set to an alarm only or trip as well. In case of an alarm but no trip, we recommend blocking the tap-changer for further operations and call a specialist for consultation as soon as possible. Plan for a possible outage to check the diverter switch. Open the control panel (BUE only). In case of a trip of the transformer, immediately call a specialist and do not try to energize the transformer again until a proper inspection of the diverter switch has been carried out. Prepare for a diverter switch lift. Check by feeling with a finger on the protection plate that the heater has been functioning. In both scenarios, collect the following information before calling the specialist: Close the control panel (BUE only). Reconnect the incoming auxiliary power. – – Serial number of the tap-changer – – Counter reading of the motor-drive mechanism – – If the trip/alarm came during switching. If so, between which positions. – – The load at the time of the trip/alarm – – Which devices have given the trip/alarm – – In case there are more than one tap-changer unit, try to figure out which one has tripped/alarmed. – – Any special service conditions at the time of the trip/alarm, such as overload, thunderstorms, etc. Disconnect the incoming auxiliary power. Complete the inspection by turning the selector-switch to the REMOTE position and close the cabinet door. 7. Checking of the oil filter unit (option) If the tap-changer is equipped with an oil filter unit from ABB: –– Read the pressure gauge. Check according to the oil filter manual. – – Note the reading so the change from year to year can be seen. If moisture is suspected to have come into the tap-changer compartment, the filter insert should be replaced. If a filter insert replacement is needed, call a specialist. Also check for leakages. All leakages should be repaired! 8 User's manual UC | 1ZSE 5492-155 en, Rev. 4 Before a specialist arrives, prepare for a lift of the diverter switch by making sure that a safe disconnection and grounding of the transformer is done. In case no local specialist is available, contact the after sales department. The contact information is found on the last page of this manual. 1 2 1 3 4 5 6 9 7 10 8 Layout of on-load tap-changer. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Bevel gears Horizontal drive shaft with protective tubes Oil valve Pressure relay Top section Vertical drive shaft with protective tubes Rating plate Motor-drive mechanism Diverter switch housing Tap selector 1ZSE 5492-155 en, Rev. 4 | User's manual UC 9 1 3 2 8 4 6 5 7 9 10 11 8 12 15 14 13 16 Cabinet layout of motor-drive mechanism, type BUE. 1. 2. 3. 4. 5. 6. 7. 8. 9. Locking device prepared for padlock Emergency stop Air vent LOCAL/REMOTE switch RAISE/LOWER switch Outgoing shaft Lamp (40 W socket E27) Lifting eye Counter 10 User's manual UC | 1ZSE 5492-155 en, Rev. 4 10. Tap-change in progress indicator 11. Position indicator with drag hands for max. and min. position 12. Shaft for hand crank 13. Protective motor switch 14. Door-operated switch for lamp 15. Hand crank 16. Descriptions and circuit diagram 1 2 14 4 3 5 12 6 8 7 16 9 10 11 13 15 6 Cabinet layout of motor-drive mechanism, type BUL2. 1. 2. 3. 4. 5. 6. 7. Position indicator with drag hands for max. and min. position Tap-change in progress indicator (Red: in progress, White: in position) Counter Outgoing shaft with multi-hole coupling half Shaft for hand crank Locking device prepared for padlock (Option) Outlet 8. 9. 10. 11. 12. 13. 14. 15. 16. Emergency stop RAISE/LOWER switch LOCAL/REMOTE switch Protective motor switch Air vent Door-operated switch for lamp Lamp Descriptions and circuit diagram Hand crank 1ZSE 5492-155 en, Rev. 4 | User's manual UC 11 ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents © Copyright 2013 ABB, All rights reserved. 1ZSE 5492-155 en, Rev. 4, 2013-04-15 Contact us 1ZSC000562-AAY en, Rev. 1 On-load tap-changers, type UCG and VUCG Installation and commissioning guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted. Recommended practices ABB recommends careful consideration of the following factors when installing on-load tap-changers: Before you install or commission a unit, make sure that the personnel doing the job have read and fully understood the installation and commissioning guide provided with the unit. To avoid damaging the unit, never exceed the operating limits stated in delivery documents and on rating plates. Do not alter or modify a unit without first consulting ABB. Follow local and international wiring regulations at all times. Use only factory authorized replacement parts and procedures. Safety warnings The following warnings and notes are used in the manual: WARNING Safety precautions WARNING Unused transformer oil is harmful. Fumes from unused warm oil may irritate the respiratory organs and the eyes. After long and repeated contact with transformer oil, skin becomes very dry. Used tap-changer oil from diverter switch housings and selector switch housings contains harmful substances. Fumes are irritating to the respiratory organs and the eyes and are highly flammable. Used transformer oil may well be carcinogenic. Avoid contact with the oil and use oil-tight protective gloves when handling the oil. First aid: Skin contact: Wash your hands. Use skin cream to counteract drying. In the eyes: Rinse your eyes in clean water. Swallowing: Drink water or milk. Avoid vomiting. Call a doctor. WARNING indicates an imminently hazardous situation, which if not avoided will result in death or serious injury. This signal word is to be limited to the most extreme situations. Collect used oil in oil drums. WARNING also indicates a potentially hazardous situation, which if not avoided could result in death or serious injury. In the event of fire: Any fires should be extinguished with powder, foam or carbonic acid extinguishing agents. CAUTION WARNING CAUTION indicates a potentially hazardous situation, which if not avoided may result in minor or moderate injury. It may also be used to alert of unsafe practices. Be aware of the risk for slipping caused by oil spillage, for instance when working on the transformer cover. Waste and clean-up: Should be absorbed by an absorber. Treat it as hazardous to the environment. WARNING CAUTION may also indicate property-damage-only hazards. INFO provides additional information to assist in carrying out the work described and to provide trouble-free operation. The motor-drive mechanism must not be installed in an explosive atmosphere. The electrical equipment creates sparks that can cause an explosion. WARNING Before any work is carried out on the tap-changer: Make sure that the transformer is disconnected and that grounding is properly conducted. Obtain a signed certificate from the engineer in charge. WARNING CAUTION Before carrying out work on the tap-changer, put the LOCAL/REMOTE switch on the motor-drive mechanism to position 0. It is also advisable to shut the door of the motor-drive mechanism and pad lock it when work is carried out on the tap-changer. The key should be kept by the operator. This is done to avoid an unexpected start of the motor-drive mechanism. To avoid seizing, do not operate the tap-changer during the drying process or afterwards until it is filled with oil. WARNING Before starting any work inside the motor-drive mechanism, the auxiliary power must be switched off. NOTE: The motor, contactors and heating element may be energized from separate sources. During drying of the transformer CAUTION Mounting of gaskets CAUTION Sealing surfaces and gaskets must be clean and undamaged. Diametrically opposed bolts in sealing joints must be tightened alternately several times, beginning with a low tightening torque and finally with the recommended tightening torque as described in Section 1.8 Tightening torques in this guide. During oil filling WARNING The diverter switch should not be installed during drying, since the process removes grease needed for operation. When oil that has been used in a diverter switch housing is pumped out, grounded conducting tubes and hoses should be used to avoid the risk of explosion due to the gases produced by arcs during service. CAUTION CAUTION While drying with hot air and vacuum, the maximum permitted pressure difference for the diverter switch housing is 100 kPa at the maximum permitted temperature of 135 °C (275 °F). Do not fill the diverter switch housing with oil if the transformer tank is under vacuum and the diverter switch housing is not. CAUTION CAUTION During drying with the vapor phase process, the cover of the diverter switch housing and the bottom valve should be left open. The valve is opened with the special bottom valve key – a long hexagonal rod. The maximum permitted temperature is 135 °C (275 °F). Do not fill the transformer tank with oil if the diverter switch housing is under vacuum and the transformer tank is not. After oil filling CAUTION CAUTION Use the special bottom valve key only (delivered with the tap-changer) to operate the bottom valve through the oil draining tube. The use of a stiffer tool may damage the valve. Do not energize the transformer earlier than three hours after oil filling at atmospheric pressure. This waiting period is needed to allow air bubbles to dissipate. During service WARNING Small amounts of explosive gases may be emitted from the breathing devices (dehydrating breather or one-way breather). Make sure that no open fires, hot surfaces or sparks occur in the immediate vicinity of the breathing devices. WARNING If a power supply failure occurs during operation, the operation will be completed when the power returns. WARNING The hand crank must not be inserted during electrical operation. WARNING If the tap-changer is not at its exact position and the hand crank is pulled out, the motor-drive mechanism will start and go to the exact position if the power supply is on. CAUTION After a pressure relay trip, follow the instructions in the chapter “Trip or alarm from supervisory devices” in the user's manual. CAUTION The pressure relay is a calibrated monitoring instrument. It must be handled with care and protected against careless handling or any kind of mechanical damage. Do not open the pressure relay package until just prior to installation on the tapchanger. Content 1. Introduction...........................................................................................................................8 1.1 Type designation............................................................................................................10 1.2 Required tools...............................................................................................................11 1.3 Required material...........................................................................................................11 1.4 Oil..................................................................................................................................11 1.5 Oil conservator...............................................................................................................11 1.6 Oil filter unit for continuous oil filtration...........................................................................12 1.7 Weights.........................................................................................................................12 1.8 Tightening torques.........................................................................................................12 2. Receiving...............................................................................................................................14 2.1 Unpacking.....................................................................................................................14 2.2 Inspection on receipt......................................................................................................14 2.3 Temporary storage before assembly..............................................................................14 3. Installation in the transformer.................................................................................................15 3.1 Cover-mounting.............................................................................................................16 3.1.1 UCG/VUCG with tap selector size C........................................................................16 3.1.2 UCG/VUCG with tap selector size III or F.................................................................19 3.2 Yoke-mounting..............................................................................................................22 3.2.1 Mounting when the transformer ratio measurement is carried out before drying.......23 3.2.2 Mounting when the transformer ratio measurement is carried out after drying..........25 3.2.3 Mounting on transformer cover (after the drying process)........................................26 3.3 Connection to terminals.................................................................................................28 3.4 Transformer ratio measurement......................................................................................30 3.4.1 Transformer ratio measurement before drying..........................................................30 3.4.2 Transformer ratio measurement after drying.............................................................30 4. Drying....................................................................................................................................31 4.1 Precautions before processing.......................................................................................31 4.2 Precautions after processing..........................................................................................31 4.3 Installation of diverter switch..........................................................................................31 5. Final assembly.......................................................................................................................33 5.1 Mounting of motor-drive mechanism..............................................................................33 5.2 Mounting of external drive shafts....................................................................................37 5.2.1 Mounting of vertical drive shaft................................................................................37 5.2.2 Mounting of horizontal drive shaft for one unit..........................................................39 5.2.3 Mounting of horizontal drive shaft for two units........................................................41 5.2.4 Mounting of horizontal drive shafts for three units....................................................43 5.2.5 Before operation......................................................................................................43 5.3 Supervisory equipment..................................................................................................43 5.4 Assembly of accessories................................................................................................43 5.5 Connection to the oil conservator...................................................................................43 5.6. Connection of tube for oil sampling for VUC..................................................................44 6. Oil filling.................................................................................................................................45 6.1 Filling methods and restrictions......................................................................................45 6.2 Before filling...................................................................................................................45 6.3 Filling at atmospheric pressure.......................................................................................45 6.4 Filling under vacuum......................................................................................................45 6.4.1 Oil conservator filled under vacuum.........................................................................45 7. Electrical connection and testing...........................................................................................47 7.1 General..........................................................................................................................47 7.2 Connecting and testing the motor-drive mechanism and the tap-changer...........................47 7.3 Electrical tests on the transformer..................................................................................47 7.4 After energizing..............................................................................................................47 8. Transport...............................................................................................................................48 8.1 Dismantling before transport..........................................................................................48 8.1.1 Dismantling preparations.........................................................................................48 8.1.2 Removal of the vertical drive shaft...........................................................................48 8.1.3 Removal of horizontal drive shaft for one unit...........................................................48 8.1.4 Removal of horizontal drive shafts for two units........................................................ 48 8.1.5 Removal of horizontal drive shafts for three units.....................................................48 8.1.6 Accessories.............................................................................................................49 8.2 Oil level during transport................................................................................................49 8.2.1 Transformer filled with oil..........................................................................................49 8.2.1.1 Conservator mounted......................................................................................49 8.2.1.2 Conservator unmounted..................................................................................49 8.2.2 Transformer drained................................................................................................49 8.2.2.1 Conservator mounted......................................................................................49 8.2.2.2 Conservator unmounted..................................................................................49 9. Commissioning......................................................................................................................50 9.1 Connection to the oil conservator...................................................................................50 9.2 Mounting the motor-drive mechanism and the drive shafts............................................50 9.2.1 Mounting of the motor-drive mechanism..................................................................50 9.2.2 Mounting of the external drive shafts.......................................................................50 9.2.3 Mounting of the vertical drive shaft..........................................................................51 9.2.4 Mounting of horizontal drive shaft for one unit..........................................................52 9.2.5 Mounting of horizontal drive shafts for two units......................................................53 9.2.6 Mounting of horizontal drive shafts for three units ...................................................54 9.2.7 Before operation......................................................................................................54 9.3 Supervisory equipment..................................................................................................54 9.4 Accessories...................................................................................................................54 9.5 Oil filling.........................................................................................................................54 9.6 Electrical connection and testing....................................................................................54 9.6.1 Motor protection......................................................................................................54 9.6.2 Disk brake...............................................................................................................55 9.6.3 Counter...................................................................................................................55 9.6.4 Position transmitter and other position switches......................................................55 9.6.5 Light........................................................................................................................55 9.6.6 Heater.....................................................................................................................55 9.7 Putting into operation.....................................................................................................55 1. Introduction The arrangement of on-load tap-changers types UCG and VUCG, and of the tap-changer system, are shown in Figs. 1 and 2. The tap-changer may consist of one, two or three units driven by the same motor-drive mechanism. The tap-changer is delivered in three main parts: diverter switch housing, tap selector and motor-drive mechanism. The tap-changer is available in designs for cover-mounting or for yoke-mounting. Cover-mounting means that the diverter switch housing is lowered through the hole in the transformer tank and then bolted straight onto the transformer cover, followed by mounting of the tap selector. Yoke-mounting means that the tap-changer is temporarily put on a fork located on the active part of the transformer. Yoke-mounting allows the transformer manufacturer to connect the windings to the tap-changer before drying and without having the transformer cover-mounted. The transformer cover is then lowered onto the tank, and the tap-changer is lifted and bolted to the cover. Use the appropriate instruction for covermounting or yoke-mounting in Chapter 3. At cover-mounting the diverter switch housing is installed on the transformer cover before joining with the tap selector. The exception is the UCG/C and VUCG/C where the tap selector and the diverter switch housing is joined before the entire tapchanger is lowered through the hole in the transformer cover. After the transformer drying process, the motor-drive mechanism and bevel gear are fitted to the transformer tank and the drive shafts are fitted to complete the assembly of the motor-drive mechanism, bevel gear and tap-changer before oil filling and testing. Position numbers in this guide, for example SA11 (see Chapter 5), correspond to those on the packing list for the tap-changer. All instructions are for one tap-changer unit. When there is more than one unit on the transformer, carry out the same procedures for each unit. Horizontal drive shaft and protective tubes Bevel gear Pressure relay Vertical drive shaft and protective tubes Motor-drive mechanism Fig. 1. On-load tap-changer system (single-unit shown). 8 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Oil valve Horizontal drive shafts and protective tubes Bevel gear Bevel gear Vertical drive shafts and protective tubes Shielding caps (only for insulation level above 380 kV) Type of connection, N or E Rating plate Shielding rings (only for insulation level above 380 kV) Hand crank (inside the cover) Motor-drive mechanism Not used for selector, size C Unit -1 Type of connection, B Unit -1 Unit -2 Type of connection, T Unit -1 Unit -2 Unit -3 Fig. 2. Example of on-load tap-changer systems. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 9 1.1 Type designation UCG.. VUCG.. XXXX/YYYY/C,III,F XXXX/YYYY/C,III,F UCG Diverter switch with arc quenching in oil VUCG Diverter switch with vacuum interrupters Example: UCGRE 650/900/III Tap selector size Type of switching L Linear R Plus/Minus D Coarse/Fine Impulse withstand voltage to ground Maximum rated through-current Type of connection N Three-phase star point (one unit) E Single-phase (one unit) T Three-phase fully insulated (three units) B Three-phase delta (two units; single-phase and two-phase Serial No. Serial No. in the bottom of the diverter switch Serial No. Serial No. Serial No. Tap selector size C Tap selector size III Fig. 3. Diverter switch housing UCG/VUCG, and tap selectors size C, III and F. 10 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Tap selector size F 1.2 Required tools – – Standard set of open-end wrenches (up to 24 mm) – – Standard set of sockets (up to 24 mm) – – Standard set of screwdrivers – – Socket handle – – Set of pliers, including cutting pliers – – Dynamometric wrench, 5-85 Nm – – Sliding caliper – – Allen key sockets, 2–10 mm – – Pipe wrench – – Bottom valve key (delivered with the tap-changer) – – Lifting device, article no. LL 135 016-A – – Special hand crank for operating the tap-changer on the bevel gear, article no. LL 117 016-M – – Hack saw (only for installation) – – File – – Folding ruler/tape measure – – Air pump with hose, pressure gauge (0–250 kPa) and connection with internal thread R 1/8” – – Container, 50 liters – – Small oil pump with connection to the oil valve. (For connection size, see the dimensional drawing for the tapchanger.) 1.3 Required material – – Rags for cleaning – – Single-phase diagram for tap-changer – – Gasket for transformer flange – – Insulating paper – – Insulating bushings – – Wooden block as spacer – – Grease (ball bearing grease) GULF-718 EP, Mobil Grease 28, SHELL Aero Shell Grease 22 or similar – – Oil, see Section 1.4 – – Dimensional drawing for the tap-changer for connection dimensions of the oil valve – – Flange for connection to the oil conservator flange when filling under vacuum; see Fig. 38. – – Oil valves for connection to flange with dimensions according to Fig. 51. Can be ordered from ABB. – – Equipment for oil filling – – Sealing tape – – Maintenance guide for tap-changer – – Circuit diagram the motor-drive mechanism – – Oil filter (when there is a common conservator for both the transformer and the tap-changer, this can be ordered from ABB). 1.4 Oil The oil quality should be I -30° according to IEC 60296:2012, and comply with IEC 60422:2008. Upon commissioning, the break-down value should be at least 40 kV/2.5 mm according to IEC 60156. Type designation Oil weight (kg) (The oil for the conservator is not included.) UCG.., VUCG.. 380/..., 650/..., 750/... 150 UCG.., VUCG.. 1050/... 185 Table 1. Weight of oil in kg. WARNING Do not energize the transformer until oil has been filled according to Chapter 6. An UCG.B/VUCG.B requires twice and UCG.T/VUCG.T three times the amount specified above since they have two and three diverter switch housings respectively. 1.5 Oil conservator The tap-changer must be connected to an oil conservator. ABB recommends using a separate conservator for the tapchanger with both the oil and air side separated from the main conservator of the transformer. The volume of the conservator should be such that there is still oil in the conservator even at the lowest expected oil temperature, and such that no flooding can occur at the expected highest oil temperature. Even tap-changers consisting of more than one unit require only one conservator. A suitable dimension of the tube for connection to the conservator is an inner diameter of approximately 20 mm. The tube should be inclined at least 3 degrees to avoid gas pockets in the tube. A valve in the connection to the conservator is recommended. The conservator must be equipped with a breathing device that does not allow moist air into the conservator and that permits the gas to dissipate. The conservator should also be equipped with an oil level indicator, and an alarm contact for low oil level is recommended. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 11 1.6 Oil filter unit for continuous oil filtration If the tap-changer should have an oil filter unit for continuous oil filtration from ABB, installation and commissioning instructions are found in the manual delivered with the unit. 1.7 Weights – – Motor-drive mechanism type BUE: approximately 155 kg – – Motor-drive mechanism type BUL2: approximately 95 kg The weights of the motor-drive mechanism and drive-shaft system are not included in the weights given in Tables 2 and 3. 1.8 Tightening torques The following tightening torques are recommended: For metallic screw joints: M6........... 10 Nm M8........... 24.5 Nm M10.......... 49 Nm M12.......... 84 Nm For non-metallic screw joints: M10.......... 9 Nm M12.......... 13 Nm M16.......... 22 Nm if not otherwise stated in this guide. 12 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 ±10 ±10 ±10 ±10 ±10 ±10 ±10 % % % % % % % On-load tap changer type designation UCG.N UCG.T UCG.B UCG.E Required oil Selector C Selector III Selector F BIL Current in kg Without oil Total Without oil Total Without oil Total 380 300-600 185 319 504 1235 1420 545 730 650 300-600 185 329 514 1415 1600 562 747 1050 300-600 230 349 579 1475 1705 582 812 380 300-600 555 917 1472 985 1540 1185 1740 650 300-600 555 947 1502 1105 1660 1365 1920 1050 300-600 690 1007 1697 1145 1835 1425 2115 380 1200-1500 555 1007 1562 985 1540 1185 1740 650 1200-1500 555 1037 1592 1105 1660 1365 1920 1050 1200-1500 690 1097 1787 1145 1835 1425 2115 380 300-600 370 633 1003 370 740 1010 1380 650 300-600 370 653 1023 430 800 1130 1500 1050 300-600 460 693 1153 450 910 1170 1630 380 300-600 185 289 474 395 580 395 580 650 300-600 185 299 484 455 640 455 640 1050 300-600 230 319 549 475 705 475 705 380 1200-1500 185 319 504 395 580 395 580 650 1200-1500 185 329 514 455 640 455 640 1050 1200-1500 230 349 579 475 705 475 705 Table 2. Weights for type UCG. On-load tap changer type designation VUCG.N VUCG.T VUCG.B VUCG.E Required Selector C Selector III Selector F BIL Current oil in kg Without oil Total Without oil Total Without oil Total 380 450-800 185 344 529 440 625 570 755 650 450-800 185 354 539 450 635 587 772 1050 450-800 230 374 604 470 700 607 837 380 450-800 555 942 1497 1101 1656 1260 1815 650 450-800 555 972 1527 1131 1686 1440 1995 1050 450-800 690 1032 1722 1191 1881 1500 2190 380 800-1800 555 1032 1587 1224 1779 1260 1815 650 800-1800 555 1062 1617 1254 1809 1440 1995 1050 800-1800 690 1122 1812 1314 2004 1500 2190 380 450-800 370 658 1028 816 1186 1060 1430 650 450-800 370 678 1048 836 1206 1180 1550 1050 450-800 460 718 1178 876 1336 1220 1680 380 450-800 185 314 499 367 552 420 605 650 450-800 185 324 509 377 562 480 665 1050 450-800 230 344 574 397 627 500 730 380 800-1800 185 344 529 408 593 420 605 650 800-1800 185 354 539 418 603 480 665 1050 800-1800 230 374 604 438 668 500 730 Table 3. Weights for type VUCG. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 13 2. Receiving 2.1 Unpacking Check that the packages are free from transport damage. Open the covers of the transport boxes, Remove the supporting block of wood. If any package is damaged, a careful investigation must be carried out. Lift the tap-changer parts by their lifting eyes according to Fig. 4. 2.2 Inspection on receipt 1. Check that the diverter switch housing, tap selector, motor-drive mechanism and accessories are undamaged. 2. If transport damage is found, and it is judged that correct operation of the tap-changer is not possible, a damage report should be sent to the insurance company. It is also recommended that photographs be taken of the damaged parts. Mark the photos with ABB’s reference number and the serial number of the tap-changer and send them to ABB. 3. Check that the parts delivered, type designations and the serial numbers agree with the delivery documents, e.g. the packing list or ABB’s order acknowledgement. The serial numbers to be checked are those on the rating plate, on the diverter switch housing and on the tap selector. For locations; see Fig. 3. The serial number on the parts belonging to one tap-changer unit should all be the same. 2.3 Temporary storage before assembly If the tap-changer is not to be assembled immediately, once the delivery has been approved, the tap-changer and the motor-drive mechanism must be stored at a warm and dry indoor location. Keep the units in their plastic enclosures and do not remove the drying agent until assembly. 14 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 3. Installation in the transformer WARNING Either the cover-mounting method or yoke-mounting method is used. The angle between the lifting slings should be no more than 90°. WARNING WARNING The intermediate gear and the insulating shaft of the diverter switch housing moves during operation. Maintain a safe distance during operation to avoid injuries! Lowering the complete tap-changer to the floor without support entails a risk for tipping, personal injury and equipment damage. The diverter switch housing and the tap selector are designed to be lifted by the lifting eyes; see Fig. 4. Max 90° Diverter switch housing Max 90° Max 90° Max 90° Tap selector C Tap selector III Tap selector F Fig. 4. How to lift the diverter switch housing and the tap selector. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 15 3.1 Cover-mounting The diverter switch housing and the tap selector are delivered in separate packaging. 3.1.1 UCG/VUCG with tap selector size C 1. Unpack the diverter switch housing and the tap selector, and remove the drying agent. 2. Fit the gasket into the tap-changer flange on the transformer cover; see Fig. 6. (This gasket is not included in the delivery). 3. Remove the transport locking and the lifting eyes with fasteners from the top section of the tap selector; see Fig. 8. 8. Lift the tap-changer by the lifting eyes as shown in Fig. 4 and lower it carefully through the opening in the transformer top cover; see Fig. 5. Correctly position the tap-changer for mounting the outer shaft system (see transformer drawing). The studs on the flange on the transformer cover shall fit into the holes in the flange of the diverter switch housing. Fit twenty-four washers and M12 nuts (not included in the delivery); see Fig. 6. Tighten the nuts. WARNING The diverter switch housing and the tap selector contain moving parts. Observe caution! CAUTION Do not operate the tap selector until it is connected to the diverter switch housing. 4. Lift the diverter switch housing by the lifting eyes and remove the transport support. Remove the three limbs, see Fig. 9. 5. Lift the diverter switch housing into position and fit the tap selector to the diverter switch housing; see Fig. 10. The tap selector drive pin must fit into the large gear wheel slot; see view A-A. Diverter switch Tap selector size C Opening in the transformer cover CAUTION The drive crank on the tap selector may only be moved slightly to engage the slot in the large gear wheel of the diverter switch housing. Fig. 5. 6. Insert the fastening screws (six hexagon screws M8x35) and washers. Tighten the screws. 7. If the tap-changer is equipped with a tie-in resistor for mounting under the tap selector, the tie-in resistor is mounted after joining the tap selector to the diverter switch housing. After mounting the tie-in resistor, the tap-changer must not be set down so that it stands on the tie-in resistor. It must be suspended from an overhead crane, for example. Top section Stud M12 Nut M12 (24x) Washer (24x) Flange WARNING Gasket Lowering the complete tap-changer to the floor without support entails a risk for tipping, personal injury and equipment damage. Transformer top cover Fig. 6. 16 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 ~ 3 mm 9. Connect the supplied conductors between the diverter switch housing and tap selector; see Fig. 10. The conductor ends and their connecting points have the same markings. The number of conductors varies depending on the rated through-current and the type of connection. 10. If the impulse withstand voltage to ground (BIL) exceeds 380 kV, insulate the connections on the tap selector by winding paper around them to a thickness of approximately 3 mm; see Fig. 7. The paper should be of the same quality as used for insulation of conductors within the active part of the transformer. ~ 100 mm Locking nut Conductor Spring washer Insulating paper Plain washers Connection point on the tap selector Socket screw CAUTION Fig. 7. After mounting the shielding ring, the tap-changer must not stand on the shielding ring. 11. Continue with section 3.3. Transport locking (to be removed) Driving crank Screws (4 pcs) (to be removed) Fig. 8. Tap selector size C, top view. Diverter switch housing, lower part Limbs (3 pieces) Hexagon screws and nut (3 pieces) Transport supports Fig. 9. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 17 Washer 14x30x2,5 Spring washer Locking nut M12 Socket-head cap screw M12 Diverter switch housing Shielding rings F F B–B Conductor Insulating shaft B B F–F Conductors Locking nut M10 Spring washer Washer 10.5x24x3 D A A Socket-head cap screw Large gear wheel Conductor C–C D Tap selector, size C Diverter switch housing Current collector C C Tap selector Washer 8.4x20x2 Spring washer Hexagon headed screw M8x35 Conductors D–D Insulating bolt M16x110 Slot in the large gear wheel of the diverter switch housing Insulating nut M16 Cleats Driving pin of the tap selector A–A Fig. 10. Diverter switch UCG/VUCG, and tap selector, size C. 18 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 3.1.2 UCG/VUCG with tap selector size III or F 1. Unpack the diverter switch housing and the tap selector, and remove the drying agent. 2. Fit the gasket into the tap-changer flange on the transformer cover; see Fig. 12. (This gasket is not included in the delivery.) 3. Lift the diverter switch housing by the lifting eyes as shown in Fig. 4 and lower it carefully through the opening in the transformer top cover; see Fig. 11. Correctly position the diverter switch housing correctly for mounting the outer shaft system (see transformer drawing). The studs on the flange on the transformer cover shall fit into the holes in the flange of the diverter switch housing. Fit twenty-four washers and M12 nuts (not included in the delivery); see Fig. 12. Tighten the nuts. 4. Position the tap selector for joining to the diverter switch housing. Lift by the lifting eyes as shown in Fig. 4. 5. If the tap-changer is equipped with a tie-in resistor for mounting under the tap selector, the tie-in resistor is mounted after joining the tap selector to the diverter switch housing. After mounting the tie-in resistor, the tap-changer must not be set down so that it stands on the tie-in resistor. It must be suspended from an overhead crane, for example. If the tap-changer is equipped with a tie-in resistor switch, the switch is mounted under the tap selector upon delivery. A special support in the box ensures that it stands on the tap selector bottom. If this special support is removed from the box, the tap selector can stand on this when joining to the diverter switch housing. After joining, the complete tap-changer is lifted and the special support is removed. The complete tap-changer must not be set down on the special support. It must be suspended from an overhead crane, for example. 7. Lift the diverter switch housing into position and fit the tap selector to the diverter switch housing; see Fig. 14. The tap selector drive pin must fit into the large gear wheel slot; see view A-A. CAUTION The drive crank on the tap selector may only be moved slightly to engage the slot in the large gear wheel of the diverter switch housing. Diverter switch Opening in transformer cover Tap selector size III or F Fig. 11. Top cover WARNING Lowering the complete tap-changer to the floor without support entails a risk for tipping, personal injury and equipment damage. Top section Nut M12 (x24) Washer (x24) Stud (x24) 6. Remove the transport locking and the lifting eyes with fasteners from the top section of the tap selector; see Fig. 13a-b. Gasket CAUTION Transformer top cover Do not operate the tap selector until it is connected to the diverter switch housing. Fig. 12. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 19 8. Insert four M10x40 screws and washers through the tap selector upper part to the four supports of the diverter switch housing. Tighten the screws; see view E-E, Fig. 14. Transport locking (to be removed) WARNING Drive crank The diverter switch housing and the tap selector contain moving parts. Observe caution! 9. Connect the supplied conductors between the diverter switch housing and tap selector. The conductor ends and their connecting points have the same markings. Fasten the conductors with cleats. The number of conductors varies depending on the rated through-current and the type of connection. Screw (to be removed) Fig. 13a. Tap selector size III, top view. WARNING The wires coming from the transformer’s regulating winding may not pass through the spaces between the change-over selector and the fine selector. 10. If the impulse withstand voltage to ground (BIL) exceeds 380 kV, insulate the connections on the tap selector by winding paper around them to a thickness of approximately 3 mm; see Fig. 9. The paper should be of the same quality as used for insulation of conductors within the active part of the transformer. 11. If the impulse withstand voltage to ground (BIL) exceeds 380 kV, mount the supplied shielding ring (TS 11) at the bottom plate of the tap selector; see view D–D. Transport locking (to be removed) Screw (to be removed) Fig. 13b. Tap selector size F, top view. CAUTION After mounting the shielding ring, the tap-changer must not stand on the shielding ring. 12. Continue with Section 3.3. 20 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Lifting eyes with fasteners (to be removed) Washer 14x30x2,5 Spring washer Locking nut M12 Socket-head cap screw M12 Diverter switch housing F F B–B B Conductor B F–F Insulating shaft Conductors Locking nut M12 Spring washer E A A Socket-head cap screw Washer 14x30x2.5 E Conductor C–C Socket-head cap screw M8x25 Spring washer C C Locking nut M8 Current collector D–D Tap selector, size III D Shielding ring, TS 11 Diverter switch support D Tap selector Cleats Insulating nut M16 Washer 10.5x24x3 (x4) Spring washer Insulating stud M16x120 E–E Socket-head cap screw M10x40 (x4) Slot in the large gear wheel of the diverter switch housing Conductors A–A Driving pin of the tap selector Fig. 14. Diverter switch UCG/VUCG, and tap selector III or F. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 21 3.2 Yoke-mounting (Pre-mounting on active part of the transformer.) The top section of the diverter switch housing is designed to be divided into an upper and a lower flange (see Figs. 16 and 18) to fit the yoke-mounting. Before lifting and joining the diverter switch housing to the transformer cover, it is placed on a yoke fork (two beams) that is fastened on the upper transformer yoke; see Fig. 15. Bevel gear On-load tap-changer The guide pins used on the yoke fork should be insulated with bushings in order to prevent circulating current in the yoke fork when the transformer is in operation. Mounting of the tap-changer on the yoke fork can be carried out by two alternative methods depending on when the transformer ratio measurement is carried out: Fig. 15. Yoke-mounting principle. – – Transformer ratio measurement is carried out before the drying process; see Section 3.2.1. –– Transformer ratio measurement is carried out after the drying process; see Section 3.2.2. For mounting on the transformer cover after the drying process; see Section 3.2.3. CAUTION To avoid seizing, do not operate the tap-changer, neither during the drying process nor afterwards, until the diverter switch housing is filled with oil and the tap selector is immersed in oil. 22 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Transformer active part Yoke fork 3.2.1 Mounting when the transformer ratio measurement is carried out before drying 1. Assemble the diverter switch housing and the tap selector according to Section 3.1.3, steps 1, and 4-12. 2. Lift the tap-changer onto the yoke fork (use the lifting eyes at the top of the tap-changer; see Fig. 4). Place the tapchanger in position for mounting the outer shaft system (see transformer drawings). Insert and tighten the supplied guide pins DS 7 and insulating bushings (not included in delivery) in the lower flange; see Fig. 16. The guide pins must be secured by center punch marks in the pins. 3. Mount the conductors between the regulating winding and the tap selector according to Section 3.3. 4. Carry out transformer ratio measurement according to Section 3.4 in this guide. 5. Remove the diverter switch housing cover (see Fig. 18) by removing the screws. Store the cover, fasteners and O-ring at a dust-free location. 6. If the vapor phase process will be used: Remove the plug in the T-coupling for the oil drainage tube. To open the bottom valve, let the bottom valve key (DS16), slide down through the oil drainage tube, and when it has gripped the valve, rotate it in a counter-clockwise direction until it stops after approximately 6 turns; see Fig. 19. Refit the plug. 7. Remove the diverter switch by carefully lifting it straight out of the diverter switch housing by its lifting eye; see Fig. 18. Store the diverter switch at a dry and dust-free location. WARNING For VUCG: The vacuum interrupters are sensitive and the diverter switch must thus be handled with care. 8. Remove the oil drainage tube by hand or by means of a pipe wrench, placing a cloth between the tube and the pipe wrench to protect the tube. Store the tube in the diverter switch housing until it is remounted. 9. Remove the four clamp screws, M10 x 35, and the washers that hold the bevel gear; see Fig. 18. Note the position of the bevel gear. Carefully remove the gear housing, and put the parts in a safe place. Store the bevel gear at a dust-free location. CAUTION Do not remove the locking device for the bevel gear. 10. Mount the locking device DS 4 on the drive shaft of the tap-changer. Secure with center punch marks Upper flange Lower flange 42 mm O-ring Yoke fork Diverter switch housing Insulating bushing (not included) Guide pin DS 7 (outer diameter = 12 mm) Fig. 16. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 23 CAUTION The drive shaft must not be rotated. 11. The guide bar for positioning the diverter switch in the housing is secured in the upper flange with screws and washers. Remove the screws and washers. Store the guide bar in the diverter switch housing until it is remounted. Save the screws and washers. 12. Remove the nuts and washers inside the upper flange and remove the flange by lifting it by the lifting eyes. Store the upper flange, and the O-ring at a dust-free location. Save the nuts and washers. 13. The tap-changer is now ready for drying together with the transformer. Follow the instructions in Chapter 4. Oil drainage plug Socket handle Bottom valve key DS16, key width 10 mm Oil drainage tube Position indicator Red mark Fig. 17. Bevel gear. Fig. 19. Cover O-ring Bevel gear Lifting eye for the diverter switch O-ring Upper flange O-ring Lower flange Fig. 18. 24 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Locking device DS 4 3.2.2 Mounting when the transformer ratio measurement is carried out after drying 1. Assemble the diverter switch housing and the tap selector according to Section 3.1.3, steps 1 and 4-12. 2. Follow the instructions according to Section 3.2.1, steps 5-13. 3. Attach the lifting device LL 135 016-A according to Fig. 20. Max. 90° The lifting device must be tilted when attaching. Lifting device Lift the tap-changer onto the yoke fork. Place the tapchanger in position for mounting the outer shaft system (see transformer drawing). Insert the supplied guide bolts DS 7 and insulating bushings (not included in delivery) in the lower flange; see Fig. 16. The guide bolts must fit into the holes in the yoke fork and be secured by punch marks in the pins. When the tap-changer is in place, remove the lifting device. 4. Mount the conductors between the transformer winding and the tap selector according to Section 3.3. 5. The tap-changer is now ready for drying together with the transformer. Follow the instructions in Chapter 4. Fig. 20. Attachment of lifting device. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 25 3.2.3 Mounting on transformer cover (after the drying process) 1. After the transformer cover is mounted, place the gasket in the flange for the tap-changer. (This gasket is not included in the tap-changer delivery.) 7. Place the O-ring for the bevel gear in its groove in the upper flange; see Fig. 22. Remount the bevel gear unit in the position it had before removal, and make sure that the pin in the spherical shaft end fits into the drive shaft slot without rotating the drive shaft. Secure the gear unit in the flange with its four clamping screws M10x35 and washers. Do not insert the studs for the upper flange in the transformer cover flange. This is carried out at step 8. CAUTION The gear box must not be forced down. If the coupling does not engage, lift the gear box and adjust the setting of the drive pin. 2. Remove the locking device DS 4 from the drive shaft; see Fig. 18. CAUTION Be careful not to drop the locking device and the screw. CAUTION The drive shaft must not be rotated. 3. Place the O-ring in its groove in the lower flange; see Fig. 16. 4. Place the upper flange over the opening in the transformer cover. Turn the upper flange so that the flange for the bevel gear is aligned with the drive shaft. The screws in the lower flange must fit into the holes in the upper flange; see Fig. 21. 5. Lift the tap-changer slowly until it just touches the upper flange. Use lifting device LL 136 016-D. Attach the device at the lower flange sides. The lifting device must be tilted when attaching and removing; see Fig. 20. 6. When the flanges touch, fit twenty M8 locking nuts and washers. Turn the nuts alternately until fully tightened. Retighten all nuts to 24.5 Nm. After tightening the nuts, remove the lifting device. 8. Insert 24 studs; see Fig. 21, through holes in the upper flange, down into the threaded holes in the flange of the transformer cover. If the studs do not fit, the position of the tap-changer must be adjusted, which may require lifting. Lift by the lifting eyes as shown in Fig. 4. After mounting the studs, remove the lifting device and tighten the nuts. 9. Mount the oil drainage tube; see Fig. 19. If a pipe wrench is used, there must be cloth protection between the wrench and the tube. 10. Mount the guide bar for the diverter switch; see Fig. 18. Fit the washers and screws and tighten. 11. Remove the plug at the end of the T-coupling (see Fig. 23), slide down the bottom valve key and close the valve by turning the key clockwise approximately 6 turns. Tighten to 40 Nm. Refit the plug. 12. Install the diverter switch according to Section 4.3. 26 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Locking nut M8 (20x) Upper flange Studs M12 (24x) Spring washer Nuts M12 Flat washer 8.4x20x2 Washers O-ring Lower flange Yoke fork Fig. 21. Plug Attachment clamps 40 Nm Pin O-ring Slot in drive shaft Fig. 22. Oil drainage tube Fig. 23. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 27 3.3 Connection to terminals Connection to the tap selector should follow the connection diagram supplied with the tap-changer. In order to obtain maximum reliability for the tap selector contacts, the temperature rise of the conductors connected to the tap selector should be kept as low as possible and should never be more than 30K above the surrounding oil. CAUTION All connections should be made carefully and in such a way that there is no risk that they can loosen. The conductors must not cause mechanical strain on the tap selector terminal. Each conductor should be curved to take up expansion. See Fig. 25. CAUTION CAUTION All terminals must have conductors or connections. If there are connections between parallel conductors from the diverter switch on the tap selector terminal, the parallel conductors from the active part of the transformer should also be connected on the tap selector terminals (in order to avoid circulation currents through the tap selector contacts; see Fig. 27). If the impulse withstand voltage to ground exceeds 380 kV, the conductor connections on the tap selector shall be insulated by winding paper around them to a thickness of 3 mm; see Fig. 9. The paper should be of the same quality as used for insulating conductors within the active part of the transformer. Tap selector It is advisable that the distance between the cylinders or the bars of the tap selector and any conductor be at least 50 mm. The transformer manufacturer is responsible for maintaining sufficiently large insulation distances. When yoke-mounted, inserts (wooden blocks, or similar) are placed between the yoke fork and the lower flange of the diverter switch housing (see Fig. 27), so that the conductors can be mounted at the correct height. The wooden blocks must be removed before mounting the tap-changer on the transformer cover. Conductors from diverter switch Conductors from active part of the transformer Connection Fig. 24. 28 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Connection Tap selector Terminal Expansion bend Faulty Correct Fig. 25. Connection of conductors to the selector. NOTE: The cable for the marked contact must be attached under the fixed contact so that space is sufficient up to the top flange. This is only applies to the top phase. NOTE: Caps must be used for this type of connection. Cable aligned with fixed contact les ab c llel ra Pa Fig. 26. Connection of conductors to tap selector C. Lower flange Yoke fork beam Inserts Fig. 27. Mounting of tap-changer on the yoke fork. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 29 3.4 Transformer ratio measurement The transformer ratio measurement may be taken before or after the drying process. If it is taken before drying, no drive system is mounted. The tap-changer thus must be operated directly on the shaft coupling of the bevel gear on the upper flange. A special hand crank can be ordered from ABB; see Section 1.2. If it is taken after drying, it is advisable to do this when the drive system is mounted, after final assembly (see Chapter 5), to simplify operation of the tap-changer. 3.4.1 Transformer ratio measurement before drying 1. Remove the locking device from the gear unit on the upper flange; see Fig. 28. Save the locking device for reuse after transformer ratio measurement. Also remove the cover of the bevel gear to access the position indicator. Save all fasteners and the gasket for reuse. Note the position of the tap-changer. 2. Operate the tap-changer by putting the special hand crank on the shaft coupling of the bevel gear. Adjust the length of the handle. Be careful not to damage the coupling. When operating through the middle position on a tapchanger with the change-over selector, the torque on the hand crank will be higher. CAUTION The tap-changer should be operated through the whole operating range, both in the lower and raise direction, when taking the ratio measurement. CAUTION Before the process, the tap-changer may be operated a maximum of three times through the regulating range as long as it is immersed in oil. After the process, the tap-changer must be immersed in oil before operating. CAUTION The end-positions must not be overrun during ratio measurement. When operating the tap-changer without the drive system, check the designation of the end-positions on the single-phase diagram and monitor the position indicator on the bevel gear to avoid overrunning the end-position. 3. After the measurement, the tap-changer must be operated in the direction and to the position shown in the singlephase diagram as the delivery position. The right position designation should be shown in the window in the position indicator on the bevel gear of the tap-changer, and the window should exactly face the red mark in the bevel gear housing; see Fig. 17. Remount the locking device on the bevel gear and the cover of the bevel gear. Carefully fit the gasket. 3.4.2 Transformer ratio measurement after drying Take this measurement after the drive system is mounted. Operate the tap-changer by means of the motor-drive mechanism, in the direction and to the position shown in the single-phase diagram as the delivery position after the measurement. Locking device CAUTION Check the voltmeter during tap-changer operations. No rapid voltage drops may occur during operation. If such drops occur, the diverter switch is installed incorrectly or the tap-changer is not correctly connected to the winding. UCG and VUCG.N or E Fig. 28. 30 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 UCG and VUCG.T or B 4. Drying The tap-changer is dried together with the transformer using one of the following processes: alternating hot air and vacuum, or vapor phase at a temperature of no more than 135 °C (275 °F). 3. If a tie-in resistor from ABB is supplied, its screw joints are to be retightened (tightening torque 15 Nm) and locked using the method specified by the transformer manufacturer for similar screw joints. 4.1 Precautions before processing 1. If not done earlier, lift the diverter switch out from the housing; see Section 3.2.1, steps 5 and 7. The pressure relay with its test vent and oil filter, if any, should be removed and protected from dust, e.g. placed in a plastic bag or in their original packing. 2. Do not expose the diverter switch housing to any pressure difference between the inside and outside during the vapor phase process. During the hot air and vacuum process, the maximum permitted pressure differential is 100 kPa at a temperature of 135 °C (275 °F). During the vapor phase process, the bottom valve of the diverter switch housing should be open. To open the bottom valve, proceed as follows; see Fig. 19: a. Remove the plug on top of the oil drainage tube. b. Use the bottom valve key through the oil drainage tube. c. Turn the valve counter-clockwise to its stop, approximately 6 turns. d. Refit the plug. e. Remove the O-ring in the lower flange (for mounting on active part only) before the process. 4.3 Installation of diverter switch When yoke-mounted, carry out the steps in Section 3.2.3 before installing the diverter switch. WARNING For VUCG: The vacuum interrupters are sensitive and the diverter switch must thus be handled with care. CAUTION Check the serial numbers to make sure that the diverter switch is mounted in the correct housing; see Fig. 3. CAUTION Make sure that the diverter switch housing is clean and dry, and that no foreign objects (tools, etc.) are left in the housing. CAUTION 4.2 Precautions after processing CAUTION To avoid seizing, do not operate the tap-changer, neither during the drying process nor afterwards, until it is filled with oil. 1. Make sure that all liquid has been drained from the diverter switch housing after the vapor phase process has been carried out. When cover-mounted, close the bottom valve; see Section 3.2.3, step 10. When yoke-mounted, the valve is closed during refitting of the top section. CAUTION Make sure that the bottom valve key is removed after the valve has been closed. 2. The cleats on the upper section of the tap selector that hold the conductors between the diverter switch housing and the tap selector should be retightened (tightening torque 15 Nm) and locked by a method specified by the transformer manufacturer for similar screw joints. Carefully lower the diverter switch into its housing so that neither the diverter switch nor the housing is damaged. The diverter switch is provided with guide slots that fit against the guide bar and the oil drainage tube in the diverter switch housing; see Fig. 29. Rotate the diverter switch so the crescent-shaped guide slot is aligned with the oil draining tube. When the diverter switch is lowered, visually check that its plug-in contacts are aligned with the contacts in the cylinder wall. In order to ensure that the diverter switch pin has engaged the coupling disk, carry out at least three tap change operations in one direction. A distinct sound is heard when the diverter switch falls into place. If no sound is heard, the reason can be that the pin fits directly into the slot or that the diverter switch might need to be pushed down while operating the motor-drive. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 31 Carry out another three operations in the same direction while pushing down the diverter switch. when lowered to its final position. Only the springs of the lifting device should be above this level. For UCG, it may be necessary to push and pull the lifting device for the diverter switch a little back and forth while pushing down. Insert the O-ring for the cover in the upper flange. Mount the tap-changer cover. Turn the cover so that the guide pin in the housing is facing the guide hole in the cover. (The cover must be pressed down in order to overcome the force of the springs that hold the diverter switch pressed in place.) Fit the screws and washers and tighten them. The top part of the diverter switch lifting device should be below the level of the upper part of the housing for the cover Buffer springs Lifting device Shielding-ring (when the impulse withstand voltage to earth exceeds 380 kV) (not on UCG short version) Transition resistors (Layed down on UCG short type) Transition resistor Serial number (on the opposite side of the diverter switch) A A Plug-in contacts Guiding pin Guiding pin Plug-in contacts A A Tie rod Coupling with driving-pin Driving pin UCG Guiding pins VUCG Coupling disc Notch for the driving pin Slot for guiding bar Holes for guiding pins Guiding pins Guiding bar for the diverter switch Slot for oil draining tube Oil draining tube Diverter switch housing, view from above Fig. 29. 32 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 A–A 5. Final assembly 5.1 Mounting of motor-drive mechanism See Figs. 30 and 31. Proceed as follows: 1. Mount the motor-drive mechanism onto the transformer. The mounting holes on the transformer should be level within 1 mm. If adjustment is needed, shims should be used. 2. Install the bevel gear SA 21 on the edge of the transformer cover; see Fig. 32. 3. Check that the position indicator on the motor-drive mechanism shows the same position as the indicator inside the bevel gear of the tap-changer. (The cover has to be removed.) WARNING Do not energize the transformer before the tapchanger and the motor-drive mechanism are correctly assembled. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 33 Exact position Max. deviation Transformer The same indicated tap position Position indicator Brake disc Adjustment nuts Red mark Brake assembly Fig. 30. Position alignment for UCG/VUCG with motor-drive mechanism BUE. 34 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Exact position Transformer Max. deviation The same indicated tap position Indicator flag 4 5 6 7 10 11 12 8 9 3 2 1 13 14 15 16 17 18 19 12 34567 Position indicator Roller on the brake arm in the notch of the cam disc Brake arm Cam disc Contra nut Brake disc Adjusting screw Fig. 31. Position alignment for UCG/VUCG with motor-drive mechanism type BUL. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 35 Connection type T Unit –1 SA10 SA10 SA10 Unit –2 SA25 SA21 SA10 SA25 Unit –3 SA10 SA10 SA25 SA33 SA17 SA18 SA19 SA20 SA23 SA10 SA22 SA24 SA31 SA30 SA32 SA35 SA34 SA36 NOTE The slot in the protective tube faces downwards Connection type B Unit –1 SA10 SA10 SA10 Unit –2 SA25 SA21 SA10 SA25 SA33 SA17 SA18 SA19 SA20 SA23 SA10 SA22 SA24 SA31 SA30 SA32 Connection type N or E SA 10Hose clip Unit –1 SA 11Coupling halves SA 12Allen screw M6 SA 13Washer SA10 SA10 SA25 SA21 SA 14Vertical square shaft SA 15Vertical protective tube SA17 SA18 SA19 SA 16Vertical protective tube SA 17Clamp SA 18Hex head bolt M10 SA20 SA10 SA23 SA22 SA 19Washer SA24 SA12, SA13 SA11 SA16 SA14 SA 20O-ring SA 21Bevel gear SA25 SA15 SA11 SA12, SA13 SA10 SA 22Horizontal square shaft for unit -1 SA 23Horizontal protective tube for unit -1 SA 24Horizontal protective tube for unit -1 SA 25Information label SA 30Horizontal square shaft for unit -2 SA 31Horizontal protective tube for unit -2 SA 32Horizontal protective tube for unit -2 Motor-drive mechanism SA 33Cover SA 34Horizontal square shaft for unit -3 SA 35Horizontal protective tube for unit -3 SA 36Horizontal protective tube for unit -3 Fig. 32. Shaft system. 36 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 5.2 Mounting of external drive shafts The external drive shafts consist of square tubes and should be connected to the spherical shaft ends on the bevel gears and motor-drive mechanism by means of two coupling halves. The square shafts and protective tubes must be cut before mounting. CAUTION Before mounting of shafts and couplings, everything must be cleaned and greased for correct function and to avoid corrosion. Apply a thin layer of grease, GULF-718EP Synthetic Grease or Mobil Grease 28 or SHELL Aero Shell Grease 22 to all spherical shaft ends and unpainted surfaces of the bevel gears. 5.2.1 Mounting of vertical drive shaft 1. Mount the bevel gear SA21 on the transformer, with O-ring SA20, four clamps SA17, hex head bolts M10, SA18 and washers SA19; see Fig. 32. 2. Determine the distance K2 between the spherical shaft ends; see Fig. 33. 3. Cut the vertical square shaft, SA14, to length = K2 minus 6 mm. Remove burrs. 4. Cut the protective tubes SA15 and SA16 to the same length LB2 according to Table 4. K2 = 200 to 290 mm K2 = 291 to 600 mm K2 = greater than 600 mm K2+180 mm LB2 = 2 K2+220 mm LB2 = 2 LB2 = K2+410 mm 2 Example: K2 measured at 350 mm. LB2 is then = 350+220 570 = = 285 mm 2 2 Table 4. Lengths for LB2. The multi-hole couplings should be greased. The inclination of the shaft (the square tube) must not be more than 40 (=70 mm for every 1000 mm shaft length). The tubes around shafts and couplings are for protection. The arrangement of the drive shaft system is shown in Fig. 32. CAUTION Make sure that all locking devices (on the bevel gear, on the tap-changer and in the motor-drive) are mounted and the tap-changer and the motor-drive are at the same service position. Check that the motor-drive mechanism is at its exact position according to Fig. 30 or 31. (BUE: The red mark on the brake disk facing the red mark on the brake assembly. BUL: The roller in the middle of the notch in the cam disk). If not, loosen the locking device (see Fig. 50) and adjust it to the exact position. Remount the locking device. Let the parts of the shaft system that should be removed before transporting the transformer to the site keep their identification numbers according to the packing list to simplify remounting of the shaft system on site. 5. See Fig. 38. Fit two coupling halves, SA11, on one end of the square shaft with six screws SA12 and washers SA13. Push the shaft to the bottom of the fitting in the coupling halves. Tighten the two screws; A first and then the other. Fit the two protective tubes, SA15 and SA16, (the larger diameter at the top) and two hose clips SA10; see Fig. 35. 6. See Fig. 34. Connect the square shaft with the mounted coupling halves to the shaft of the bevel gear. Mount two coupling halves SA11 to the other end of the square shaft and the shaft of the motor-drive mechanism. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Tighten the screws lightly and check that the shaft can be moved approximately 2 mm in the axial direction (axial play). Check the dimension shown in Fig. 36. Tighten the two screws; A first and then the other. 7. See Fig. 35. Mount the tube with the larger diameter, SA16, to the bevel gear with a hose clip and the other SA15 to the flange on the motor-drive mechanism with a hose clip. Leave about 3 mm of play to the flange ring for water drainage. The tube with the larger diameter is mounted on the bevel gear. Tighten the two screws; A and then the other, according to Fig. 38. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 37 SA21 SA11 SA10 SA10 SA16 SA16 SA15 SA15 SA10 SA14 SA14 SA26 SA27, SA28 SA29 SA15 SA10 Min. 3, max. 5 mm K2 BUE BUL Fig. 34. Fig. 35. A Max. 3 mm Drive pin Max. 6 mm Fig. 33. Square shaft SA11 SA13 SA12 A Fig. 36. Fig. 37. 38 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 Fig. 38. 5.2.2 Mounting of horizontal drive shaft for one unit The following applies to the fitting of the drive shaft and protective tube when the tap-changer consists of one unit, UCG.N/VUCG.N or UCG.E/VUCG.E. 1. Determine the distance K1 between the spherical shaft ends; see Fig. 39. 2. Cut the horizontal square shaft SA22 to length = K1 minus 6 mm. Remove burrs. 3. Cut the protective tubes SA23 and SA24 at the nonslotted end to the same length LB1 according to Table 5. Protective tube SA23 has one slotted end. K1 = 170 to 290 mm K1 = 291 to 600 mm K1 = greater than 600 mm K1+200 mm LB1 = 2 K1+250 mm LB1 = 2 LB1 = K1+500 mm 2 Example: K1 measured at 400 mm. LB1 is then = 400+250 2 = 650 2 = 325 mm 7. See Figs. 30 and 31. The motor-drive mechanism and the tap-changer should have the same indicated tap position and be in their exact positions. Remove the cover of the gear box on the tap-changer to access the position indicator. The motor-drive mechanism and tap-changer are in the same position when the position indicators on both of them show the same position. The motor-drive mechanism is at the exact position since the steps in Section 5.2 have been carried out. The tap-changer is in the exact position when the window where the position is read on the bevel gear is exactly facing the red mark in the gear box housing. If the gear box is not at its exact position, loosen the two screws in the multi-hole coupling on the gear box and find the position of the screws that positions the opening in the brass-toothed wheel closest to the red mark in the gear box housing. The maximum deviation from exact alignment is given in Figs. 30 and 31. Tighten the screws. Remount the cover and the gasket of the gear box on the tap-changer; see Fig. 22. Table 5. Length for LB1. WARNING If K1 is greater than 600 mm, the mounted tubes must overlap by at least 300 mm. Removal and inspection of the couplings should be possible when one of the tubes is pushed into the other. 4. Mount two coupling halves, SA11, on one end of the square shaft with six screws SA12 and washers SA13. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Tighten the two screws; A first and then the other; see Fig. 38. Mount the two protective tubes, SA23 and SA24, the slotted end of SA23 in the non-overlapping end, and two hose clips SA10; see Fig. 40. 5. Remove the locking device on the bevel gear of the diverter switch housing by loosening the two set screws; see Fig. 42. 6. Connect the square shaft with the mounted coupling halves to the shaft of the bevel gear SA21; see Fig. 44. Mount two coupling halves SA11 to the other end of the square shaft and to the shaft of the bevel gear on the tap-changer. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Lightly tighten the screws and check that the shaft can be moved approximately 2 mm in the axial direction (axial play). Check the dimension shown in Fig. 36. Tighten the two screws; A first and then the other; see Fig. 38. Assembly with the tap-changer and the motor-drive mechanism at different operating positions may cause transformer failure. WARNING The bevel gear contains moving gears. Observe caution! 8. Push the two protective tubes onto the bevel gears and clamp them with hose clips, SA10; see Fig. 45. The slot on the protective tube SA23 should be facing downwards. Apply the self-adhesive information plates SA25 around the tubes at about the middle of the tube length. Carefully turn the multi-hole coupling on the gear box until the gear box is at the exact position. Find the two holes matching each other in the multi-hole coupling and refit the two screws. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 39 LB1 Slotted end K1 SA14 Fig. 39. SA24 SA10 SA23 SA11 Fig. 40. Locking device Disc M8 screw Drive pin Fig. 41. Fig. 42. Locking device, single-unit tap-changer. A Spherical coupling part SA12 SA13 SA24 SA10 SA23 Slot SA21 SA11 Fig. 43. SA10 SA24 SA25 SA23 SA25 SA10 SA21 Slot facing downwards SA23 Fig. 44. 40 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 5.2.3 Mounting of horizontal drive shaft for two units The following applies to the fitting of drive shafts and their protective tubes when the tap-changer consists of two phases UCG.B/VUCG.B. The tap-changer unit, which is placed closest to the drive mechanism, is called unit -1, and the second unit -2; see Fig. 32. Mount the shaft between the motor-drive mechanism and unit-1 according to Section 5.2.2. Mount the shaft between unit-1- and unit-2 according to the following instructions: 1. Determine the distance K3 between the spherical shaft ends; see Fig. 45. 2. Cut the horizontal square shaft SA30 to length = K3 minus 6 mm. Remove burrs. 3. Cut the protective tubes SA31 and SA32 at the nonslotted end to the length LB3 = (K3+500 mm)/2; see Fig. 46. 4. Fit two coupling halves, SA11, on one end of the square shaft with six screws SA12 and washers SA13. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Tighten the two screws; A first and then the other; see Fig. 47. Fit the two protective tubes, SA31 and SA32, the slotted end of SA31 in the non-overlapping end, and two hose clips SA10; see Fig. 46. 5. Remove the locking device on the bevel gear of the diverter switch housing by loosening the two set screws; see Fig. 49. 6. Connect the square shaft with the mounted coupling halves to the shaft of the bevel gear closest to the motordrive; see Fig. 47. Mount two coupling halves SA11 to the other end of the square shaft and to the shaft of the bevel gear on the tap-changer. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Lightly tighten the screws and check that the shaft can be moved approximately 2 mm in the axial direction (axial play). Check the dimension shown in Fig. 36. Tighten the two screws; A first and then the other. The unit should be at the same service position as the adjacent unit and be at the exact position. Compare with the adjacent unit and adjust this unit as described in Section 5.2.3, point 7 if necessary. WARNING The bevel gear contains moving gears. Observe caution! 7. Push the two protective tubes on the bevel gears and clamp them with the hose clips SA10; see Fig. 48. Apply the self-adhesive information plates SA25 around the tubes at about the middle of the tube length. The slot on the protective tubes should be facing downwards. 8. Mount the protective cover SA33. Tighten the two set screws, (taken from the locking device); see Fig. 49. LB3 K3 A SA30 Fig. 45. SA32 SA10 SA31 SA11 Fig. 46. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 41 Disc Coupling SA12 SA13 A SA11 SA10 SA32 SA10 SA30 SA31 Fig. 47. Locking device Set screw Cover SA 33 SA10 SA10 SA25 SA32 SA31 Fig. 48. Locking device Set screws Cover SA 33 Fig. 49. Locking device and cover, multiple-unit tap-changer. 42 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 5.2.4 Mounting of horizontal drive shafts for three units The following applies to the fitting of drive shafts and their protective tubes when the tap-changer consists of three phases UCG.T/VUCG.T or UCGYD/VUCGYD. The tapchanger unit, which is placed closest to the drive mechanism, is called unit -1, the next unit -2 and the last unit -3; see Fig. 32. 1. Mount the drive shaft to the tap-changer unit -1 according to Section 5.2.2, steps 1–8. 2. Mount the drive shaft between unit -1 and unit -2 according to Section 5.2.3, steps 1–8. 3. Mount the drive shaft between unit -2 and unit -3 according to Section 5.2.3, steps 1–8. The shaft here is SA34, the protective tube closest to unit -2 is SA35 and the other protective tube is SA36. When a support bearing is used, follow the appropriate parts of Section 5.2.3, steps 2–8. If transformer ratio measurement is to be conducted after drying, this is a suitable stage to carry it out; see Section 3.4.2. 5.3 Supervisory equipment Accessories and safety devices are described in a separate document, Accessories and protection devices for on-load tapchangers, 1ZSC000562-AAD. 5.4 Assembly of accessories All parts that have been removed for transport are specified on the packing list. The openings on the tap-changer are sealed by a transport cover. 1. Remove the transport covers. 2. Check the O-rings. Make sure that they are pressed into the bottoms of the grooves on the flanges. 3. Assemble all remaining accessories. Tightening torque for the nuts is according to Section 1.8. 5.5 Connection to the oil conservator WARNING If oil filling is carried out under a vacuum without the oil conservator, the steps in this section are performed after oil filling. The bevel gear contains moving gears. Observe caution! 5.2.5 Before operation 1. Check again that the tap-changer and the motor-drive mechanism are at the same position. 2. Remove the locking device for the motor-drive mechanism; see Fig. 50. Remove the transport cover on the flange for connection to the oil conservator. Make sure that the O-ring is in place on the flange and connect the pipe to the oil conservator. Tighten the nuts; see Fig. 51. Locking device BUE BUL Fig. 50. Locking device for motor-drive mechanism. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 43 5.6. Connection of tube for oil sampling for VUC Preparation for oil sampling is done at the transformer workshop as part of the tap-changer installation. – – The oil valve (see Fig. 45) should be removed and reconnected at the end of the draining tube at operable ground level. – – The tube, through which oil samples are taken, must be connected to a sample pipe, see Fig. 47. The tube shall be of ½ inch. – – Information regarding the flanges, view A-A and view B-B, see Fig. 46. A-A B-B O-ring Ø 44.2 x 5.7 Ø 75 Ø 75 45° 45° 4 x M10 Ø 106 Fig. 51. Oil valve. Ø 106 Fig. 52. Sample pipe dimensions. Extra oil valve shall be removed and used as a sample valve Tube ½” UCG top cover Transformer cover Oil valve Fig. 53. Extra oil sampling valve. The valve is removed and then refitted at the end of the sampling tube. 44 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 4 x Ø 11 6. Oil filling 6.1 Filling methods and restrictions Oil filling can be carried out at atmospheric pressure or under a vacuum. The wall between the diverter switch housing and the transformer tank is designed to withstand a vacuum on one side and atmospheric pressure on the other. It is not permitted to have a vacuum on one side and the pressure of a high oil column on the other. The pressure difference between the inside and outside of the tap-changer cylinder may not exceed 100 kPa at any time. Oil filling may be carried out in different ways depending on what the transformer manufacturer finds convenient as long as the instructions above are followed and the tap-changer is filled with oil to the correct level. The methods below are recommended, and if they are followed in detail, no pressure limits will be exceeded and the oil levels will be correct. 6.2 Before filling Upon commissioning, open the cover and check that the diverter switch housing is dry and clean and that the diverter switch is in place. Check that the bottom valve is closed. Follow step 11 in Section 3.2.3. Tightening torque 40 Nm (see Fig. 18). 6.3 Filling at atmospheric pressure 1. Open the conservator valve, if any. 2. Remove the breathing device on the conservator for the tap-changer. 3. Remove the cover. 4. Pump oil into the diverter switch housing via the oil valve, see Fig. 53 (for connection dimensions, see the dimensional drawing for the tap-changer). 5. Refit the cover as per Section 4.3. WARNING Do not energize the transformer earlier than three hours after oil filling at atmospheric pressure. This waiting period is needed to allow air bubbles to dissipate. CAUTION The valve is located at ground level. 6. Continue to pump in oil until the conservator is filled to its correct level. Also see Section 1.5. 7. Shut the oil valve and disconnect the pump. 8. Refit the breathing device. Make sure that the connection to the breathing device is properly sealed. 6.4 Filling under vacuum Filling under a vacuum is not necessary but may be carried out with the conservator. After filling under a vacuum, no standing time is needed. The methods below ensure that no permitted pressure differences are exceeded. For vacuum filling without the conservator connected, contact the manufacturer for advice. 6.4.1 Oil conservator filled under vacuum 1. Establish a connection between the oil conservator for the transformer and the oil conservator for the tap-changer. 2. Open the valve between all tap-changer units and the conservator and close the oil valve. 3. Put the transformer under vacuum. (The tap-changer is put under vacuum automatically.) 4. Let oil in through the oil valve of the tap-changer. (For connection dimensions, see the dimensional drawing for the tap-changer.) 5. When the needle of the oil level indicator in the oil conservator starts to move, close the oil valves on all units. Open one at a time and close each when the needle in the oil level indicator starts to move. Fill the conservator to the right level before closing the oil valve for the last unit. (This is done to make sure that all units are properly filled. Differences in flow rates might otherwise cause some of the units to not completely fill.) 6. When atmospheric pressure is restored in the transformer, remove the connection between the two conservators and connect the breathing device to the oil conservator for the tap-changer. Make sure that the connection to the breathing device is properly sealed. When filling more than one unit, fill all of them according to points 3 to 5. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 45 Pipe connection Vacuum Oil Ø 75 Stud M10 Transformer Tap-changer Ø 44.2 Ø 5.7 Oil O-ring Ø 20 Fig. 54. Assembly O-ring. Fig. 55. Oil filling under vacuum. 46 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 7. Electrical connection and testing 7.1 General Before the transformer is energized, tests must be carried out to ensure that all mechanical and electrical connections are correct, and to check the proper function of the motor-drive mechanism and the tap-changer. When testing the transformer, the tap-changer can be operated either by the hand crank or electrically. When operating electrically, the motor-drive mechanism is connected according to Section 7.2. WARNING Dangerous voltage! For BUE: Run the motor-drive mechanism and check again that the red mark on the brake disk stops within the tolerance of ± 25° from the exact position; see Fig. 30. For BUL: Run the motor-drive mechanism and check that the center of the notch in the cam disk stops within ±2 mm from the center of the roller on the brake arm; see Fig. 31. WARNING For adjustment of the motor-drive mechanisms, see If 2 kV insulation testing is to be performed, some equipment must be disconnected in order to avoid damage. Examples of equipment to be disconnected are the measuring transducer, pressure relay, diodes (for example, N4) and temperature relays. 7.2 Connecting and testing the motor-drive mechanism and the tap-changer Connect the ground connection from the transformer to the ground terminal on the tap-changer flange. Connect the ground connector from the transformer to the ground terminal on the motor-drive mechanism. Connect the motor supply and the control supply to the correct terminals on the motor-drive mechanism as shown by the circuit diagram supplied with the tap-changer. Operate the motor-drive mechanism by means of the hand crank to a position at the middle of the range but not in a through-position ( = a position with a letter in). Operate the drive mechanism electrically between the endpositions. Check the end-stops. When attempting to operate electrically beyond the end-position, the motor should not be started. Check the mechanical end-stop by attempting to hand crank it beyond the end-position. After a couple of turns on the hand crank, it should be mechanically stopped. Hand crank back to the end-position (where the indicator flag is positioned at the middle for BUE and when the indicator flag is white for BUL). Operate the tap-changer electrically to the other end-position and repeat the test procedure above. WARNING The transformer must never be energized when the end-stop is inoperable. 7.3 Electrical tests on the transformer Acceptance tests on the transformer or commissioning can now be performed. Turn the control selector switch to position LOCAL. Now send a pulse for a RAISE operation. If the phase sequence is wrong, (three-phase supply), the motor-drive mechanism will start in the LOWER direction. The motor-drive mechanism will stop when it has made approximately half of the complete operation and will operate back and forth without the tapchanger changing position until the control selector switch is turned to position 0. Maintenance guide 1ZSC000498-ABH. 7.4 After energizing WARNING Before any work is carried out on the tap-changer: Make sure that the transformer is disconnected and grounding is properly performed. Obtain a signed certificate from the engineer in charge. If the phase sequence is wrong, reverse two of the motor supply cables to attain the correct sequence. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 47 8. Transport 8.1 Dismantling before transport The tap-changer is usually transported without accessories (pressure relay, motor-drive mechanism, bevel gear and drive shafts) to prevent damage to these parts. To make sure that everything is set up properly on site with a minimum amount of work, it is important to put the tap-changer at the position and operated from the position given in the single-phase diagram delivered with the unit, and to fit locking devices properly during dismantling at the transformer factory. Removal of the motor-drive mechanism and drive shafts is performed in the opposite order of assembly. 8.1.1 Dismantling preparations Before dismantling, mark the parts to facilitate identification. Check the position of the motor-drive mechanism according to Fig. 30 (BUE) or Fig. 31 (BUL). Use the hand crank to adjust it to its exact position. Install the locking device on the motor-drive mechanism; see Fig. 50. The arrangement of the drive shaft system is shown in Fig. 32. 8.1.2 Removal of the vertical drive shaft 1. Loosen the hose clips holding the protective tubes to the bevel gear and motor-drive mechanism. Push one of the protective tubes into the other. Remove the screws holding the bevel gear SA21. Detach the bevel gear by carefully lifting it off the shaft while holding the vertical drive shaft. Detach the vertical shaft including the protective tubes by lifting it off the coupling of the motor-drive mechanism. Mark the parts. 2. Pack screws, clamps, protective tubes, shafts, hose clips, protective cover, coupling halves, bevel gear and seals for transportation to the site. 8.1.3 Removal of horizontal drive shaft for one unit 1. Lock the bevel gear with the locking device, and two set screws see Fig. 42. 2. Loosen the hose clips holding the protective tubes to the bevel gears. Push one of the protective tubes into the other. Loosen the screws holding the coupling halves at one end of the shaft and detach them. Detach the horizontal shaft. Mark the parts. 3. Pack screws, clamps, protective tubes, shafts, hose clips, protective cover, coupling halves, bevel gear and seals for transportation to the site. 8.1.4 Removal of horizontal drive shafts for two units 1. Detach the protective cover SA33 on the bevel gear of unit -2, and lock the bevel gear with the locking device marked -2, and two set screws; see Fig. 42. 2. Loosen the hose clips holding the protective tubes to the bevel gears for units -1 and -2. Push one of the protective tubes into the other. Loosen the screws holding the coupling halves at one end of the shaft and detach them. Detach the horizontal shaft between units -1 and -2. 3. Lock the bevel gear for unit -1 with the locking device marked -1, and two set screws; see Fig. 49. 4. Loosen the hose clips holding the protective tubes to the bevel gear SA21 and the bevel gear of tap-changer unit -1. Push one of the protective tubes into the other. Loosen the screws holding the coupling halves at one end of the shaft and detach them. Detach the horizontal shaft between unit -1 and bevel gear SA21. Mark the parts. 5. Pack screws, clamps, protective tubes, shafts, hose clips, protective cover, coupling halves, bevel gear and seals for transportation to the site. 8.1.5 Removal of horizontal drive shafts for three units 1. Detach the protective cover SA33 on the bevel gear for unit -3, and lock the bevel gear with the locking device and set screws marked -3; see Fig. 42. 2. Loosen the hose clips holding the protective tubes to the bevel gears of unit -2 and unit -3. Push one of the protective tubes into the other. Loosen the screws holding the coupling halves at one end of the shaft and remove them. Detach the horizontal shaft between units -2 and -3. 3. Lock the bevel gear for unit -2 with the locking device marked -2 and two set screws. 4. Loosen the hose clips holding the protective tubes to the bevel gears of units -1 and -2. Push one of the protective tubes into the other. Loosen the screws holding the coupling halves at one end of the shaft and remove them. Detach the horizontal shaft between units -2 and -1. 5. Lock the bevel gear for unit -1 with the locking device marked -1 and set screws; see Fig. 49. 6. Loosen the hose clips holding the protective tubes to the bevel gear SA21 and the bevel gear for tap-changer unit -1. Push one of the protective tubes into the other. Loosen the screws holding the coupling halves at one end of the shaft and remove them. Detach the horizontal shaft between unit -1 and bevel gear SA21. Mark the parts. 7. Pack screws, clamps, protective tubes, shafts, hose clips, protective cover, coupling halves, bevel gear and seals for transportation to the site. 48 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 8.1.6 Accessories If the pressure relay is to be removed, see the assortment guide, 1ZSC000562-AAD. 8.2.1.2 Conservator unmounted The oil level of the diverter switch housing should be lowered to 150 mm below the upper edge of the housing. If other accessories are to be removed for transport reasons, pack them in the packages they were delivered in and refit the transport covers. Fit the O-rings and tighten the nuts. When the conservator is removed, take off the cover of the diverter switch housing and drain the oil with a pump to 150 mm below the upper edge of the housing. Refit the cover. Turn the cover so that the guide pin in the housing is facing the guide hole in the cover. Make sure the gasket is properly positioned. Seal all flange connections by fitting gaskets and covers. Close all valves. 8.2 Oil level during transport The following adjustments of the oil level should be carried out when the tap-changer is to be transported. 8.2.2 Transformer drained When the transformer is transported without oil, the tapchanger should also be transported without oil. CAUTION Take care to avoid intake of moist air when oil is drained. If the ambient air is moist, let incoming air pass through a dehydrating breather with a slow air flow to obtain proper dehydration. 8.2.2.1 Conservator mounted Drain the oil from the diverter switch housing by means of a pump connected to the oil valve. Let the tap-changer maintain contact with the ambient air through the breathing device on the conservator. 8.2.1 Transformer filled with oil When the transformer is transported filled with oil, the tapchanger should also be transported filled with oil. 8.2.1.1 Conservator mounted The diverter switch housing should be filled to the normal operating level, and the valve for the conservator should be open. 8.2.2.2 Conservator unmounted Drain the oil as described in Section 8.2.2.1. Now remove the conservator connection. Seal the diverter switch housing against ambient air by fitting covers with gaskets and closing all valves. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 49 9. Commissioning This chapter describes tasks to be carried out on the tapchanger when the transformer is being installed and tested on site. Check all fittings and alignments, even if the shaft system has been set up in the transformer factory. The identification numbers on critical parts from the packing list are specified in the following instructions; see Sections 5.1 and 5.2. CAUTION The motor-drive mechanism must be protected against condensation. 9.2.1 Mounting of the motor-drive mechanism See Figs. 30 and 31. Proceed as follows: Energize the heater when power is available. When not, put drying agent inside the motor-drive cabinet and seal the vents. 1. Mount the motor-drive mechanism on the transformer. The mounting holes on the transformer should be level within 1 mm. If adjustment is needed, shims should be used. 2. Install the bevel gear, SA21, on the edge of the transformer cover. 3. Check that the position indicator on the motor-drive mechanism shows the same position as the indicator inside the bevel gear of the tap-changer. 4. Remove the drying agent inside the cabinet. Fig. 1 shows the arrangement of the tap-changer, motor-drive mechanism and drive shafts. The pressure relay is usually delivered in a separate package and installed upon commissioning. Depending on the transport requirements, the transformer may be delivered with or without the motor-drive mechanism and drive shaft system attached. The tap-changer may be delivered filled with oil or without oil. Use the relevant parts of this manual to perform commissioning. For information about tools, materials and oil required, see the relevant parts of Chapter 1. 9.1 Connection to the oil conservator Follow the appropriate parts of the instructions in Section 5.5. WARNING Do not energize the transformer before the tapchanger and the motor-drive mechanism are correctly assembled. 9.2.2 Mounting of the external drive shafts The external drive shafts consist of square tubes and should be connected to the spherical shaft ends on the bevel gears and motor-drive mechanism by means of two coupling halves. Connect the cables to the low level alarm contact on the oil level indicator. 9.2 Mounting the motor-drive mechanism and the drive shafts The motor-drive mechanism and drive-shaft system should have been assembled and disassembled in the transformer factory according to the instructions in this guide. Locking devices should have been installed when it was disassembled. If all locking devices are in place according to the transport sections in this guide, there should be no need for adjustments. CAUTION Before mounting shafts and couplings, everything must be cleaned and greased for correct function and to avoid corrosion. Apply a thin layer of grease, GULF 718EP Synthetic Grease or Mobil Grease 28 or SHELL Aero Shell Grease 22 to all spherical shaft ends and unpainted surfaces on the bevel gears. If necessary, Sections 5.1 and 5.2 provide complete information for fitting and adjusting of the shaft system. The arrangement of the drive shaft system is shown in Fig. 32. 50 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 The multi-hole coupling should be greased. The tubes around shafts and couplings are for protection. CAUTION SA18, SA19 Make sure that all locking devices (on the bevel gear, on the tap-changer and in the motor drive) are mounted and the tap-changer and the motor-drive are in the same service position. SA17 SA21 SA20 Driving pin Check that the motor-drive mechanism is at its exact position according to Figs. 30 or 31. (BUE: The red mark on the brake disk facing the red mark on the brake assembly, BUL: The roller at the middle of the notch in the cam disk.) If not, loosen the locking device and adjust it to its exact position. See Fig. 50. Refit the locking device. 9.2.3 Mounting of the vertical drive shaft 1. Mount the bevel gear SA21 on the transformer with an O-ring, SA20, clamps SA17 screws and washers; see Figs. 56 and 57. 2. Fit the square shaft SA14 with protective tubes SA15 and SA16 and hose clips according to Fig. 34. Connect the square shaft with the mounted coupling halves to the motor-drive. Mount two coupling halves SA11 to the other end of the square shaft and the shaft of the bevel gear; see Fig 34. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Tighten the screws lightly and check that the shaft can be moved approximately 2 mm in the axial direction (axial play). Check the dimension shown in Fig. 36. Tighten the two screws; A first and then the other; see Fig. 38. 3. Mount the protective tube with the larger diameter, SA16 to the bevel gear with a hose clip, and the other tube SA15 to the flange of the motor-drive mechanism; see Fig. 35. Leave about 3 mm of play to the flange ring for water drainage. SA11 SA16 SA10 SA15 SA14 Motor-drive mechanism Fig. 56. SA20 SA18, SA19 SA17 Attachment flange for the bevel gear Fig. 57. Bevel gear assembly. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 51 9.2.4 Mounting of horizontal drive shaft for one unit 1. Fit the square shaft SA22, protective tubes SA23 and SA24 and hose clips according to Fig. 40. 2. Connect the square shaft with the mounted coupling halves to the shaft of the bevel gear; see Fig. 58. Mount two coupling halves SA11 to the other end of the square shaft and the shaft of the other bevel gear. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Tighten the screws lightly and check that the shaft can be moved approximately 2 mm in the axial direction (axial play). Check the dimension shown in Fig. 36. Tighten the two screws; A first and then the other; see Fig. 38. 3. See Figs. 30 and 31. The motor-drive mechanism and the tap-changer should have the same indicated tap position and be at their exact positions. The motor-drive mechanism and the tap-changer are at the same position when the position indicators for both of them show the same position. The motor-drive mechanism is at the exact position since the steps in Section 9.2.2 have been carried out. The tap-changer is at the exact position when the window where the position is read on the bevel gear is exactly facing the red mark in the gear box housing. If the gear box is not at its exact position, carry out point 5 and loosen the two screws in the multi-hole coupling on the gear box and find the position of the screws that positions the opening in the brass-toothed wheel closest to the red mark in the gear box housing. The maximum deviation from exact alignment is given in Fig. 30. Tighten the screws. WARNING Assembly with the tap-changer and the motor-drive mechanism in different operating positions may cause transformer failure. 4. Push the two protective tubes onto the bevel gears and clamp them with hose clips SA10; see Fig. 48. The slot of the protective tube SA23 should be facing downwards. The self-adhesive information plates SA25 are at about the middle of the tube length. Do not remove the locking device before one end of the shaft of the bevel gear is connected to the drive shaft. SA11 Fig. 58. 52 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 SA21 9.2.5 Mounting of horizontal drive shafts for two units Mount the shaft between the motor-drive mechanism and unit-1 according to Section 9.2.4. Mount the shaft between unit-1 and unit-2, as follows: 1. Loosen the set screws for the locking device of the bevel gear on the top of the tap-changer; see Fig. 48. Remove the locking device. 2. Mount the cover SA33 and tighten the set screws (from the locking device). 3. Fit the square shaft SA30, protective tubes SA31 and SA32 and hose clips according to Fig. 47. 4. Connect the square shaft with the mounted coupling halves to the shaft of the bevel gear; see Fig. 47. Mount two coupling halves SA11 to the other end of the square shaft and the shaft of the other bevel gear. Push the shaft to the bottom of the fitting in the coupling halves; see Fig. 37. Tighten the screws lightly and check that the shaft can be moved approximately 2 mm in the axial direction (axial play). Check the dimension shown in Fig. 36. Tighten the two screws; A first and then the other; see Fig. 38. If the exact position of the closest unit has been adjusted, the locking device might have to be removed (step 6) before step 3 can be carried out. 5. See Figs. 30 and 31. The motor-drive mechanism and the tap-changer should have the same indicated tap position and be at their exact positions. The motor-drive mechanism and the tap-changer are at the same position when the position indicators for both of them show the same position. The motor-drive mechanism is at the exact position since the steps in Section 9.2.2 have been carried out. The tap-changer is at the exact position when the window where the position is read on the bevel gear is exactly facing the red mark in the gear box housing. If the gear box of this unit is not at its exact position, carry out point 6 and loosen the two screws in the multihole coupling on the gear box and find the position of the screws that positions the opening in the brass-toothed wheel closest to the red mark in the gear box housing. The maximum deviation from exact alignment is given in Fig. 30. Tighten the screws. WARNING Assembly with the tap-changer and the motor-drive mechanism in different operating positions may cause transformer failure. 6. Push the two protective tubes onto the bevel gears and clamp them with hose clips SA10; see Fig. 48. Apply the self-adhesive information plates SA25 around the tubes at about the middle of the tube length. 7. Loosen the two set screws (see Fig. 49) and remove the locking device. 8. Mount the cover SA33. Tighten the two set screws (see Fig. 44) taken from the locking device. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 53 9.2.6 Mounting of horizontal drive shafts for three units The following applies to the fitting of drive shafts and their protective tubes when the on-load tap-changer consists of three insulated units UCG.T/VUCG.T or UCGYD/VUCGYD. The on-load tap-changer unit, which is placed closest to the drive mechanism, is called unit -1, the second unit -2 and the last unit -3; see Fig. 41. 1. Mount the drive shaft on the on-load tap-changer unit -1 according to Section 9.2.5, steps 1–5. Remove the set screws according to Fig. 49. 2. Mount the drive shaft between unit -1 and unit -2 according to Section 9.2.5, steps 1-6. Remove the set screws according to Fig. 49. 3. Mount the drive shaft between unit -2 and unit -3 according to Section 9.2.5, steps 2-7. The shaft here is SA34, the protective tube closest to unit -2 is SA35 and the other protective tube is SA36. Do not remove the locking device before one end of the shaft of the bevel gear is connected to the drive shaft. In cases where a support bearing is used, follow the appropriate parts of Section 9.2.5, steps 2-5. 9.3 Supervisory equipment Accessories and safety devices are described in Accessories and protection devices for on-load tap-changers, 1ZSC000562‑AAD . 9.4 Accessories Refit all other accessories, if any, that have been removed for transport. Follow the appropriate parts of Section 5.4. 9.5 Oil filling Follow the appropriate parts of Chapter 6. 9.6 Electrical connection and testing Carry out all wiring work and appropriate tests according to Chapter 7. Remove the drying agent inside the cabinet of the motor-drive mechanism. 9.6.1 Motor protection The function of the protective motor switch is checked. For three-phase AC motors, one of the phase fuses is removed and the function time of the protective motor switch is checked by a RAISE or LOWER operation. The protective motor switch should release within 60 seconds at a current setting equal to the rated current of the motor at the actual voltage. WARNING 9.2.7 Before operation 1. Check again that the on-load tap-changer and the motordrive mechanism are at the same operating position; see Section 5.1. 2. Remove the locking device for the motor-drive mechanism; see Fig. 50. The motor power voltage is dangerous. CAUTION If the protective motor switch has not released within 60 seconds, disconnect the power and check the settings against the rating plate of the motor. Adjust if necessary and check again when the motor has cooled down. WARNING Assembly with the on-load tap-changer and the motor-drive mechanism at different operating positions may cause transformer failure. The door of the motor-drive mechanism can be locked with a padlock (not included in the delivery). Protective motor switches for DC motors and for single-phase AC motors are not tested. Do not remove the locking device before one end of the shaft of the bevel gear is connected to the drive shaft. 54 Installation and commissioning guide UCG/VUCG | 1ZSC000562-AAY en, Rev. 1 9.6.2 Disk brake For BUE: Run the motor-drive mechanism and check again that the red mark on the brake disk stops within the tolerance of ± 25° from the exact position; see Fig. 30. For BUL: Run the motor-drive mechanism and check that the center of the notch in the cam disk stops within ±2 mm from the center of the roller on the brake arm; see Fig. 31. For adjustment of the motor-drive mechanisms, see the maintenance guide: 1ZSE 5492-124 for UCG or 1ZSC000498‑ABD for VUCG . 9.6.3 Counter Check that the counter is functioning for RAISE and LOWER operations. 9.6.4 Position transmitter and other position switches Check the function of the position transmitter and other position switches. 9.6.5 Light Check that the light is switched on when the door is opened and goes out when the door is closed. 9.6.6 Heater Switch off all power sources and check with a finger that the heater has warmed up during earlier tests. Switch on the power afterwards. 9.7 Putting into operation Set the LOCAL/REMOTE switch to REMOTE. Reset the drag hands. Make sure that no tools or foreign objects are left in the motor-drive cabinet or on the transformer cover. Close the door to the motor-drive. 1ZSC000562-AAY en, Rev. 1 | Installation and commissioning guide UCG/VUCG 55 ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents © Copyright 2015 ABB, All rights reserved. 1ZSC000562-AAY en, Rev. 1, 2015-10-30 Contact us 1ZSE 5492-124 en, Rev. 6 On-load tap-changer, type UCG Maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted. Recommended practices ABB recommends careful consideration of the following factors when installing on-load tap-changers: Before you install or commission a unit, make sure that the personnel doing the job have read and fully understood the installation and commissioning guide provided with the unit. To avoid damaging the unit, never exceed the operating limits stated in delivery documents and on rating plates. Do not alter or modify a unit without first consulting ABB. Follow local and international wiring regulations at all times. Use only factory authorized replacement parts and procedures. Safety warnings The following warnings and notes are used in the manual: WARNING WARNING indicates an imminently hazardous situation, which if not avoided will result in death or serious injury. This signal word is to be limited to the most extreme situations. WARNING also indicates a potentially hazardous situation, which if not avoided could result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation, which if not avoided may result in minor or moderate injury. It may also be used to alert of unsafe practices. CAUTION may also indicate property-damage-only hazards. INFO provides additional information to assist in carrying out the work described and to provide trouble-free operation. Safety precautions WARNING The Maintenance guide should be read and understood before any work is started, and the procedures in this document should be followed at all times. WARNING Before any work is carried out on the tap-changer: Make sure that the transformer is disconnected and that grounding is properly conducted. Obtain a signed certificate from the engineer in charge. WARNING Before carrying out work on the tap-changer, put the LOCAL/REMOTE switch on the motor-drive mechanism to position 0. It is also advisable to shut the door of the motor-drive mechanism and pad lock it when work is carried out on the tap-changer. The key should be kept by the operator. This is done to avoid an unexpected start of the motor-drive mechanism. WARNING Before starting any work inside the motor-drive mechanism, the auxiliary power must be switched off. NOTE: The motor, contactors and heating element may be energized from separate sources. WARNING In no case should any person go down into the diverter switch housing. The cleaning of the diverter switch housing should be carried out by using brushes and rags and by flushing with oil. CAUTION Approval should be given for inspection as well as for operating the on-load tap-changer. CAUTION ABB recommends that only maintenance engineers trained by ABB carry out contact replacement. During service During oil handling WARNING WARNING Small amounts of explosive gases may be emitted from the breathing devices (dehydrating breather or one-way breather). Make sure that no open fires, hot surfaces or sparks occur in the immediate vicinity of the breathing devices. Unused transformer oil is harmful. Fumes from unused warm oil may irritate the respiratory organs and the eyes. After long and repeated contact with transformer oil, skin becomes very dry. WARNING If a power supply failure occurs during operation, the operation will be completed when the power returns. WARNING The hand crank must not be inserted during electrical operation. WARNING If the tap-changer is not at its exact position and the hand crank is pulled out, the motor-drive mechanism will start and go to the exact position if the power supply is on. Used tap-changer oil from diverter switch housings and selector switch housings contains harmful substances. Fumes are irritating to the respiratory organs and the eyes and are highly flammable. Used transformer oil may well be carcinogenic. Avoid contact with the oil and use oil-tight protective gloves when handling the oil. First aid: Skin contact: Wash your hands. Use skin cream to counteract drying. In the eyes: Rinse your eyes in clean water. Swallowing: Drink water or milk. Avoid vomiting. Call a doctor. Collect used oil in oil drums. CAUTION Waste and clean-up: Should be absorbed by an absorber. Treat it as hazardous to the environment. After a pressure relay trip, follow the instructions in the chapter “Trip or alarm from supervisory devices” in the user's manual. In the event of fire: Any fires should be extinguished with powder, foam or carbonic acid extinguishing agents. WARNING When oil that has been used in a diverter switch housing is pumped out, grounded conducting tubes and hoses should be used to avoid the risk of explosion due to the gases produced by arcs during service. WARNING The oil in the selector switch compartment may be hot. Be cautious! WARNING There is always a cushion of explosive gases in the top of the diverter switch housing. No open fire, hot surfaces or sparks may be present during opening of the housing or draining from the valve. After the cover is removed let the gas vent away approximately 15 min before any work is started. After oil filling CAUTION Do not energize the transformer earlier than three hours after oil filling at atmospheric pressure. This waiting period is needed to allow air bubbles to dissipate. WARNING Mounting of gaskets Be aware of the risk for slipping caused by oil spillage, for instance when working on the transformer cover. CAUTION Take care to avoid ingestion of moist air when oil is drained. If the ambient air is moist, let incoming air pass through a dehydrating breather with slow air flow to obtain proper dehydration. CAUTION Do not fill the diverter switch housing with oil if the transformer tank is under vacuum and the on-load tap-changer is not. CAUTION Do not fill the transformer tank with oil if the on-load tap-changer is under vacuum and the transformer tank is not. CAUTION Leave a gas cushion on top of the oil in the diverter switch housing. CAUTION Sealing surfaces and gaskets must be clean and undamaged. Diametrically opposed bolts in sealing joints must be tightened alternately several times, beginning with a low tightening torque and finally with the recommended tightening torque as described in section 1.3 Tightening torque, in this guide. Content 1. Introduction...........................................................................................................................9 1.1 General..........................................................................................................................9 1.2 Maintenance schedule...................................................................................................10 1.2.1 Inspection................................................................................................................10 1.2.2 Overhaul..................................................................................................................10 1.2.3 Contact replacement...............................................................................................12 1.3 Tightening torque...........................................................................................................12 2. Inspection..............................................................................................................................13 3. Overhaul................................................................................................................................14 3.1 Required tools and materials..........................................................................................14 3.2 Procedure......................................................................................................................14 3.3 Preparations..................................................................................................................14 3.3.1 On-load tap-changer position..................................................................................14 3.3.2 Disconnection and earthing of the transformer.........................................................15 3.3.3 Oil volumes and lifting heights..................................................................................15 3.3.4 Recommended set of spare parts...........................................................................15 3.4 Oil testing and oil draining..............................................................................................15 3.5 Lifting and cleaning the diverter switch................................................................................16 3.6 Cleaning........................................................................................................................17 3.6.1 Cleaning the diverter switch housing........................................................................17 3.6.2 Cleaning the oil filter in the conservator pipe (if any).................................................17 3.7 Oil filtration.....................................................................................................................17 3.8 Checking of the breathing device...................................................................................17 3.9 Checking the contact positions......................................................................................18 3.10 Checking the contact wear..........................................................................................20 3.11 Checking the transition resistors..................................................................................20 3.12 Checking before closing...............................................................................................20 3.13 Installation of the diverter switch..................................................................................20 3.14 Checking and replacing supervisory equipment...........................................................21 3.15 Lubrication of the on-load tap-changer and the drive shaft system....................................22 3.16 Checking of the motor-drive mechanism......................................................................22 3.17 Oil filling.......................................................................................................................22 3.17.1 Filling methods and restrictions..............................................................................22 3.17.2 Before filling...........................................................................................................22 3.17.3 Filling at atmospheric pressure..............................................................................22 3.17.4 Oil level..................................................................................................................22 3.17.5 Restoring the gas cushion.....................................................................................23 3.17.6 Waiting period.......................................................................................................24 3.18 Check of contact timing...............................................................................................24 3.19 Putting into operation...................................................................................................24 4. Contact replacement.............................................................................................................27 4.1 Dismantling the boards..................................................................................................29 4.2 Dismantling the moving main contacts...........................................................................29 4.3 Dismantling the moving transition contacts....................................................................31 4.4 Mounting the moving transition contacts........................................................................32 4.5 Mounting the moving main contacts..............................................................................33 4.6 Replacing the fixed main contacts..................................................................................34 4.7 Replacing the fixed transition contacts...........................................................................34 4.8 Mounting the boards with transition resistors and fixed contacts....................................34 5. Specification of materials.......................................................................................................35 5.1 General..........................................................................................................................35 5.2 Diverter switch housing..................................................................................................35 5.3 Diverter switch...............................................................................................................35 5.4 Tap selectors.................................................................................................................35 5.5 Conductors....................................................................................................................35 5.6 Gearing mechanism.......................................................................................................35 5.7 Drive shaft systems........................................................................................................35 1. Introduction 1.1 General The UC range of on-load tap-changers manufactured by ABB has been developed over many years to provide maximum reliability. The simple and rugged design gives a service life equal to the service life of the transformer. Minimum maintenance is required for trouble-free operation. The only parts requiring maintenance are contacts that might need replacement during the service life, the insulating oil and the motor-drive mechanism. The design allows excellent access to all parts, making inspection and maintenance quick and simple. The on-load tap-changer, type UCG, is housed in the transformer tank. The motor-drive mechanism is attached to the transformer tank and connected to the on-load tapchanger by means of drive-shafts and a bevel gear, see Fig. 1. Bevel gear Horizontal drive-shaft and protection tube Pressure relay Bevel gear Shielding-rings (when impulse withstand voltage to earth exceeds 380 kV) Vertical drive-shaft and protection tube Insulating shaft Diverter switch housing containing the diverter switch Hood and screws Conductors Hand crank Motor-drive mechanism On-load tap-changer Shielding-ring (when impulse withstand voltage to earth exceeds 380 kV). (Not on tap selector size C) Fig. 1. On-load tap-changer and motor-drive mechanism. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 9 Fig. 2 shows the general arrangement of an on-load tapchanger type UC. The main components are the springoperated diverter switch and the tap selector with sliding contacts. For maintenance the diverter switch is lifted. The contacts are then immediately accessible and can be inspected for wear. The drive-shafts should not be dismantled when lifting the diverter switch. Maintenance is normally not required on the parts operating in the oil of thetransformer tank. However, when the on-load tap-changer has made one million operations a check of the tap selector is recommended. The diverter switch has its own housing separate from the transformer oil. This is to prevent contamination of the transformer oil since the diverter switch oil deteriorates due to the switching operations. The oil needs to be checked and filtered at regular intervals to maintain adequate dielectric strength as well as to prevent mechanical wear. It is necessary to inspect the contacts and clean the insulation parts of the diverter switch as well as to clean the housing inside at regular intervals. The main components of the diverter switch are: – – Fixed main contacts – – Moving main contacts – – Fixed transition contacts – – Moving transition contacts – – Transition resistors – – Spring-driven polygon link system Besides the maintenance of the diverter switch and cleaning of the oil, the motor-drive mechanism should be checked and lubricated. The pressure relay, the device that protects the transformer from damages due to excessive pressure in the diverter switch housing, should also be checked. One on-load tap-changer of UCG type may consist of one, two or three units driven by a common motor-drive mechanism. The instructions in this guide deals with one unit. If there are two or three units, all work decribed should be carried on all units unless otherwise is stated. If more than one diverter switch is lifted out at the same time, make sure the right diverter switch is lowered into the right housing (compare with the serial numbers, see Fig. 2). 10 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 1.2 Maintenance schedule Maintenance of the on-load tap-changer consists of three major steps: –– Inspection –– Overhaul –– Contact replacement 1.2.1 Inspection It is recommended to perform an inspection once a year. This principally concerns the motor-drive mechanism and refers to a visual inspection inside the motor-drive cabinet to check that nothing is loose and the heater is functioning. In the motor-drive mechanism a counter registers every tapchanger operation. During inspection the counter is read. If possible, motor and counter are tested by operating one step and then back. If the on-load tap-changer has its own oil conservator, the breather and the oil level indicator are checked according to the instructions from the transformer manufacturer. The inspection is carried out while the transformer is in service. If the on-load tap-changer is equipped with an oil filter unit from ABB, it should be inspected once a year according to the oil filter unit manual. 1.2.2 Overhaul The contact life and the frequency of operations or the time in service determine the time interval between overhauls. The number of operations run by the on-load tap-changer is recorded by a counter, housed in the motor-drive mechanism cabinet. The registered number of operations should be noted at every inspection and overhaul. The on-load tap-changer should normally be overhauled regularly at intervals of 1/5 of the estimated contact life. The relevant information is stated on the rating plate. Hereby, the contact wear can be followed and necessary preparations can be made for replacing the contacts. If the tap-change operations occur infrequently and a very long time elapses until the number of operations amounts to 1/5 of the contact life, the interval between overhauls should be limited to the time stated on the rating plate (normally 7 years). Cover Diverter switch housing Oil valve Pressure relay Bevel gear Position indicator Top-section Serial No. Shielding-ring 1) Earthing terminal Draining tube Connection flange for gas operated relay Insulating cylinder Insulating shaft Shielding-ring Diverter switch 1) Shielding-ring 2) Plug-in contacts Transition resistors Fixed and moving contacts Bottom section Serial No. Guide-pins Current terminal Tap selector Driving disc for the diverter switch Bottom valve for drying process Intermediate gear 1) Only at impulse withstand voltage to earth of 650 kV and 1050 kV. 2) Not on UCG of the short type. Geneva gear Change-over selector Moving fineselector contacts Current collector Fixed fine-selector contacts Fig. 2. General arrangement of on-load tap-changer, type UC. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 11 1.2.3 Contact replacement On the rating plate of the on-load tap-changer the estimated contact life of the breaking contacts in the diverter switch at rated load is stated. The contacts will withstand a very large number of switching operations. For normal power transformers the number of operations of the diverter switch is approximately 20 per day, which means that replacement of the contacts is not normally necessary during the life of the transformer. (In case of onload tap-changers on furnace transformers, the frequency of operations may be considerably higher). CAUTION The number of operations must in no case exceed 500 000, due to weakening spring tension of the contacts. 1.3 Tightening torque The following tightening torques are recommended: For metallic screw joints: M6........... 10 Nm M8........... 24.5 Nm M10.......... 49 Nm M12.......... 84 Nm ±10 ±10 ±10 ±10 For non-metallic screw joints: M10.......... 9 Nm M12.......... 13 Nm M16.......... 22 Nm ±10 % ±10 % ±10 % if not otherwise stated in this guide. 12 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 % % % % 2. Inspection The inspection mainly consists of a visual check of the motordrive mechanism and the conservator once a year while the transformer is in service. In the motor-drive mechanism the following points are to be checked: – – Motor and counter –– Heater – – The counter’s value – – Visual check of the toothed belt See the maintenance guide for motor-drive mechanisms (1ZSC000498-ABH) for information about the procedure. On the conservator the following are to be checked: – – Oil level – – Breather WARNING The breathers and the tube from the conservator contains explosive gases. No open fire, hot surfaces or sparks may be present when loosening the breather. CAUTION Approval should be given for inspection as well as for operating the on-load tap-changer. 1. Check the breathers according to the instructions for the transformer. 2. Check the oil level in the conservator for the on-load tap-changer. The oil level should be according to the transformer documentation. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 13 3. Overhaul WARNING Before any work is carried out on the on-load tap-changer: Make sure that the transformer is disconnected and that earthing is properly carried out. Obtain a signed certificate from the engineer in charge. 3.1 Required tools and materials Necessary for the overhaul is the following equipment: –– Standard hand tools (keywidth up to 19 mm) –– Standard set of combination spanners –– Pipe wrench –– Thickness gauges (0.40; 0.50; 1.20 mm) –– Small hammer –– Sliding caliper –– Spring balance (10 N) –– Watch (with hand for seconds) –– Oil can –– Ohmmeter (1-30 Ohm) –– Air pump with pressure gauge (0-200 kPa) and connection to R 1/8” male thread –– Telpher (at least 150 kg lifting force) –– Empty and clean barrels for transformer oil (calculate with max. 225 l for each diverter switch housing) –– Oil draining and filtering equipment with connections –– Test equipment according to IEC 00156, 1995-08 –– Two buckets (approximately 10 l) –– Rags (lint-free) –– 50 l of new transformer oil (class II according to IEC 00296, 2012-02) –– Standard lithium complex or calcium complex grease with EP additive NLGI 2. Temperature range from -30°C to +100°C. Suggested products: Dow Corning Molykote Multilub, Gulf Crown EP 2 or similar. –– Oil (for plain ball and roller bearings) –– Degreasing agent –– Protective glooves, oil proof –– Dimension drawing for the on-load tap-changer –– Pen and note pad –– Set of spare contacts (see the spare parts list) –– Brass shims according to Fig. 7 (12 pcs) –– New O-ring for the cover (435x8) When restoring the gas cushion. (section 3.17.5): –– Small oil pump with connection to the oil valve –– Empty and clean barrel for transformer oil ( ~ 15 l) –– Box wrench, 6 mm 14 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 When measuring contact timing, add this equipment: –– See section 3.18 When replacing contacts (chapter 4), add this equipment: –– Universal pliers –– Pipe wrench –– 4 mm mandrel –– 5 mm brass mandrel, 320 mm long –– Steel ruler –– Round file –– Torque wrench (10 Nm) –– Piece of wood, 50 mm thick, 400 mm long 3.2 Procedure The overhaul procedure includes the following points: –– Oil testing and oil draining –– Lifting and cleaning the diverter switch –– Cleaning the diverter switch housing and the oil filter (if any) –– Oil filtration –– Checking the breathers –– Checking the contact positions –– Checking the contact wear –– Checking the transition resistors –– Checking before lowering the diverter switch –– Lowering the diverter switch –– Checking the pressure relay –– Lubrication –– Checking the motor-drive mechanism (see the maintenance guide for motor-drive mechanisms) –– Oil filling –– Check of contact timing –– Putting into operation 3.3 Preparations If the on-load tap-changer is oil filled under atmospheric pressure, a waiting period of three hours is needed before energizing. To save out of service time of the transformer, carry out all work on the on-load tap-changer and the oil filling before the maintenance of the motor-drive mechanism is started. 3.3.1 On-load tap-changer position Note the position of the on-load tap-changer to enable restart of the transformer in the right tap position. 3.3.2 Disconnection and earthing of the transformer WARNING Before starting any work in the on-load tap-changer the protective motor switch and the LOCAL/REMOTE switch must be set at 0. WARNING Before any work is carried out on the on-load tap-changer: make sure that the transformer is disconnected and that earthing is properly carried out. Obtain a signed certificate from the engineer in charge. 3.3.3 Oil volumes and lifting heights The necessary number of empty drums for collecting and filtering of the oil in the diverter switch housing should be kept ready. The drums must be carefully cleaned and free from water. New oil needed should be of class II according to IEC 60296, 2012-02. 3.4 Oil testing and oil draining The diverter switch housing is equipped with an oil valve placed on the top section. For connection dimensions, see the dimension drawing for the on-load tap-changer. WARNING The oil in the diverter switch housing may be hot. Be cautious! Take an oil-sample from the oil valve and carry out the dielectric strength test according to IEC 60156, 1995-08 (between spherical calottes, distance 2.5 mm). This test is carried out for deciding whether the oil can be filtered or must be exchanged. The dielectric strength of the oil should not be allowed to be less than 120 kV/cm for an on-load tap-changer in service. When taking the oil-sample, first drain some oil into a bucket to clean the valve. Quantity of oil in the diverter switch housing and lifting height for the diverter switch UCG.. 380/... Approx. 170 litres (lifting height 1.4 m) UCG.. 650/... Approx. 170 litres (lifting height 1.4 m) UCG.. 1050/... Approx. 205 litres (lifting height 1.7 m) If the oil conservator of the on-load tap-changer is common with the oil conservator of the transformer tank, close the valve in the pipe connection to the oil conservator and open the oil valve. After a while, open the air release valve. See Fig. 10. The volume of the oil conservator is not included. CAUTION Alternatively, the oil may be replaced by new oil and the used oil filtered at some later occasion. A certain quantity of new oil, at least 50 litres, should be kept ready to replace waste oil and for cleaning. CAUTION Do not energize the transformer until oil has been filled as per section 3.17 ”Oil filling” in this guide. 3.3.4 Recommended set of spare parts It is recommended to have a set of contacts for the diverter switch available during the overhaul, see the spare parts list for ordering. Never block the hole in the draining tube! If the on-load tap-changer is equipped with an oil filter unit for continuous oil filtration from ABB and it is maintained and operated according to our instructions, oil draining and filtering is not needed, provided that the dielectric strength is at least 160 kV/cm (IEC 60156, 1995-08). There is a hole in the upper part of the draining tube to prevent air from being trapped inside the tube when oil filling. The air sucked in through this hole when draining might disturb the function of some types of pumps. In such case, drain the oil using a hose instead. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 15 Use the filtering equipment or the pump to drain oil from the on-load tap-changer into carefully cleaned oil drums. Connect the pump to the oil valve and drain the oil from the diverter switch housing and the conservator. Draining can be effected quickly if filtering equipment is used and at the same time the whole oil quantity will be filtered once. Remove the cover of the diverter switch housing while draining. 3.5 Lifting and cleaning the diverter switch The weight of the diverter switch is approximately 90 kg. Lift the diverter switch partly so you can flush it with oil. After careful flushing, lift the diverter switch from the housing and wipe it with rags. Lift according to Fig. 4. WARNING WARNING There is always a cushion of explosive gases in the top of the diverter switch housing. No open fire, hot surfaces or sparks may be present during opening of the housing or draining from the valve. After the cover is removed let the gas vent away approximately 15 minutes before any work is started. Make sure the lifting equipment is properly fixed to the cover flange before the diverter switch is lifted. CAUTION WARNING When lifting the diverter switch, use a manually operated telpher to avoid damages on the diverter switch. Make sure that the end of the tie-rod or its coupling is kept clear of the inner edge of the flange. When oil that has been used in a diverter switch housing is pumped out, conducting tubes and hoses that are earthed should be used to avoid the risk of explosion due to the gases produced by the arcs during service. If the on-load tap-changer is equipped with an oil filter unit for continuous oil filtration from ABB and it is maintained and operated according to our instructions, the flushing and wiping of the diverter switch is not necessary. Drain the remaining oil in the bottom of the housing by using a hose. Manually operated telpher Buffer springs Lifting eye Lifting eye Lifting device Shielding ring (only for impulse withstand voltages to earth exceeding 380 kV). Tie-rod Coupling with drivingpin Fig. 3. Diverter switch, general arrangement. 16 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 Plug-in contacts Guiding pins Fig. 4. Lifting arrangement. 3.6 Cleaning 3.6.1 Cleaning the diverter switch housing Clean the inner walls of the housing by means of a nylon brush, then flush with oil. Drain the oil. Wipe the bottom and inner walls with rags. WARNING In no case should any person go down into the diverter switch housing. The cleaning of the diverter switch housing should be carried out by using brushes and rags and by flushing with oil. If the on-load tap-changer is equipped with an oil filter unit for continuous oil filtration from ABB and it is maintained and operated according to our instructions, the cleaning of the diverter switch is not necessary. Drain the housing completely by using a hose before oil filling is carried out. 3.6.2 Cleaning the oil filter in the conservator pipe (if any) The diverter switch housing and the oil conservator are connected by a pipe. The diverter switch oil is contaminated due to the arcing that occurs when the contacts operate. In case of a common conservator with the transformer the impure oil in the diverter switch housing must be prevented from entering the oil conservator. An oil filter is therefore mounted in the pipe. 3.7 Oil filtration The drained oil should be filtered until it is cleaned and has regained the high dielectric strength required. The breakdown value for purified oil should be at least 160 kV/cm according to IEC 60156,1995-08. To check the result of the filtering, take test sample after the oil has been filled into the on-load tap-changer. If the on-load tap-changer is equipped with an oil filter unit for continuous oil filtration from ABB and it is maintained and operated according to our instructions, no further oil filtration is necessary. Only take an sample and measure the dielectric strength of the oil, see section ”Oil testing and oil draining” in this guide. 3.8 Checking of the breathing device Check the breathing device according to the instructions from the transformer manufacturer. WARNING The breathers and the tube from the conservator contains explosive gases. No open fire, hot surfaces or sparks may be present when loosening the breather. The filter, which is mounted in a flange pipe on the top of the diverter switch housing, is screwed from the inside. It can easily be screwed out for inspection and cleaning. The oil filter does not need to be replaced nor cleaned in any other way than by washing with oil. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 17 3.9 Checking the contact positions Those parts of the fixed contacts and the moving contacts which are exposed to arcing during an operation are tipped by copper-tungsten. In a tap position, the moving main switching contacts and the fixed main switching contacts should have a clearance of min. 0.5 mm as shown in Fig. 5. For checking the clearance on both sides of the diverter switch it has to be operated. Operate it by turning the coupling with a pipe wrench. Note the position of the diverter switch before operation. WARNING Take care to avoid finger injuries when operating the diverter switch. Oil splash occurs during operation, especially in the moving direction. If the clearance is too small you may adjust the clearance by installing a shim of brass between the board and the current bar. The shims are included in the spare parts set. The shim dimensions are also shown in Fig. 5. Operate the diverter switch to the opposite side when mounting the shims. 18 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 Operate the diverter switch back to the first side and check the clearance again. If still too small, put in a shim more and test again. CAUTION Never mount more than three shims on each other. Make sure all washers and screws are put back and tighten. Proceed with the other side of the diverter switch. When finished, operate the diverter switch back to the position it had before the first operation. Fig. 5 shows the current carriers through the fixed main contact and the copper part of the moving contact. Fig. 6 shows the copper-tungsten tips of the transition contact touching each other in a tap position. Make sure that all flexible connections, operating springs, contact springs and all plug-in contacts are in good condition. Make sure that no bolts have worked loose. 0.5–2 mm Fixed main switching contact Moving main switching contact 20 14 Copper part Ø6.4 26 14 Thickness 1 mm Current bar Fixed main contact Moving main contact Board Fig. 5. Fixed and moving contacts clearance. Fig. 6. Transition contacts. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 19 3.10 Checking the contact wear The contact system consists of fixed and moving contacts. Check the degree of contact burning on the breaking contacts. For a new contact with tips of copper-tungsten (Fig. 7), the thickness at (A) and (B) is 5.5 mm in the upper end of the contact. In the lower end, the thickness is 3 mm. Estimate the degree of contact burning and record this to enable comparison with the condition at the next overhaul. Do not file or smooth the burned and pitted contact surfaces. A contact with a tip of copper-tungsten should be replaced when the thickness at (A) and (B) in the upper end of the contact is approximately 0.5 mm. (The thickness in the upper and the lower end of the tip will be approximately the same when close to the limit for replacement). 3.11 Checking the transition resistors Measurement is carried out on the side with open contacts. Connect one cable from the ohmmeter to a fixed main contact and the other cable to a fixed transition contact. Measure the resistance. Measure the resistance of each resistor branch across the open switch. Operate the diverter switch to the other side as described in section 3.9 and measure the resistance with open contacts. Check that the resistors are undamaged and compare with the value on the rating plate. The values must not differ by more than 10 %. Check that nothing has worked loose. Operate the diverter switch back to its previous position. Also replace contacts which are assumed to wear out before the next overhaul. 3.12 Checking before closing Before installing the diverter switch, make sure that no foreign objects, tools, wires, rags etc. are left in the diverter switch housing. The dimensions above are valid for both main contacts and transition contacts. For contact replacement, see chapter 4 ”Contact replacement”. 3.13 Installation of the diverter switch CAUTION A B Check the serial numbers to make sure that the diverter switch is mounted in the correct housing, see Fig. 2. CAUTION Make sure that the diverter switch housing is clean and dry and that no foreign objects (tools etc.) are left in the housing. CAUTION Lower the diverter switch into its housing carefully so that neither the diverter switch nor the housing are damaged. The UCG diverter switch is provided with a guiding slot that fits against the oil draining tube in the diverter switch housing, see Figs. 8 and 9. Rotate the diverter switch so the half-circle shaped guiding slot is aligned with the oil draining tube. Fig. 7. Tolerance limits for contact erosion. 20 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 When the diverter switch is lowered, check visually that its plug-in contacts are aligned with the contacts in the cylinder wall. In order to ensure that the diverter switch pin has engaged the coupling disc, carry out at least three tap change operations in one direction. A distinct sound is heard when the diverter switch operates which indicates that the driving pin of the diverter switch has been connected. If no sound is heard, the diverter switch might need to be pushed down while operating the motor-drive. 3.14 Checking and replacing supervisory equipment Accessories and safety devices that are not standard, but might be mounted at delivery, are described in instruction 1ZSC000562-AAD. Springs Lifting device Lifting eye Carry out another three operations in the same direction while pushing the diverter switch down. Shielding-ring (when the impulse withstand voltage to earth exceeds 380 kV) (not on UCG short version) The top part of the diverter switch lifting device should be below the level of the machined surface for the cover when lowered to its final position. Only the springs of the lifting device should be above this level. If a check of contact timing should be carried out, proceed with that according to section 3.19 before mounting the cover. Serial number (on the opposite side of the diverter switch) A A Plug-in contacts Guiding pin Insert a new O-ring for the cover in the upper flange. Mount the on-load tap-changer cover. Turn the cover so the guiding pin in the housing is facing the guiding hole in the cover. (The cover has to be pressed down in order to overcome the spring force of the springs which hold the diverter switch pressed in place.) Insert screws and washers and tighten them. Coupling disc Guiding pin Tie rod Driving pin Fig. 8. Diverter switch. Notch for the guiding pin Oil draining tube Holes for guiding pins Guiding pins Slot for the oil draining tube Slot for guiding bar A–A Fig. 9. UCG diverter switch housing, view from above. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 21 3.15 Lubrication of the on-load tap-changer and the drive shaft system The bevel gears are greased at delivery and the same type of grease is used for the couplings of the outer shaft system. For access to the couplings, loosen the hose-clips and push the protective tubes together. For access to the bevel gears, dismount the covers. WARNING The bevel gear contains moving gears. Be cautious! The connection to the oil conservator is designed to automatically give a gas cushion when filling at atmospheric pressure. If new oil, especially degassed oil, is filled into the diverter switch housing and the number of operations is low, the gas cushion may be dissolved in the oil. The oil level in the oil conservator should then be checked after a month in service and if the oil level is lower than after the oil filling, (corrected for temperature differencies), the gas cushion should be restored according to section 3.17.5 ”Restoring the gas cushion” in this guide. WARNING 3.17.2 Before filling Rotating shafts. Be cautious! Check and lubricate with grease if necessary. Use standard lithium complex or calcium complex grease with EP additive NLGI 2. Temperature range from -30°C to +100°C. Suggested products: Dow Corning Molykote Multilub, Gulf Crown EP 2 or similar. Remount the covers (make sure the gaskets are properly in place). 3.16 Checking of the motor-drive mechanism See the maintenance guide for the motor-drive mechanism. 3.17 Oil filling If check of contact timing is to be carried out, see section 3.18, fill the diverter switch housing with oil up to the level of the fixed main breaking contacts by easiest possible method before checking. Oil fill completely according to the instructions below after check of contact timing. 3.17.1 Filling methods and restrictions Oil filling can be carried out at atmospheric pressure or under vacuum. The wall between the diverter switch housing and the transformer tank is designed to withstand vacuum on one side and atmospheric pressure on the other side. It is not allowed to have vacuum on one side and the pressure of an oil column on the other side. After maintenance oil is normally filled at atmospheric pressure. This procedure is described in section 3.17.3. If filling is to be carried out under vacuum, see the Installation and commissioning guide. After oil filling, a gas cushion should remain on the top of the oil in the diverter switch housing. 22 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 Oil filling may be carried out in different ways depending on what is convenient as long as the rules above are fulfilled and the on-load tap-changer is filled with oil to the correct level with a gas cushion on the top. The method below is recommended and if it is followed in detail no pressure limits are exceeded and oil levels and gas cushion will be correct. If the on-load tap-changer consists of more than one unit, fill one at a time. 3.17.3 Filling at atmospheric pressure See Fig. 10. 1. Close the air release valve 2. Open the conservator valve, if any. 3. Dismantle the breathing device on the conservator for the on-load tap-changer. 4. Pump oil into the diverter switch housing via the oil valve (connection dimensions, see the dimension drawing for the on-load tap-changer). Continue until the conservator is filled to the correct level at the actual temperature. See section 3.17.4. If there is more than one unit connected to the same conservator, fill all of them until the oil level indicator starts to move and fill up to the right level when filling the last unit. 5. Shut the oil valve and disconnect the pump. 6. Remount the breathing device. Make sure the connection to the breathing device is properly sealed. 3.17.4 Oil level For correct oil level in the oil conservator, see the transformer documentation. 3.17.5 Restoring the gas cushion Check the oil level in the oil conservator one month after oil filling. If the oil level is lower now than when the oil filling was finished (correct for temperature differencies!) and no leakages are observed, the gas cushion has been solved in the oil and has to be restored. The procedure below is used for on-load tap-changers without oil filter unit for continuous oil filtration. In case the on-load tap-changer is equipped with an oil filter unit for continuous oil filtration from ABB, and it is installed according to our recommendations, follow the instructions in the oil filter unit manual. In case the on-load tap-changer consists of more than one unit, do the restoring in one unit at a time. WARNING The oil in the diverter switch housing may be hot. Be cautious! Procedure 1. Close the valve in the tube to the conservator. 2. Connect the oil pump to the oil valve. (For connection dimensions, see the dimension drawing for the on-load tap-changer), see Fig. 10. 3. Open the oil valve and the air release valve. 4. Start the oil pump and drain approximately 15 litres of oil into a clean and dry container. 5. Close the air release valve. 6. Close the oil valve and disconnect the pump. 7. Connect the output side of the pump to the oil valve. 8. Open the oil valve. 9. Open the valve in the tube to the conservator! 10. Pump the earlier drained 15 litres of oil back into the diverter switch housing. 11. Close the oil valve and disconnect the pump. 12. The level in the oil conservator and the gas cushion are now restored. If the on-load tap-changer consists of more than one unit, proceed with the other one until the last one has been restored. WARNING CAUTION Before any work is carried out on the on-load tap-changer: Make sure that the transformer is disconnected and that earthing is properly carried out. Obtain a signed certificate from the engineer in charge. Avoid to do the restoring in damp weather since moisture will get into the diverter switch housing. If the restoring has to be done in such weather, the incoming air has to be dehydrated and the drained oil protected from water. CAUTION To operate the on-load tap-changer with a too small or no gas cushion means a risk for a trip of the pressure relay. Open end wrench key width 6 mm Oil valve Open Air release valve Oil valve Fig. 10. Air release valve (position may be on another vertical flange). 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 23 3.17.6 Waiting period The test is to be made on all three-phases and is to be carried out as follows: CAUTION Do not energize the transformer earlier than three hours after oil filling in atmospheric pressure. This waiting period is needed to allow airbubbles to disappear. 3.18 Check of contact timing Checking the contact timing is a good check of the condition of the on-load tap-changer, but it is not necessary to check contact timing at every overhaul. It is recommended to be carried out after every 500 000 operations. The test requires: –– Two indicator lamps (glow discharge lamps for the minimum possible magnetisation of the transformer) –– Necessary leads –– Two stiff insulated leads or bars Find the exact position of the on-load tap-changer by adjusting the disc brake as shown in the maintenance guide for motor-drive mechanisms. 1. Note the number of whole turns and parts of turns on the hand crank, during a slow manual operation. 2. Note when each tap-selector arm breaks and makes (the corresponding lamp goes out or lights). 3. Note when the diverter switch flicks over (a distinct sound is heard). After this, compare the operations with the contact-timing diagram applicable to the on-load tap-changer in Figs. 13 and 14. One operation corresponds to 25 turns of the hand crank on the motor-drive mechanism, type BUE and 15 turns for BUL. WARNING Remove the equipment for contact-time measuring. Never force DC current through the transformer windings. Mount the cover of the diverter switch housing according to section 3.13. The insulated leads (or bars) are used for connection to the moving contact arms of the tap selector via the plugin contacts of the diverter switch (They can be made of an insulating tube with a lead inside.) Connect the lamps as shown in Fig. 11. The diverter switch contacts are designated as shown in Fig. 12. Determine if x or v contacts are closed. In the contact-timing diagram for the on-load tap-changer you can find out the corresponding position. See Figs. 13 and 14. The diverter switch housing shall be filled with transformer oil up to the fixed main contacts to secure the correct function of the dash pots during operation of the diverter switch, see section 3.17. At repeated operations in the same direction the selector arms V and H operate every second time. When the direction of operation is reversed, the contact arms will be at rest during the first operation. The operation is then performed by means of the diverter switch only. When testing, the operation must be carried out in the same direction as the previous operation. 24 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 Complete the oil filling according to section 3.17. CAUTION If the result is beyond the limits given here, please contact ABB. For BUE, the diverter switch must have switched over before the 20th turn is finished with the hand crank. For BUL, the diverter switch must have switched over before the 12th turn is finished with the hand crank. 3.19 Putting into operation Operate the on-load tap-changer to the position noted in section 3.3.1. Put the LOCAL/REMOTE switch to REMOTE. Reset the drag hands. Make sure that no tools or foreign objects are left in the motor-drive mechanism cabinet. Close the door. Make sure that nothing is left on the transformer cover. Sign the revision protocol and give it to the engineer in charge and inform that the on-load tap-changer is ready for energizing. y u Fig. 11. Indicator lamp connection during contact timing test. x-contacts v-contacts Fig. 12. The diverter switch outlet marking. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 25 Position Min. 3 turns Position –—— Contact closed Min. 3 turns Position Turns of the hand crank of the mechanism Fig. 13. Example of contact-timing diagram, BUE. Position Min. 2 turns Position Min. 2 turns V H x u y V –—— Contact Fig. 14. Example of contact timing diagram, BUL. 26 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 Turns of the hand crank of the mechanism Position 4. Contact replacement CAUTION ABB recommends that only authorized personnel from ABB carry out contact replacement. Replace worn-out main switching contacts and transition contacts as required. (It is not necessary to replace both main switching contacts and transition contacts if, for instance, only the main switching contacts are worn out). CAUTION Fixed contacts and its corresponding moving contacts should always be replaced at the same time. Also replace contacts which are assumed to wear out before the next overhaul. Replacement of contacts is described in the following sections. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 27 Fixed main switching contact Conical springwasher Plain washer Fixed transition contact Locking washer (mounted vertically on some types) Plain washer Conical spring washer Moving transition contact Guide pin Conical spring washer Nut Plain washer Connection for transition resistor Fixed transition contact Moving main switching contact Fig. 15. Diverter switch, contact design. 28 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 4.1 Dismantling the boards Dismantle the boards from the frame by removing the six screws and the locking washers from each board (Fig. 16). Punch the guide pins with a 4 mm mandrel. Note that the guide pins are placed high on one board and low on the other board in order to make the boards non-reversible. When mounting, use new locking washers and guide pins. Lift away the boards in the lifting eye, see Fig. 7 with fixed contacts and transition resistors from the contact-mechanism (Fig. 17). The boards, which are made of insulating material, shall be wiped with rags. 4.2 Dismantling the moving main contacts Dismantle the moving main contacts according to Figs. 18 and 19. Take away split pins, washers and springs in both ends of shafts 1–3. There is one shaft for each pair of contacts. Notice that the outer end of the outer phase have washers with a larger diameter, see Fig. 18. Do the same for the contacts on the opposite side. Pull out shaft 1. Take care of the silver washers. Do the same with shaft 3. Punch out the middle shaft 2 by means of a 5 mm mandrel of brass. Shaft 2 must then be passed through the holes for shafts 1 or 3 and remain there until new contacts are mounted. Repeat the procedure for the contacts on the opposite side. Board Guide pin Locking washer Fig. 16. Contact replacement, dismantling the boards. Screw Fig. 17. Contact replacement, boards lifted away. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 29 Contact Washer with larger diameter Shaft 1 Shaft 2 Fig. 18. Contact replacement, taking away split pins. Contact Shaft 1 Fig. 19. Contact replacement, pulling out shaft. 30 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 Shaft 3 4.3 Dismantling the moving transition contacts Dismantling of the moving transition contacts should be carried out according to Figs. 20 and 21. The transition contacts are held by a common shaft 4 going through all the contacts. The shaft 4 is locked with two split pins (Fig. 21). Remove the split pins and punch out the shaft with a 5 mm mandrel of brass and take care of the springs, washers and contacts when the mandrel is pulled out. Shaft 4 The springs in view A – A, are loosened in the following way: Punch out the locking pin in one end of the pin with a 2 mm mandrel. Thereafter the spring holder can be loosened and the contacts with springs can be removed. Take care of the pin. Repeat the above procedure on the other side of the diverter switch. Fig. 20. Contact replacement, moving transition contacts. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 31 4.4 Mounting the moving transition contacts Mount the moving transition contacts according to Fig. 21. A replacement contact consists of a contact with mounted spring. Punch the shaft through the first bearing hole and put a contact, spring, insulating washer and another contact on the shaft as it is continuously punched in. Then proceed with the next phase. Finally lock it with new split pins. Mount the springs by means of the pin and new locking pins. Proceed with the other side of the diverter switch. Put a ruler on the linings of the tran-sition contacts. No lining should lie more than 1 mm from the ruler. If any lining does, adjust these contacts closer to the board by filing off material on the surface of the contact that lies against the stop shaft. When all transition contacts on both sides are mounted, make sure that the contacts move easily in the bearings and that the springs are functioning. Split pins A A Shaft Spring Washer (insulating) Pin Contact Spring Locking pin View A - A Fig. 21. Transition contact construction. 32 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 4.5 Mounting the moving main contacts Fig. 22 shows how to mount the moving main contacts, and how to place washers and springs. The contacts are equipped with copper-tungsten tips. Proceed with the outer phases. Put the outermost silver washer and contact on the shaft and punch the shaft into the bearing hole. Put the next silver washer and contact into position and punch in the shaft. Mount washers, springs and split pins. Check that all containing details are correctly assembled. CAUTION The outer end of the outmost phases should have the washers with larger diameter, (Ø=25 mm) see Fig. 22. View A – A shows the replacement contact which consist of two contacts with a mounted spring, mounted on the current bridge. Begin with the middle phase. Put the contact and the silver washers on the shaft and punch the shaft in to the bearing hole with the 5 mm mandrel. Put the next silver washer and contact in position and punch in the shaft. Mount washers, springs and split pins. Put a ruler on the linings of the moving main contacts. No lining should lie more than 1 mm from the ruler. If any lining does, adjust these contacts closer to the board by filing off material on the surface of the contact that lies against the stop shaft. Carry out the same procedure on the other side of the diverter switch. A Washer with larger diameter Contact Contact Silver washers Spring A View A - A Split pin Insulating washer Spring Steel washer Fig. 22. Moving main contacts with tips of copper-tungsten, washers and springs. 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 33 4.6 Replacing the fixed main contacts Unscrew the fixed main contacts, see Fig. 15. Mount new contacts. Use new conical spring washers and locking nuts. Put the washers as shown in the figure. Press the contacts against their bracket when tightening the screws. Tightening torque approximately 10 Nm, (not critical). Check that the linings of the fixed main contacts are aligned with the linings of the moving main contacts. If not, loosen the nuts slightly and adjust the fixed main contacts. Tighten the nuts. Check (and adjust, if necessary) the alignment of the transition contacts as described for the main contacts. Tighten the screws and lock the locking washers. Proceed with the other side of the diverter switch by first operating it to the other side as described in section 3.9. The conical end of the nut should be turned upwards. 4.7 Replacing the fixed transition contacts Unscrew the screw and nut holding the connection for the transition resistors. WARNING Take care to avoid finger injuries when operating the diverter switch. Unscrew the fixed transition contact. Mount new contacts. Put the washers as shown in Fig. 15. Use new locking washers. Tighten the screws, tightening torque approximately 10 Nm. Check (and adjust, if necessary) the diverter switch according to section 3.9. Operate it and check that the contact movement is correct. Remount the diverter switch into the housing according to section 3.13. Mount the connection for the transition resistors. Tightening torque approximately 10 Nm. Use new conical spring washers and locking nuts. The conicial end of the nut should be turned upwards. 4.8 Mounting the boards with transition resistors and fixed contacts To assemble the mechanism and the boards with transition resistors and fixed contacts, do as follows: Fixed main contact When the boards are lowered, put one side of the mechanism on an approximately 50 mm high piece of wood to make the fixed and moving contacts free from each other (Fig. 23). Moving main contact The boards should be fixed with new guide pins (4 x 30 mm, spring-type straight pin slotted). Guide by inserting a 6 mm mandrel into an adjacent screw hole. Put in and tighten all screws. Secure the screws with new locking washers (Fig. 18). The plain washers should be closest to the board. Piece of wood Fig. 23. Contact replacement, mounting the boards. 34 Maintenance guide UCG | 1ZSE 5492-124 en, Rev 6 5. Specification of materials 5.1 General On disposal of this product, it is recommended that local environmental regulations in each country are met. For environmental reasons, materials used are specified. 5.5 Conductors Material Approx. amount Copper 5–10 kg Cellulose 5.2 Diverter switch housing 5.6 Gearing mechanism Material Approx. amount Steel 15 kg Material Approx. amount Aluminium 75 kg Steel 15 kg Copper and alloys 5 kg Copper and alloys 5 kg Epoxy resin 35 kg Transformer oil 150–200 kg 5.7 Drive shaft systems 5.3 Diverter switch Material Approx. amount Steel 8 kg Material Approx. amount Aluminium 2 kg Steel 25 kg Brass 2 kg Copper and alloys 10 kg Polyethylene 2 kg Silver 25 g Tungsten 0–1 kg Polyester resin 20 kg Presspan 1 kg Resistor wire (mainly copper and 5-50 kg CAUTION Materials listed in the table above without any specification of amount are included because they may cause pollution problems during decommissioning, even in the small quantities used. nickel alloys with small amounts of aluminium and manganese) 5.4 Tap selectors Material Tap selector C Tap selector III Approx. amount Approx. amount Steel 5 kg 10 kg Aluminium 15 kg 40 kg Copper and alloys 20 kg 50 kg Silver 70 g 10 g Polyester resin 5 kg 10 kg Epoxy resin 15 kg 20 kg 1ZSE 5492-124 en, Rev. 6 | Maintenance guide UCG 35 ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents © Copyright 2015 ABB, All rights reserved. 1ZSE 5492-124 en, Rev. 6, 2015-09-15 Contact us 1ZSC000498-ABH en, Rev. 1 Motor-drive mechanisms, types BUE and BUL2 Maintenance guide Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. Contravention will be prosecuted. Recommended practices ABB recommends careful consideration of the following factors when installing on-load tap-changers: Before you install or commission a unit, make sure that the personnel doing the job have read and fully understood the Installation and commissioning guide provided with the unit. To avoid damaging the unit, never exceed the operating limits stated in delivery documents and on rating plates. Do not alter or modify a unit without first consulting ABB. Follow local and international wiring regulations at all times. Use only factory-authorized replacement parts and procedures. WARNING, CAUTION and INFO WARNING WARNING indicates an imminently hazardous situation which if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme situations. Safety precautions WARNING The maintenance guide should be read and understood before any work is started, and the procedures in the document should be followed at all times. WARNING Before starting any work inside the motor-drive mechanism, the auxiliary power must be switched off. N.B. The motor, the contactors and the heating element may be energized from separate sources. During service WARNING Small amounts of explosive gas might come out from the breathing devices (dehydrating breather or one-way breather). Make sure that no open fire, hot surfaces or sparks occur in the immediate surroundings of the breathing devices. WARNING WARNING also indicates a potentially hazardous situation which if not avoided, could result in death or serious injury. If a failure in power supply occurs during operation, the operation will be completed when the power returns. CAUTION WARNING CAUTION indicates a potentially hazardous situation which if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. The hand crank must not be inserted during electrical operation. WARNING CAUTION may also indicate property-damage-only hazards. INFO provides additional information to assist in carrying out the work described and to provide trouble-free operation. If the tap-changer is not in its exact position and the hand crank is pulled out, the motor-drive mechanism will start and run to the exact position if the power supply is on. Content 1. Introduction...........................................................................................................................7 1.1 General .........................................................................................................................7 1.2 Design...........................................................................................................................7 1.3 Legend..........................................................................................................................7 2. Inspection..............................................................................................................................12 2.1 Required tools and material...........................................................................................12 2.2 Procedure......................................................................................................................12 3. Overhaul................................................................................................................................13 3.1 Required tools and materials..........................................................................................13 3.2 Motor protection............................................................................................................13 3.3 Ground fault protector (option).......................................................................................13 3.4 Counter.........................................................................................................................13 3.5 Heater............................................................................................................................13 3.6 Toothed belt...................................................................................................................14 3.7 Motor cable connections...............................................................................................14 3.8 Overhaul type BUE........................................................................................................14 3.8.1 Disc brake...............................................................................................................14 3.8.2 Brake for the holding contact...................................................................................15 3.8.3 Position transmitter and other position switches......................................................15 3.8.4 Lubrication..............................................................................................................15 3.9 Overhaul type BUL2.......................................................................................................17 3.9.1 Disc brake...............................................................................................................17 3.9.2 Position the transmitter and other position switches................................................17 3.9.3 Lubrication..............................................................................................................17 3.10 Operation test..............................................................................................................18 4. Specification of materials.......................................................................................................19 1. Introduction 1.1 General The motor-drive mechanisms, types BUE and BUL2, manufactured by ABB, have been developed over many years to provide maximum reliability. The simple and robust design gives a service life equal to the service life of the transformer. Minimum maintenance is required for trouble-free operations. The motor-drive mechanism is attached to the transformer tank and connected to the on-load tap-changer by means of drive shafts and a bevel gear. 1.2 Design The design and layout of the motor-drive mechanisms are shown in Figs. 1 and 2 (BUE) and Figs. 3 and 4 (BUL2). 1.3 Legend Towards motor-drive upper limit Towards motor-drive lower limit LOCAL control REMOTE control 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 7 1 3 2 8 4 6 5 7 9 10 11 8 12 15 14 13 16 Fig. 1. Cabinet layout of motor-drive mechanism, type BUE. 1. 2. 3. 4. 5. 6. 7. 8. 9. Locking device prepared for padlock Emergency stop Air vent LOCAL/REMOTE switch RAISE/LOWER switch Outgoing shaft Lamp (40 W socket E27) Lifting eye Counter 8 Maintenance guide BUE/BUL2 | 1ZSC000498-ABH en, Rev. 1 10. Tap-change in progress indicator 11. Position indicator with drag hands for max. and min. position 12. Shaft for hand crank 13. Protective motor switch 14. Door-operated switch for lamp 15. Hand crank 16. Descriptions and circuit diagram Brake Brake disc Holding contact Roll pin Supporting shaft Brake block Arm system Brake for holding contact Drive roller Cam disc One turn shaft Toothed belt Geneva wheel Position transmitter Contact plate Motor Fig. 2. Mechanical design of motor-drive mechanism, type BUE. 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 9 1 2 14 4 3 5 12 6 8 7 16 9 10 11 13 15 6 Fig. 3. Cabinet layout of motor-drive mechanism, type BUL2. 1. 2. 3. 4. 5. 6. 7. Position indicator with drag hands for max. and min. position Tap-change in progress indicator (Red: in progress, White: in position) Counter Outgoing shaft with multi-hole coupling half Shaft for hand crank Locking device prepared for padlock (Option) Outlet 10 Maintenance guide BUE/BUL2 | 1ZSC000498-ABH en, Rev. 1 8. 9. 10. 11. 12. 13. 14. 15. 16. Emergency stop RAISE/LOWER switch LOCAL/REMOTE switch Protective motor switch Air vent Door-operated switch for lamp Lamp Descriptions and circuit diagram Hand crank Operation counter Roller (Grease) Notch Cam disc (Grease) Brake arm Geneva wheel Adjusting screw Holding contact (Grease) Bracket Brake disc Limit switch Toothed belt Multi-position switches (Grease) Fig. 4. Mechanical design of motor-drive mechanism, type BUL2. 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 11 2. Inspection The inspection mainly consists of a visual check of the motor-drive mechanism once a year while the transformer is in service. It is recommended to perform the inspection of the motor-drive mechanism and the other parts of the tapchanger at the same time. See the respective maintenance guide. 2. Check that the motor works properly, the position indicator increases (decreases) one step and the counter advances one step for each operation. Record the counter’s value. The counter shows the number of operations run by the tap-changer (the overhaul schedule can be determined with the help of this information). In the motor-drive mechanism, the following points are to be checked: 3. Turn the control switch to the LOWER (RAISE) position for 1-2 seconds. Check that the motor also works properly in that direction, the position indicator decreases (increases) one step and the counter advances one more step. Reset the drag hands. –– –– –– –– Motor and counter Heater The counter’s value Visual check of toothed belt 2.1 Required tools and material The following equipment is required for the inspection: – – Set of screw drivers 4. Check the emergency stop. Trigger a RAISE or LOWER impulse and after about one second, press the emergency stop. The operation should be interrupted. Reset the emergency stop by turning the knob clockwise and by switching on the protective motor switch. The started operation should now be completed. Operate back to the service position. 2.2 Procedure WARNING This work must be carried out from ground level since the transformer is energized! 5. Check the ground fault protector (option). If the motor-drive mechanism is equipped with an outlet, the ground fault protector should be tested by pressing the test knob on the outlet. 6. Disconnect the incoming auxiliary power. WARNING 7. Open the control panel. Before starting any work inside the motor-drive mechanism, the auxiliary power must be switched off. N. B. The motor, contactors and heating element may be energized from separate sources. 1. Open the cabinet door of the motor-drive mechanism and turn the selector switch to the LOCAL position. Then turn the control switch to the RAISE (LOWER) position. 12 Maintenance guide BUE/BUL2 | 1ZSC000498-ABH en, Rev. 1 8. Check by feeling with a finger that the elements have been functioning. 9. Close the control panel and reconnect the incoming auxiliary power. 10. Complete the inspection by turning the switch to the REMOTE position and closing the cabinet door. 3. Overhaul WARNING Before any work is carried out on the tap-changer: Make sure that the transformer is disconnected and that grounding is properly carried out. Obtain a signed certificate from the engineer in charge. 3.1 Required tools and materials Necessary for the overhaul is the following equipment: –– –– –– –– –– Normal hand tools (wrench sizes up to 19 mm) Standard set of combination wrenches Sliding caliper Spring balance (10 N) Grease (GULF-718 EP synthetic grease, Mobilgrease 28, Shell-Aero Shell grease 22 or similar – – Oil (for plain ball and roller bearings) The motor-drive mechanism should normally be regularly overhauled at intervals of 300,000 operations. The number of operations must not exceed 1,500,000, which is the mechanical lifetime of the motor-drive mechanism. It is recommended to perform the overhaul of the motor-drive mechanism and the other parts of the tap-changer at the same time. See the appropriate maintenance guide for the tap-changer. 3.2 Motor protection WARNING The motor power voltage is dangerous. The function of the protective motor switch is checked. For three-phase AC motors, one of the phase fuses is removed and the function time of the protective motor switch is checked by a RAISE or LOWER operation. The protective motor switch shall release within 60 seconds at a current setting equal to the rated current of the motor at actual voltage. If the protective motor switch does not trip within 60 seconds, switch off the power and adjust the current setting. Repeat the test when the motor is cold. Protective motor switches for DC motors and for single-phase AC motors are not tested. 3.3 Ground fault protector (option) If the motor-drive mechanism is equipped with an outlet, the ground fault protector should be tested by pressing the test knob on the outlet. The overhaul includes the following points: 3.4 Counter Check that the counter is functioning for RAISE and LOWER operations. Before disconnecting the power supply: – – Motor protection function (Section 3.2) –– Ground fault protector (option) (Section 3.3) – – Counter function (Section 3.4) Check that the position indicator increases (decreases) one step and the counter advances one step for each operation. Record the counter's value. The counter shows the number of operations run by the tap-changer. After disconnecting the power supply: – – Heater function (Section 3.5) – – Toothed belt (Section 3.6) – – Cable connections (Section 3.7) – – Disc brake function (Section 3.8.1 for BUE; Section 3.9.1 for BUL2) – – Position transmitter and other position switches (Section 3.8.3 for BUE; Section 3.9.2 for BUL2) – – Lubrication (Section 3.8.4 for BUE; Section 3.9.3 for BUL2) 3.5 Heater Reconnect the power supply and carry out operation tests according to the instructions in the tap-changer installation guide. WARNING Before starting any work inside the motor-drive mechanism, the auxiliary power must be switched off. N. B. The motor, contactors and heating element may be energized from separate sources. Check by feeling with a finger that the elements have been functioning. 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 13 3.6 Toothed belt Check that the toothed belt is sufficiently tight. If tightening is required, adjust the motor support. The tightness of the belt can be checked by a spring balance attached to the belt halfway between the pulleys (see Fig. 5). At a 10 N load the belt should yield about 5 mm on BUE, and at a 6 N load the belt should yield about 2 mm on BUL2. 3.7 Motor cable connections Check that all cable connections within reach are secure. 3.8 Overhaul type BUE 3.8.1 Disc brake Wipe the brake disc free from grease. See Fig. 6. The kinetic energy in the motor and the toothed wheels should be absorbed by the brake, and the motordrive mechanism should stop with a tolerance of ± 25° as measured on the brake disc (± 125° measured on the hand crank). This can be adjusted by tightening both of the spring bolts on the brake. Using the hand crank, operate the motor-drive mechanism until the brake is fully open. At this point the length of the springs must not be less than 35 mm. If the brake still does not function with that spring length, oil or grease has entered the brake linings, which will then need cleaning. Yield Clean as follows: Using a pair of tongs, remove the roll pins that hold the supporting shafts on the brake blocks; see Fig. 2. Then remove the shaft and the brake blocks. Clean the brake linings on the two brake blocks with degreasing agent. Apply load Fig. 5. Check of toothed belt. When refitting the brake, check that the brake disc is completely free from grease. Adjust the spring force of the brake until the motor-drive mechanism stops within the tolerances given above. Adjusting nuts Brake disc Red mark ±25° from mark on brake pad Red mark Brake pads Fig. 6. Brake adjustment, type BUE. 14 Maintenance guide BUE/BUL2 | 1ZSC000498-ABH en, Rev. 1 CAUTION If the motor-drive still does not stop when the brake is adjusted to a spring length of 35 mm when the brake is fully open, please contact ABB for advice. 3.8.2 Brake for the holding contact Check that the brake for the holding contact prevents the arm system on the holding contact shaft from swinging beyond its normal position when the roller on the drive arm moves free from the cam disc; see Fig. 2. At the end of the operation, contacts for operation in the opposite direction should not move when the arm system swings back towards its normal position. Unpermitted swinging should be prevented by raising the braking force, i. e. tightening the spring bolt. An adjusted, increased spring force on the brake makes the holding contact arm swing back with a different speed, and the brake for the holding contact must be adjusted. 3.8.3 Position transmitter and other position switches Clean the contact plates and arms (Fig. 7) from dust and dirt with a dry cloth. Check and adjust the resilience of the moving contacts in the multi-position switches. The moving contact shall in all positions, have a clearance between the nut and the contact arm of 0.5–1.1 mm. Adjustment is made with the nuts on the contact. 3.8.4 Lubrication See Fig. 8. The bearing points of the brake blocks and the links should be sparingly lubricated with oil. (Use oil for plain ball and roller bearings.) The spur gears, the Geneva wheel with the limit-stop, the cam discs, the cam bar and the big wheel attached on the outgoing shaft, are sparingly lubricated with the same type of grease as for the shaft system when necessary. Other bearing points do not need lubrication. Protect the brake disc and the brake linings against lubricants. Wipe off excess lubricant. Reconnect the power supplies. Contact arm Moving contact Contact arm +0.3 0.8 mm -0.3 Geneva wheel Contact plate Fixed contact View A – A Fig. 7. Contact arm play. 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 15 Grease Grease Oil Oil Grease Grease NOTE: The small bevel gear for the position indicator shaft must be greased. Grease Fig. 8. Lubrication points, type BUE. 16 Maintenance guide BUE/BUL2 | 1ZSC000498-ABH en, Rev. 1 3.9 Overhaul type BUL2 3.9.1 Disc brake Run the motor-drive mechanism and check that the center of the notch in the cam disc stops within ±2 mm from the center of the roller on the brake arm, see Fig. 9. If it does not stop within the tolerances, adjust the braking force with the adjusting screw at the lower end of the brake arm. Loosen the contra nut. Tightening the screw (clockwise) makes the stop occur earlier and loosening the screw (counterclockwise) makes the stop occur later. Tighten the contra nut after the adjustment. CAUTION 3.9.3 Lubrication Lubrication is not needed under normal operating conditions. All ball bearings have rubber seals and are permanently lubricated. All cam discs and some gears are made of selflubricating material. If needed, the gear for the outgoing shaft, the bevel gears for the hand crank, the Geneva wheels and the bevel gears for the position indicator can be sparingly lubricated with the same grease as for the shaft system. (GULF-718EP Synthetic Grease, Mobilgrease 28, Shell-Aero Shell Grease 22 or similar). See Fig. 4. Reconnect the power supplies. If the motor-drive still does not stop when the brake is adjusted to min. 15 mm according to Fig. 9, please contact ABB for advice. 3.9.2 Position the transmitter and other position switches Check the contact function in all positions for both RAISE and LOWER operations. Transparent cover Contact arm Circuit board No adjustment of the contacts should be made. If there is excessive dust, it can be removed from the circuit boards and the transparent covers with a vacuum cleaner without disassembling the multi-position switch. Fig. 10. Check of position transmitter. Roller on the brake arm in center of the notch in the cam disc Brake arm Cam disc Contra nut Adjusting screw Brake disc Min. 15 Fig. 9. Brake adjustment, type BUL2. 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 17 3.10 Operation test Operate the motor-drive mechanism, first with manual operation and then electrically between the limit-positions. Check the limit-stops by operating the tap-changer to one of the end-positions. When trying to operate it electrically beyond the end-position, the motor should not start. Check the mechanical end-stop by trying to hand crank it beyond the end-position. After a couple of turns on the hand crank, it should be mechanically stopped. Hand crank back to the end-position (where the indicator flag is positioned in the middle for the BUE, and when the indicator flag shows white color for the BUL2). Operate the tap-changer electrically to the other end-position and carry out the same test procedure as above. Check the emergency stop by triggering a RAISE or LOWER impulse and after about one second, press the emergency stop. The operation should be interrupted. Reset the emergency stop by turning the knob clockwise and switch on the protective motor switch. The started operation should now be completed. Check the run-through protection with the step-by-step function disengaged. This is done by first removing the connection between terminals X4:1 and X4:2 and then keeping the RAISE/LOWER switch engaged. The motordrive mechanism should stop before the fourth operation is completed. This check must be performed at least five steps from the end-position. After the test, reset the time relay by setting the LOCAL/REMOTE switch to 0 and then back. Reset the protective motor switch to ON. Reconnect the connection between X4:1 and X4:2. Check the step-by-step relay by keeping the RAISE/LOWER switch engaged in RAISE. The tap-changer shall advance only one step. Repeat the check for LOWER. Check the function of the position transmitter and other multiposition switches in all positions. 18 Maintenance guide BUE/BUL2 | 1ZSC000498-ABH en, Rev. 1 4. Specification of materials BUE BUL BUL2 Approx. Approx. Approx. amount amount amount Steel 100–120 kg 55 kg 25 kg Aluminium and alloys – 10 kg 5 kg Copper and alloys 5–10 kg 5 kg 65 kg Silver 10 g 10 g x x x x x x Material Plastics: chlorsulphonated polyethylene polyamide with MoS2 phenol resin laminate x polyester x x x PVC x x x carbonate plastic x x x nitrile rubber x x x fluorine rubber x x x Rubbers: CAUTION Materials listed in the table above without any specification of amount are included because they may cause pollution problems during decommissioning, even in the small quantities used. 1ZSC000498-ABH en, Rev. 1 | Maintenance guide BUE/BUL2 19 ABB AB Components SE-771 80 Ludvika, Sweden Phone: +46 240 78 20 00 Fax: +46 240 121 57 E-Mail: sales@se.abb.com www.abb.com/electricalcomponents © Copyright 2012 ABB, All rights reserved. 1ZSC000498-ABH en, Rev. 1, 2012-11-15 Contact us 2750 515-1 EN, REV. 13, 2019-05-22 Transformer bushing, type GOE 250 to 2550 Installation and commissioning guide The information contained in this document may be subject to change without prior warning and should not be considered as binding on ABB AB’s behalf. ABB AB accepts no liability for any errors that may appear in this document. ABB AB is not liable for any damage resulting from the incorrect interpretation of this document. This document, or parts thereof, may not be reproduced or copied without ABB AB’s consent. It may not be distributed to others, or used by unauthorized parties. Any breaches to the above will be penalized with the support of applicable laws. Contents 1 2 3 4 Safety Levels of safety risks ................................................................................................................................................................... 5 1.2 Hazardous working situations ..................................................................................................................................................... 6 1.3 Safety precautions....................................................................................................................................................................... 6 1.4 Competence level........................................................................................................................................................................ 6 Product description 7 2.1 Design ......................................................................................................................................................................................... 7 2.2 Technical specification................................................................................................................................................................. 12 2.2.1 General specifications ............................................................................................................................................... 12 2.2.2 Mechanical loading.................................................................................................................................................... 12 Delivery 15 3.1 Incoming inspection..................................................................................................................................................................... 15 3.2 Transportation ............................................................................................................................................................................. 15 3.3 Storage ........................................................................................................................................................................................ 15 3.4 Lifting ........................................................................................................................................................................................... 16 3.4.1 Lifting the transport box ............................................................................................................................................. 16 3.4.2 Lifting the bushing out of the transport box ............................................................................................................... 17 Installation 19 4.1 Tools ............................................................................................................................................................................................ 19 4.2 Consumables .............................................................................................................................................................................. 19 4.3 Preparations ................................................................................................................................................................................ 20 4.3.1 Lifting the bushing ..................................................................................................................................................... 20 4.3.2 Oil-filling of the bushing for horizontal installation ..................................................................................................... 22 4.4 Horizontal installation of the bushing on the transformer ............................................................................................................ 24 4.5 Installation with draw lead ........................................................................................................................................................... 26 4.6 4.7 5 5 1.1 4.5.1 Calculation of the lenght of the draw lead ................................................................................................................. 26 4.5.2 Installation with draw lead ......................................................................................................................................... 27 Installation with draw rod at transformer factory.......................................................................................................................... 32 4.6.1 Removal of the lower draw rod with bottom contact from the bushing ..................................................................... 32 4.6.2 Installation of the small bottom contact in the transformer ........................................................................................ 36 4.6.3 Installation of the large bottom contact in the transformer ........................................................................................ 38 4.6.4 Installation of the bushing on the transformer ........................................................................................................... 40 Installation with draw rod at site .................................................................................................................................................. 44 4.7.1 Preparations at site ................................................................................................................................................... 44 4.7.2 Installation of the bushing on the transformer at site................................................................................................. 47 4.8 Hydraulic tightening of the draw-rod nut...................................................................................................................................... 51 4.9 Manual tightening of the draw-rod nut ......................................................................................................................................... 55 4.10 Oil-filling....................................................................................................................................................................................... 57 4.11 Installation of the outer terminal .................................................................................................................................................. 58 4.12 Grounding of the bushing flange ................................................................................................................................................. 61 Commissioning 63 5.1 Waiting time before energization ................................................................................................................................................. 63 5.2 Recommended test before energization ..................................................................................................................................... 64 5.2.1 Overview ................................................................................................................................................................... 64 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 3 6 8 9 10 Tightness test of bushing outer terminal.................................................................................................................... 64 5.2.4 Measurement of capacitance and dissipation factor ................................................................................................. 65 5.2.5 Measurement of through-resistance.......................................................................................................................... 68 69 Recommended maintenance ...................................................................................................................................................... 69 Re-packing 73 7.1 Removal of horizontally installed bushings ................................................................................................................................. 73 7.2 Removal of the bushing from the transformer, draw rod ............................................................................................................. 74 7.3 Re-packing of the bushing........................................................................................................................................................... 78 Spare parts and special tools 79 8.1 Summary ..................................................................................................................................................................................... 79 8.2 Spare parts .................................................................................................................................................................................. 79 8.3 Special tools ................................................................................................................................................................................ 81 Disposal and environmental information 83 9.1 Overview ..................................................................................................................................................................................... 83 9.2 Disposal and recycling ................................................................................................................................................................ 83 References 10.1 4 Tightness test between transformer and bushing flange........................................................................................... 64 5.2.3 Maintenance 6.1 7 5.2.2 85 Summary ..................................................................................................................................................................................... 85 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 1 Safety 1.1 Levels of safety risks Throughout the manual, various types of safety risks are indicated. The most serious level on this scale provides a warning about serious personal injury or possible death, or major damage to a product, if the instructions are not observed. Symbols and their meanings The following describes the symbols that appear in the manual, along with their meaning. DANGER! The yellow, filled warning triangle warns that an accident will occur if the instructions are not complied with and that it will result in serious personal injury or death and/or major damage to the product. It is used, for example, to warn of such dangers as: contact with high voltage, explosion or fire risk, risk for toxic gases, risk of crushing, impacts, falls from high places, etc. CAUTION! The round warning symbol warns that an accident could occur if the instructions are not observed, and that this could result in personal injury and/or damage to the product. It is also used to warn of risks that entail burns, eye or skin injuries, impaired hearing, crushing or slipping injuries, tripping, impacts, falls from high places, etc. In addition, it is used to warn of functional requirements when assembling or removing equipment where there is a risk of damage to the product or downtime. NOTE! The comment symbol identifies important information and conditions. Also used to indicate any danger that could lead to property damage. Torque The torque symbol indicates tightening torque. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 5 1.2 Hazardous working situations Hazard Action Working close to high voltage. Disconnect all plant power. Ground all objects at the workplace. If work must be done close to live plant components, make sure that the safety distance is in compliance with the applicable safety regulations. Working on ladders and platforms. Work must be done in accordance with the applicable safety regulations. Do not use ladders or platforms in poor weather conditions. Working with heavy objects. Do not walk under lifted objects. Make sure that heavy objects are stable before starting work. 1.3 Safety precautions Precaution Action Transformer oil Collect used transformer oil in drums. Transformer oil is dangerous. Fumes from hot oil can cause irritation to the respiratory organs and the eyes. Long and repeated contact with transformer oil can cause damage to your skin. Waste and cleaning up Clean up liquid waste with an adsorbent. Treat waste as hazardous to the environment. Fire Extinguish fires with powder, foam or carbon dioxide. 1.4 Competence level Installation of the bushing should only be performed by authorized personnel. CAUTION! Incorrect installation can lead to catastrophic failure of the transformer. 6 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 2 Product description 2.1 Design Overview The GOE is a capacitance graded oil impregnated paper bushing made for immersed oil/air service. For a detailed description, please refer to the Technical guide, 1ZSE 2750-105. G001889 General schematics 1 Top housing 2 Porcelain insulator, air side 3 Test tap 4 Extension for current transformer 5 Porcelain insulator, oil side 6 Bottom nut 7 Mounting flange 8 Oil sampling valve 9 Oil plug 10 Oil-level gauge, GOE 1050 to 2600 11 Lifting eye 12 Sight glass, GOE 250 to 950 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 7 Terminal system The bushing can be configured with one of two terminal systems: the draw-lead system, or the draw-rod system. The draw-rod system can be configured with a small, or a large bottom contact. Terminal system Option Draw-lead system - Draw-rod system Small bottom contact G004488 Large bottom contact 8 A Draw-lead system B Draw-rod system with small bottom contact, N1 = 4 C Draw-rod system with large bottom contact, N1 = 6 1 Inner terminal 2 Draw lead 3 Draw rod 4 Small bottom contact, N1 = 4 5 Large bottom contact, N1 = 6 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Draw-rod system The draw rod can be configured with an optional joint (3) to fit transformers with short bushing turrets. The bottom-contact joint (6) is locked with threadlocking fluid as standard, but can be unlocked as an option. G006279 Large bushings with long draw rods have one or two upper joints (1), they are always locked with threadlocking fluid. All joints must be locked with threadlocking fluid when the bushing is in operation at site. 1 Upper joint (only on large bushings). 2 Lower joint (at flange level). 3 Additional joint (option). 4 Thread is locked with threadlocking fluid. 5 Thread is NOT locked with threadlocking fluid. 6 Bottom-contact joint, locked with threadlocking fluid. Unlocked as option. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 9 Horizontal installation CAUTION! Do not install bushings that does not have the oil passage (2) in the horizontal position. If the bushing will be installed in the horizontal position, then this must be specified in the order. Because horizontally installed bushings must be fully filled with oil (there is no expansion space for the oil), the oil must flow freely to and from the transformer tank through an oil passage (2). The bushing is delivered with expansion space for the oil, and the bushing must be filled at installation. G004983 When the bushing is delivered, the oil passage (2) is covered with a covering plate (1) and a rubber gasket. This configuration makes sure that it will be removed at installation on the transformer. 10 Type Dimension A (mm) GOE 250 - GOE 450 55 GOE 550 - GOE 950 60 GOE 1050 - GOE 1175 67 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Test tap The bushing has a test tap that is connected to the outermost conductive layer of the condenser core. The test tap is used to measure the bushing insulation by capacitance and dissipation factor. The cover connects the outermost conductive layer to ground, and must always be installed when the bushing is energized. The maximum one minute test voltage for this test tap is 20 kVrms. The test tap can be used as a power source, if it is connected to an external capacitance. The operating voltage is limited to 6 kV. G000388 CAUTION! Do not energize the bushing without a test adapter or the cover installed. The bushing is grounded through the cover to prevent damage to the bushing. 1 Stud 2 Cover 3 Grounding spring 4 O-ring Test adapter, 2769 522-C, optional equipment G003049 The test adapter 2769 522-C is available for permanent connection to measuring circuits. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 11 2.2 Technical specification 2.2.1 General specifications Refer to the table for the standard technical specifications of the bushing. For conditions exceeding the specifications, please contact ABB. Application: Transformers/reactors Classification: Tranformer bushing • Oil impregnated paper, capacitance graded, oil immersed. • For outdoor and indoor use. Ambient temperature limits: -50 °C to +40 °C, limit temperatures, according to temperature class 2 of IEC 60137. Maximum altitude of site: 1000 m (Bushings for other altitudes can be provided on request.) Level of rain and humidity: 1-2 mm rain/minute horizontally and vertically, according to IEC 60060-1 and IEEE Std 4. Maximum pollution level: According to the specific creepage distance, and IEC 60815. Immersion medium: Transformer oil. • Maximum daily mean oil temperature: +90 °C. • Maximum temporary oil temperature, at short time overload: +115 °C. Oil-level in transformer: Not lower than 30 mm from the bushing flange. Maximum pressure of medium: pg 100 kPa (pg = relative to ambient pressure). Angle of installation: 0 to 60° from vertical. (GOE 1300, 1425 and 2550-1675 0° to 30°.) Test tap: Test tap with 8 mm male contact pin. According to IEEE type A. Conductor: Center-tube conductor, or draw lead. Markings: Conforming to IEC/IEEE. 2.2.2 Mechanical loading Maximum permitted static load on the outer terminal The load must be applied below the midpoint of the outer terminal. The total cantilever load must be perpendicular to the bushing axis. The bushing installation angle can be 0° – 60° from vertical. Only bushings that are specefied for horizontal installation can be installed at 90° from vertical. In the axial direction, the bushing can withstand a static load of 20 kN. NOTE! The loads described in this section are static loads, for dynamic loads such as earthquakes and extreme wheather conditions, please contact your ABB sales representative. 12 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 G001888 1 Maximum cantilever load at installation angle 0° 2 Maximum cantilever load at installation angle 30° 3 Maximum cantilever load at installation angle 60° 4 Maximum axial static load 5 Load applied at the midpoint Type Test load 1 minute (N) Maximum cantilever load in operation at installation angle (N) 0° 30° 60° Maximum axial static load (N) GOE 250, 380, 650 5700 2800 2300 1700 20000 GOE 950 5000 2500 2000 1500 20000 GOE 1050 13000 6500 4300 3100 20000 GOE 1175 12000 6000 4300 3100 20000 GOE 1300, 1425 9000 4500 2500 - 20000 GOE 1550, 1675, 1800 13000 6500 4300 1500 20000 GOE 2550 - 1600 13000 6500 3700 1600 20000 GOE 2550 - 1675 12200 6100 2900 - 20000 Maximum permitted torque on the outer terminal The maximum torque that is permitted on the outer terminal is 250 Nm. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 13 14 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 3 Delivery 3.1 Incoming inspection • • Make sure that all items have been delivered, refer to the packing list. Carefully inspect the bushings for shipping damage. NOTE! The bushing has been routine tested in oil, and there can be small quantities of oil remaining on the oil-side of the bushing. Vaseline is used for lubrication of threads, and at some temperatures Vaseline can appear as oil. NOTE! The oil-level is not shown correctly when the bushing is in the horizontal position. 3.2 Transportation • • • The bushing must be transported in the transport box. The bushing must be transported in the horizontal position. Carefully inspect the bushing for damage after transportation. 3.3 Storage Short term storage, less than 6 months • • • The bushing can be stored outdoors, if it is in the transport box. Keep the transport box protected from water, when the bushing is stored outdoors. Keep the bushing dry, clean and protected against mechanical damage. The bushing can be stored in both the vertical, and horizontal positions. NOTE! The oil-level is not shown correctly when the bushing is in the horizontal position. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 15 Long term storage, more than 6 months • The bushing can be stored outdoors, if it is in the transport box. Keep the transport box protected from water, when the bushing is stored outdoors. Keep the bushing dry, clean and protected against mechanical damage. Lift the bushing to the vertical position with the top end upwards, and put it in a safe stand. – As an alternative: keep the bushing in the transport box and lift it to an inclined position, with the top end upwards and at an angle of at least 7°. • • The bushing is delivered from ABB in a transport box, and the bushing is held in place by support blocks and fiberboard in the box. G005075 The transport box is marked with Top end, this identifies the end to lift when the bushing is in storage. 3.4 Lifting 3.4.1 Lifting the transport box G003042 Overview 16 1 Center of gravity 2 Soft lifting slings Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Procedure 1. Make sure that the crane and the soft lifting slings are approved for the total weight of the transport box and bushing. Refer to the weight in the packing list. 2. Attach soft lifting slings (2). 3. Make sure that the angle of the soft lifting sling is not more than 20°. 4. Carefully lift the transport box. 5. Set down the transport box on a flat surface. End of instruction 3.4.2 Lifting the bushing out of the transport box G005004 Overview 1 Top end nut Procedure 1. Make sure that the crane is approved for lifting the weight of the bushing. Refer to the net weight on the packing list. 2. Open the transport box. NOTE! The cover is attached with bolts. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 17 3. Remove the support blocks from the transport box and put them on the ground. CAUTION! Make sure that the ground is flat. Attach a soft lifting sling to the lower part of the flange and then to the crane hook. 5. Attach a soft lifting sling to the outer terminal (1) and then to the crane hook. G004688 4. CAUTION! Attach the soft lifting sling as close to the top housing as possible, or damage will occur. G004689 NOTE! If the outer terminal is not installed, please contact ABB. 6. Carefully lift the bushing. 7. Make sure that the support blocks are in the same positions as the support blocks in the transport box. CAUTION! Do not apply force to the ceramic insulator, it will break. 8. Lower the bushing onto the support blocks. End of instruction 18 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 4 Installation 4.1 Tools Tool Part number Note Lifting tool 9760 668-A - Soft bedding - E.g. rubber mat or wood board Soft lifting slings - - Pull-through cord 9760 669-A With M8 terminal. For assembly and disassembly of the draw rod. Torque wrench key for hex socket screws, 16 mm (M10) and 13 mm (M8), torque 20 to 40 Nm. - - Wrench for hex socket screws 45 mm or adjustable wrench for 45 mm bolts or larger. - For the test tap cover. Shackles - To fit Ø 28 mm holes, for connection of the soft lifting slings to the bushing flange. Hydraulic jack PDV2330 For removal, and installation of the bottom contact. Draw-rod system. (2769 897-A) Box spanner 9760 669-B For removal, and installation of the bottom contact. Draw-rod system. Tackle - For installation of the bushing at a specific angle. 4.2 Consumables Item Brand Part number Note Oil based Vaseline Fuchs 1171 5011-102 For treatment of contact surfases. Does not react with transformer oil. Mobilgrease 28 MOBIL 1171 4014-407 Lubricates and protects metals against corrosion. Protects rubber. Does not react with transformer oil. Molykote Multilub Dow Corning 1236 0011-127 For lubrication of draw-rod threads and bolts on the outer terminal. Thread-locking fluid grade 42 - - High strength thread-locking fluid, permanent locking. Thread-locking activator grade 47 - - Activator for thread-locking fluid grade 42. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 19 4.3 Preparations 4.3.1 Lifting the bushing G005005 Overview 1 Lifting tool 2 Soft bedding, e.g. rubber mat or woodboard 3 Shackle Procedure 1. Make sure that the crane can lift the bushing. Refer to net weight in the packing list. 2. Loosen the M8 bolts (1). G004684 NOTE! It is not necessary to remove the M8 bolts. 20 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 3. Remove the M10 bolts (6) and washers (7), and then remove the outer terminal (6). G004690 NOTE! Keep the outer terminal (5), washers (7) and bolts (6), they will be used again. 4. Install the lifting tool (1), the M10 bolts (6) and the washers (7). • For GOE 250 to 950: align the side of the lifting tool with the oil-level glasses (25). • For GOE 1050 to 2550: align the side of the lifting tool with the oil-level guage (26). G005056 NOTE! The lifting tool is thinner than the outer terminal, use stacks of washers or shorter bolts to correctly install the lifting tool. Torque 40 ±4 Nm 5. Attach soft lifting slings (8) from the lifting holes through the lifting tool to the crane hook. G005015 NOTE! The diameter of the holes for the lifting-slings in the lifting tool is Ø50 mm. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 21 For installation at a specific angle: attach soft lifting slings with a shackle (9) from the flange to the crane hook. 7. Align the crane hook with the lifting tool on the bushing. 8. Carefully lift the bushing. G005058 6. CAUTION! Make sure that the bushing does not rotate. 9. Adjust the shackle (9) until the bushing flange has the same angle as the transformer flange. End of instruction 4.3.2 Oil-filling of the bushing for horizontal installation Overview • • This procedure applies to bushings that will be oil-filled with an atmospheric process. This procedure does NOT apply when the bushing will be oil-filled with the vacuum process, refer to Horizontal installation of the bushing on the transformer, page 24. This procedure must be done immediately before installation of the bushing on the transformer, because there is no expansion space for the oil after this procedure is completed. Thus, changes in the ambient temperature will cause the oil to expand or contract, this will cause damage to the seals in the bushing. CAUTION! Do not leave the bushing fully filled with oil. Installation must be done immediately after the bushing is sealed. If not, changes in the ambient temperature will cause damage to the seals in the bushing. 22 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Procedure Install the lifting-tool: 1. Remove the bolts (6) and washers (7). 2. Install the lifting tool (1), and align the side of the lifting tool with the oil-level glasses (25). 3. Install he bolts (6) and washers (7). G006666 1. Torque 40 ±4 Nm Lift the bushing to the vertical position. 3. Remove one of the oil-plugs (9). 4. Add clean and dry transformer oil until the bushing is completely filled. G006353 2. CAUTION! Make sure that the bushing is completely full of transformer oil. Air left in the bushing can cause damage. 5. Install the oil-plug (9). 6. Lower the bushing to the horizontal position. 7. Install the bushing in the transformer immediately, refer to Horizontal installation of the bushing on the transformer, page 24. CAUTION! Do not leave the bushing fully filled with oil. Installation must be done immediately after the bushing is sealed. If not, changes in the ambient temperature will cause damage to the seals in the bushing. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 23 4.4 Horizontal installation of the bushing on the transformer Overview The bushing is installed without removal of the bottom contact. Procedure Install the springs (15), the guiding sleeves (16), the pressing ring (17), and the hex screws (18) to the bottom contact. 2. Remove the covering plate (1). G003036 G006299 1. 24 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 3. Install the nuts and washers. Tighten the nuts in a crosswise sequence. CAUTION! Make sure that the nuts are tightened evenly. G006296 First tighten all nuts to half the torque, then to the full torque. Torque Please refer to the transformer documentation. 4. Remove the lifting gear (1): 1. Remove the long bolts (6), washers (7) and lifting gear (1). 2. Install the original bolts (6) and washers (7). G006297 NOTE! The lifting gear uses longer bolts (6), use the original bolts (6) to attach the outer terminal. Put the winding cables through the end-shield. 6. Install the winding cables to the bottom contact. G005024 5. CAUTION! Make sure that there is no tension in the winding cables. Tension in the winding cables will cause damage to the bottom contact. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 25 Install the end shield: 1. Push the end shield carefully against the pressing ring (17). 2. Turn the end shield approximately 20°, to its locked position. G006298 7. End of instruction 4.5 Installation with draw lead 4.5.1 Calculation of the lenght of the draw lead Overview Because of the tolerances in the length of the porcelain, a nominal lenght for the draw lead can not be given. G000379 The actual distance between the inner terminal and the bottom of the bushing must be calculated. Procedure 1. 26 Measure the length (L2). Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 2. Subtract 350 mm from the L2 measurement. L2 - 350 = draw lead lenght CAUTION! Make sure that the draw lead is sufficiently long. End of instruction 4.5.2 Installation with draw lead G004512 Overview 1 Bushing 2 Inner terminal 3 Draw lead 4 Pull-through cord Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 27 Procedure 1. Remove the inner terminal from the bushing. 2. Remove the nut (19) and washers. G006520 1. Solder the draw lead (2) from the transformer windings to the inner terminal (1). 3. Carefully clean the bottom end of the bushing, and the inside of the center hole. Look for damage. 4. Install the springs (15), the guiding sleeves (16), the pressing ring (17), and the hex screws (18) to the bottom end of the bushing. G005016 G004513 2. Torque 40 Nm 28 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Install the end shield: 1. Push the end shield carefully against the pressing ring (17), until the hex screw heads come through the holes in the end shield. 2. Turn the end shield clockwise approximately 20°, to its locked position. G005032 5. 6. Put the washers and the nut (19) on the pull-through cord. G004515 CAUTION! Make sure that the washers are in the correct order. Nut 20 Plain washer 21 Conical spring washer 22 Contact washer Lower the pull-through cord (10) through the bushing. G001893 7. 19 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 29 8. Apply Molykote Multilub to the pull-through cord (10), and attach it to the inner terminal (7). G004516 NOTE! The terminal (7) has M8 threads. 9. Hold the pull-through cord (12) in tension, while lowering the bushing onto the transformer. CAUTION! Do not damage the stud bolts on the transformer. There is a risk of metal falling into the transformer. G003058 CAUTION! Make sure that the draw lead is entering the bushing correctly. Monitor the draw lead through the inspection openings on the transformer. NOTE! Plastic sleeves put on two or three of the stud bolts will help to guide the flange, and will prevent damage to the stud bolts. If necessary, adjust the length of the inner terminal: 1. Lift the bushing from the transfomer and lower the inner terminal with the pull-through cord. 2. Remove the bolts (15). 3. Move the lower part (14). 4. Apply Molykote Multilub to the threads of the bolts (15), and install the bolts (15). CAUTION! Make sure that there is no tenison in the straded cable, or too much slack. NOTE! The lower part of the inner terminal can be moved in steps of 30 mm. 30 G004514 10. Torque 37.5 Nm Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 If the bushing is installed in a non vertical position: • For GOE 250 to 950: the sight glasses (25) must be perpendicular to the angle of the bushing. • For GOE 1050 to 2600: the oil-guage (26) must point down. G006197 11. 12. Install the nuts and washers. Tighten the nuts in a crosswise sequence. CAUTION! Make sure that the nuts are tightened evenly. G005043 First tighten all nuts to half the torque, then to the full torque. Torque Please refer to the transformer manufacturer. 13. Install the inner terminal: 1. Apply Molykote Multilub on the threads of the nut (19). 2. Install the washers and the nut (19). 3. Remove the pull-through cord. 4. Tighten the nut (19). G005051 NOTE! The guide pins (23) fit the holes in the top tube. Torque 80 Nm Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 31 Remove the M10 bolts (6), the washers (7), and the lifting tool (1). 15. Continue with Installation of the outer terminal, page 58. G004679 14. End of instruction 4.6 Installation with draw rod at transformer factory 4.6.1 Removal of the lower draw rod with bottom contact from the bushing Overview G005052 The bottom contact is usually installed in the bushing when it is delivered from ABB, the first step at the transformer factory is thus to remove it. 32 1 Upper draw rod 2 Lower draw rod with bottom contact 3 Bottom contact 4 Bushing Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Procedure Install the shaft (16) on the draw rod (1), and put the box-spanner (12) on the shaft (16). 2. Make sure that more than 10 mm of the threads on the upper draw rod (1) are used. 3. Put the hydraulic jack (8) on the shaft (16), and install the nut (17) and washer but do not tighten it. G005066 G004873 1. G005147 NOTE! The hydraulic jack must be in the middle of its stroke. If not, the tension of the draw rod cannot be released when the draw rod nut is loosened. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 33 4. Loosen the draw rod nut (10): 1. Pull the draw rod with 40 kN. 2. Carefully increase the force until you can loosen the draw rod nut with your hand. If 45 kN is reached, and the draw rod nut is not loose, turn the box-spanner with a wrench. DANGER! Apply the hydraulic pressure carefully. Incorrectly used high-pressure hydraulics can break with explosive force. G006521 Refer to the instructions for the hydraulic jack. CAUTION! Do not remove the compensation device. NOTE! The draw rod is installed with a tension of 40 kN. Loosen the nut (17). 6. Turn the shaft (16) counter clockwise to remove the shaft-socket from the upper draw rod (1). 7. Remove the hydraulic jack (8) from the bushing. G005068 G005067 5. 34 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 8. Apply Molykote Multilub to the threads on the pull-through cord (12), then connect it to the upper draw rod. NOTE! The terminal on the pull-through cord (12) has M8 threads. G004686 NOTE! Or use a lubricant with equal properties to Molykote Multilub. 9. Remove the draw rod nut (10). G003055 NOTE! The draw rod will fall out of the bushing if it is not in the horizontal position. 10. Pull down the draw rod from the bottom end of the bushing, and disassemble it at the lower joint (8). NOTE! The upper thread (7) is locked with thread-locking fluid grade 42. The guiding cone (21) is loose. 11. G005033 NOTE! As standard the thread joint (20) between the draw rod and the bottom contact is locked with thread-locking fluid grade 42. Carefully look for damage at the bottom end of the bushing, and the inside of the center hole. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 35 4.6.2 Installation of the small bottom contact in the transformer G005031 Overview 1 Small bottom contact Procedure 1. Install the springs (15), the guiding sleeves (16), the pressing ring (17), and the hex screws (18) to the bottom end of the bushing. G005016 NOTE! The pressing ring (17) cannot be installed to the small bottom contact. Torque 40 Nm 36 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Put the winding cables through the end-shield. 3. Install the winding cables to the bottom contact. G005024 2. G005036 CAUTION! Make sure that there is no tension in the winding cables. Tension in the winding cables will cause damage to the bottom contact. Torque 68 ±6 Nm 4. Lift the bushing above the opening in the transformer. 5. Continue with Installation of the bushing on the transformer, page 40. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 37 4.6.3 Installation of the large bottom contact in the transformer Overview G005017 The end-shield can be installed to both the bottom contact, and the bottom nut of the bushing. This procedure describes installation on the bottom contact, for installation on the bottom nut, refer to Installation of the small bottom contact in the transformer, page 36. 1 Large bottom contact Procedure Install the springs (15), the guiding sleeves (16), the pressing ring (17), and the hex screws (18) to the top of the bottom contact. G005018 1. Torque 40 Nm 38 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 2. Install the winding cables to the bottom contact. G005019 CAUTION! Make sure that there is no tension in the winding cables. Tension in the winding cables will cause damage to the bottom contact. Torque 68 ±6 Nm Install the end shield: 1. Push the end shield carefully against the pressing ring (17), until the hex screw heads come through the holes in the end shield. 2. Turn the end shield approximately 20°, to its locked position. G005037 3. 4. Lift the bushing above the opening on the transformer. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 39 4.6.4 Installation of the bushing on the transformer Overview G006788 It is important to install the draw-rod correctly, thus the ends of the draw-rod parts must make contact at (9). CAUTION! Do not disassemble the joints (1), these are correctly assembled and locked with tread-locking fluid by ABB. Procedure Connect the upper draw-rod (1) to the lower draw-rod (4). G005038 1. 40 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 2. Make sure that the joint is correctly threaded: 1. Calculate the nominal distance: H = L5 - 25 mm(± 2 mm). 2. Measure the distance H and compare it to the nominal distance H. 3. Record the measured distance H and keep it with the substation documentation. NOTE! When the joint is correctly threaded, 2 threads on the upper (7) and lower (8) threads are visible. If the bushing has the small bottom contact, then install the end shield: 1. Push the end shield carefully against the pressing ring (17), until the hex screw heads comes through the holes in the end shield. 2. Turn the end shield approximately 20°, to its locked position. G005039 3. G006282 Refer to the rating plate for the distance L5. 4. Hold the pull-through cord (12) in tension, while lowering the bushing onto the transformer. CAUTION! Do not damage the stud bolts. There is a risk of metal falling into the transformer. G003058 NOTE! Plastic sleeves put on two or three of the stud bolts will help to guide the flange, and will prevent damage to the stud bolts. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 41 If the bushing is installed in a non vertical position: • For GOE 250 to 950: the sight glasses (25) must be perpendicular to the angle of the bushing. • For GOE 1050 to 2600: the oil-guage (26) must point down. G006197 5. Install the nuts and washers. Tighten the nuts in a crosswise sequence. G005053 6. Torque Please refer to the transformer documentation. Install the draw-rod nut (10): 1. Apply a generous quantity of Molykote Multilub to the nut (10), and the threads of the draw rod. 2. Install the washer (11) and nut (10) on the draw rod, tighten with your fingers. 3. Remove excess Molykote Multilub with a rag. CAUTION! If the nut (10) is not lubricated correctly, it will not be tighten to the correct torque. This can cause the bushing to fail. G004300 7. CAUTION! Make sure that the centering ring (28) is in position. It is necessary for the correct installation of the draw rod. 42 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Tighten the draw-rod nut (10). G006663 8. Torque 10 Nm Remove the pull-through cord (12). 10. Remove the bolts (6), the washers (7) and the lifting gear (1). 11. Tighten the draw-rod nut, refer to Hydraulic tightening of the draw-rod nut, page 51, or Manual tightening of the draw-rod nut, page 55. G004679 9. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 43 4.7 Installation with draw rod at site 4.7.1 Preparations at site Overview G004532 This procedure is only applicable if the lower draw rod with the bottom contact (5) is installed in the transformer. Procedure Loosen the M8 bolts (1). G004684 1. 44 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Remove the M10 bolts (6), and then remove the outer terminal (5). 3. Install the lifting tool (1), the M10 bolts (6) and the washers (7). G004691 2. For GOE 250 to 950: align the side of the lifting tool with the oil-level sight glasses (25). • For GOE 1050 to 2550: align the side of the lifting tool with the oil-level guage (26). G005056 • Torque 40 ±4 Nm Put the pull-through cord (12) through the box-spanner (13). G004680 4. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 45 5. Apply Molykote Multilube to the thread on the pull-through cord (12), and then connect it to the draw rod. G004686 NOTE! Or use a lubricant with equal properties to Molykote Multilube. Remove the M16 nut (10). 7. With a soft cloth, carefully clean the bottom end of the bushing, and the inside of the center hole. Look for damage. 8. Pull down the upper draw rod (1) from the bottom end of the bushing. G005040 G003055 6. 46 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Remove the transport cover (13) from the transformer (11) and the lower draw rod (4). 10. Lift the bushing to a position above the installation opening on the transformer. G005041 9. End of instruction 4.7.2 Installation of the bushing on the transformer at site Procedure 1. Apply locking fluid on the threads (8) on the lower draw-rod (4). • If the bottom contact is removed from the lower draw-rod (4): apply locking fluid on the threads (20). Make sure that the guiding cone (21) is in position. NOTE! Use thread-locking fluid grade 42 and activator grade 47. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 G005042 CAUTION! Make sure that all joints in the draw rod are locked with thread-locking fluid. 47 Connect the upper draw-rod (1) to the lower draw-rod (4). 3. Make sure that the joint is correctly threaded: G005038 2. 1. Measure the distance H and compare it to the nominal distance H. 2. Calculate the nominal distance: H = L5 - 25 mm(± 2 mm). Refer to the rating plate for the distance L5. G006282 NOTE! When the joint is correctly threaded, 2 threads on the upper (7) and lower (8) threads are visible. If the bushing has the small bottom contact, then install the end shield: 1. Push the end shield carefully against the pressing ring (17), until the hex screw heads comes through the holes in the end shield. 2. Turn the end shield approximately 20°, to its locked position. G005039 4. 48 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 5. Hold the pull-through cord (12) in tension, while lowering the bushing onto the transformer. CAUTION! Do not damage the stud bolts. There is a risk of metal falling into the transformer. G003058 NOTE! Plastic sleeves put on two or three of the stud bolts will help to guide the flange, and will prevent damage to the stud bolts. If the bushing is installed in a non vertical position: • For GOE 250 to 950: the sight glasses (25) must be perpendicular to the angle of the bushing. • For GOE 1050 to 2600: the oil-guage (26) must point down. G006197 6. 7. Install the nuts and washers. Tighten the nuts in a crosswise sequence. CAUTION! Make sure that the nuts are tightened evenly. G005043 First tighten all nuts to half the torque, then to the full torque. Torque Please refer to the transformer documentation. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 49 Install the draw-rod nut (10): 1. Apply a generous quantity of Molykote Multilub to the nut (10), and the threads of the draw rod. 2. Install the washer (11) and nut (10) on the draw rod, tighten with your fingers. 3. Remove excess Molykote Multilub with a rag. CAUTION! If the nut (10) is not lubricated correctly, it will not be tighten to the correct torque. This can cause the bushing to fail. G004300 8. CAUTION! Make sure that the centering ring (28) is in position. It is necessary for the correct installation of the draw rod. Tighten the draw-rod nut (10). G005061 9. Torque 10 Nm Remove the bolts (6), washers (7) and lifting gear (1). 11. Remove the pull-through cord (12). G004679 10. 50 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 12. Tighten the draw-rod nut, refer to Hydraulic tightening of the draw-rod nut, page 51, orManual tightening of the draw-rod nut, page 55. End of instruction 4.8 Hydraulic tightening of the draw-rod nut G005065 Overview 8 Hydraulic jack 10 Draw-rod nut Procedure 1. Measure the distance (a). G005049 NOTE! The bushing is delivered with an information sheet that specifies the draw-rod extension (b-a). These values are measured when the bushing is manufactured, and are unique to every unit. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 51 Install the shaft (16) on the draw rod (1), and put the box-spanner (12) on the shaft (16). 3. Make sure that more than 10 mm of the threads on the upper draw rod (1) are used. 4. Put the hydraulic jack (8) on the shaft (16), and install the nut (17) but do not tighten it. 5. Pull the draw rod with 40 kN. G005147 G005066 G004873 2. DANGER! Apply the hydraulic pressure carefully. Incorrectly used high pressure hydraulics can break with explosive force. NOTE! It is not necessary to compensate for variations in ambient temperature. 6. 52 Turn the nut on the upper draw rod (1) with the box-spanner, tighten with your hand. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Loosen the nut (17). 8. Turn the shaft (16) counter clockwise to remove the shaft-socket from the upper draw rod (1). 9. Remove the hydraulic jack (8) from the bushing. G005068 G005067 7. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 53 10. Make sure that the draw-rod extension is within the tolerances: 1. Measure the distance (b). 2. Calculate the extension of the draw rod: (b) minus (a). 3. Compare the calculated draw-rod extension to the measured extension, refer to the table. 11. Type Extension GOE 250 - 210 3.5 mm ±1.0 GOE 380 - 300 3.5 mm ±1.0 GOE 650 - 500 5.0 mm ±1.0 GOE 950 - 650 7.0 mm ±2.0 GOE 1050 - 750 9.0 mm ±2.0 GOE 1175 - 850 9.5 mm ±2.0 GOE 1300 - 1050 12.0 mm ±2.0 GOE 1425 - 1150 12.0 mm ±2.0 GOE 1550 - 1175 15.0 mm ±2.0 GOE 1675 - 1300 15.0 mm ±2.0 GOE 1800 - 1360 15.0 mm ±2.0 GOE 2550 - 1600 18.0 mm ±2.0 GOE 2550 - 1675 18.0 mm ±2.0 G005050 NOTE! Please contact ABB for special bushings. Measure the value (c), record it for future reference. G006303 Keep the document with the substation documentation. End of instruction 54 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 4.9 Manual tightening of the draw-rod nut Overview This procedure requires the draw-rod nut, washer and threads of the draw rod to be correctly lubricated. The draw rod will not get the correct tension if the fasteners are not correctly lubricated, this can cause the bushing to fail. If possible, ABB recommends that the draw rod is hydraulically tightened, refer to Hydraulic tightening of the draw-rod nut, page 51. Procedure Make sure that the draw-rod nut, and threads of the draw rod are correctly lubricaded, and that the draw-rod nut is tightened to 10 Nm. 2. Measure the distance (a). G005049 1. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 55 3. Turn the nut clockwise until you get the the correct extension (b). Distance (b) = (a) + extension, refer to the table. CAUTION! Make sure that you do not overtighten the nut. Use a torque wrench set to 140 Nm. Type Extension GOE 250 - 210 3.5 mm ±1.0 GOE 380 - 300 3.5 mm ±1.0 GOE 650 - 500 5.0 mm ±1.0 GOE 950 - 650 7.0 mm ±2.0 GOE 1050 - 750 9.0 mm ±2.0 GOE 1175 - 850 9.5 mm ±2.0 GOE 1300 - 1050 12.0 mm ±2.0 GOE 1425 - 1150 12.0 mm ±2.0 GOE 1550 - 1175 15.0 mm ±2.0 GOE 1675 - 1300 15.0 mm ±2.0 GOE 1800 - 1360 15.0 mm ±2.0 GOE 2550 - 1600 18.0 mm ±2.0 GOE 2550 - 1675 18.0 mm ±2.0 G005050 NOTE! One turn of the nut corresponds to a 2 mm extension of the draw rod. 4. Make sure with a torque wrench that the nut is tightened with a torque of more than 70 Nm and less than 140 Nm. 5. Measure the value (c), record it for future reference. G006303 Keep the document with the substation documentation. End of instruction 56 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 4.10 Oil-filling Overview Start this procedure when the transformer oil has reached the bottom of the bushing. This procedure is applicable to bushings that are installed in a position that is 0° – 60° from vertical. This procedure is NOT applicable if the transformer is oil-filled with the vacuum process. G006522 • • Procedure 1. Make sure that the transformer oil-level is maximum 30 mm from the flange. G006300 CAUTION! A lower oil-level will decrease the cooling of the bushing, and can cause spontaneus flashover. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 57 2. Wait until the oil-level (h) in the center-tube has risen to the same height as the oil-level in the transformers oil-conservator. • If the top of the bushing is lower than the transformers oil-conservator, wait until oil flows out from top of the bushing. G004522 NOTE! Air is soluble in transformer oil, thus as much as possible must be released from the bushing center-tube. End of instruction 4.11 Installation of the outer terminal Procedure 1. Prepare the contact surface and gasket surface: 1. Carefully clean the contact surface and gasket surface with a soft cloth. 2. Apply Vaseline to the contact surface. 3. Apply Mobilgrease 28 to the gasket surface. G000403 CAUTION! Do not use a wire brush on the zinc coating (9). 58 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 2. Prepare the contact surface, gasket surface and O-ring: 1. Carefully clean the contact surface and gasket surface with a soft cloth. 2. Apply Vaseline to the contact surface. 3. Apply Mobilgrease 28 to the gasket surface and O-ring (3). NOTE! Or use lubricants with equal properties to Vaseine and Mobilgrease 28. G006465 CAUTION! Do not use a wire brush on aluminium outer terminals. A wire brush can make scratches in the zinc coating (9). NOTE! When the outer terminal (5) is installed at site for grid operation, replace the used O-ring (3) with a new O-ring. A new O-ring is supplied with the bushing. Assemble the tightening ring (4), the O-ring (3), and the outer terminal (5). 4. Apply Molykote Multilub to the threads of the M8 bolts (1). 5. Install the M8 bolts (1), and the spring washers (2). G005055 3. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Torque Tighten with your fingers. 59 Apply Molykote Multilub to the M10 bolts (6). 7. Install the M10 bolts (6) and plain washers (7). 8. Tighten the M10 bolts (6) in a crosswise sequence. G004690 6. G003053 CAUTION! Make sure that the outer terminal moves straight down. Turn each bolt a little, and then the next bolt, until all bolts can be tightened to the correct torque. Torque 40 ±4 Nm 9. Tighten the M8 bolts (1). G004684 Tighten the bolts in a crosswise sequence. Torque 20 ±2 Nm 10. Install the external connections. Refer to the documentation from the supplier of the external connection. End of instruction 60 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 4.12 Grounding of the bushing flange Overview The bushing flange must be grounded to the transformer tank. This prevents electrical discharge between the bushing flange and the transformer tank under normal service conditions. There are two alternatives. DANGER! Make sure that the grounding is correct. An unsatisfactory grounding can cause damage to equipment, or death to personnel. Procedure with a cone point set screw 1. Apply a large quantity of Mobilgrease 28 to the cone point set screw (13). CAUTION! The quality of the cone point set screw is important, stainless steel of A4-80 quality is recommended. G005044 NOTE! Or use a lubricant similar to Mobilgrease 28. 2. Install the cone point set screw (13). NOTE! The cone point of the set screw penetrates the paint. This makes an electrical connection between the bushing and the transformer tank, keeping them at the same potential. Torque M12: 40 Nm End of instruction Procedure with a flexible cable 1. Clean the contact surfaces. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 61 Put a flexible cable (14) between the grounding hole in the bushing flange and a grounding point on the transformer. 3. Apply a large quantity of Mobilgrease 28 to the bolt (13). G005045 2. CAUTION! The quality of the bolt is important, stainless steel of A4-80 quality is recommended. NOTE! Or use a lubricant similar to Mobilgrease 28. 4. Install the bolt (13). 5. Connect the other end of the flexible cable (14) to the transformer. Torque M12: 40 Nm NOTE! This makes an electrical connection between the bushing and transformer tank, keeping them at the same potential. End of instruction 62 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 5 Commissioning 5.1 Waiting time before energization General requirements for the bushing • • • If the bushing has been stored in the vertical position with the top end upwards, then no waiting time is required. If the bushing has been stored in the horizontal position, or in an inclined position of 7°, then air bubbles must be removed from the oil before it can be energized. Refer to the table. The waiting times can be met with the bushing installed on the transformer. When the bushing is in the vertical position, air bubbles that are trapped in the oil collects at the top. Storage time in the horizontal position Minimum required waiting time in the vertical position Before service voltage application Before test voltage application Less than one year 12 hours 24 hours More than one year 7 days 7 days and 12 hours CAUTION! If you do not obey this procedure, flashovers or partial discharges can occur inside the bushing. Waiting times after oil-filling of the transformer Some waiting time is necessary after the transformer has been oil-filled, before the bushing is energized. The reason for this is that air bubbles stick to the bushings surface when the transformer is filled with oil, and flashovers and partial discharges can form in the bubbles. Thus, it is important to let the necessary waiting time pass, to make sure that all the air bubbles have risen to the surface of the oil before the bushing is energized. Refer to the table. The transformer is oil-filled with Necessary waiting time The vacuum process No waiting time is necessary, air bubbles does not form in vacuum. Refer to the transformer manuafacturers instructions. Gas-saturated transformer oil After the oil-filling process has been completed, wait for 24 hours before energizing the transformer. De-gassed transformer oil After the oil-filling process has been completed, wait for 6 hours before energizing the transformer. A reduced oil-level After the oil-level has been restored, wait 24 hours before energizing the transformer. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 63 5.2 Recommended test before energization 5.2.1 Overview The tests should be done to check the insulation, sealing and current path of the bushing. NOTE! The tests should be done after installation, but before connecting the outer terminal of the bushing to the power circuit. 5.2.2 Tightness test between transformer and bushing flange Several different methods can be used and we thus refer to the instructions given by the company responsible for field erection. As an example, the tightness of the seal between the transformer and the bushing flange can be checked when the transformer is oil-filled by using chalk or, perhaps easier, with paper strips. 5.2.3 Tightness test of bushing outer terminal Overview Because the outer terminal is often situated above the oil level of the transformer oil expansion system, a leak at the outer terminal is serious. Water could enter directly into the transformer insulation. It is thus recommended to do a tightness test after installation of the bushing, both with vacuum and pressure. Different methods can be used, and ABB refers to the instructions given by the company responsible for the field erection of the bushing. Example procedure 1. Put tracer gas into the center tube before installation of the outer terminal. NOTE! The oil level of the transformer must be above the bottom end of the bushing, but below the bushing flange. 2. 64 Increase the oil level to just below the bushing flange, to raise the pressure in the center tube. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Find leaking gas with gas detector (sniffer) near the gasket. G005046 3. End of instruction 5.2.4 Measurement of capacitance and dissipation factor Overview After installation of the bushing, it is recommended to measure the capacitance values for future reference, such as repairs, service etc. This can be done on an installed bushing because it has an insulated test tap. Refer to 2750 515-142, “Bushing diagnostics and conditioning”. • C1 is the capacitance between the test tap and the outer terminal. • C2 is the capacitance between the test tap and ground. Nominal capacitance The capacitance (C2) depends on the transformer, and it is not possible to give a nominal value that is valid for all service conditions. Thus, it is important to measure and record the capacitance (C 2) for future reference, such as repairs, service etc. Type Space for CT = 305 mm Space for = CT 605 mm C1 C2* C1 C2* GOE 250-210 448 290 594 480 GOE 380-300 448 290 594 480 GOE 650-500 392 300 498 480 GOE 950-650 377 658 466 790 GOE 1050-750 383 390 450 590 GOE 1175-850 420 480 490 840 GOE 1300-1050 536 640 570 896 GOE 1425-1150 536 640 570 896 GOE 1550-1175 500 700 512 700 GOE 1675-1300 500 700 512 700 GOE 1800-1360 500 700 512 700 GOE 2550-1600 558 4610 560 4820 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 65 Type GOE 2550-1675 Space for CT = 605 mm Space for CT = 905 mm C1 C2* C1 C2* 610 5000 660 5700 * Reference values from ABB Components. Dissipation factor, tan δ The dissipation factor varies with the temperature of the bushing body, and thus the measured dissipation factor must be multiplied with the correction factor given below. Bushing body temperature °C Correction factor to 20 °C (IEC) 3-7 0.85 8-12 0.90 13-17 0.95 18-22 1.00 23-27 1.05 28-32 0.10 33-37 1.15 38-42 1.20 43-47 1.25 48-52 1.30 Procedure 1. De-energize the transformer. 2. Disconnect the external connections from the outer terminal of the bushing. 3. Remove the cover (2). Article number Cover 2769 522-M O-ring 1ZSC004442-CAK G005047 Part 66 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Connect the measuring equipment. 1. Connect the low voltage cable to the stud (1). 2. Connect the high voltage cable to the outer terminal. 3. Connect the ground cable to the bushing flange (3). G005048 4. 5. Measure the capacitance (C1) between the outer terminal and the stud (1). NOTE! Refer to the table for the nominal capacitance (C1), Nominal capacitance, page 65. 6. Measure the capacitance (C2) between the stud (1) and the flange (3). • 7. Record the capacitance (C2) for future reference. Install the cover (2). CAUTION! The test tap is not self-grounding! The bushing can be destroyed if the test tap is not grounded. Because the capacitance (C2) is usually relatively small, the test tap must never be open-circuited when applying a voltage to the bushing. It must always be grounded or connected to an external impedance. CAUTION! Do not energize the bushing without the cover or a test adapter installed. The cover connects the outermost conductive foil to ground and will prevent damage to the bushing. CAUTION! Make sure that the cover is correctly installed with the O-ring in place, when the bushing is not in use. The purpose is to prevent dust and water from entering the tap. 8. Connect the outer terminal of the bushing to the external connections. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 67 5.2.5 Measurement of through-resistance Overview The method to use for measuring the through-resistance depends on the design of the transformer. In general, a current is applied from bushing to bushing. The voltage drop from the outer terminal to outer terminal is measured. The resistance is calculated with Ohm's law, R=U÷I. (R: total circuit resistance, U: measured voltage drop, I: through-current). The total through-resistance is the sum of the transformer winding, lead resistance, the bushing conductor, and contact resistance. The additional resistance from the bushing conductor should not be more than 150 μΩ. Because the through-resistance of the HV winding of a typical power transformer is in the order of 0.1 to 1 Ω, this is a very rough method that can only be used to detect very large faults in the current path, such as open circuits. Small faults in the current path can only be detected by making sensitive measurements across each connection point, or by measuring the temperature increase during operation with an infrared sensitive camera (thermovision). The through-resistance of an installed bushing can only be measured from the outer terminal of one bushing, to the outer terminal of the other bushing on the same transformer winding. The through-resistance will include the resistance of both bushings, all connections and the transformer winding. Do the measurement of through-resistance before connecting any of the external circuits. Because the result of the measurement depends on the temperature and the accuracy with which the temperature can be measured, this can be a source of errors. Procedure 1. Record the temperature of the transformer winding. NOTE! The resistance of metals depends on their temperature. Because the transformer winding usually dominates the total resistance, the average winding temperature at the time of measurement must be recorded. 2. Measure the through-resistance from outer terminal to outer terminal. 3. Calculate the measured resistance to the reference temperature. Then compare the calculated resistance to the reference resistance. A difference of less than 2% is acceptable. NOTE! The transformer manufacturer gives the reference temperature for through-resistance measurements. 4. 5. If the calculated difference of resistance is more than 2% from the reference resistance: 1. Make sure that the external connections have low resistance, and make sure that the outer terminal and the internal connections are correctly installed. 2. Measure the through-resistance again. If the calculated difference of resistance again is more than 2%: • Wait 24 hours and do steps 1 through 5 again. End of instruction 68 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 6 Maintenance 6.1 Recommended maintenance General The bushings are maintenance free, no regular maintenance is necessary. DANGER! Risk of electrocution! Do not go near the bushing while it is energized, or ungrounded. High voltages can kill you. Make sure that the bushing is de-energized, and grounded before you do work on it. Cleaning of the insulator surface If the insulator shed is exposed to very high pollution, it can be necessary to clean the surface. Remove the pollution with a moist cloth, or a low pressure water jet. If necessary, put isopropyl alcohol on the cloth. DANGER! 1,1,1 -Trichloroethane or Methyl-chloride are not recommended as detergents, because they are dangerous to persons and the environment. G003060 CAUTION! Do not wash the insulator sheds with a high pressure water jet. This can cause damage to the joints in the insulator shed, and between the insulator shed and metal parts. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 69 Measurement of capacitance and dissipation factor Please refer to Measurement of capacitance and dissipation factor, page 65. Thermovision (infrared camera) check for local overheating on connectors At the maximum rated current, the bushing outer terminal normally operates at a temperature of about +35 °C to +45 °C above the ambient temperature. Significantly higher temperatures can be a sign of bad connections, especially at lower current loading. Checking of oil leakage Make a visual inspection for oil leakage during regular station supervision. Checking of oil-level The oil-level at normal and high temperatures, must always be above the red area on the oil-level indicator. If the oil-level is in the red area (10), clean and dry transformer oil must be added. For the correct oil-level, please contact ABB. Adding oil is only allowed when the temperature of the bushing is between +5 °C and +35 °C. G005057 CAUTION! Be careful when the oil plug is removed, contamination can enter the bushing. Use a new gasket with the oil plug (9). Tighten the oil plug (9) to 20 Nm. CAUTION! Make sure that the oil plug is correctly installed, and that there is no leakage. 70 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 Taking oil-samples Taking oil samples is generally not recommended. G000400 Take an oil sample only if a problem is known, for example a high power factor over C1, or visible oil leakage. Please refer to product information 2750 515-142 "Bushing diagnostics and conditioning". Take the oil sample from the oil valve (8) in the flange, and close the oil valve (8). CAUTION! Make sure that the oil valve (8) is correctly closed. NOTE! It is generally not necessary to add oil after an oil sample is taken. But it can be necessary to add oil when many oil samples have been taken. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 71 72 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 7 Re-packing 7.1 Removal of horizontally installed bushings Overview This procedure applies to bushings that are connected to the transformer oil-system. It is important to remove a small quantity of transformer oil to make space for thermal expansion. Procedure Remove the bushing from the transformer, refer to Removal of the bushing from the transformer, draw rod, page 74. 2. Drain a small quantity of transfomer-oil. 3. Install the covering plate (1) and the gasket over the oil-passage. G003036 1. Torque M12 50 ±5 Nm 4. Put the bushing in the vertical position. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 73 Remove the oil-plug (9). 6. Remove transformer oil until the oil-level is correct for storage. G006353 5. CAUTION! Make sure that the oil level is correct. If not, changes in the ambient temperature will cause damage to the seals in the bushing. NOTE! The correct oil-level is between the sight-glasses. 7. Install and tighten the oil-plug (9). Use a new gasket. Gasket part number: 2152 899-132 CAUTION! Use only a gasket that is made from nitrile rubber, with a hardness of 70 shore. Other materials will cause oil-leakage. End of instruction 7.2 Removal of the bushing from the transformer, draw rod Procedure 1. 74 Install the lifting tool, refer to Lifting the bushing, page 20. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 2. Put the pull-through cord (12) through the box-spanner (13). NOTE! ABB Components recommends that the hydraulic jack is used for the removal of the bottom contact, refer to Removal of the lower draw rod with bottom contact from the bushing , page 32 steps 1 through 8. 3. G004924 NOTE! The terminal on the pull-through cord (12) has M8 threads. Apply Molykote Multilub to the thread on the pull-through cord (12), then connect it to the draw rod. G004686 NOTE! Or use a lubricant with equal properties to Molykote Multilub. Remove the M16 nut (10) on the draw rod with the box spanner (13). G003055 4. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 75 Remove the nuts and washers. 6. Lift the bushing from the transformer. G005053 5. G006428 CAUTION! Do not damage the stud bolts, there is a risk of metal falling into the transformer. 7. Disassemble the draw rod at the lower joint (8). Use the key grip on the lower draw rod. DANGER! Make sure that the upper draw rod does not fall down when the lower joint (8) is disassembled. NOTE! The bushing can have an optional joint, or the bottom contact unlocked (20), refer to the specifications for your bushing. G005033 NOTE! The upper thread (7) is locked with thread-locking fluid grade 42. The guiding cone (21) is loose. 76 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 8. Pull up the draw rod, and install the washer (11) and nut (10). G004300 CAUTION! Make sure that the centering ring (28) is in position, it is necessary for the correct installation of the draw rod. 9. Remove the pull-through cord (12). 10. Lower the bushing to the floor. CAUTION! Make sure that there is soft bedding, or support blocks on the floor. Install the lower draw rod (4) in the transport cover (13). 12. Install the transport cover (13) on the transformer turret (11). G004681 11. End of instruction Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 77 7.3 Re-packing of the bushing G001910 Overview Procedure 1. Put plastic wrap on the draw-rod, and attach it to the transport box. CAUTION! Do not put the draw rod into the bushing, the threads on the draw rod will scratch the inside of the center-tube conductor. 2. Lift the bushing. Refer to Lifting the bushing out of the transport box, page 17. 3. Lower the bushing into the transport box. CAUTION! Make sure that the there is soft bedding in the transport box. CAUTION! Make sure that the oil valves and test tap does not make contact with the transport box, or other objects. 4. Attach the bushing to the transport box in the same way as when it was delivered. CAUTION! Make sure that the bushing cannot move or rotate in the transport box. 5. Close the transport box. NOTE! Refer to Lifting the transport box, page 16 and Transportation, page 15. End of instruction 78 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 8 Spare parts and special tools 8.1 Summary If the bushing is damaged, we recommend that it is returned to ABB for repairs and re-testing. Some parts that are damaged or lost during transportation or installation, can be ordered from ABB. 8.2 Spare parts Cover For the test tap. Part Article number Note 1 Cover 1ZSC004579-AAA - 2 O-ring 1ZSC00442-CAK - G006192 Position Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 79 Oil-plug 2522 731-A Part Article number Note 1 Oil-plug 2121 738-18 - 2 Gasket 1ZSC001591-AAC - G006193 Position Cover for oil-plug 2522 731-A For new design of the top chamber. This cover gives protection to the oil-plug 2522 731-A. Article number Note 1 Cover 2522 732-42 M24 2 Gasket 2152 795-67 - G006277 Position Part 80 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 8.3 Special tools Lifting tool Article number Note Lifting tool 9760 668-A - Part Article number Note Pull-through cord 9760 669-A With M8-terminal. G006196 Part G006198 Pull-through cord Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 81 Hydraulic jack Article number Note Hydraulic jack PDV2330 - Part Article number Note Box-spanner 9760 669-B - G006275 Part G006276 Box-spanner 82 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 9 Disposal and environmental information 9.1 Overview This chapter specifies the materials used in the bushing. Comply with local environmental regulations on disposal of this product, the materials used are specified for this purpose. 9.2 Disposal and recycling ABB strives to minimize the product's impact on the environment throughout its entire life cycle. Technical and product development focuses on environmental aspects. The ecocycle approach is striven for, and consideration is taken to the materials' environmental impact and recycling alternatives. The manufacturing processes are selected to be as safe for the environment as possible. Disposal of worn-out equipment Worn-out equipment must be disposed of in an environmentally sound manner. Much of the material, or the energy content in the material, can be recycled if it is sorted and cleaned. The quantity of material that can be recycled varies depending on the technical resources and capabilities in each country. Non-recyclable components should be sent to an approved environmental waste treatment plant for destruction or disposal. DANGER! Be careful when dissembling the bushing. There is a large quantity of mechanical energy stored in the bushing from its assembly, disassembly of the bushing can cause it to break with explosive force. The bushing has these parts and materials • • • • • • • • The conductor is made of copper or low-alloy aluminum. The terminals are made of copper or low-alloy aluminum. The terminals can be plated with silver, tin, gold or nickel, with a thickness up to 20 μm. Transformer oil, refer to IEC 60296, class 2. The condenser core is made of paper and 1 % aluminum foil, impregnated with transformer oil. The top housing, top end nut, test tap and flexible connection are made of aluminum alloys. The flanges are made of aluminum. The press ring for the oil-level sight glass is made of plated brass. The oil-level sight glass is made of glass. The insulators are made of quartz-silicate or alumino-silicate based porcelain. Porcelain After cleaning, the porcelain can be sent for disposal or used for other purposes, such as for use as filling material. Electronics Electronics equipment should be sent to an approved recycling plant, or sorted into different component materials for correct processing. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 83 Metals Metals should be sorted according to type and surface coating, and sent to an approved recycling plant. After the removal of paint or other surface coatings, clean metal can usually be melted down and used in new products. Many metal components of iron, steel and aluminum are large and easy to identify, e.g. support structures. ABB strives to reduce the use of precious metals and the release of environmentally hazardous metals. The recycling of precious metals is particularly important. Metals such as copper and silver are expensive, and are only present in small quantities in the earth's crust. Copper is primarily used in current conductors, contacts and cables. Some contacts are silver plated. Fumes from some metals can cause environmental damage, this applies to zinc and nickel, which are used sparingly as surface coatings. Plastics The different types of plastic should be separated and sent to an approved environmental waste treatment plant or recycling plant. The energy content in thermoplastics and thermosetting plastics can often be recovered through combustion at a plant built for the purpose. Thermoplastics can usually be melted down and reused without significant loss of quality. Composites can be fractioned and used as filling materials in other materials, or be disposed of. Oils and greases Before disposal of the bushing, oil, grease and similar products must be removed and sent to an approved environmental waste treatment plant or recycling plant. By utilizing gravimetric forces, oil waste can be separated into oil, water and a range of contaminants. In many cases, the oil can then be reused. As an alternative, the energy content in oil can be recovered through combustion at a plant designed for the purpose. Rubber Send rubber to an approved environmental waste treatment plant, either for disposal or reuse for different purposes. Rubber is used in seals and gaskets. Other materials Sort other materials and send them to an approved environmental waste treatment plant. 84 Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 10 References 10.1 Summary • • • • Markings: Conforming to IEC/IEEE. Bushing diagnostics and conditioning, 2750 515-142. Test adapter, Installation and maintenance guide, 1ZSC000563-ACD. Transformer oil, IEC 60296, class 2. Installation and commissioning guide 2750 515-1 EN, REV. 13, 2019-05-22 85 ABB AB, Components SE-771 80 Ludvika, Sweden © Copyright 2019 ABB, All rights reserved. Specifications subject to change without notice. 2750 515-1 EN, REV. 13, 2019-05-22 www.abb.com/transformercomponents 2750 515-115 EN, REV. 7, 2019-08-12 Transformer bushing, type GSA-OA Installation and maintenance guide The information contained in this document may be subject to change without prior warning and should not be considered as binding on ABB AB’s behalf. ABB AB accepts no liability for any errors that may appear in this document. ABB AB is not liable for any damage resulting from the incorrect interpretation of this document. This document, or parts thereof, may not be reproduced or copied without ABB AB’s consent. It may not be distributed to others, or used by unauthorized parties. Any breaches to the above will be penalized with the support of applicable laws. Contents 1 2 3 4 Safety Levels of safety risks ................................................................................................................................................................... 5 1.2 Hazardous working situations ..................................................................................................................................................... 6 1.3 Safety precautions....................................................................................................................................................................... 6 Product description Design ......................................................................................................................................................................................... 7 2.2 Technical specifications ............................................................................................................................................................... 10 2.2.1 General specifications ............................................................................................................................................... 10 2.2.2 Mechanical loading.................................................................................................................................................... 12 Delivery Incoming inspection..................................................................................................................................................................... 13 3.2 Transportation ............................................................................................................................................................................. 13 3.3 Storage ........................................................................................................................................................................................ 13 3.4 Lifting ........................................................................................................................................................................................... 14 3.4.1 Lifting the transport box ............................................................................................................................................. 14 3.4.2 Lifting the bushing out of the transport box ............................................................................................................... 15 Installation 17 4.1 Tools ............................................................................................................................................................................................ 17 4.2 Consumables .............................................................................................................................................................................. 17 4.3 Preparations ................................................................................................................................................................................ 18 Lifting the bushing ..................................................................................................................................................... 18 Installation on the transformer ..................................................................................................................................................... 20 4.4.1 Installation with draw lead ......................................................................................................................................... 20 4.4.2 Installation with solid-rod conductor .......................................................................................................................... 24 4.4.3 Oil-filling..................................................................................................................................................................... 30 4.4.4 Installation of the outer terminal ................................................................................................................................ 31 4.4.5 Grounding of the bushing flange ............................................................................................................................... 34 Commissioning 37 5.1 Waiting time before energization ................................................................................................................................................. 37 5.2 Recommended tests before energization.................................................................................................................................... 37 5.2.1 Overview ................................................................................................................................................................... 37 5.2.2 Tightness test between transformer and bushing flange........................................................................................... 37 5.2.3 Tightness test of bushing outer terminal.................................................................................................................... 38 5.2.4 Measurement of capacitance and dissipation factor ................................................................................................. 38 5.2.5 Measurement of through-resistance.......................................................................................................................... 42 Maintenance 6.1 7 13 3.1 4.3.1 6 7 2.1 4.4 5 5 1.1 Re-packing 7.1 45 Recommended maintenance ...................................................................................................................................................... 45 47 Re-packing of the bushing........................................................................................................................................................... 47 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 3 8 9 4 Spare parts 49 8.1 Summary ..................................................................................................................................................................................... 49 8.2 Spare parts .................................................................................................................................................................................. 49 8.3 Special tools ................................................................................................................................................................................ 50 Disposal and environmental information 51 9.1 Overview ..................................................................................................................................................................................... 51 9.2 Disposal and recycling ................................................................................................................................................................ 51 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 1 Safety 1.1 Levels of safety risks Throughout the manual, various types of safety risks are indicated. The most serious level on this scale provides a warning about serious personal injury or possible death, or major damage to a product, if the instructions are not observed. Symbols and their meanings The following describes the symbols that appear in the manual, along with their meaning. DANGER! The yellow, filled warning triangle warns that an accident will occur if the instructions are not complied with and that it will result in serious personal injury or death and/or major damage to the product. It is used, for example, to warn of such dangers as: contact with high voltage, explosion or fire risk, risk for toxic gases, risk of crushing, impacts, falls from high places, etc. CAUTION! The round warning symbol warns that an accident could occur if the instructions are not observed, and that this could result in personal injury and/or damage to the product. It is also used to warn of risks that entail burns, eye or skin injuries, impaired hearing, crushing or slipping injuries, tripping, impacts, falls from high places, etc. In addition, it is used to warn of functional requirements when assembling or removing equipment where there is a risk of damage to the product or downtime. NOTE! The comment symbol identifies important information and conditions. Also used to indicate any danger that could lead to property damage. Torque The torque symbol indicates tightening torque. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 5 1.2 Hazardous working situations Hazard Action Working close to high voltage. Disconnect all plant power. Ground all objects at the workplace. If work must be done close to live plant components, make sure that the safety distance is in compliance with the applicable safety regulations. Working on ladders and platforms. Work must be done in accordance with the applicable safety regulations. Do not use ladders or platforms in poor weather conditions. Working with heavy objects. Do not walk under lifted objects. Make sure that heavy objects are stable before starting work. 1.3 Safety precautions Precaution Action Transformer oil Collect used transformer oil in drums. Transformer oil is dangerous. Fumes from hot oil can cause irritation to the respiratory organs and the eyes. Long and repeated contact with transformer oil can cause damage to your skin. 6 Waste and cleaning up Clean up liquid waste with an adsorbent. Treat waste as hazardous to the environment. Fire Extinguish fires with powder, foam or carbon dioxide. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 2 Product description 2.1 Design Overview The GSA type is a transformer bushing. It is made for immersed oil to air service. The bushing is of the dry, gas-free type, with a resin impregnated paper RIP condenser core as the primary insulation, and silicone rubber (SiR) sheds as outdoor insulation. Bushings of this design can be installed at any angle from vertical to horizontal. For a detailed description, please refer to the Technical guide, 1ZSE 2750-111. G000128 General schematics 1 Outer terminal 2 Outdoor insulator (SiR) 3 Mounting flange 4 RIP condenser core 5 Conductor 6 Test tap Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 7 Test tap The bushing has a test tap that is connected to the outermost conductive layer of the condenser core. The test tap is used to measure the bushing insulation by capacitance and dissipation factor. The cover connects the outermost conductive layer to ground, and must always be installed when the bushing is energized. The maximum one minute test voltage for this test tap is 2 kVrms. The test tap can be used as a power source, if it is connected to an external capacitance. The operating voltage is limited to 600 V. G000411 CAUTION! Do not energize the bushing without a test adapter or the cover installed. The bushing is grounded through the cover to prevent damage to the bushing. 1 Stud 2 Grounding spring 3 Cover 4 O-ring Test adapter, 1ZSC003881-AAC, optional equipment G001876 The test adapter 1ZSC003881-AAC is available for permanent connection to measuring circuits. Please refer to Test adapter – Technical guide 1ZSC000563-ACS and Installation and maintenance guide 1ZSC000563-ACD. 8 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Arcing horns, optional equipment Arcing horns are available as optional equipment, they are made of galvanized steel. G004587 Refer to the table for the gap distances (K) of standard arcing horns, other gap distances are available on request. Bushing type K (mm) C (mm) H (mm) GSA 52 230-440 315 112 GSA 73 400-620 315 112 GSA 123 620-960 315 114 GSA 145 700-1080 380 224 GSA 170 820-1290 380 224 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 9 2.2 Technical specifications 2.2.1 General specifications Refer to the table for the standard technical specifications of the bushing. For conditions exceeding the specifications, please contact ABB. 10 Application: Transformers Classification: Tranformer bushing • Resin impregnated paper, capacitance graded, oil immersed. • For outdoor and indoor use. • Temperature class E (120 °C) according to IEC 60137. Ambient temperature limits: -40 °C to +40 °C. Maximum altitude of site: 1000 m (Bushings for other altitudes can be provided on request.) Level of rain and humidity: 1-2 mm rain/minute horizontally and vertically, according to IEC 60060-1 and IEEE Std 4. Maximum pollution level: According to the specific creepage distance, and IEC 60815. Immersion medium: Transformer oil. • Maximum daily mean oil temperature: +90 °C. • Maximum temporary oil temperature, at normal load: +100 °C. • Maximum temporary oil temperature, at short time overload: +115 °C. Oil-level in transformer: Not lower than 25 mm from the bushing flange. Maximum pressure of medium: pg 100 kPa (pg = relative to ambient pressure). Angle of installation: From horizontal to vertical. Test tap: Test tap with 4 mm male contact pin. Capacitance C2 of test tap: <5000 pF Arcing horns: Optional Conductor: Solid-rod conductor or draw lead. Markings: Conforming to IEC/IEEE. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 List of bushings applicable to this installation guide Type GSA-OA 52/2000 GSA-OA 73/2000 GSA-OA 100/1600 GSA-OA 123/1600 GSA-OA 145/1600 GSA-OA 170/1600 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Article number /0 LF 130 052 -BA /0.3 -BB /0.5 -BC /0 LF 130 073 -BA /0.3 -BB /0.5 -BC /0 -DA /0.3 -DB /0 LF130 100 -BA /0.3 -BB /0.5 -BC /0 LF 130 123 -BA /0.3 -BB /0.5 -BC /0 -CA /0.3 -CB /0.5 -CC /0 LF 130 145 -BA /0.3 -BB /0.5 -BC /0 LF 130 170 -BA /0.3 -BB /0.5 -BC /0 -CA /0.3 -CB /0.5 -CC 11 2.2.2 Mechanical loading G004711 Maximum permitted static load on the outer terminals 12 Type Type test load 1 minute (N) Maximum cantilever operating load (N) GSA-OA 52/2000 4000 2000 GSA-OA 73/2000 4000 2000 GSA-OA 100/1600 4000 2000 GSA-OA 123/1600 4000 2000 GSA-OA 145/1600 4000 2000 GSA-OA 170/1600 4000 2000 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 3 Delivery 3.1 Incoming inspection • • Make sure that all items have been delivered, refer to the packing list. Carefully inspect the bushings for shipping damage. 3.2 Transportation • • The bushing must be transported in the transport box. Carefully inspect the bushing for damage after transportation. 3.3 Storage Short term storage, less than 6 months • • • • Make sure that the bushing is wrapped in the original (or equivalent) moisture-proof wrapping. If the drying agent inside the wrapping has been exposed to the atmosphere, replace it. The bushing can be stored outdoors, if it is in the transport box. Keep the transport box protected from water, when the bushing is stored outdoors. Keep the bushing dry, clean and protected against mechanical damage. The bushing can be stored in both the vertical, and horizontal positions. Long term storage, more than 6 months • • • • • • Use a transport container on the oil side of the bushing, this has to be ordered separately. Put drying agent in the transport container. Make sure that the air side of the bushing is wrapped in the original (or equivalent) moisture-proof wrapping. If the drying agent inside the wrapping has been exposed to the atmosphere, replace it. The bushing can be stored outdoors, if it is in the transport box. Keep the transport box protected from water, when the bushing is stored outdoors. Keep the bushing dry, clean and protected against mechanical damage. The bushing can be stored in both the vertical, and horizontal positions. The outer terminal must be installed on the bushing. The bushing is delivered from ABB in a transport box, and the bushing is held in place by support blocks and fiberboard in the box. The transport box is marked with Top end. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 13 3.4 Lifting 3.4.1 Lifting the transport box G000701 Overview 1 Center of gravity 2 Soft lifting slings Procedure 1. Make sure that the crane and the soft lifting slings are approved for the total weight of the transport box and bushing. Refer to the weight in the packing list. 2. Attach soft lifting slings (2). 3. Make sure that the angle of the soft lifting sling is not more than 20°. 4. Carefully lift the transport box. 5. Set down the transport box on a flat surface. End of instruction 14 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 3.4.2 Lifting the bushing out of the transport box G000096 Overview Procedure 1. Make sure that the crane is approved for lifting the weight of the bushing. Refer to the weight on the rating plate. NOTE! Light bushings can be lifted by hand. 2. Open the transport box. NOTE! The cover is attached with bolts. 3. Attach a soft lifting sling to the bottom end housing, as close to the flange as possible, and then to the crane hook. CAUTION! Do not put the soft lifting slings on the silicone insulator, damage will occur. 4. Attach a soft lifting sling to the outer terminal and then to the crane hook. 5. Carefully lift the bushing. 6. Lower the bushing onto soft bedding. End of instruction Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 15 16 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 4 Installation 4.1 Tools Tool Part number Note Lifting tool 2183 789-2 For solid rod conductor Ø 49 mm. Max load 125 kg. Soft bedding - E.g. rubber mat or wood board Soft lifting slings - - Pull-through cord 9760 669-A, -D With M8 terminal. For assembly and disassembly of the draw rod. Torque wrench key for hex socket screws, 16 mm (M10) and 13 mm (M8), torque 20 to 40 Nm. - - Wrench for hex socket screws 30 mm or adjustable wrench for 30 mm bolts or larger. - For the test tap cover. Tackle - For installation of the bushing at a specific angle. 4.2 Consumables Item Brand ABB part number Note Oil based Vaseline Fuchs 1171 5011-102 For treatment of contact surfases. Does not react with transformer oil. Mobilgrease 28 MOBIL 1171 4014-407 Lubricates and protects metals against corrosion. Protects rubber. Does not react with transformer oil. Molykote 1000 Dow Corning 1171 2016-618 For the sealing and lubrication of the contact on the outer terminal. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 17 4.3 Preparations 4.3.1 Lifting the bushing G000217 Overview 1 Lifting tool 2 Soft bedding, e.g. rubber mat or woodboard 3 Lifting eye Procedure 1. Make sure that the crane can lift the bushing. Refer to net weight in the packing list. 2. Loosen the M8 bolts (1). G004717 NOTE! It is not necessary to remove the M8 bolts. 18 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 3. Remove the M10 bolts (4) and washers (5), and then remove the outer terminal (6). G001869 NOTE! Keep the outer terminal (6), nuts (5) and bolts (4), they will be used again. 4. Remove the item (7): 1. Attach the pull-through cord to item (7). 2. Remove item (7) and the divided ring (6). NOTE! Item (7) is the inner terminal, or soild-rod conductor. G006174 NOTE! Keep item (7) and the divided ring (6), they will be used again. 5. Install the lifting tool (1), and install the bolts (7) with the washers (5). G001870 NOTE! The bolts (7) are not supplied with the lifting tool (1), use three M10x20 bolts. Torque 40 ±4 Nm 6. Align the crane hook with the lifting tool on the bushing. 7. Carefully lift the bushing. CAUTION! Make sure that the bushing does not rotate. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 19 8. Lower the bushing onto soft bedding. CAUTION! Make sure that the bottom contact does not come in contact with the ground, or the floor. The bottom contact is made of soft metal. End of instruction 4.4 Installation on the transformer 4.4.1 Installation with draw lead G004712 Overview 20 1 Bushing 2 Inner terminal 3 Draw lead 4 Pull-through cord Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Procedure 1. Solder the draw lead from the transformer windings to the inner terminal G006170 NOTE! As an alternative, the draw lead can be crimped to the inner terminal. Carefully clean the bottom end of the bushing, and the inside of the center hole. Look for damage. 3. Lower the pull-through cord (10) through the bushing. 4. Apply Molykote 1000 to the pull-through cord (10), and attach it to the inner terminal (7). G000098 2. G006849 NOTE! The terminal (7) has M8 threads. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 21 5. Hold the pull-through cord (12) in tension, while lowering the bushing onto the transformer. CAUTION! Make sure that the draw lead is entering the bushing correctly. Monitor the draw lead through the inspection openings on the transformer. G004713 CAUTION! Do not damage the stud bolts on the transformer. There is a risk of metal falling into the transformer. NOTE! Plastic sleeves put on two or three of the stud bolts will help to guide the flange, and will prevent damage to the stud bolts. When installing the bushing at the transformer factory: 1. Make sure that the bushing is installed in the correct orientation. 2. Make permanent markings (16) on the bushing flange and the transformer turret. G006164 6. 7. Install the bolts and washers. Tighten the bolts in a crosswise sequence. • When installing the bushing at site, make sure that the marking (16) on the bushing flange lines up with the marking on the transformer turret. CAUTION! Make sure that the bolts are tightened evenly. G006365 First tighten all bolts to half the torque, then to the full torque. Torque M12 50 ±5 Nm 1/2” UNC 55 ±5 Nm 22 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Put the divided ring (6) in the slot in the inner terminal (7). 9. Carefully lower the inner terminal (7) with the pull-through cord (10) until the divided ring (6) touches the bushing top surface. G004591 8. G004716 NOTE! The divided ring is held in position only by the weight of the inner terminal. Install the outer terminal as soon as possible. Remove the M10 bolts (6), the washers (7), and the lifting tool (1). 11. Continue with Installation of the outer terminal, page 31. G004714 10. End of instruction Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 23 4.4.2 Installation with solid-rod conductor G006166 Overview 1 Bushing 2 Solid-rod conductor 3 Pull-through cord Procedure 1. Loosen the captive screws (11), and disassemble the solid-rod conductor. G004787 NOTE! The captive screws (11) cannot be removed from the upper solid-rod conductor (7). 24 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 2. Solder the winding cables (2) from the transformer to the end of the solid-rod conductor (12). G006175 NOTE! As an alternative, the winding cables can be crimped to the solid-rod conductor. 3. Apply insulation to the winding cables and the lower solid-rod conductor. G006360 NOTE! The insulation must cover the recess in the lower solid-rod conductor. Carefully clean and inspect the oil end (16) of the bushing, and the inside of the bushing. G006167 4. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 25 Lower the pull-through cord (10) through the bushing. 6. Attach the the pull-through cord (10) to the solid-rod conductor (7). 7. Pull up the upper part (7) of the solid-rod conductor until the joining surface (17) is accessible. G006168 G004788 G006165 5. 26 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 8. Clean the contact surfaces (17) on the lower (12) and the upper (7) parts of the solid-rod conductor. Apply Mobilegrease 28 to the contact surfces (17). G006169 NOTE! Or use a lubricant similar to Mobilegrease 28. 9. Connect the upper (7) and lower (12) parts of the solid-rod conductor: 1. Apply Mobilgrease 28 to the threads of the captive screws (11), and the washers. 2. Assemble the solid-rod conductor, and tighten the captive screws (11). G006417 NOTE! Or use a lubricant similar to Mobilegrease 28. Torque 35-40 Nm 10. Hold the pull-through cord (12) in tension, and at the same time lower the bushing onto the transformer. NOTE! Plastic sleeves put on two or three of the stud bolts will help to guide the flange, and will prevent damage to the stud bolts. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 G004713 CAUTION! Do not damage the stud bolts. There is a risk of metal falling into the transformer. 27 When installing the bushing at the transformer factory: 1. Make sure that the bushing is installed in the correct orientation. 2. Make permanent markings (16) on the bushing flange and the transformer turret. G006164 11. 12. Install the bolts and washers. Tighten the bolts in a crosswise sequence. NOTE! When installing the bushing at site, make sure that the marking (16) on the bushing flange lines up with the marking on the transformer turret. First tighten all bolts to half the torque, then to the full torque. G000204 CAUTION! Make sure that the bolts are tightened evenly. Torque M12 50 ±5 Nm 1/2” UNC 55 ±5 Nm Put the divided ring (6) in the slot in the solid-rod conductor (7). G000101 13. 28 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Carefully lower the inner terminal (7) with the pull-through cord (10) until the divided ring (6) touches the bushings top surface. 15. Remove the pull-through cord. 16. Remove the M10 bolts (6), the washers (7), and the lifting tool (1). 17. Continue with Installation of the outer terminal, page 31. G004714 G004716 14. End of instruction Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 29 4.4.3 Oil-filling Overview Start this procedure when the transformer oil has reached the bottom of the bushing. • This procedure is NOT applicable if the transformer is oil-filled with the vacuum process. G006859 The purpose of this procedure is to remove as much air as possible from the center tube of the bushing. Because air is soluble in transformer oil, air will go into the transformer oil and will cause its performance to deteriorate. The amount of air that can be removed depends on the bushings position in relation to the transformers oil-conservator. Oil spillage Oil spillage attracts dirt and this can reduce the performance of the electrical insulation. Large quantities of oil can cause the silicone rubber to expand and deform. Remove oil-spills with paper towels. CAUTION! Do not allow oil that has been in contact with silicone-rubber to enter the transformer. It can contain small amounts of silicone oil that will reduce the surface tension of the transformer oil, this will cause foaming in forced oil circulation. Procedure 1. Make sure that the transformer oil-level is maximum 25 mm from the flange. G006367 CAUTION! A lower oil-level will decrease the cooling of the bushing, and can cause spontaneus flashovers. 30 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 2. Wait until the oil-level (h) in the center-tube has risen to the same height as the oil-level in the transformers oil-conservator. • If the top of the bushing is lower than the transformers oil-conservator, wait until oil flows out from top of the bushing. G004720 NOTE! Air is soluble in transformer oil, thus as much as possible must be released from the bushing center-tube. End of instruction 4.4.4 Installation of the outer terminal Procedure 1. Carefully clean the contact and gasket surfaces with a soft cloth, and then apply Mobilgrease 28. CAUTION! Do not use a wire brush on aluminium surfaces, or zinc coated surfaces. A wire brush can make scratches in the surfaces. 2. Carefully clean the contact and gasket surfaces with a soft cloth, and then apply Mobilgrease 28 to the contact surfaces and the O-ring (3). NOTE! When the outer terminal (5) is installed at site for grid operation, replace the used O-ring (3) with a new O-ring. A new O-ring is supplied with the bushing. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 G006409 NOTE! Or use a lubricant with equal properties to Mobilgrease 28. 31 Assemble the tightening ring (4), the O-ring (3), and the outer terminal (5). 4. Apply Molykote 1000 to the washers (2) and (10), and the threads of the M8 bolts (1). 5. Install the M8 bolts (1), the spring washers (2), and the plain washers (10). 6. Put the outer terminal (5) on the bushing. 7. Apply Molykote 1000 to the washers, and to the threads and the shank of the M10 bolts (2). G000702 3. G000103 Torque Tighten with your fingers. G000105 NOTE! Or use a lubricant with equal properties to Molykote 1000. 8. Install the M10 bolts (2) and plain washers. Tighten the bolts in a crosswise sequence. Torque 40 ±4 Nm CAUTION! Do NOT use an impact driver / wrench! 32 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 9. Prepare the contact surface of the outer terminal for the external connection: 1. Carefully remove oxide with a wire-brush. 2. Clean with a soft cloth. 3. Apply Vaseline. NOTE! Or use a lubricant with equal properties to Vaseline. 10. Install the external connections. Refer to the documentation from the supplier of the external connection. End of instruction Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 33 4.4.5 Grounding of the bushing flange Overview The bushing flange must be grounded to the transformer tank. This prevents electrical discharge between the bushing flange and the transformer tank under normal service conditions. There are two alternatives. DANGER! Make sure that the grounding is correct. An unsatisfactory grounding can cause damage to equipment, or death to personnel. Procedure with a cone point set screw 1. Apply a large quantity of Mobilgrease 28 to the cone point set screw (13). CAUTION! The quality of the cone point set screw is important, stainless steel of A4-80 quality is recommended. G006171 NOTE! Or use a lubricant similar to Mobilgrease 28. 2. Install the cone point set screw (13). NOTE! The cone point of the set screw penetrates the paint. This makes an electrical connection between the bushing and the transformer tank, keeping them at the same potential. Torque M12: 40 Nm End of instruction 34 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Procedure with a flexible cable Clean the contact surfaces. 2. Put a flexible cable (14) between the grounding hole in the bushing flange and a grounding point on the transformer. 3. Apply a large quantity of Mobilgrease 28 to the bolt (13). G006172 G006861 1. CAUTION! The quality of the bolt is important, stainless steel of A4-80 quality is recommended. NOTE! Or use a lubricant similar to Mobilgrease 28. 4. Install the bolt (13). 5. Connect the other end of the flexible cable (14) to the transformer. Torque M12: 40 Nm NOTE! This makes an electrical connection between the bushing and transformer tank, keeping them at the same potential. End of instruction Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 35 36 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 5 Commissioning 5.1 Waiting time before energization Waiting times after oil-filling of the transformer Some waiting time is necessary after the transformer has been oil-filled, before the bushing is energized. The reason for this is that air bubbles stick to the bushings surface when the transformer is filled with oil, and flashovers and partial discharges can form in the bubbles. Thus, it is important to let the necessary waiting time pass, to make sure that all the air bubbles have risen to the surface of the oil before the bushing is energized. Refer to the table. The transformer is oil-filled with Necessary waiting time The vacuum process No waiting time is necessary, air bubbles does not form in vacuum. Refer to the transformer manuafacturers instructions. Gas-saturated transformer oil After the oil-filling process has been completed, wait for 24 hours before energizing the transformer. De-gassed transformer oil After the oil-filling process has been completed, wait for 6 hours before energizing the transformer. A reduced oil-level After the oil-level has been restored, wait 24 hours before energizing the transformer. 5.2 Recommended tests before energization 5.2.1 Overview The tests should be done to check the insulation, sealing and current path of the bushing. NOTE! The tests should be done after installation, but before connecting the outer terminal of the bushing to the power circuit. 5.2.2 Tightness test between transformer and bushing flange Several different methods can be used and we thus refer to the instructions given by the company responsible for field erection. As an example, the tightness of the seal between the transformer and the bushing flange can be checked when the transformer is oil-filled by using chalk or, perhaps easier, with paper strips. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 37 5.2.3 Tightness test of bushing outer terminal Overview Because the outer terminal is often situated above the oil level of the transformer oil expansion system, a leak at the outer terminal is serious. Water could enter directly into the transformer insulation. It is thus recommended to do a tightness test after installation of the bushing, both with vacuum and pressure. Different methods can be used, and ABB refers to the instructions given by the company responsible for the field erection of the bushing. Example procedure 1. Put tracer gas into the center tube before installation of the outer terminal. NOTE! The oil level of the transformer must be above the bottom end of the bushing, but below the bushing flange. Increase the oil level to just below the bushing flange, to raise the pressure in the center tube. 3. Find leaking gas with gas detector (sniffer) near the gasket. G006173 2. End of instruction 5.2.4 Measurement of capacitance and dissipation factor Overview After installation of the bushing, it is recommended to measure the capacitance values for future reference, such as repairs, service etc. This can be done on an installed bushing because it has an insulated test tap. Refer to 2750 515-142, “Bushing diagnostics and conditioning”. • C1 is the capacitance between the test tap and the outer terminal. • C2 is the capacitance between the test tap and ground. NOTE! The transport container must be removed before measuring the capacitance and dissipation factor (tan δ). 38 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Nominal capacitance The capacitance (C2) depends on the transformer, and it is not possible to give a nominal value that is valid for all service conditions. Thus, it is important to measure and record the capacitance (C 2) for future reference, such as repairs, service etc. GSA-OA 52 Article number Space for CT = 0 mm Space for CT = 300 mm Space for CT = 500 mm C1 C1 C1 LF 130 052-BA 215 - - LF 130 052-BB - 417 - LF 130 052-BC - - 543 Space for CT = 0 mm Space for CT = 300 mm Space for CT = 500 mm C1 C1 C1 LF 130 073-BA 325 - - LF 130 073-BB - 512 - LF 130 073-BC - - 636 LF 130 073-DA 303 - - LF 130 073-DB - 460 - Space for CT = 0 mm Space for CT = 300 mm Space for CT = 500 mm C1 C1 C1 LF 130 100-BA 294 - - LF 130 100-BB - 397 - LF 130 100-BC - - 488 Space for CT = 0 mm Space for CT = 300 mm Space for CT = 500 mm C1 C1 C1 LF 130 123-BA 216 - - LF 130 123-BB - 319 - LF 130 123-BC - - 369 LF 130 123-CA 200 - - LF 130 123-CB - 260 - LF 130 123-CC - - 356 GSA-OA 73 Article number GSA-OA 100 Article number GSA-OA 123 Article number Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 39 GSA-OA 145 Article number Space for CT = 0 mm Space for CT = 300 mm Space for CT = 500 mm C1 C1 C1 LF 130 145-BA 233 - - LF 130 145-BB - 326 - LF 130 145-BC - - 386 LF 130 145-CA 254 - - LF 130 145-CB - 417 - LF 130 145-CC - - 400 Space for CT = 0 mm Space for CT = 300 mm Space for CT = 500 mm C1 C1 C1 LF 130 170-BA 311 - - LF 130 170-BB - 404 - LF 130 170-BC - - 467 LF 130 170-CA 312 - - LF 130 170-CB - 404 - LF 130 170-CC - - 467 GSA-OA 170 Article number Dissipation factor, tan δ The dissipation factor varies with the temperature of the bushing body, and thus the measured dissipation factor must be multiplied with the correction factor given below. 40 Bushing body temperature °C Correction factor to 20 °C (IEC) 0-2 0.76 3-7 0.81 8-12 0.87 13-17 0.93 18-22 1.00 23-27 1.07 28-32 1.14 33-37 1.21 38-42 1.27 43-47 1.33 48-52 1.37 53-57 1.41 58-62 1.73 63-67 1.43 68-72 1.42 73-77 1.39 78-82 1.35 83-87 1.29 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 Procedure De-energize the transformer. 2. Disconnect the external connections from the outer terminal of the bushing. 3. Remove the cover (2). 4. Connect the measuring equipment. G000106 1. 5. 1. Connect the low voltage cable to the stud (1). 2. Connect the high voltage cable to the outer terminal. 3. Connect the ground cable to the bushing flange (3). Measure the capacitance (C1) between the outer terminal and the stud (1). • Record the capacitance (C1) for future reference. NOTE! Refer to the table for the nominal capacitance (C1), Nominal capacitance, page 39. 6. Measure the capacitance (C2) between the stud (1) and the flange. • 7. Record the capacitance (C2) for future reference. Measure the dissipation factor: 1. Start the measurements with a low sensitivity setting on the measuring bridge. 2. Gradually increased the sensitivity setting on the measuring bridge to the highest possible. 3. Calculate the dissipation factor with the correction factor, refer to Dissipation factor, tan δ, page 40. NOTE! In some cases, external interference can make it difficult to set the measuring bridge to zero. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 41 8. Install the cover (2). CAUTION! The test tap is not self-grounding! The bushing can be destroyed if the test tap is not grounded. Because the capacitance (C2) is usually relatively small, the test tap must never be open-circuited when applying a voltage to the bushing. It must always be grounded or connected to an external impedance. CAUTION! Do not energize the bushing without the cover or a test adapter installed. The cover connects the outermost conductive foil to ground and will prevent damage to the bushing. CAUTION! Make sure that the cover is correctly installed with the O-ring in place, when the bushing is not in use. The purpose is to prevent dust and water from entering the tap. 9. Connect the outer terminal of the bushing to the external connections. End of instruction 5.2.5 Measurement of through-resistance Overview The method to use for measuring the through-resistance depends on the design of the transformer. In general, a current is applied from bushing to bushing. The voltage drop from the outer terminal to outer terminal is measured. The resistance is calculated with Ohm's law, R=U÷I. (R: total circuit resistance, U: measured voltage drop, I: through-current). The total through-resistance is the sum of the transformer winding, lead resistance, the bushing conductor, and contact resistance. The additional resistance from the bushing conductor should not be more than 10 to 100 mΩ. Because the through-resistance of the HV winding of a typical power transformer is in the order of 0.1 to 1 Ω, this is a very rough method that can only be used to detect very large faults in the current path, such as open circuits. Small faults in the current path can only be detected by making sensitive measurements across each connection point, or by measuring the temperature increase during operation with an infrared sensitive camera (thermovision). The through-resistance of an installed bushing can only be measured from the outer terminal of one bushing, to the outer terminal of the other bushing on the same transformer winding. The through-resistance will include the resistance of both bushings, all connections and the transformer winding. Procedure 1. Record the temperature of the transformer winding. NOTE! The resistance of metals depends on their temperature. Because the transformer winding usually dominates the total resistance, the average winding temperature at the time of measurement must be recorded. 2. 42 Measure the through-resistance from outer terminal to outer terminal. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 3. Calculate the measured resistance to the reference temperature. Then compare the calculated resistance to the reference resistance. A difference of less than 2% is acceptable. NOTE! The transformer manufacturer gives the reference temperature for through-resistance measurements. 4. 5. If the calculated difference of resistance is more than 2% from the reference resistance: 1. Make sure that the external connections have low resistance, and make sure that the outer terminal and the internal connections are correctly installed. 2. Measure the through-resistance again. If the calculated difference of resistance again is more than 2%: • Wait 24 hours and do steps 1 through 5 again. End of instruction Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 43 44 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 6 Maintenance 6.1 Recommended maintenance General The bushings are maintenance free, no regular maintenance is necessary. DANGER! Risk of electrocution! Do not go near the bushing while it is energized, or ungrounded. High voltages can kill you. Make sure that the bushing is de-energized, and grounded before you do work on it. Cleaning of the insulator surface If the insulator is exposed to very high pollution, it can be necessary to clean the surface. Remove the pollution with a moist cloth. If necessary, put isopropyl alcohol on the cloth. DANGER! 1,1,1 -Trichloroethane or Methyl-chloride are not recommended as detergents, because they are dangerous to persons and the environment. CAUTION! Do not wash the insulators with a high pressure water jet. This can cause damage to the insulators. Measurement of capacitance and dissipation factor Please refer to Measurement of capacitance and dissipation factor, page 38. Thermovision (infrared camera) check for local overheating on connectors At the maximum rated current, the bushing outer terminal normally operates at a temperature of about +35 °C to +45 °C above the ambient temperature. Significantly higher temperatures can be a sign of bad connections, especially at lower current loading. Checking of oil leakage Make a visual inspection for oil leakage during regular station supervision. After repairs ABB recommends that the capacitance is measured after repairs have been done, after maintenance of connected equipment, or after work near the bushing is completed. It is important to compare the capacitance before energization with the capacitance that was measured at commisioning. A change in capacitance gives indication of a fault. Refer to Measurement of capacitance and dissipation factor, page 38. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 45 46 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 7 Re-packing 7.1 Re-packing of the bushing G000096 Overview Procedure 1. Lift the bushing. Refer to Lifting the bushing out of the transport box, page 15. 2. Lower the bushing into the transport box. CAUTION! Do not apply force to the polymeric insulator, deformation will occur. CAUTION! Make sure that the there is soft bedding in the transport box. CAUTION! Make sure that the test tap does not make contact with the transport box, or other objects. 3. Attach the bushing to the transport box in the same way as when it was delivered. CAUTION! Make sure that the bushing cannot move or rotate in the transport box. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 47 4. Close the transport box. NOTE! Refer to Lifting the transport box, page 14 and Transportation, page 13. End of instruction 48 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 8 Spare parts 8.1 Summary If the bushing is damaged, we recommend that it is returned to ABB for repairs and re-testing. Some parts that are damaged or lost during transportation or installation can be ordered from ABB. 8.2 Spare parts Cover For the test tap. Part Article number Note 1 Cover 2749 528-B - 2 O-ring 1ZSC001606-AAW - G006192 Position Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 49 8.3 Special tools Lifting tool Article number Note Lifting tool 2183 789-2 - Part Article number Note Pull-through cord 9760 669-A With M8-terminal. G006839 Part G006198 Pull-through cord 50 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 9 Disposal and environmental information 9.1 Overview This chapter specifies the materials used in the bushing. Comply with local environmental regulations on disposal of this product, the materials used are specified for this purpose. 9.2 Disposal and recycling ABB strives to minimize the product's impact on the environment throughout its entire life cycle. Technical and product development focuses on environmental aspects. The ecocycle approach is striven for, and consideration is taken to the materials' environmental impact and recycling alternatives. The manufacturing processes are selected to be as safe for the environment as possible. Disposal of worn-out equipment Worn-out equipment must be disposed of in an environmentally sound manner. Much of the material, or the energy content in the material, can be recycled if it is sorted and cleaned. The quantity of material that can be recycled varies depending on the technical resources and capabilities in each country. Non-recyclable components should be sent to an approved environmental waste treatment plant for destruction or disposal. Porcelain After cleaning, the porcelain can be sent for disposal or used for other purposes, such as for use as filling material. Electronics Electronics equipment should be sent to an approved recycling plant, or sorted into different component materials for correct processing. Metals Metals should be sorted according to type and surface coating, and sent to an approved recycling plant. After the removal of paint or other surface coatings, clean metal can usually be melted down and used in new products. Many metal components of iron, steel and aluminum are large and easy to identify, e.g. support structures. ABB strives to reduce the use of precious metals and the release of environmentally hazardous metals. The recycling of precious metals is particularly important. Metals such as copper and silver are expensive, and are only present in small quantities in the earth's crust. Copper is primarily used in current conductors, contacts and cables. Some contacts are silver plated. Fumes from some metals can cause environmental damage, this applies to zinc and nickel, which are used sparingly as surface coatings. Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 51 Plastics The different types of plastic should be separated and sent to an approved environmental waste treatment plant or recycling plant. The energy content in thermoplastics and thermosetting plastics can often be recovered through combustion at a plant built for the purpose. Thermoplastics can usually be melted down and reused without significant loss of quality. Composites can be fractioned and used as filling materials in other materials, or be disposed of. Oils and greases Before disposal of the bushing, oil, grease and similar products must be removed and sent to an approved environmental waste treatment plant or recycling plant. By utilizing gravimetric forces, oil waste can be separated into oil, water and a range of contaminants. In many cases, the oil can then be reused. As an alternative, the energy content in oil can be recovered through combustion at a plant designed for the purpose. Rubber Send rubber to an approved environmental waste treatment plant, either for disposal or reuse for different purposes. Rubber is used in seals and gaskets. Other materials Sort other materials and send them to an approved environmental waste treatment plant. 52 Installation and maintenance guide 2750 515-115 EN, REV. 7, 2019-08-12 ABB AB, Components SE-771 80 Ludvika, Sweden © Copyright 2019 ABB, All rights reserved. Specifications subject to change without notice. 2750 515-115 EN, REV. 7, 2019-08-12 www.abb.com/transformercomponents http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 1 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:05 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:05 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:13 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:14 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:15 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:15 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:15 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:15 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 2 10/4/2013 10:15 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 2 of 2 10/4/2013 10:15 AM http://pdf.directindustry.com/pdf/eberle/voltage-regulator-reg-d/15254-1... 1 of 1 10/4/2013 10:15 AM PART 5 DISMANTLING AND TRANSPORT This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 33 - 5 DISMANTLING AND TRANSPORT 5.1 RESPONSIBILITIES AFTER TRANSFORMER TEST AND PREPARATION FOR SHIPMENT GENERAL OVERVIEW +FIGURE F5.1+APPENDIX A5.1 5.2 METHODS OF TRANSPORTATION 5.3 TRANSPORT MODES 5.3.1 TRANSPORT WITH DRY AIR FILLING + DRAWING 1ZYN 4601-204 5.3.2 INSTRUCTIONS FOR FILLING DRY AIR (AT WORKS) 5.4 HANDLING DURING LOADING AND ON SITE 5.4.1 LIFTING TRANSFORMERS 5.4.2 SUSPENDING TRANSFORMERS + FIGURE: F 5.2 5.4.3 MOVING TRANSFORMERS 5.4.4 TRANSPORT OF ACCESSORIES 5.4.5 TRANSPORTATION EQUIPMENT AND TOOLS 5.5 SHIPPING ARRANGEMENTS 5.5.1 GENERAL 5.5.2 SHIPPING BRACES 5.5.3 BUSHINGS 5.5.4 CURRENT TRANSFORMERS 5.5.5 SHUT OFF DEVICES 5.5.6 TIGHTNESS SURVEILLANCE 5.6 PACKING LIST AND TRANSPORT MONITORING 5.6.1 GENERAL 5.6.2 PACKING LIST 5.6.3 ASSEMBLY PACKAGES 5.6.4 TRANSPORT MONITORING This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 34 - - INDEX Section Description 5.1.1 Scope 5.1.2 Shipping Information 5.1.2.1 Packing List 5.1.2.2 Shipping braces and covers 5.1.3.0 Transportation 5.1.3.1 General 5.1.3.2 Impact Recorder (If Applicable) 5.1.3.3 Other Data 5.1.4.0 Successful Shipment Verification 5.1.4.1 General 5.1.4.2 Impact Recorder 5.1.4.3 Other Checks 5.1.4.3.1External Inspection 5.1.4.3.2Internal Inspection 5.1.5.0 Arrival at Customer’s Mounting Pad 5.1.5.1 General 5.1.5.2 Storage on Site 5.1.6.0 Re-Assembly Instructions 5.1.6.1 Oil Handling and Filling 5.1.7.0 Commissioning Tests This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 35 - 5.0 5.1 DISMANTLING AND TRANSPORT [REF: 1ZBA 4601-200] RESPONSIBILITIES AFTER TRANSFORMER TEST AND PREPARATION FOR SHIPMENT GENERAL OVERVIEW. 5.1.1 SCOPE Provide a specification outlining the actions to be taken and the documentation to be delivered to meet the Customer’s needs after a transformer has been tested and subsequently prepared for shipment. Guidelines will be offered, and where applicable example documents provided, to allow the Power Transformer Plants to meet Customer expectations in the transportation, verification of successful shipment, installation, commissioning, operation and life cycle management of their equipment. This specification will detail in general terms the information and services a Customer requires to complete the relationship after the transformer has been successfully tendered, designed, manufactured, tested and prepared for shipment. 5.1.2 5.1.2.1 SHIPPING INFORMATION PACKING LIST Who Uses a Packing List? Manufacturer - to catalogue parts removed for shipment and to confirm the removed, required parts have been packaged for delivery. Transport Company - to identify packages to be picked up and delivered, to assess shipping cost. Customer - to confirm that the required parts have been received, to aid in re-assembly. What should be on a Packing List? Identification of all parts, dimensions and weights of major components and accessory boxes. Shipped components can be grouped into major and accessory parts. Major parts would include the stripped down transformer, conservator, bushings, surge arresters, coolers and drums of top up oil. These parts may be packaged (boxed or on skids) to allow for convenient transport. Accessories would include all parts removed for shipment from the transformer and the major components such as all required hardware, gauges, devices, valves, spare components, etc. These parts are packed in boxes. The packing list must include the weights and dimensions of the major components and packed boxes to allow the Transport Company to cost the move and for the specification of cranes at the Customer’s site. There must be a correlation between the parts shipped, and the completed transformer, to facilitate re-assembly of the equipment. A determination should be made if there is a need to differentiate between the packing list for a truck shipment versus a rail shipment or other transport mode. Export packing will require a different packing list (and packing instructions) than a packing list for domestic transport. See SECTION 5.6 [REF: 1ZBA 4601-201] for additional Packing List guidelines. 5.1.2.2 SHIPPING BRACES AND COVERS Shipping covers and sometimes special braces are required to prepare the transformer for shipment. These braces and covers must be removed after arrival at Customer’s site during the re-assembly process. The covers and braces are identified in the shipping documentation and are painted a contrasting colour, such as yellow, for easy identification. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 36 - 5.1.3 TRANSPORTATION 5.1.3.1 GENERAL Transportation from the factory to the Customer’s site, nearest rail siding or nearest port is often arranged by the manufacturer. If the transformer is not delivered directly to a mounting pad at the Customer’s site, crane handling and/or heavy equipment moving capability as well as additional transport will be required. Once at the mounting pad, a large capacity crane and/or heavy equipment moving capability for the main unit, and small crane capability for the transformer accessories will be required. The manufacturer must be prepared to make arrangements with reputable, reliable transport, crane and heavy equipment moving companies on behalf of the Customer for the complete voyage from factory to Customer’s mounting pad. The Customer or Customer’s agent may wish to establish some or all of the transportation and off loading arrangements, but the manufacturer must be in a position to assist when required. For critical shipments by rail, sometimes a rider is required. The rider accompanies the transformer (generally riding in the train’s caboose) and can monitor the condition of the journey as well as report to the manufacturer and Customer on trip progress. 5.1.3.2 IMPACT RECORDER (If applicable) The use of a three dimension impact recorder (also known as a bump recorder or accelerometer) to monitor the quality of the trip and to chronicle potential excessive shocks to the transformer, is in many cases a Customer specified requirement. The impact recorder should be mounted on the transformer cover (rather than the rail car) to provide a representative record of the impact shocks that the transformer will receive on its journey. Also, if the transformer is moved from one mode of transportation to another, the impact recorder can travel the entire journey from the factory to the Customer’s mounting pad. Core form transformers are to be shipped upright, with the transformer mounted on the rail car or truck such that the long axis is in the same direction as the direction of travel. Plan view of a Transformer placed on a Rail Car or Truck <<<<Direction of Travel>>>> Transformer Rail Car or T rack Figure 5.1 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 37 - The impact recorder must be mounted on the transformer to ensure: the Longitudinal Acceleration direction lines up with the direction of travel the Lateral Acceleration direction lines up with the direction a right angles to the direction of travel the Vertical Acceleration will detect the up and down movement. Care must be taken to properly set-up and mark the start-up of the impact recorder at the factory. This same care is critical when marking the impact recorder tape at change of transportation mode and/or at final removal at the Customer’s pad. In the event of the transformer being exposed to excessive mechanical shock, a properly set-up and monitored impact recorder can help pinpoint the time, place, level and direction of the potentially damaging forces. 5.1.3.3 OTHER DATA Prior to shipping the transformer, tests for future comparison at change of transportation mode and/or at final unloading at the Customer’s pad should be made. These tests and checks must include the following: core ground insulation resistance (megger) water content (ppm) and dielectric strength (kV) of the oil shipped in unit, if applicable pressure gauge reading, if applicable temperature gauge reading, if applicable dew point reading (- o C), if applicable This information must be included with the shipping documentation to allow easy access and reference for comparison. 5.1.4.0 SUCCESSFUL SHIPMENT VERIFICATION 5.1.4.1 GENERAL After leaving the factory, whenever the transformer and components are transferred from one mode of transportation (rail car, truck, ship, etc.) to another or when they reach the final destination, checks must be made to confirm that shipping damage has not been sustained. These checks must be made before the equipment is moved from the transport mode. Since transformers are shipped partially disassembled, electrical testing to confirm fitness cannot be performed at this stage. Care must be taken to properly and completely perform the limited amount of inspection that can be done at this time. In the event of apparent or suspected damage, claims must be made against the transport carrier, and ABB and Customer are to be notified immediately. 5.1.4.2 IMPACT RECORDER (If Applicable) Separate instructions are be given in APPENDIX A5.1 AT THE END OF THIS PART, to be used when impact recorder is provided, on removing the impact recorder at final destination. Acceptable impact levels for the Longitudinal, Lateral and Vertical Acceleration will be defined by the individual Factories. If the transformer and components are being inspected at an interim point, at a change of transportation mode, the impact recorder tape should be marked with a line and the date, time and signature of an inspector indicted on the tape below this line. The impact recorder should not be removed from the transformer and the tape examined until the transformer has reached it’s final destination. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 38 - 5.1.4.3 OTHER CHECKS If Shipping weight and dimension limits allow, smaller transformers are shipped with all or most of the oil required in the main tank. Some of these smaller units may also be shipped with dry air in the gas space on top of the oil, this gas will be at a positive pressure when the transformer leaves the factory. To reduce shipping weight, larger units are totally drained of oil and then filled with dry gas air to maintain winding and insulation dryness during transit. Of the gas filled units, some will be filled in the factory and then be equipped with temporary gas cylinders for adding gas to the tank during transit as needed. Other gas filled units will leave the factory with an initial filling only and no supplementary cylinders added. In all cases, the gas filled units will leave the factory with a positive pressure of dry gas. For transformers shipped in oil, check for oil leaks at valves, flanges, bushings and welded seams. If evidence of oil leaks are observed, take an oil sample for moisture content and dielectric strength analysis. The laboratory results can be compared to the results obtained at the factory prior to shipment. For transformers shipped in oil with a gas layer on top of the oil, perform oil leak checks and draw oil from suspect units. In addition, theses transformers will be equipped with a vacuum/pressure gauge to monitor the gas layer pressure. This gauge must be checked and value of pressure/vacuum noted along with the oil temperature as read from the top oil temperature gauge. Although the transformer leaves the factory with the gas at a positive pressure (2 - 3 psi), the pressure reading may be negative if transformer is exposed to colder temperatures or conversely read a higher pressure if the ambient temperature is higher. The worst case condition is a reading of zero pressure which may be indicating a leak. If the gauge reads zero, take and oil sample for moisture and dielectric strength analysis. (a dew point measurement of this gas is meaningless) For transformers shipped dry gas filled , the monitoring of the vacuum/pressure gauge and the temperature gauge is critical and is often checked at various stages of the journey. A leak will compromise the winding and insulation integrity. The pressure and temperature gauge values must be recorded and compared to the readings obtained in the factory prior to shipment. The transformers are shipped with a positive pressure but a negative (vacuum) reading may occur if the ambient temperature is substantially lower than recorded in the factory. The worst case condition is a reading of zero pressure which may be indicating a leak. In conditions of zero pressure or a pressure/temperature relationship that conflicts with the factory results, a dew point measurement must be taken. The dew point measurement will establish the moisture content of the gas which can be compared to the measurement made in the factory prior to shipment., PART 6 [REF: 1ZBA 4601203 and 1ZBA 4601-204] for further information on monitoring dry gas filled units during shipment. The following is a general listing of tests and checks that should be performed on shipped transformers. Not all checks are required for all shipping variations. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 39 - 5.1.4.3.1 EXTERNAL INSPECTION Any external evidence of damage or evidence indicating the possibility of hidden damage must be reported to the carrier’s representative and to an ABB representative before off-loading the transformer. Take pictures of external damage. The receiver must assume all responsibility for offloading damaged transformers. The external inspection prior to off-loading the transformer should include the following. Measure the core insulation resistance to ground. when measured at 1000 V DC, corrected to 20 oC. The minimum acceptable value is 500 k ohms Are all tie rods undamaged and nuts tight, all cables tight. Is all blocking tight and in good condition. Is there any evidence of load shifting in transit. Does the impact recorder tape indicate any impacts beyond the acceptance zones on the tape. Are there indications of external damage such as broken glass on gauges, broken welds on flanges. Is the paint finish damaged. Are all fittings, which were shipped attached, still in place and undamaged (see the outline drawings). Is there any evidence of oil leakage around valves, fittings, flanges and tank seams. Is the pressure in the gas filled transformer tank acceptable according to PART 06. [REF: 1ZBA 4601-203 or 1ZBA 4601-204]. Inspect bushings which are assembled to the tank, or are in crates or boxes for signs of breakage, are they chipped or otherwise damaged. Is oil level in bushings normal. Check the Packing List to confirm delivery of all major components and accessory boxes. Do crates or boxes show evidence of damage or moisture entrance. Check the temporary shipping silica gel breather, moisture ingress will be indicated by the normally blue coloured silica gel desiccant turning pink. Check that detached radiators, coolers and pumps have openings closed of with blind flanges and plugs. If there is no evidence of shipping damage, proceed to off-load the transformer. If shipping damage is found, contact the nearest ABB Power Transformers representative for further instructions prior to off-loading the transformer. Written notations of apparent loss and damage must be made on the carrier’s delivery receipt. Concealed damage must be reported immediately to the delivering carrier with a request for an inspection. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 40 - See Product Information for specific Receiving Inspection - PART 7 OF THIS MANUAL: REFERENCES: 1ZBA 4601-207 Transformer Designed with Oil Conservator, Shipped Dry-Gas Filled, Partially Disassembled 5.1.4.3.2 INTERNAL INSPECTION During the inspection process, if internal damage is indicated or requires confirmation, an internal inspection may be required. This internal inspection should only be carried out by factory personnel or a recognized service organization under factory personnel guidance. Entry into oil filled or temporary gas filled transformer tank requires training and experience and must not be attempted by non factory-approved personnel. Special procedures must be followed for safety and equipment integrity reasons. 5.1.5.0 ARRIVAL AT CUSTOMER’S MOUNTING PAD 5.1.5.1 GENERAL Upon arrival at the Customer’s site, the transformer and accessories must be inspected to confirm that shipping damage has not been sustained. Refer to Section 5.1.4.above. At this point some Customer’s will require as a standard procedure, an inspection, refer to Section5.1.4.3.1.and 5.1.4.3.2 After confirmation of successful shipment, the transformer and components can be unloaded. Depending on the main unit weight and the site conditions, a crane may be used to off-load the transformer or it may be jacked and rolled into place onto the Customer’s mounting pad. PART 8: [REF 1ZBA 4601-202], for guidelines about Unloading and Moving a Transformer. 5.1.5.2 STORAGE ON SITE There may be occasions when the transformer and components arrive on site before the Customer is able to begin re-assembly. This time delay can be weeks or several months. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 41 - The delivered equipment must be maintained and monitored to ensure that the as built and as transported conditions are preserved to ensure successful and safe installation when re-assembly can be completed. PART 8:[REF: 1ZBA 4601-211], Storage on Site Before Assembly. 5.1.6.0 RE-ASSEMBLY INSTRUCTIONS Although it is not practical to provide an all encompassing procedure for the re-assembly of the often complex and individual transformer configurations, PART 11 [REF:1ZBA 4601-212], Transformer Assembly Instructions, provides a general overview. See also PART 10 [REF:1ZBA 4601-218], Oil Conservators Without Air Cell and PART 10:[1ZBA 4601-219], Oil Conservators With Air Cell, for further assembly instructions. 5.1.6.1 OIL HANDLING AND FILLING See PART 10:[1ZBA 4601-213], Receiving and Handling Transformer Oil on Site - Quality Control for an overview of oil requirements. For filling transformers and components with oil see PART 10 REF: [1ZBA 4601-214, Final Oil Filling on Site - Atmospheric Pressure and PART 10: [REF: 1ZBA 4601-215], Vacuum Oil Filling on Site. 5.1.7.0 COMMISSION TESTS After the transformer has been fully assembled and filled with oil, commissioning tests must be performed to confirm fitness prior to energization. See PART 12 [REF: 1ZBA 4601-216], Acceptance Testing and Energization for a general overview of test to be performed and utilize PART 13 [REF:1ZBA 4601-217], Field Test Record to report the test data findings. APPENDIX :A5. 1 Impact Recorder Receive and Return Instructions. Before unloading the transformer or reactor, the recorder chart must be inspected by a qualified technician. The unit must not be off-loaded unless the chart reading is within the safe limits, (see sketch below), and there is no visible signs of damage. No liability will be accepted by ABB unless this instruction is followed. Exceptions to these instructions must be authorized by the shipper (ABB). Safe Limits Vertical Acceleration To be defined by individual Factories. Will vary from Country to Country. -5g C/L Lateral Acceleration +5g -5g C/L +5g -10g Longitudinal Acceleration C/L +10g The recorder has been set to operate for a range relative to the center line (C/L) of ± 5g vertical acceleration, ± 5g lateral acceleration, and ± 10g longitudinal acceleration. For the vertical and lateral portion of the chart each graduation represents 1g. For the longitudinal portion of the chart, each graduation represents 2g. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 42 - To determine the tape speed, refer to the recorder nameplate, then refer to the tape speed marking on the side of the tape to determine the daily running record. Removing Recorder From Transformer Open the recorder cover and turn off the electrical switch. Record the finish of the tape movement by drawing a line across the tape. date, and sign the tape below the line. Inspect the tape for indications of rough handling. Record the time, the Inspect the car for signs of damage and record findings on the end of the impact recorder tape. If there is any indication of potential shipping damage, either through signs of damage on the car or by impact recorder readings outside of the acceptable limits, then contact the shipper (ABB) for instructions (ABB Factory phone #) Return the Impact Recorder to: ABB Power Transformer Division, MANEJA, VADODARA Mark on the PARCEL “Delicate Instrument, Handle with Care”. 5.2 METHODS OF TRANSPORTATION The selection of the most suitable method of transportation for the transformer is dependent on size, weight, customer‘s wishes, and on local conditions. The following points should always be observed during transport: 5.2.1 A maximum inclination of 30 degrees A maximum acceleration which equals a shunting impact of approximately (7 miles/ 11.25 km per hour the permissible speed for heavy loads) 5.2.2 A maximum surface load on cover of 1000 kg/m2 These figures must not be exceeded. Suitable measures must be taken to prevent the transformer from sliding during transport. For example: Placing the transformer on soft wooden boards or beams, and anchoring it with chains and/or wire ropes in both longitudinal and transverse axes. The anchoring equipment should be appropriated to the size and weight of the transformer. The positions of lifters, hauling can be used as anchoring points 5.3 TRANSPORT MODES Depending on its size and weight, the transformer is transported either with oil filling (lowered oil level) or with dry gas filling for these transformers. In the factory, all transformers are carefully dried, filled with degassed and dried oil, and subjected to a series of several tests before delivery. The instructions given in this section are intended to prevent damage occurring during transport, and to illuminate the reasoning behind the measures to be carried out when the transformer arrives on site, which are described in the following sections. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 43 - 5.3.1 TRANSPORT WITH DRY AIR FILLING Transformers which, with an oil filling would exceed the permissible or economical maximum transport weight, are transported without oil filling. In order to prevent moisture penetrating the transformer tank, it is filled with dry air while the oil is being drained off, and when the gas filling is completed, the tank is connected to one or more dry gas cylinders, which are secured to the tank, and are fitted with reducing valve and a positive pressure valve to provide a constant positive pressure inside the transformer tank (Please refer drawing No. 1ZYN 4601-204). The valves are adjusted to give a positive pressure of approx. 0.035 bar. The dry gas cylinders have, e.g., a content of 50 litres at a pressure of approx. 200 bar. To protect the active part against moisture the transformer is filled with dry air at a positive pressure of 0.175 kg/sq cm( 2.5 psi) at ABB works before despatch. THE INTERNAL PRESSURE AT THE TIME OF SHIPMENT IS INDICATED ON DOCUMENTS PROVIDED WITH THE TANK. All openings resulting from the removal of fittings for shipment are sealed with suitable gasketted blanking plates during transport. Transformer despatched according to this method may normally be stored upto 3 months after arrival at site or else where. The high pressure of 120 to 140 kg/sqcm is reduced to low pressure of 0.175 kg/sqcm using regulator, regulator is fixed at factory. One gauge is provided to indicate the cylinder gas pressure where as other gauge is provided to indicate tank pressure. When the tank pressure falls below 0.15 kg/sqcm due to leakage / fall of ambient temperature , the gas from cylinders must be fed manually, to build up required pressure in the tank. The gas consumption during transport and possible storage is difficult to estimate as it depends on ambient temperature variation, possible leakages as well as on the duration of transport and storage When the pressure in the first cylinder falls below 10 kg/sqcm this should be considered as empty and immediately its valve should be closed and another cylinder filled properly with gas, should be connected, if required..Dry air to IS: 1747 with 50 ppm moisture and 1% oxygen by volume should be used. Dry air should be continuously maintained at a positive pressure during storage of transformer. INSTRUCTIONS FOR FILLING DRY AIR CYLINDER (AT WORKS) Lower the oil level to the minimum necessary to dismantle the items such as bushing and turretswhich must be removed for shipping. Pull 500 mm mercury vacuum after blanking of all openings. Continue to supply dey air until it maintains a steady pressure of 0.17 +0.02 kg/sq.cm above atmosphere. Pressure of dry air gas shall be maintained at 0.17 +0.02 kg/sq cm at reference temperature. Pressure should be monitored by taking three readings within 24 hours to ensure that there is no leakage of gas. Shut off the gas supply valve and fit dry air cylinder through dry air regulatory valve. The gas should have moisture content of max. 250 ppm (weight) and contain max. 0.3% (volume) of foreign admixtures. The transformer tank filled with dry gas must on no account be opened during transport, nor must the gas cylinder be removed, if it cannot be reconnected within 48 hours. If the transformer tank has an obvious leak, or if the gas cylinder shows a significant pressure drop during transport, make sure that the leak is sealed, and inform ABB 5.4 HANDLING DURING LOADING, AND ON SITE Caution! Transformers must only be transported in an upright position. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 44 - 5.4.1 LIFTING TRANSFORMERS Hydraulic hoists may only be used at the jacking pads provided (see outline drawing). Lifting must be carried out simultaneously and uniformly for at least two adjoining jacking pads. Note: Pipe flanges and valves must never be used as lifting or support points. 5.4.2 SUSPENDING TRANSFORMERS Every transformer is fitted with lifting bolts for suspension purpose (see outline drawing). When suspending transformers on crane hooks, observe the following points: The transformer must be suspended from points shown in the outline drawing. The ropes must never form smaller angle than 60 degrees to the horizontal. Thus, dimension „L“ must be equal to or larger than dimension „M“ (As shown in Fig. 5.2). FIGURE 5.2: ROPE LENGTH FOR TRANSFORMER SUSPENSION 5.4.3 MOVING TRANSFORMERS Transformers are moved or relocated on moving devices or on skids. When skids are used, armoured rollers can be placed under the transformer, or sliding surfaces (with the aid of lubricants) can be used. Note: The presence of paint or dirt on the sliding surfaces or on the skids will increase the frictional resistance and lead to a sharp increase in the tractive forces required. 5.4.4 TRANSPORT OF ACCESSORIES For components which must be removed for transport see outline drawing. Accessory components which are transported without packing must only be lifted by the suspension lugs provided. Accessory crates, especially those containing porcelain parts, must not be dropped and must be protected against slipping. 5.4.5 TRANSPORTATION EQUIPMENT AND TOOLS For transporting, sliding, moving or relocating a transformer, the following tools and equipment will be needed: hydraulic jack, hardwood planks hardwood beams, softwood beams electric cable winch or grippers guide pulleys This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 45 - wire ropes, shackles transport rails, tie bars connecting links. 5.5 SHIPPING ARRANGEMENTS 5.5.1 GENERAL Large Power Transformers are normally shipped on special low bed trailor. General rules for unloading transformers from their vehicles are given in PART 8 . Also, always check the Packing List, which includes a transport outline drawing for the transformer, with shipping dimensions, weights, etc. indicated. Accessories will be despatched separately by road, oil drums by road. Major quantity of oil by tankers (road transport) when supply is in the scope of ABB or as agreed in contract.. Important Notes: a) After dismantling the sub-assemblies like Bushing assembly, conservator assembly, radiator assembly, header assembly, A-frame assembly, roller assembly etc, all the hardware and gaskets pertaining to that sub-assembly shall be packed and put in the same crate as that of the sub-assembly. b) Each crate has to be marked legibly with the names of the contents packed and suitable signs shall be marked for opening the boxes. 5.5.2 SHIPPING BRACES For protection, all openings resulting from shipping disassembly must be closed, oil-tight and gas-tight, with caps or blind flanges during transport. Temporary shipping covers, braces and similar hardwares must be replaced or removed before the transformer is energized. 5.5.3 BUSHINGS In cases where bottom-connected bushings have been disassembled for shipping, the bushing leads are supported by temporary shipping braces, which are an integral part of the blind flange cover. For bushings with draw-through bushing leads, the lead is looped and fastened to the support structure above the core and coils, or fastened to the bushing flange cover. The bushing leads, lead structure and coils can be severely damaged if you attempt to remove the covers without first disconnecting the shipping supports. 5.5.4 CURRENT TRANSFORMERS Current transformers must be short-circuited and earthed (grounded) for Shipping. 5.5.5 SHUT-OFF DEVICES Shut-off devices shall be in transport position, and throttle valves shall be closed for shipping. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 46 - 5.5.6 TIGHTNESS SURVEILLANCE Extreme care has been taken to prevent moisture entering the transformer. It is important to regularly check tank pressure during shipping and storage times to verify that no indication of leaks appears. For gas-filled compartments, the instructions are given in PART 6 5.6 PACKING LIST AND TRANSPORT MANUAL 5.6.1 GENERAL In order to meet shipping clearances and to avoid transport damage, some accessories-bushings for instance- are often disassembled from the tank during shipment and packed separately. Detailed information on this is given in this instruction. The Packing List also describes, how the dismantled parts of a large transformer are packaged and marked. The shipment consists of „the Heavy Parcel“-that is, the sealed transformer tank, containing the core and coils - and the dismantled parts in crates and boxes. 5.6.2 PACKING LIST The Packing List is a drawing-numbered document. A full set is contained in a separate box together with other technical documentation. Each crate or box has the separate sheets of its own contents packed. The table carries the identification of the items by name, quantity, and article number or equivalent. In order to meet shipping clearances and to avoid shipping damage, some accessoriesbushings for instance- are often disassembled from the tank during shipment and packed separately. Detailed information on this is given in the Packing List enclosed with despatch documents. 5.6.3. ASSEMBLY PACKAGES The parts are organized in Assembly Packages. An Assembly Package consists of all parts which are needed for a certain group or operation during the assembly, which shall be completed in a sequence without interruption. „Bushings“ and „Oil preservation systems are examples of Assembly Packages. Everything belonging to a certain Assembly Package is packed together in a group of crates and boxes. Those parcels are identified on the Packing List as belonging to that Package. The advantage with this system is that only a few pieces have to be opened at a time. Remaining crates and boxes are to be left closed until they are needed. This keeps the parts under protection and in good order. The numbering of the Assembly Packages shows the recommended order of progress which our Field Service organization has found practical. Of course it is possible to proceed in a different order, depending on conditions on the site. At the end of the list of Assembly Packages you find references to the set of fresh gaskets to be used during assembly, touch-up paint, and a box with documents. 5.6.4. TRANSPORT MONITORING The monitoring instructions deal with lifting and bracing of the Heavy Parcel, and various items of checking and visual inspection. Two of these monitoring duties are the following: This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 47 - The tank is filled with dry air to a slight over-pressure this has to be monitored en route. The final checkpoint is, when the shipment is received on site. The numbering of the Assembly Packages shows the recommended order of progress which our Field Service organization has found practical. Of course it is possible to proceed in a different order, depending on conditions on the site. At the end of the list of Assembly Packages you find references to the set of fresh gaskets to be used during assembly, touch-up paint, and a box with documents. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 48 - PART 6 MONITORING OF DRY-GAS FILLING OF TRANSFORMERS DURING SHIPMENT AND STORAGE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 49 - INDEX 6.0 MONITORING OF DRY-GAS FILLING OF TRANSFORMERS DURING SHIPMENT AND STORAGE 6.1 PRESSURE GAUGE AND FILLING COCK 6.2 PRESSURE LIMITS + FIGURE F 6.1 6.3 MONITORING UNDER STORAGE 6.4 INSPECTION AND REPORTING 6.5 LONG-TIME STORAGE. CHANGE OF GAS CYLINDERS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 50 - 6.0 MONITORING OF DRY-GAS FILLING OF TRANSFORMERS DURING SHIPMENT AND STORAGE This transformer is shipped without oil and with accessories and fittings removed. The tank has been filled with dry gas to a slight over-pressure in the factory. It is important that the transformer remains perfectly sealed during shipment and storage. The gas- over pressure shall be monitored at regular intervals. [REF: 1ZBA 4601-203, 1ZBA4601-204] 6.1 PRESSURE GAUGE AND FILLING COCK A pressure gauge and filling cock unit are fitted on the side of the tank. The pressure gauge has a range range 0 -210 kg/sq cm on dry air cylinder side and kg/sqcm towards transformer tank side 6.2 0 to 2.5 PRESSURE LIMITS The gas pressure in the tank when the transformer leaves the factory is 20 kPa (0.2 atm 3psi) at a temperature of about 20°C (65-70°F). This pressure will change with the ambient temperature as shown in the figure F6.1. Even at -25°C there shall be a small positive over pressure and in a warm climate the pressure still is about 30 kPa.(0.306 kgf/sqcm) 30 20 Over pressure kPa 10 0 -20 -10 0 10 20 30 Centigrades = FIGURE F 6.1 EXAMPLE: CORRECT PRESSURE AT DIFFERENT AMBIENT TEMPERATURES If, after an inspection, the pressure is completely lost, there must be a serious leak somewhere. It is possible that there may even have been under-pressure at some time (due to a sudden temperature drop), and moisture may have entered the tank. Complete loss of gas -filling pressure must be reported immediately for further action. I f the pressure read on the gauge is not completely lost, but has fallen below 5 kPa (0.05 atm, about 1 psi), then the tank shall be filled up with dry gas to the original reading of about 20 kPa. The guaranteed dryness of the filling gas shall be such that the dew-point is below -40°C (= -40°F). Before filling, the plastic hose used shall be blown clean with gas from the bottle. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 51 - 6.3 MONITORING UNDER STORAGE When the transformer is under storage for a considerable time, the filling pressure shall be checked and recorded once a month. This transformer is shipped without oil and with accessories and fittings removed. The tank has been filled with dry air to a slight over-pressure in the factory. It is important that the transformer remains perfectly sealed during shipment and storage. 6.4 INSPECTION AND REPORTING The pressure control unit shall be inspected at the prescribed check points during shipment. It shall be checked that - The pressure in the tank stays above the minimum limit - There is still considerable pressure in the storage bottle If the over-pressure in the tank is completely lost, and the cylinder is empty, then there is a serious leak. It is possible that there may even have been under-pressure at some time (due to a sudden temperature drop), and moisture may have entered the tank . Complete loss of gas-filling pressure must be immediately reported for further action. 6.5 LONG-TIME STORAGE. CHANGE OF GAS CYLINDERS. When the transformer is in transit or stored at the site for a considerable time, the tank pressure shall be checked and recorded once a month. The pressure in the storage gas cylinder may decrease with time. If it reaches 1 MPa (10 atmospheric pressure) it should be substituted against a new bottle. The bottle gas shall have a guaranteed dryness corresponding to a dew-point not above -40°C (= -40°F). This may be checked from the sampling cock if a dew-point meter is available. The procedure is as follows: - Close first the shut-off valve towards the tank Then shut the main valve on the bottle - Disconnect between bottle and reduction valve and install the new bottle Check that the reduction pressure is correct by bleeding the sampling cock and closing again Open valve towards the tank This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 52 - PART 7 RECEIVING INSPECTION AND ARRIVAL ON SITE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 53 - 7.0 RECEIVING INSPECTION AND ARRIVAL ON SITE 7.1 RECEIVING INSPECTION [1ZBA4601- 207] 7.2 ARRIVAL AT SITE, UNPACKING AND CHECKING OF THE CONSIGNMENT 7.2.1 ARRIVAL ON SITE 7.2.2 UNPACKING AND CHECKING OF THE CONSIGNMENT 7.2.2.1 REMOVING THE PACKING MATERIAL 7.2.2.2 INTERNAL INSPECTION 7.2.3 TIGHTNESS 7.3 CHECK LIST AND LOG SHEET 7.3.1 CHECK LIST - CHECKING THE CONSIGNMENT ON ARRIVAL 7.3.2 LOG SHEETS TO BE USED FOR CHECKING TRANSFORMER ON RECEIPT 7.4 SITE ACTIVITY CHART This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 54 - 7.1 RECEIVING INSPECTION [1ZBA4601-207] COPIES OF ABB SPECIFICATIONS ARE ENCLOSED [REFERENCES]: 1ZBA 4601-207 Transformer Designed with Oil Conservator, Shipped Dry -Gas Filled, Partially Disassembled 7.2 ARRIVAL AT SITE, UNPACKING AND CHECKING OF THE CONSIGNMENT 7.2.1 ARRIVAL ON SITE Note Use the packing list enclosed with the consignment to check contents for completeness. Any pressure loss in transformer tanks filled with dry air must be included in the acceptance report. In the case of attached dry air cylinders, an excess pressure of 0.05 bar should be maintained as minimum. 7.2.2 UNPACKING AND CHECKING OF THE CONSIGNMENT 7.2.2.1 REMOVING THE PACKING MATERIAL Use suitable tools to remove the transformer packing. Packing material of accessories should be stored as it might be used later in case of return shipment for repairs or overhaul. Accessories must be kept in their transport containers until final assembly in order to avoid moisture absorption. Insulating transformer oil must be stored in accordance with the latest regulations until final oil filling. See as well PART 10. ”OIL“. 7.2.2.2 INTERNAL INSPECTION An internal inspection is necessary if transport damage is suspected. Flanged covers of bushing assembly openings and inspection covers must be removed. Core and winding supports, active part supports and cleats and leads must be checked for damage. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 55 - Page Left Blank This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 56 - Danger! Before removing the tank cover or any other cover, make sure that there is no overpressure inside the tank. Note Before any work is carried out inside the tank, always consult ABB. Danger! If any tools or other objects are left out inside the tank, they can cause shortcircuits and failure of transformer. 7.2.3 TIGHTNESS Oil-filled transformers should be checked for oil traces indicating a leak. 7.3 CHECK LIST AND LOG SHEET [PLEASE ALSO FOLLOW INSTRUCTIONS UNDER DO‘S AND DON‘TS MENTIONED EARLIER IN PART 1.9] 7.3.1 CHECK LIST - CHECKING THE CONSIGNMENT ON ARRIVAL Serial number …...………….. Type of transport: Without oil Dry air positive pressure a) in the tank …..……bar, present Not present O b) in dry air cylinder ….…….bar, present not present Silica gel in breather not present is blue form O is pink/white O Support of core -and-coil assembly In order not in order O not checked O Leads in order not in order O not checked O Core-and-coil assembly is dry is not dry drying is required O O O O O O O O O O This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 57 - Core earthing in order not in order not checked O O O Shock recorder not provided provided, no excess strain detectable provided, excess strain detectable O O Damages a) at the tank not present present and reported to ABB O O b) at the accessories not present present and reported to ABB O O c) at the painting not present slightly damaged severely damaged damages reported to ABB O O Accessories properly provided not completely provided and reported to ABB O O O O Insulating oil properly provided not properly provided Signature of customer Date O O / ABB assembly engineer /Representative Date This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 58 - 7.3.2 LOG SHEETS TO BE USED FOR CHECKING TRANSFORMER ON RECEIPT ITEM CASE NO. TYPE OF CHECK OBSERVATION SIGNATURE & DATE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 59 - 7.4 SITE ACTIVITY CHART RECEIPT AT SITE MEASURING OF NITROGEN PRESSURE CHECK OIL LEVEL AS APPLICABLE ERECTION OIL FLUSHING OF COOLERS / COOLER ASSEMBLY ERECTION EVACUATION AND OIL FILLING OIL FILLING OIL BDV AND WATER CONTENT OIL BDV AND WATER CONTENT OIL FILLING UNDER VACUUM AND TOPPING UP AIR RELEASING OIL FILTRATION COOLER BANK STANDING TIME COMMISSIONING This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 60 - PART 8 UNLOADING, MOVING, STORING THE TRANSFORMER AND PRECOMMISSIONING CHECKS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 61 - 8.0 UNLOADING, MOVING, STORING THE TRANSFORMER AND PRE- COMMISSIONING CHECKS 8.1 INSPECTIONS BEFORE UNLOADING 8.2 EXTERNAL INSPECTION 8.3 UNLOADING AND MOVING THE TRANSFORMER+ [REF:1ZBA4601-202] 8.4 STORAGE OF TRANSFORMER 8.4.1 STORING OF COMPONENTS AND ACCESSORIES BEFORE COMPLETE ASSEMBLING 8.4.1.1 STORING INDOORS IN A DRY ROOM 8.4.1.2 STORING OUT DOORS 8.4.1.3 INSTALLATION 8.4.2 8.5 STORAGE ON SITE BEFORE ASSEMBLY + PRODUCT INFORMATION 1ZBA 4601-211 PRE-COMMISSIONING CHECKS FIGURES F 8.1 EXAMPLE TRANSFORMER SHIPMENT SHOWING TIE-RODS BLOCKINGS. F8.2 BLOCKING F 8.3 TYPICAL JACKING PAD F 8.4 TYPICAL EXAMPLE TRANSFORMER RAISED. TRANSFORMER CRIBBING PLACED UNDER F 85 TYPICAL EXAMPLE: TRANSFORMER RAISED. CRIBBING AND ROLLING PLACED UNDER TRANSFORMER This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 62 - 8.0 UNLOADING AND MOVING THE TRANSFORMER INSPECTIONS BEFORE UNLOADING EXTERNAL INSPECTION Any external evidence of damage or evidence indicating the possibility of hidden damage must be reported to the transporter’s representative and to an ABB representative before unloading the transformer. Take pictures of external damage. The receiver must assume all responsibility for unloading damaged transformers. The external inspection prior to unloading the transformer should include all of the following. Are all tie rods connected to vehicle, undamaged and nuts tight? Is all blocking tight and in good condition? Is there any evidence of load shifting in transit? Does the impact recorder (when provided) tape indicate any impacts beyond the acceptance zone on the tape? Are there indications of external damage such as broken glass on gauges, broken welds on flanges? Is the paint finish damaged? Is there any evidence of oil leakage (if units are shipped in oil)? Is the pressure in the gas-filled tank acceptable? Is oil level in bushings normal? Is the Driving Mechanism of OLTC and shaft are aligned properly? Is there any visible damage? 8.2 EXTERNAL INSPECTION continued Do crates or boxes show any evidence of damage or moisture entrance? If there is no evidence of shipping damage, proceed to unload the transformer. If shipping damage is found, contact the nearest ABB representative for further instructions prior to unloading the transformer. If any damaged parts are noticed lodge claim with under-writing and report to ABB This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 63 - 8.3 UNLOADING AND MOVING THE TRANSFORMER PRODUCT INFORMATION 1ZBA 4601-202 ENCLOSED 8.4 8.4.1 STORAGE OF TRANSFORMER STORING OF COMPONENTS AND ACCESSORIES BEFORE COMPLETE ASSEMBLING Independent of the duration of the storing time, the directions below apply for dismounted components and accessories, as well as for material to be used in connection with the assembling work. 8.4.1.1 STORING INDOORS IN A DRY ROOM In such a room, the following articles should be stored Insulating material such as paper, pressboard, bakelite, wood, cotton tape etc. Insulated details as paper insulated conductors, pressboard insulated shielding bodies etc. Chemicals as solvents, glues, varnishes, hardness etc. Breathers and drying agents Terminal boxes, connection boxes, control cabinets Turrets with built in current transformers. Radiators Gas relays, oil -level indicators, thermometers, pressure valves etc. Pipes to oil conservator, pipes to radiators, pipes to turrets etc. Bushings Marshalling box, OLTC motor drive, fans, pumps, instruments and fittings Control cabinets (Heating elements provided shall be connected to supply) 8.4.1.2 STORING OUT DOORS The components mentioned below may be stored outdoors. They should be placed above ground and covered with tarpaulin etc. Oil conservator with blanking plates for all openings Radiators and coolers with blanking plates for all openings Structures, A frames, pipe supports, oil conservator supports, radiators, control cabinets etc. 8.4.1.3 INSTALLATION Before starting with the assembly the transformer must be transported to its foundation. For this purpose use the pulling lugs and jacking pads provided (see outline drawing). Before moving the transformer, take care to observe the instructions in the respective section of this manual. The foundation should be designed to allow the transformer to stand level. The assembly location must have the ventilation space necessary for proper functioning of the cooling system. The transformers should always be separated from one another and from all walls and partitions to permit free circulation of air. Please also refer IS:10028 [CODE OF PRACTICE FOR INSTALLATION AND MAINTENANCE OF TRANSFORMERS] This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 64 - After the transformer has been moved to its final position, fit the fixing devices, if any. Mounting of wheels under transformer is to be done as per roller arrangement drawing. Valves which may affect the loading gauge or which may be subjected to damages should be dismounted before delivery. Remount the valves - the positionings appearing from GENERAL ASSEMBLY DRAWING. The gaskets surfaces shall be cleaned well and new gaskets fitted. Check that all valves are closed. When exchanging a damaged bushing or other component on the cover of a fully oil filled transformer, we should proceed according to the following: Close the valve in the pipe between the transformer and the oil conservator. Pump oil from the transformer tank into the oil conservator so that the oil quantity which need to be drained off to lower the oil enough below the transformer cover is pushed to the conservator. As the oil is being transferred from tank to conservator, fill up the tank with dry air via suitable valve on the cover or in turrets. Exchange the faulty bushing and then transfer the oil from conservator to tank by opening the valve in the pipe between conservator and main tank. De-air the bushings and turrets. STORAGE ON SITE BEFORE ASSEMBLY PRODUCT INFORMATION 1ZBA 4601-211 ENCLOSED 8.5 PRE-COMMISSIONING CHECKS The following are salient points to be checked before commissioning Check all the gasketed joints to ensure that there is no leakage of transformer oil at any point. Check any breakages of porcelain. Bushings with cracks or any other defects should be immediately replaced. Oil level in condenser type bushings should be upto the level mark on oil gauge on side of top cap. Check the tightness of top cap for condensor bushing. Release trapped air through air release plugs and valves fitted for the purpose on various fittings like headers, radiators, and oil communicating bushings, buchholz petcock etc. Check alarm and trip contacts of buchholz relay, WTIs, dial type thermometer, magnetic oil level gauge, oil flow indicator, pressure relief device etc. Ensure that conservator is filled upto the filling level mark on prismatic oil level gauge side and corresponding to the pointer reading on MOLG side. Special attention to be paid for conservator with flxi separator. Make sure that neutral bushings are effectively earthed. Tank and cooler bank should be earthed at two pints Check the direction of rotation of fan blades to ensure right blast towards radiators. Check the direction of rotation of pumps. Ensure that silica gel in the breather is active and colour is blue and oil in the breather cup is present. Check that the thermometer pockets on tank cover, header etc. are filled with oil. CTs secondary terminals must be shorted and earthed if not in use. Check that the proper terminals in the marshalling box are connected to WTI CT terminals Check for tightness of all external electrical connections Check for the arcing horn gap on bushings if provided. Clear off extraneous materials like tools, earthing rods, pieces of clothes, waste etc Lock the rollers for accidental movement on rails. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 65 - PART 9 TRANSFORMER ASSEMBLY INSTRUCTIONS, SUGGESTED ERECTION EQUIPMENT / TOOLS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 66 - 9.0 TRANSFORMER ASSEMBLY INSTRUCTIONS, ERECTION EQUIPMENT / TOOLS CONTENT 9.1 SCOPE [REFERENCE 1ZBA 4601-212] 9.2 SAFETY NOTATIONS 9.3 GENERAL 9.4 PREPARATION 9.5 EXTERNAL ASSEMBLY 9.5.1 RADIATORS, COOLERS AND PUMPS 9.5.2 NEW GASKETS 9.5.3 MOUNTING THE NITROGEN BLANKET OIL PRESERVATION SYSTEM 9.5.4 LOAD TAP-CHANGERS 9.6. INTERNAL ASSEMBLY 9.6.1.1 GENERAL PRECAUTIONS 9.6.1.2 ASSEMBLY INSTRUCTIONS FOR BUSHINGS CONDENSER BUSHINGS FOR 245 kV AND 145 kV CLASS LOW VOLTAGE BUSHINGS CHECKING BEFORE MOUNTING THE BUSHINGS CHECKING THE SECONDARY LEADS OF CTS 9.6.2 BUSHING INSTALLATION 9.6.3 BUSHING CURRENT TRANSFORMERS 9.7 CLOSING THE TRANSFORMER AND FINAL DEWPOINT MEASUREMENTS 9.8 ELECTRICAL TESTS 9.9 ERECTION EQUIPMENTS/ TOOLS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 67 - 9.0 TRANSFORMER ASSEMBLY INSTRUCTIONS 9.1 SCOPE [REFERENCE PRODUCT INFORMATION 1ZBA 4601-212] These instructions are intended to help in the installation of transformers to maintain their quality and reliability. The recommendations are not a complete manual for all the operations during the field assembly of a large transformer. It is assumed that competent and responsible supervision and workpersonnel are available for the job - that good order, cleanliness and personal safety precautions are observed - in accordance with common sense and local regulation. The following text highlights a few particular procedures and precautions that are specific for the ABB Transformer make, or are of critical importance for a good result. 9.2 SAFETY NOTATIONS Safety notations are intended to alert personnel of possible personal injury, death, or property damage. They have been inserted in the instruction text prior to the step in which the condition is cited. The safety notations are headed by one of three hazard intensity levels 1) Danger 2) Warning 3) Caution PLEASE ALSO REFER TO “PART 1”, SAFETY INSTRUCTIONS FOR DETAILS. 9.3 GENERAL PRECAUTIONS The transformer should not be opened during periods of inclement weather or when condensation is forming on the internal surfaces of the transformer. Never enter a transformer with dirty or wet clothing. Clean cloth overshoes or nitrile rubber overshoes should be worn. Tools must have working surfaces hardened so that they will not peel or chip during normal use; also, working surfaces must not be coated in any way such as painting or plating. Tools that are polished metal or have black oxide body finish are preferred . To prevent accidental disassembly during normal use, all tools with movable parts must use double side flush-riveted joints and or all fasteners or moving parts must be retained by staking or deforming the last thread by welding or coating. Tools such as hammers and screwdrivers must have one piece heads. Molded-on plastic or fiberglass handles are preferred; if the handle is wood, it must be retained by a wood or plastic wedge. Nameplates or tags attached to tools should be removed. If a nameplate is necessary for tool identification, the plate must be non -metallic and be secured with non-conducting tape. While the transformer is open, do not permit anyone access to the transformer until they have emptied all pockets, checked for loose objects, and removed watches, rings, and other objects. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 68 - Dry air must be used to ventilate the inside of the tank when it is opened for internal fitting. The air must have a dew point less than -40 C and sufficient airflow for the number of operators in the tank must be maintained. Do never use nitrogen or other gases than air for ventilation. Nitrile gaskets should be changed during the assembly operations. New gaskets are provided with transformer detail parts The mechanical relief devices shall be installed prior to beginning the assembly operations to prevent excessive pressure build-up on the tank. The transformer tank shall be grounded prior to beginning any assembling operations. 9.4 PREPARATION The transformer base shall be supported on the foundation pad or piers as appropriate. 9.5 EXTERNAL ASSEMBLY The items removed and shipped separately are listed on the General Assembly, or packing list. The items generally removed and shipped separately are the bushings, cooling equipment, forced oil pumps (if the transformer has an OFAF rating), arresters and arreseter mounting brackets and the sudden pressure relay. The number of accessory items removed will vary depending on the physical size of the transformer. All air or gas fittings and all oil fitting joints that are preassembled at the factory must be checked for leaks and resealed. 9.5.1 RADIATORS, COOLERS AND PUMPS Radiators, coolers, the associated oil pumps and piping shipped as detail items that are assembled at the final location must be thoroughly inspected prior to installation to be certain that no water or foreign material is in the oil space. Avoid opening the equipment when it is at a temperature lower than the ambient air in order to prevent condensation. The radiators or coolers should be installed on the transformer the same day they are opened. Do not permit the cooling apparatus to stand exposed after opening for inspection. The detailed illustrations for mounting and piping arrangements are shown on the General assembly drawing. Use new gasket material when installing the radiators, coolers, or pumps. 9.5.2 NEW GASKETS USE NEW GASKET MATERIAL, SUPPLIED ALONG WITH TRANSFORMER WHEN INSTALLING THE RADIATORS, COOLERS OR PUMPS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 69 - 9.5.3 MOUNTING THE NITROGEN BLANKET OIL PRESERVATION SYSTEM (If Applicable) 9.5.4.1 GENERAL MR TYPE Tap-Changers are usually shipped mounted on the transformer WARNING: DO NOT OPEN ANY COVERS OR FITTINGS UNLESS THE INTERNAL PRESSURE IS AT ZERO GAUGE. FAILURE TO RELIEVE THE PRESSURE COULD CAUSE THE PART BEING REMOVED TO BE A HAZARDOUS FLYING OBJECT. ALWAYS RELIEVE INTERNAL PRESSURE SLOWLY THROUGH VALVES. Before placing Tap-Changers in service, read the appropriate Tap-Changer instruction leaflet. The leaflets are included in PART 4.2. Always follow the inspection and filling instructions given in the Tap-Changer instruction leaflet. 9.5.4.2 TAP-CHANGERS MOUNTED FOR SHIPMENT No internal assembly operations or taping are required. Fill the Tap -Changer compartment as instructed in the Tap-Changer instruction leaflet. OLTC should not be operated unless otherwise its divertor compartment is filled with oil. 9.6 INTERNAL ASSEMBLY 9.6.1.1 GENERAL PRECAUTIONS Necessary confined entry procedures should be followed in compliance with company policy or local regulations. CAUTION Be certain the internal pressure in the transformer is a zero gauge before opening the manhole cover. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 70 - CAUTION To prevent contamination of the transformer, only the manhole and the opening for the item being installed should be opened. Cover all other openings with dry pressboard or a clean plastic sheet. This will also minimize the flow of dry air from the unit. 9.6.1.2 ASSEMBLY INSTRUCTIONS FOR BUSHINGS 9.6.1.2.1CONDENSOR BUSHINGS FOR 245 kV AND 145 kV CLASS: These are supplied by ABB Sweden. Please refer to the installation and maintenance manual of supplier for details. 9.6.1.2.2 LOW VOLTAGE BUSHINGS Bushing provided with stem type design should be assembled by opening the inspection cover. Any special instructions required for LV bushings can be referred in Part-3 of this operation and manintenance manual. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 71 - 9.6.1.2.3CHECKING BEFORE MOUNTING THE BUSHING: Check that detachable turrets, pockets/bushing mounting plates etc. Are properly mounted as per the general assembly drawing. Leads and other hardware items for connections are available and bushing CTs are properly assembled inside the turrets. Check that secondary leads from CTs are connected to respective terminal boards. 9.6.1.2.4 CHECK THAT SECONDARY LEADS OF CTS 9.6.2 BUSHING INSTALLATION On large transformers, the bushings will be removed for shipment to meet shipping clearances and to avoid shipping damage to the bushings. The bushing leads may be supported by temporary shipping braces which are an integral part of the blind flange. The flange will be indicated with a warning note if this method is used. The bushing leads must be disconnected from these temporary braces before the blind flange covers or shipping covers are removed. CAUTION Failure to disconnect the leads from the temporary shipping braces before the blind flanges or shipping covers are lifted can cause damage to the leads, bridge structure and associated coils, and may necessitate return of the transformer to the factory for repair and retesting. 9.6.3 BUSHING CURRENT TRANSFORMERS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 72 - WARNING AN ENERGIZED CURRENT TRANSFORMER IS DANGEROUS IF THE SECONDARY IS AN OPEN CIRCUIT. DEATH OR SERIOUS INJURY CAN RESULT FROM CONTACT WITH THE TERMINALS. THE SHORT CIRCUITING DEVICES MUST BE CONNECTED TO THE APPROPRIATE TERMINALS IN THE CONTROL CABINET IF THERE IS NO LOAD CONNECTED TO THE TRANSFORMER. 9.7 CLOSING THE TRANSFORMER AND FINAL DEWPOINT MEASUREMENTS When taking dewpoint measurements, it is advisable to take the measurement in the early morning hours prior to sunrise. When this is done, the insulation temperature can be taken to closely match the gas temperature. When taking the dewpoint during periods of extreme ambient temperature variation or during the afternoon hours, the insulation temperature should be measured directly after the dewpoint is taken. 9.8 ELECTRICAL TESTS CAUTION If the transformer tank is not filled with oil, the test voltage on the windings must be limited to low voltage preferably 415 volts on HV side. Measure the power factor and capacitance of the bushings before installing the bushings in the transformers. Refer to the appropriate bushing instruction leaflet for the proper procedures. 2. Measure the core resistance to ground. The minimum acceptable value is 500 kOhm when measured at 1000 volts. 3. Measure the core clamp resistance to ground. The minimum acceptable value is 500 kOhm when measured at 1000 volts. 4. Measure the ratio of all bushing current transformers and verify proper polarity. 5. Check the turns ratio of the transformer (TTR) at all tap positions. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 73 - The measured turns ratio should be + 0.5 % of the nameplate voltage ratio. FOR OIL FILLING PLEASE REFER TO OTHER PARTS 10 AND 11. 9.9 SUGGESTED ERECTION EQUIPMENTS/ TOOLS ONE OR TWO NOS. MOBILE CRANES HAVING A FREE VERTICAL LIFT SUITABLE FOR LIFTING HV BUSHINGS AND LIFTING CAPACITY OF 3 TONNES EACH. STEEL/ MANILA / NYLON ROPES AND “D “ SCHACKLES FOR LIFTING 3 TONNES WEIGHT FILTER MACHINE OF CAPACITY MINIMUM 6000 LITRES PER HOUR IN EXCELLENT WORKING CONDITION. IT MUST BE CAPABLE OF HEATING TRANSFORMER OIL UP TO 80 DEG. C (HEATING SHOULD BE INDIRECT) AND MUST BE EQUIPPED WITH INBUILT HIGH VACUUM DEGASSING CHAMBER FILTER ELEMENTS. THE FOLLOWING ACCESSORIES SHOULD ALSO BE PROVIDED NON-COLLAPSABLE HOSEPIPES OF ADEQUATE LENGTH AND SIZE PROVIDED WITH NIPPLES / ADAPTORS. - TWO NOS. FLANGES EACH OF SIZES 25, 50 AND 80 MM PIPE SUITABLY THREADED FOR CONNECTING THE HOSE PIPES AND PROVIDED WITH HOLES FOR FASTENING ON MAIN UNIT VALVES -THE INCOMING ELECTRICITY SUPPLY CAPACITY MUST BE ADEQUATE TO OPERATE THE MACHINE WITH ALL ITS HEATERS “ON”. VACUUM PUMP OF CAPACITY 1500-2500 LPM WITH BOOSTER OF 600- 900 cub-m /hour AND CAPABLE OF ULTIMATE VACUUM OF I X 10 -3 [TEN TO POWER MINUS THREE] MILLI BAR], ALONG WITH FOLLOWING ACCESSORIES -NON-COLLAPSIBLE HOSES WITH SUITABLE FLANGES FOR CONNECTING TO MAIN TANK CONDENSER FOR CONDENSATION OF MOISTURE -SUITABLE GAUGE FOR MEASURING UPTO 10 -3 PRESSURE MILLI BAR TO CONFIRM EFFICIENCY OF VACUUM PUMP WHENEVER REQUIRED STORAGE TANK FOR TRANSFORMER OIL OF ADEQUATE CAPACITY PROVIDED WITH 50 MM BOTTOM DRAIN - CUM FILTER VALVE AND ANOTHER 50 MM TOP VALVE. THE TANK SHOULD HAVE AN AIRTIGHT INSPECTION COVER AT THE TOP AND MUST BE PROVIDED WITH A BREATHER AND OIL LEVEL SIGHT WINDOWS. TANK SHOULD BE PAINTED WITH OIL RESISTANT PAINT FROM INSIDE AND MUST BE CLEANED THOROUGHLY BEFORE STORING THE OIL. CAPACITY OF STORAGE TANK SHOULD BE EQUAL TO THE TOTAL OIL QUANTITY OF COMPLETE UNIT. ADEQUATE NUMBER OF ALUMINIUM TRAYS FOR SALVAGING TRANSFORMER OIL LEAKAGES 9.9.7 TWO SETS OF FIXED ENDED SPANNERS METRIC SIZES 4 TO 36 9.9.8 TWO COMPLETE SETS OF RING ENDED SPANNERS METRIC SIZES 4 TO 36 9.9.9 ONE COMPLETE SET OF ALLEN KEYS SET OF SCREWDRIVERS, CENTERING TUMMIES, FLAT ENDED TUMMIES, PIPE WRENCHES, PLIERS, HAMMERS, ADDERS, HOLE PUNCHES, OTHER TOOLS NORMALLY REQUIRED FOR SUCH WORK. SIX MM THICK 3 PLY NYLON ROPES OF 15 METRES LONG 9.9.11 HOLDITE, ARALDITE, AND QUICK SETTING M-SEAL 9.9.12 OIL TEST SET IN GOOD WORKING CONDITION HAVING 2.5MM GAUGES FOR ADJUSTING THE SPHERE GAP This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 74 - 9.9.13 FIVE kV MEGGAR PREFERABLY MOTOR DRIVEN AND CAPABLE OF READING UP TO 50000 MEGA OHMS HAND DRIVEN 500 VOLT MEGGAR CAPABLE OF READING UPTO ATLEAST 50 MEGA OHMS TWO NOS. MULTI METERS PREFERABLY DIGITAL TYPE HAVING FOLLOWING RANGES AC VOLTAGE: 0 - 2.5, 0 - 25, 0- 100, 0 - 250, 0- 1000 AC CURRENT: 0- 100 milli AMPS, 0- 1 A, 0 - 10 A 9.9.16 SINGLE/ 3 PHASE SUPPLY WITH DP SWITCHES 9.9.17 2.5 MM SINGLE CORE COPPER LEADS (APPROXIMATELY 50 METERS) THREE LITERS OF CARBON TETRA CHLORIDE 9.9.19 MUSLIN CLOTH AND WASTE CLOTH IN SUFFICIENT QUANTITY AS REQUIRED AT SITE. 9.9.20 HOT AIR BLOWER FOR DRYING PORCELAIN BUSHINGS 9.9.21 VACUUM HOSEPIPES FOR OIL CONNECTIONS SHOULD BE OF OIL RESISTANT MATERIAL. NATURAL RUBBER SHOULD NOT BE USED. THEY SHOULD WITHSTAND FULL VACUUM. NECESSARY ADAPTERS FOR CONNECTING TO FILTER MACHINE OUTLET, FILTER MACHINE, INLET, FILTER VALVES ON MAIN UNIT, BUCHHOLZ RELAY PIPE, OIL FILLING PIPE ON CONSERVATOR, ETC. 9.9.22 INSTRUMENTS FOR CHECKING HUMIDITY. ADEQUATE LENGTH OF 10 MM INNER DIA. PVC PIPE SUITABLE FOR VACUUM WITH SUITABLE ADAPTORS FOR CONNECTING THIS PIPE TO STANDARD 25 MM OR 50 MM FLANGED VALVES. 9.9.23 PULLING WINCHES / PULLING EYES 9.9.24 STEEL ROPES 9.9.25 STEEL PLATES 9.9.26 RAILS 90 LBS/YARD GREASE 9.9.27 WOODEN SLEEPERS 9.9.28 HYDRAULIC/ MECHANICAL SCREW JACKS WITH LOCKING ARRANGEMENT, CAPACITY OF EACH SHOULD BE MINIMUM 50 % OF THE TOTAL WEIGHT OF MAIN UNIT WITH OIL. POWER PACK SYSTEM TO OPERATE ALL THE JACKS SIMULTANEOUSLY 9.9.29 MEASURING TAPES MINIMUM 25 METRES LONG 9.9.30 LEVEL TUBE/ LEVEL BOTTLE (PLASTIC) 9.9.31 STAINLESS STEEL/ SUITABLE GLASS BOTTLES FOR OIL SAMPLES 9.9.32 DRY AIR CYLINDER WITH REGULATOR AND PRESSURE GAUGES 9.9.33 WELDING MACHINE 9.9.34 GAS CYLINDERS WITH NOZZLES, TORCH FOR GAS CUTTING OXY ACETYLENE 9.9.35 PRESSURE/ VACUUM EQUALISATION PIPES AND VALVES 9.9.36 ADAPTERS 80 TO 25 MM THREE NOS. EACH 80 TO 50 MM THREE NOS. EACH 50 TO 25 MM THREE NOS. EACH This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 75 - 9.9.37 VALVES: 25 MM FLANGED TYPE WITH POSITION INDICATORS AND LOCKING DEVICES 50 MM FLANGED TYPE WITH POSITION INDICATORS AND LOCKING DEVICES 9.9.38 ADAPTERS SUITABLE FOR VALVE AND PRESSURE GAUGE BUSHING LIFTING EQUIPMENTS AS SPECIFIED IN THE INSTRUCTIONS ON BUSHINGS VACUUM GAUGE RANGE 0 - 50 MILLI BAR WITH LEAST COUNT OF ONE MILLI BAR TUBE: 5 INNER DIA TRANSPARENT TUBE TO USE AS OIL GAUGE SHALL BE CAPABLE OF WITHSTANDING FULL VACUUM. 9.9.39 TINTED GLASS BOTTLES WITH GROUND GLASS STOPPER ALUMINIUM CANS WITH SCREW ON CAPS (PREFERABLE FOR LONG TRANSPORTATION DISTANCES) UNTINTED GLASS BOTTLES, WRAPPED IN NON -TRANSPARENT FOILS FOR PROTECTION AGAINST LIGHT. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 76 - PART 10 OIL SPECIFICATION TESTING PURIFICATION RECEIVING AND HANDLING FILLING ON SITE AND VACUUM OIL FILLING ON SITE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 77 - 10 OIL 10.1 GENERAL 10.2 SPECIFICATION FOR INSULATING OIL + TABLE T +TABLE T 10.2: SPECIFICATION FOR INSULATING OIL 10.1 DIELECTRIC STRENGTH 10.3 TESTING OF THE OIL + TABLE T 10.3 10.4 INTERPRETATION OF TESTS ON OIL + TABLE T 10.4 10.5 OIL SAMPLING +FIG F10.1 10.6 LABORATORY TESTING 10.7 DIELECTRIC STRENGTH + TABLE T10.5, T10.6, T10.7 10.8 OIL PURIFICATION + FIG F10.2 10.9 STORAGE 10.10 LABELLING, HANDLING, SAFETY AND DESTRUCTION OF INSULATING OIL 10.11 OIL FILLING 10.11.1 OIL FILLING RECEIVING AND HANDLING OF TRANSFORMER OIL ON SITE [PRODUCT INFORMATION 1ZBA 4601-213] 10.11.2 FINAL OIL FILLING ON SITE - ATMOSPHERIC PRESSURE [PRODUCT INFORMATION 1ZBA 4601-214] 10.11.3 OIL CONSERVATORS WITHOUT AIR CELL [PRODUCT INFORMATION 1ZBA 4601-218]] 10.12 VACUUM OIL FILLING ON SITE [PRODUCT INFORMA TION 1ZBA 4601 -215] This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 78 - 10.1 GENERAL . GENERAL REQUIREMENTS 10.2 SPECIFICATION FOR INSULATING OIL The insulating oil must meet the values given in Tables T10.1 and T10.2 below, before being filled into the tank. TABLE T 10.1: DIELECTRIC STRENGTH Breakdown voltage Operating voltage New transformers prior to the first energization (kV) IEC 156 kV / 2.5 mm Transformers having been in service IEC 156 kV / 2.5 mm > 170 50 50 70 - 170 50 40 < 70 50 30 MATERIAL SPECIFICATION FOR TRANSFORMER OIL This material specification describes the requirements on unused, uninhibited, Insulating mineral oil of standard quality and grade. It essentially corresponds to IS 335. The oil may be used in transformers and in reactors. 10.2.1. HEALTH ASPECTS The oil may be harmful. See directions for labelling, handling, safety and destruction below in 10.10 10.2.2. GENERAL REQUIREMENTS The oil shall consist of severely solvent refined and/or severely hydrotreated mineral oils. It shall be clear and free from sediment and suspended matter. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 79 - TABLE T 10.3: TIME INTERVALS FOR OIL CHECKINGS YEARS AFTER INITIAL OPERATION OPERATING VOLTAGE (kV) 73 - 170 > 170 TEST (A) TO (F) TEST (A) TO (G) (G) (G) (G) TEST (A) TO (F) (G) in 3 year intervals(G) in 5 year intervals :all tests (A) TO (F) TEST (A) TO (G) 73 0(initial operation) 1 2 3 4 5 6 afterwards 10.4 TEST (A) TO (F) TEST (A) TO (F) in 5 year intervals INTERPRETATION OF TESTS ON OIL INTERPRETATION CRITERIA: TABLE T 10.4 Criteria Operation voltage Test method Breakdown voltage > 170 kV 70 - 170 kV IEC 156 < 70 kV Water content > 170 kV ISO R 760 < 170 kV Dielectric all voltages IEC 247 dissipation factor IEC 250 Neutralization value all voltages IEC 296 Interfacial tension 10.5 in 2 year intervals(G) in 5 year intervals: all tests (A) TO (F) IEC 296 Permissible limiting value > 50 kV > 40 kV > 30 kV < 20 mg / l < 30 mg/l < 0,2 (20 %) at 90 °C < 0,5 mg KOH/g oil > 15 mN/m Measures to be taken if values are not permissible Filtering Drying (Purification) Drying (Purification) Exchange of the oil Exchange of the oil Exchange of the oil OIL SAMPLING Samples of oil must only be taken at the provided extraction points (drain valves / oil sampling valves as shown in the outline drawing). Oil sampling can be done from top, middle and lower part of tank. Suitable pipe work is provided inside transformer tank for sampling from the parts and the three sampling valves are provided at easily accessible heights . Before taking an oil sample clean the drain valve and slowly drain off at least 5 liters of oil. This oil is not suitable for sampling as it may lead to wrong evaluation of the condition of the complete oil filling. Take test samples only after the above mentioned amount of oil has been drained. Use clean and dry sample containers only. Be sure to remove all residue of cleaning fluids. Before filling the sample container, rinse it with the oil to be sampled. Protect the oil sample from light. The following sampling containers are recommended: - Tinted glass bottles with ground glass stopper - Aluminium cans with screw-on caps (preferable for long transportation distances) - Untinted glass bottles, wrapped in non-transparent foils for protection against light This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 83 - Take at least 1 litre of oil for testing. Samples to be tested for water-, gas- or air content must be taken in special containers as shown in Fig.1 to prevent leakage or penetration of gases and water. Fig. F10.1 EXAMPLE OIL SAMPLING FOR TESTING OF GASES AND WATER 1 OIL DRAIN VALVE Oil drain valve 2 ADAPTER FLANGE 3 SYNTHETIC RUBBER HOSE Synthetic rubber hose 4 HOSE CLIP Hose clip 5 GLASS BOTTLE Glass bottle 10.6 LABORATORY TESTING For a comprehensive determination of the serviceability of the insulation oil, full chemical and physical analysis is required. Such analyses are usually performed in specially equipped laboratories only. Testing of the dielectric strength is described below in 10.7 10.7 DIELECTRIC STRENGTH 10.7.1 IEC-METHOD The IEC test gap consists of two 12.5 mm (=0.5 inch) spheres, or VDE semispheres, spaced 2.5 mm (0.1 inch) apart. The test cup is filled slowly to avoid the formation of air bubbles. The oil should have a temperature of 15-25°C (59-78°F). Testing is started right after completion of the filling. The test voltage of 2 kV/s is raised six times consecutively, each time until breakdown occurs. A fter each breakdown the oil in the gap is stirred with a clean, dry glass rod of 2 mm (0.080 inch) diameter. The average value of the six results is considered to be the dielectric strength of the oil which must comply with the values of table one. If any one of the six breakdown voltages lies more than 15% below the specified value the test must be repeated with a new sample: The dielectric strength of the oil can be improved by filtering and drying. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 84 - 10.7.2 ASTM D-1816 METHOD This method is compatible with the IEC method; it also employs spherically capped electrodes spaced at 0.080 or 0.040 inch. Six breakdowns are performed and the average value of the last five is the valid value. (That of the first breakdown is disregarded). 10.7.3 ASTM D-877 METHOD This method specifies 1-inch-diameter circular disc square-edged electrodes spaced at 0.1inch. One breakdown on each of five samples is made. This method is not recommended for oil tests by ABB because it has, during repeated tests, been established as non -responsive to contamination and even to water in oil. 10.7.4 GAS ANALYSIS ON TRANSFORMER OIL Incipient faults in oil filled transformer are usually the result of electrical or thermal excess stress of either transformer oil or insulating materials. It is known that such excessive stresses produce a mixture of gases characteristic of which give an indication of the type of faults and materials associated with the faults. It is recommended that analysis of dissolved gases in transformer oil by gas chromatographic equipment is made at the time of commissioning and then at an interval of maximum six months 10.7.5 ANALYSIS METHOD 10.7.5.1 SAMPLING OF OIL FROM TRANSFORMERS Oil in transformers can be sampled through drain or sampling valve near bottom of tank. Special care shall be taken not to introduce air, foreign matter or dirty oil into sampling container. For this purpose, first 0.5 to 1.0 litre of oil from the transformer shall be over-flown through the oil container. Shape of the sampling container and sampling method shall be in accordance with standard procedures and IS: 9497 Sampled oil shall not be exposed to air before analysis. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 85 - 10.7.5.2 GAS ANALYSIS : TABLE T 10.5 Gases to be analysed and criteria for the gases found in transformer oil are tabulated below. 1 Gases to be analysed normally O2, N2 , H2,CO, CO2, CH4 2 Gases to estimate abnormality H2, CH4, C2H2,C2H4,C2H6 3 Gases to estimate deterioration CO, CO2, CH4 10.7.5.3 GAS CONTENT IN OIL BY FAULTS TABLE T 10.6 SL NO DECOMPOSIBLE GASES IN TRANSFORMER OIL TYPE OF FAULTS 1 OVER HEAT OF OIL CH4, C2H4,H2, (C2H6,C2H2,C3H6,C3H8) 2 ARCING IN OIL H2, C2H2, (CH4,C2H4) 3 OVER HEAT OF SOLID INSULATING MATERIAL OVER HEAT OF SOLID INSULATING MATERIALS ARCING OF OIL AND PAPER COMBINATION CO, CO2, ( H2, C2H4) 4 5 CH4, C2H4, CO, CO2,H2 H2, C2H2,CO, ( C2 H4) GASES IN ( ) SHOWS CONTENTS WHICH APPEAR RARELY 10.7.5.4 PERMISSIBLE CONCENTRATIONS OF DISSOLVED GASES IN THE OIL OF A HEALTHY TRANSFORMER (IN PPM) TABLE T 10.7 GAS LESS THAN 4 YEARS IN SERVICE 4 -10 YEARS IN SERVICE HYDROGEN H 2 METHANE CH4 ETHANE C2H6 ETHYLENE C2H4 ACTYLENE C2H2 CARBON MONOXIDE CARBON DIOXIDE 110- 150 50- 70 30- 50 100- 150 20- 30 200- 300 3000- 3500 200- 300 100- 150 100- 150 150- 200 30- 50 400 -500 4000-5000 MORE THAN 10 YEARS IN SERVICE 200- 300 200- 300 800 -1000 200- 400 100- 150 600- 700 9000- 12000 NOTE: 1 PLEASE REFER IS:10593 FOR DISSOLVED GAS ANALYSIS, FAULT IDENTIFICATION AND REMEDIAL ACTION. AND ALSO REFER IS 3638, IEEE STANDARD C57.104-1991, IEC 599, This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 86 - NOTE 2: TRANSFORMER OVER HEATING CAN LEAD TO CELLULOSE DECOMPOSITION AND PRODUCTION OF CO AND CO2. THESE TWO GASES ARE ALSO PRODUCED DURING THERMAL DECOMPOSITION OF OIL. THERFORE ANALYSIS OF GAS MEASUREMENT OF CO AND CO2 CANNOT BE USE D AS UNAMBIGUOUS INDICATION OF PAPER DEGRADATION. IN ADDITION TO CO AND CO2, THE AGEING PROCESS OF THE PAPER PRODUCES SEVERAL OIL SOLUBLE BYPRODUCTS, MOST NOTABLY THE FURANIC COMPOUNDS (FFA). THE MONITORING OF FURANIC COMPOUNDS BY ANNUAL SAMPLING OF OIL AND USING HIGH PERFORMANCE LIQUID CHROMOTOGRAPHY (HPLC) IS RECOMMENDED AS A PREVENTIVE MEASURE. 10.8 OIL PURIFICATION Oil purification comprises drying, de-gassing and filtering. Drying removes free and dissolved water, de-gassing removes dissolved gasses and filtering removes all floating solids above a size to be defined. Oil purification is done under vacuum. Therefore, only purification plants must be used which employ vacuum processing. Vacuum oil purification plants remove all water from the oil through evaporation under vacuum, while degassing the oil at the same time. Fig. F 10.2 shows the usual circulation method employed for field oil purification. To prevent the oil from re-absorbing moisture while in the tanks, vacuum-proof tanks should be used and a vacuum maintained above the oil surface. Thereby the oil is also prevented from being saturated with air. If no vacuum-proof tank is available, mount a silica gel breather on each tank to minimize moisture ingress. The oil purification is finished when the dielectric strength of the oil meets the specified value. Sufficient tanks must be available to hold the total oil volume. However, even then purified and nonpurified oil is mixed constantly during the purification process. In addition, it is possible that pockets of untreated oil might remain in a tank. In any case, oil circulation is rather time consuming. The "Alternating Tank Method" avoids this disadvantage, but it requires two tanks, each large enough to hold the total oil volume. The tanks should be vacuum proof, or equipped with silica gel breathers. The oil is processed from one tank into the other via the oil purification plant which considerably reduces the processing period. FIG. F10. 2 FLOW DIAGRAM FOR TRANSFORMER OIL PROCESSING 1 Oil tank (preferably vacuum tight) 2 Oil purification plant 3 Connection to vacuum pump or silica gel breather This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 87 - 10.9 STORAGE Insulating oil must be stored in clean containers designated for oil storage; Mixing with other type of oil such as used oil, cable oil, lubricating oil, fuel oil and contamination with solids must be strictly avoided. Even small quantities of contaminants can considerably impair the insulating properties of the oil. Containers used for oil storage should be individually and carefully examined for cleanliness and tightness. The containers must be protected against penetration of moisture during storage. If cleaning of containers must be done on site, the following procedure must be employed: 1) 2) 3) Rinse the container thoroughly with lead-free gasoline or kerosene until the solvent shows no discoloration after using. Drain the container completely and dry it. Immediately after drying, seal the container to avoid moisture condensation. Oil drums should be stored at site in horizontally laid down condition. In order to avoid environmental pollution special care should be taken to prevent leaking of the drums. 10.10 LABELLING, HANDLING, SAFETY AND DESTRUCTION OF INSULATING OIL 10.10.1 GENERAL This document offers general recommendations on safe handling practices for mineral-based oils and precautions to avoid adverse health effects. The legal requirements and local rules for different countries must be followed for each specific case of handling mineral based oils. It is emphasized that the supplier must forward specific advice on individual products. The specific product information is recommended to include: Transportation classification Information on composition Biological, properties Labelling Health hazard Fire and explosion hazard Preventive measures Personal protective equipment First aid Emergency action in case of fire Spillage and decontamination 10.10.2 LABELLING The labelling has to be done in accordance to the rules and guidelines issued by the various central and state government bodies from time to time. 10.10.3 SAFE HANDLING Most insulating oils have a low level of toxicity but the range of exposures can be very wide. To prevent adverse effects, the extent of possible exposure in any situation needs to be assessed and appropriate precautions established to control that exposure is at an acceptable level In all cases it is desirable to minimize exposure. The main contact areas from exposure to oils are the skin and eyes. Some processes also create oil mist which is fine enough to enter the upper and lower respiratory tract and cause contamination of body surface. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 88 - 10.10.4 PREVENTIVE MEASURES The main preventive measures can be summarized as follows: Avoid inhalation of any mist, fumes or vapour generated during use. Avoid contact with the skin. Avoid contact with the eyes. 10.10.5 PERSONAL PROTECTIVE EQUIPMENT The personal hygiene is of big importance. Therefore: - Wash hands carefully before eating and drinking. Ms -i - Change heavily contaminated clothing. 10.10.6 FIRST AID , First Aid due to inhalation is unlikely to be needed under normal use For skin contact, the first aid is to wash " with soap and water”. For eye contact, wash out eyes thoroughly with water. Better consult a doctor if there is risk of swallowing 10.10.7 SPILLAGE AND DECONTAMINATION Take up spills with dry chemical absorbent. The spill should be disposed by normal disposal methods based on state and local codes. 10.10.8 DESTRUCTION Insulating mineral oil can be destructed by burning or can be reused for other purposes than as insulating oil. Before choosing the way of destruction the oil has to be classified regarding the degree of contamination 10.10.9 1. 2. 3. 4. USED OIL CAN BE SEPARATED IN FOUR GROUPS: Non contaminated and also free of water. Contaminated oil and free of water. Oil containing water. Spilled oil 10.10.10 NON CONTAMINATED OIL Non, contaminated oil is free of particles free of water and free of PCB (Polychlorinated Biphenyles). Prior to destruction the oil has to be tested for PCB. The non-contaminated water free oil is destructed by burning. 10.10.11 CONTAMINATED OIL FREE FROM WATER Contaminated oil free from water is an oil with particles and/or containing PCB. It shall be filled in drums, approximately 209 litres of size, and sent to the local authority for disposal. 10.10.12 OIL BLENDED WITH WATER This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 89 - Oil blended with water should be sucked up and collected in a tank and delivered to the local authorities. There the water is separated from the blend and the oil can thereafter be used for asphalt production. 10.10.13 SPILLED OIL Oil spills is taken up with a dry chemical absorbent. It should be assembled and put on a platform and passed on to a container made of concrete. After the sedimentation of the absorbent the oil can be used for asphalt Production. 10.11 OIL FILLING 10.11.1 OIL FILLING: RECEIVING AND HANDLING OF TRANSFORMER OIL ON SITE PRODUCT INFORMATION 1ZBA 4601-213 ENCLOSED [THREE PAGES] 10.11.2 FINAL FILLING ON SITE -ATMOSPHERIC PRESSURE PRODUCT INFORMATION 1ZBA-4601-214 ENCLOSED, 3 PAGES 10.11.3 OIL CONSERVATORS WITHOUT AIR CELL [PRODUCT INFORMATION 1ZBA 4601-218] 2 PAGES 10.12.0 VACUUM OIL FILLING ON SITE PRODUCT INFORMATION 1ZBA 4601-215 ENCLOSED [13 PAGES]. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 90 - PART 11 ERECTION AND ASSEMBLY This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 91 - 11 ERECTION AND ASSEMBLY 11.1 GENERAL 11.2 MOUNTING OF ACCESSORIES 11.3 BOLTING/ SCREWING CONNECTIONS 11.4 PAINT 11.5 CONSERVATOR AND BRACKETS 11.6 COOLING EQUIPMENT 11.7 BUSHINGS 11.8 PIPES AND FITTINGS 11.9 OTHER ACCESSORIES 11.10 ELECTRICAL CONNECTIONS 11.11 OIL FILLING TABLES T 11.1 A MAXIMUM RECOMMENDED TORQUE T 11.1 B MAXIMUM RECOMMENDED TORQUE T 11.1 C TORQUE FOR GAKETETTED JOINTS FIGURE F11.1 ARRANGEMENTS FOR OIL FILLING - SCHEMATIC PICTURE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 92 - 11 ERECTION AND ASSEMBLY 11.1 GENERAL Commissioning of a transformer should, as a rule, be carried out by the manufacturer's experts. Should this not be possible or the user decides to have the commissioning carried out by his own personnel, the following instructions should prove as useful guidelines. However, the assembly of transformers must only be carried out by well-trained staff who is familiar with the relevant safety regulations. Also refer parts EARLIER DESCRIBED regarding arrival on site, unpacking and checking of the consignment, installation, checklist for the consignment on arrival. 11.2 MOUNTING OF ACCESSORIES The transformer should be assembled when the weather is dry. In order to minimize the penetration of humidity and dust into the inside of the tank during assembly, all openings must be re-closed as soon as possible. Caution! Blank flanges must only be removed from tank and accessories if this is necessary for the assembly and immediately before starting with the mounting procedure Separately supplied parts must be checked for cleanliness, humidity and damages before the assembly. The inside of conservator, radiator, pipes, etc. must be clean and dry. The inner coating must not be damaged. If parts are soiled, they must be cleaned thoroughly. Only those kind of cleaning agents are to be used, which do not leave any residues. Humidity can be removed by flushing with hot air or with hot transformer oil. Accessories like cooling fans, pumps, OLTC and components for supervision and control, oil level indicator, flow indicators, gauges, buchholz relay, PRV, thermometers etc. are assembled according to leaflet/ description valid for the components. After assembling locking strip/card /pin shall be removed for correct functioning of Oil Flow Indicator. 11.3 BOLTING/SCREWING CONNECTIONS All oil tight and / or vacuum tight screwing connections must be made with special care. Only the gaskets supplied by ABB or gaskets of the same quality must be used. Sealing surfaces must be checked for damages of any kind. They must also be free of rust, paint, oil and grease. Caution Roughness on surfaces resulting from transport handling must be evened. Contaminations must be removed. After the gasket and the connection parts have been fitted, the screws must only be turned a little, one by one (about 1-2 turns). This shall be repeated until all screws around the gasket are tightened. This procedure guarantees, that the pressure on the gasket is applied evenly. When remounting blanking plates, connection flanges etc., the gasketting surface shall be cleaned well and new gaskets fitted. Assemble the control cables according to the drawing of wiring system and connect the cable ends to terminal blocks in instruments, terminal boxes, junction boxes and control cabinets according to valid connection diagram. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 93 - 11.3.1 SPECIFICATION OF TORQUES FOR BOLTS AND NUTS 11.3.2 GENERAL The maximum recommended torque can be calculated on the basis of the material properties and 70% of the proof stress can be considered as limit value for tightening torque. The general classification can be made as follows. For all inspection covers, pin screws are used. 11.3.3 BOLTS AND NUTS Bolts and Nuts should conform to property class of 4.6 of IS 1367 having UTS of 4200 kg/sq mm and yield stress of 2400 kg/sqcm. EXAMPLE FOR PIPE CONNECTIONS: [HIGHLIGHTED BOLD IN TABLE 11.1A] TABLE T 11.1 A MAXIMUM RECOMMENDED TORQUE N -m BOLT SIZE UNPLATED: TORQUE N -m ZN PLATED GALVANISED M 10 M 12 M 16 M 20 M 24 M 30 M 36 20 36 90 175 300 600 1050 25 40 110 210 360 720 1260 11.3.4 Bolts and nuts should conform to property class of 8.8 of IS 1367 having UTS of 7000 kg/sqcm and yield stress of 4200 kg/sqcm EXAMPLE: FOR TANK- COVER CURB TABLE T 11.1 B: MAXIMUM RECOMMENDED TORQUE N-m BOLT SIZE UNPLATED: TORQUE N-m M 10 M 12 M 16 M 20 M 24 M 30 M 36 35 60 145 280 490 970 1700 ZN PLATED GALVANISED 40 70 170 340 590 1160 2040 11.3.5 Recommended torque for bolts/studs only for GASKETED JOINTS. Based on maximum pitch generally used for that class of bolt, for example: radiator valves, valves. TABLE T 11.1 C: TORQUE FOR GAKETETTED JOINTS BOLT SIZE TORQUE N -m M 10 M 12 M 16 M 20 M 24 20 30 50 70 100 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 94 - 11.4 PAINT Damaged paint coatings must be repaired. Only the paint supplied by ABB or equivalent must be used for this purpose. The damaged spot on the inside or outside must be smoothened to provide an even transition to the undamaged paint. The surface must then cleaned from dust, grease and other contaminations by using a chemical-cleaning agent. Commercial paint removers are suitable as chemical cleaning agents. The procedure described in the following is to be repeated at least three times, in order to obtain a protective, multiple -layer coat of paint: - The paint shall be applied in a thin and even layer. The paint must dry out completely (on the average over a period of approx.8 hours). Afterwards the repainted area must be smoothened carefully and all dust shall be removed. When the third coating has dried out completely, the repaired component can be assembled. 11.5 CONSERVATOR AND BRACKETS The conservator must be assembled ready for operating before mounting the bushings and / or other components which must be filled with oil. This guarantees that oil filling of the transformer can be started immediately and without further delay after the assembly has been completed. Conservator and brackets must be mounted to the transformer as shown in the outline drawing. The distance in height between transformer tank and conservator as indicated on the outline drawing must be strictly observed. The conservator is mounted on separate A- frame assembly as shown in the general assembly drawing. The conservator is in two compartments: one for the main transformer separated by other compartment for OLTC connection. Flxi separator bag is mounted inside main conservator compartment. Magnetic oil level gauge with its float is suitable for FLXI separator mounting. Before the conservator is assembled it shall be checked that belonging equipment, example oil level indicator- functions satisfactorily. The breather is connected to the oil conservator and it is very important that joints and couplings in the pipe between breather and conservator are airtight. 11.6 COOLING EQUIPMENT Valves which are not dismantled like shut off valves for radiators, coolers and possible headers are provided with blanking plates during transport. Check that valves are closed and remove blanking plates before assembling the coolers 11.6.1 SEPARATELY STANDING RADIATOR ASSEMBLY The radiator battery is supplied separately. The radiators are mounted to the frame along with oil pumps, oil flow indicators ,non- return device and suitable valves. Openings at the radiator frame, at the transformer and at the radiators are closed by blind flanges. They must be removed before the assembly. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 95- Caution: Desiccant bags inside the radiators, if provided, must be taken out. The gasket between radiator flange and butterfly valve must be centered. The radiator battery including all accessories (piping, valves and extension joints etc.) is erected and assembled as shown in the outline drawing. Fans must be mounted to the attachments provided for this purpose on radiators as shown in the general assembly. 11.7 BUSHINGS The bushings are mounted as described earlier. Please refer supplier‘s catalogue. 11.8 PIPES AND FITTINGS The assembly is done as shown in the outline drawing and the piping scheme. The venting pipes between the transformer tank and the Buchholz relay and between the tap changer, Buchholz relay and the protective relay rise by about 3 -7 degrees to ensure an unhindered excape of any gas from the transformer. Caution The sealing surfaces of pipes and fittings must not be subjected to any kind of mechanical stress. There is sufficient space/clearance between pipes and live parts. These spaces/ clearances must be strictly observed. Breather pipe, conservator pipes, equalizing pipes, cooler pipes etc. should all be assembled properly as per the general assembly drawing. The pipes shall preferably placed 3 to 7 degrees upward from the transformer. Internal surfaces of pipes should have been treated with oil resistant paint and external surfaces as per the specification required. 11.9 OTHER ACCESSORIES All other accessories disassembled for transport and not mentioned above must be mounted now. The assembly position is shown in the outline drawing. 11.10 ELECTRICAL CONNECTIONS All electrical connections for current transformers, supervisory equipment etc. shall be made as indicated in the Circuit Diagram of Transformer supervision. For the fans, attention must be paid to the direction of rotation. Caution Cables shall not be layed over sharp edges After the cables have been connected the compression glands at control cabinet and devices must be tightened and protected against the penetration of dust and humidity by means of a permanently elastic sealing substance. In the case of steel-armored cables, the armoring is to be earthed on one side (usually inside the control cabinet). The tank must be connected with the functional grounding of the system at two diagonally opposite points. The location of the earthing pads is shown in the outline drawing. All metal parts are to be connected to the earthing pads by means of flexible conductors. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 96 - 11.11 OIL FILLING PLEASE REFER PART 10 FIG. F11.1 ARRANGEMENTS FOR OIL FILLING - SCHEMATIC PICTURE 1 -Transformer 2 -oil treatments plant 3 -vacuum hose 4 -oil hose 5 -oil filling connection 6 -gate valve for oil treatment plant 7 -air vent valve 8 -manometer 9 -lower shut-off gate valve 10 -vac. Flange with sight glass 11 -connection full vacuum Gauge connection f. vac. Gauge 12 -oil inlet slide valve oil inlet slide valve 13 -inlet pump inlet pump 14 -filter 15 -heating heating 16 -degassing chamber degassing chamber 17 -discharge pump discharge pump 18 -oil outlet gate valve oil outlet slide valve 19 -vacuum pump vacuum pump 20 -gas ballast valve gas ballast valve 21 -vacuum valve vacuum valve 22 -vacuum gauge vacuum gauge This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 97 - PART 12 ACCEPTANCE TEST AND ENERGIZATION This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 98 - 12.0 ACCEPTANCE TESTING AND ENERGIZATION 12.1 PRODUCT INFORMATION 1ZBA 4601-216 [11 PAGES] 12.2 STANDING TIMES + TABLE T 12.1 12.3 CHECKING 12.3.1 GENERAL 12.3.2 ELECTRICAL TESTS, 12.3.2.1 PROTECTIVE DEVICES 12.3.2.2 WINDING RESISTANCE 12.3.2.3 MEGGER TEST 12.3.2.4 OIL SAMPLES 12.4 RECOMMENDATIONS FOR ENERGISING 12.5 SOAKING TIME VS. MAX. OPERATING VOLTAGE OF TRANSFORMERS 12.6 RECOMMENDED REQUIREMENTS OF INSTRUMENTS USED TESTS + T 12.2 12.7 OVER LOAD PROTECTION FOR ENERGISING UNLOADED FOR PRE-COMMISSIONING TRANSFORMER + T12.3 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 99 - 12.0 ACCEPTANCE TEST AND ENERGIZATION 12.1 PRODUCT INFORMATION 1ZBA 4601-216 [ 11 PAGES] 12.2 STANDING TIMES Since it is almost impossible to remove all gas inclusions from the insulation during evacuation and, on the other hand, small quantities of residual gas can cause internal discharges, it is necessary that the residual gas in the insulation is dissolved in the insulating oil. This is a slow process which is accelerated with rising temperature of the oil penetrating into the insulation. However, residual gases can only be dissolved in oil, if the oil itself is highly de-gassed. The following soaking periods are valid for oil temperatures of appr. 20 °C starting from the time insulating material is covered by oil until putting into service. when all TABLE T 12.1: SOAKING TIME VS. MAX. OPERATING VOLTAGE OF TRANSFORMERS Highest operating voltage (k V) 72,5 > 72,5 - 123 > 123 - 170 Standing time(days) 1 > 170 - 245 > 245 - 420 > 420 5 7 7 3 3 12.3 CHECKING 12.3.1 GENERAL Before the transformer is put into service, various checkings must be performed. 12.3.2 ELECTRICAL TESTS We recommend to perform the following checks before energizing the transformer. 12.3.2.1PROTECTIVE DEVICES A functional test has to be performed on all protective devices of the transformer. 12.3.2.2WINDING RESISTANCE Winding resistances depend on the temperatures. The measured data should be converted to the same reference (say 75 deg. C) operating temperature and compared to the data mentioned in the transformer test certificate. 12.3.2.3 MEGGER TEST Check the insulation resistance beween the windings as well as each winding to ground with a 5 kV Megger-Tester. Insulation resistance of core to ground and secondary wiring to ground are to be tested with a Megger-Tester of 1 kV only. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 100 - 12.3.2.4 OIL SAMPLES Sample has to be taken and the dielectric strength must be tested. If the results of test do not comply to the requirements, the oil must be dried and de-gassed by circulating through an oil purifying plant. 12.4 RECOMMENDATIONS FOR ENERGISING When energising an unloaded transformer, overvoltages occur on the energised as well on the notloaded side. Inner flashovers can occur even when an unloaded transformer is energized. On the energised side, overvoltages occur as a consequence of reflections. On the no-loaded side capacitive and inductive voltages can interfere with voltages which are caused by vibrations of the windings. The following recommendations should be observed while energizing an unloaded transformer in order to exclude possible dangers: 1 A transformer should always be connected to the main power supply on the HV side. If the HV-winding is provided with an on-load tap-changer, the latter should be adjusted to the tap position with the maximum number of windings ( TAP 1). 2. When energizing 3-phase-transformers, the synchronism of the circuit-breakers has proved to be important with respect to formation of switching surges. Measurements have shown that the smaller the time delay between the third pole and the second one, the smaller the over voltage level. Therefore, an examination of the synchronism of the circuit breakers should be made during the first commissioning of transformers with a voltage rating 245 kV and above.. If necessary adjustment of the synchronism must be performed. 3. Lightning arresters are the best protection against switching surges for all terminals which are not grounded. To prevent capacity transmitted voltage peaks, the low voltage terminals of generator transformers and the tertiary terminals of system transformers should be connected to capacitors installed between terminal and ground. Protection with capacitors is not necessary if the capacity to the ground of the connected busbars or cables is approximately 0.05 µF/phase. 4. Before energizing an unloaded transformer ensure that all short-circuit connections are removed from the secondary terminals. If there is a short-circuit, it must be eliminated before energising the transformer. The following TABLE T 12.3 gives recommendations for over voltage protection for energising unloaded transformers with regard to the voltage ratio. 12.5 TABLE T 12.2 RECOMMENDED REQUIREMENTS OF INSTRUMENTS USED FOR PRE-COMMISSIONING TESTS SL NO. 1 TEST Ratio, polarity and phase relationship MEASURING INSTRUMENT Voltmeter INSTRUMENT RANGE 0-500 V REQUIRED ACCURACY +/- 2 % LEAST COUNT 5V -6 This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 101 - 12.6 2 Resistance Bridge 0 - 100 ohms +/- 2 % 1 x10 ohms 3 Insulation resistance Meggar 0-50,000 M -ohms +/- 5 % 4 5 Excitation current Oil BDV Ammeter BDV meter 2.5 mm gauge 0-200 m A 0-100 k V 2.5 mm +/- 0.5 % +/-2% +/- 0.1mm 5 Mohms at the lowest scale 1mA kV GONO-GO 6 Moisture in oil Moisture meter 0-100 ppm 1 ppm 1 ppm TABLE T 12.3 OVER LOAD PROTECTION FOR ENERGISING UNLOADED TRANSFORMER Voltage ratio of the transformer HV/LV or HV/LV/TV Putting in circuit on the HV-side Lightning arrestors on all not earthed terminals> 30kV Protection capacitors on the LV-or TV-side kV 110/30 110/6,3...30 X X X 110/6,3...30/10 X X 110...245/15...27 X 245/110...132/10 X 345...525/15...27 X 345...525/110...245/10...20 X 750/15...27 X 750/245...525/30 X X X X X X X X X X X X X Examination of the synchronism of the circuit breakers in case of a 3 -phase transformer X X X X X X = is recommended This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 102 - PART 13 FIELD TEST RECORD AND FIELD QUALITY PLAN This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 103 - FIELD TEST RECORD GENERAL CONTENT [REF:1ZBA 4601-217] 13.1 RATIO TEST 13.2 CHECK OF VECTOR GROUP INSULATION TEST CHECK OF POTENTIAL CONNECTION BETWEEN TANK AND TURRET 13.5 POLARITY CHECK OF CURRENT TRANSFORMERS 13.6. 13.7. CHECK OF WINDING TEMPERATURE CIRCUITS OIL TEST 13.8. OPERATIONAL TEST OF SUPERVISORY EQUIPMENT 13.9. OPERATIONAL TEST OF OTHER EQUIPMENT 13.10 FIELD QUALITY PLAN This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 104 - 13.0 FIELD TEST RECORD : GENERAL CONTENT [ REFERENCE: PRODUCT INFORMATION 1ZBA 4601-217] Order No Transformer type Tap-changer type Motor-drive Mechanism type Serial No Serial No Serial No CONTENT NOTE: MARK X for the respective test, which are carried out under Yes. Yes 13.1. No Ratio test 13.1.1 Windings 13.2. Check of vector group 13.3. Insulation test 13.3.1 Windings 13.3.2 Current Transformers 13.3.3 ... .............................................................................. ... Control-circuit cabling and auxiliary power cabling ... _________________________ 13.3.4 Core 13.4 Check of potential connection between tank and turret _______________________ 13.5. Polarity check of Current Transformers 13.6. Check of winding temperature circuits 13.7. Oil test 13.8. Operational test of supervisory equipment 13.9. Operational Test of other equipment 13.9.1 Coolers 13.9.2 On-load tap-changer with motor drive mechanism Customer represented at test This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 105 - 13.1 RATIO TEST 13.1.1 WINDINGS Tap changer Position Magnetizing on __-kV side Volt No load current measured on ___kV side Calculate d voltage Volt u-v Volt u-v-w Volt u-w Volt v-w measured on ___kV side Volt u-v Volt u-w Volt v-w Calcula ted voltage Volt u-v-w 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Voltage between phase - 0 checked? Yes No This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 106 - 13.2 CHECK FOR VECTOR GROUP Connect 1U with 2u Magnetized on kV side Measured voltage U between Vv Ww Connect 1U with Magnetized on Uv Vw Wv Connection UV Vw Wv Connection 2u kV side Measured voltage U between Vv Ww The vector group corresponds with connection diagram No Remarks 13.3 INSULATION TEST 13.3.1WINDINGS Megger kV Note Maximum 5kV megger Terminal Terminal Terminal Terminal Terminal Terminal to earth to earth to earth to earth to terminal to terminal M ohm M ohm M ohm M ohm M ohm M ohm Terminal to terminal M ohm Weather conditions: This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 107 - 13.3.2 CURRENT TRANSFORMERS Note Maximum 1kV MEGGER Location: Location: Location: Location: Location: Location: Location: Weather conditions: Megger Terminal: Terminal: Terminal: Terminal: Terminal: Terminal: Terminal: KV to earth to earth to earth to earth to earth to earth to earth M-ohm M-ohm M-ohm M-ohm M-ohm M-ohm M-ohm 13.3.3 CONTROL-CIRCUIT CABLING AND AUXILIARY POWER CABLING Megger V Note Maximum 1kV megger Cables to earth (min value) M ohm 13.3.4 CORE Megger___________ V Note Maximum 1kV megger The Megger must be of an of ABB Transformer approved type Core - earth ________________M ohm Yoke beams -earth ________________Mohm Weather conditions_____________________________________________________________ REMARKS:___________________________________________________________________ 13.4 CHECK OF POTENTIAL CONNECTION BETWEEN TANK AND TURRET The potential connection between tank and turret has been checked with buzzer This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 108 - 13.5 POLARITY CHECK OF CURRENT TRANSFORMERS Check of Current Transformers according to diagram No Location/terminal Location/terminal Location/terminal Location/terminal Location/terminal Location/terminal 13.6 CHECK OF WINDING TEMPERATURE CIRCUITS CURRENT TRANSFORMER FOR Location Location Location Measured resistance for: Current transformer ohm ohm ohm Instrument ohm ohm ohm This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 109 - 13.7 OIL TEST The oil level checked in Transformer Tap-changer/diverter switch Other separate compartments The oil system has been de aired Date Oil samples are taken from Oil conservator Transformer/reactor tank Cooling group No Cooling group No Cooling group No Breakdown voltage kV Breakdown voltage Breakdown voltage Breakdown voltage Breakdown voltage kV kV kV KV Cooling group No Breakdown voltage kV Oil test equipment type Electrode distance with electrodes mm Oil samples for dissolved gas analysis have been taken REMARKS This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 110 - 13.8 OPERATIONAL TEST OF SUPERVISORY EQUIPMENT Alarm circuit tested to Control Control circuit room Cabinet No/OK No/OK Trip circuit tested to Control Breaker circuit Cabinet No/OK No/OK No/OK No/OK Gas detector relay transformer Gas detector relay tap changer Oil level indicator tap changer High Low Oil level indicator transformer High Low Pressure relief valve for transformer Pressure relay for transformer Pressure relay for tap changer Flow indicators for coolers Cooler group 1 min oil flow max. oil flow Cooler group 2 min oil flow max. oil flow Manometers for coolers Cooler group 1 min oil pressure Max. oil pressure Cooler group 2 min oil pressure max. oil pressure No/OK Thermometer for top oil Set for alarm Deg Set for trip Deg Set for start of Cooler group 1 Deg Cooler group 2 Deg Thermometer for kV winding Set for alarm Deg Set for trip Deg Set for start of Cooler group 1 Deg Cooler group 2 Deg Thermometer for kV winding Set for alarm Deg Set for trip Deg Set for start of Cooler group 1 Cooler group 2 No/OK Deg Deg This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 111 - 13.9 OPERATIONAL TEST OF OTHER EQUIPMENT 13.9.1 COOLERS 1. 2. 3. Pump rotation direction checked Fans rotation direction checked Over current protection tipped at 2 -phase connection: Fan No After (sec.) Current setting (A) Pump No After (sec) Current setting (A) 1 2 3 4 5 7 8 9 Alarm obtained for tipped current protection at terminals _______ in the control cabinet. 13.9.2 ON-LOAD T AP-CHANGER WITH MOTOR DRIVE MECHANISM The position indicators in motor drive mechanism and tap changer indicate the same position Shaft coupling lubricated with grease Gear box filled with lubricant to correct level Motor drive mechanism checked and test runned lubricated end position contacts local/remote control interlocking switch manually and with the crank assembled setting of motor protection tripping time for blocked motor pressure relay tested heating element connected and In operation This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 112 - 13.10 FIELD QUALITY PLAN SL NO CHARACTERISTICS/ ITEMS 1 1.1 CHECK ON RECEIPT MAIN EQUIPMENT TEMPORARY STORE IF THE PERMANENT LOCATION IS NOT READY ,ENSURE THAT TEMPORARY STORAGE IS DONE IN A SUITABLE LOCATION CHECK THAT THE EQUIPMENT IS NEVER STORED IN A POLLUTED AREA CHECK THAT THE EQUIPMENT IS KEPT ON SLEEPERS/ ROLLER MOUNTED FACILITATING FREE FLOW OF AIR UNDERNEATH. FOR GAS FILLED STORAGE , PERIODICALLY CHECK THE GAS PRESSURE AND ENSURE THE READING OF PRESSURE AND TEMPERATURE AS LOGGED 1.1.1 1.1.2 1.1.3 1.1.4 1.1.5 1.1.6 1.1.7 THERMOMETER , FLOW INDICATORS ETC. CHECK THAT THESE ARE STORED WITHOUT DAMAGE TO FRAGILE PARTS. OIL DRUMS , CHECK THAT THE DRUMS ARE STORED IN PROTECTD AREA AND ARE NOT PLACED ON THEIR SIDE FACE OIL LEVEL GAUGE , BUCHHOLZ RELAY, SILICA GEL BREATHER ETC. CHECK THAT THESE ARE STORED WITHOUT DAMAGE TO FRAGILE PARTS TYPES OF CHECK QUANTUM/ FREQUENCY OF CHECK ACCEPTANCE CRITERIA REMARKS PHYSICAL AT THE TIME OF STORAGE HARD LEVEL GROUND -- AT THE TIME OF STORAGE UNPOLLUTED -- PHYSICAL PHYSICAL READING OF PRESSURE GAUGE AND RECORD PHYSICAL PHYSICAL PHYSICAL AT THE TIME OF STORAGE DAILY AT THE TIME OF STORAGE AT THE TIME OF STORAGE 100 % AT THE TIME OF STORAGE 100 % NORMAL AIR DIRECTION SHALL BE CONSIDERED -- MAINTAIN GAS PRESSURE OF 0.1 TO 0.2 Kg/Sqcm USE PRESSURE GAUGE AND RECORD ON LOG SHEET NO PHYSICAL DAMAGE -- SEALS INTACT , NO LEAKAGES -- NO PHYSICAL DAMAGE -- This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 113 - SL. NO CHARACTERISTICS/ ITEMS 1.1.8 COOLING SYSTEM, CHECK THAT ITEMS CONNECTED AS PUMP MOTOR ARE STORED INDOOR CHECK THAT SUPPORTS AND FABRICATED PARTS ARE NOT PLACED DIRECTLY ON GROUND BUT KEPT ON WOODEN BATTONS/PLANKS BUSHINGS- CHECK THAT BUSHINGS ARE STORED IN RESPECTIVE CASES IN CLOSED PLACE MARSHALLING BOXESCHECK THAT THE MARSHALLING BOXES ARE STORED IN CLOSED PLACE IN THE CASES LOOSE ITEMS-CHECK THAT LOOSE ITEMS ARE STORED IN CLOSED PLACE COMPLETE RECEIPT/STORAGE CHECK LIST ERECTION CHECK DOCUMENT CHECK FOR AVAILABILITY OF ALL RELEVANT DRAWINGS AND DOCUMENTS SITE PREPARATION CHECK THAT THE TRANSFORMER YARD IS PROPERLY LEVELED 1.1.9 1.1.10 1.1.11 1.1.12 1.1.13 2.0 2.1 2.2 2.3 2.4 CHECK THAT RAILS ARE LEVELLED AND EXACT LOCATION OF ROLLER ASSEMBLY IS MARKED IN PERMANENT LOCATION OF THE TRANSFORMER WHERE APPLICABLE. OIL FILTERATION PLANT- CHECK FOR AVAILABILITY OF OIL FILTERATION PLANT OF ADEQUATE CAPACITY TYPES OF CHECK PHYSICAL PHYSICAL PHYSICAL PHYSICAL QUANTUM FREQUENCY OF CHECK AT THE TIME OF STORAGE 100% AT THE TIME OF STORAGE 100% AT THE TIME OF STORAGE AT THE TIME OF STORAGE ACCEPTANCE CRITERIA REMARKS NO PHYSICAL DAMAGE --0 NO PHYSICAL DAMAGE COVERED STORE -- COVERED STORE PHYSICAL AT THE TIME OF STORAGE NO PHYSICAL DAMAGE AS LISTED AS LISTED INSTRUCTION MANUAL PHYSICAL VERIFICATI ON ONCE BEFORE ERECTION VISUAL ONCE BEFORE ERECTION COMPLETE SET OF ERECTION DRAWINGS, INSTRUCTIONS, TEST CERTIFICATES FOUNDATION DRAWING PHYSICAL ONCE BEFORE ERECTION FOUNDATION DRAWING USE LOG SHEET ONCE BEFORE ERECTION OPERATION MANUAL FOR FILTERING MACHINE USE LOG SHEET PHYSICAL USE CHECK LIST CHECK LIST USE LOGSHEET This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 114 - SL. NO 2.5 2.6 CHARACTERISTICS/ ITEMS CHECK FOR FACILITIES FOR OPERATION OF FILTER MACHINE SUCH AS: -PROPER POWER SOURCE -CABLE OF ADEQUATE CAPACITY AND LENGTH -HOSE PIPE OF ADEQUATE CAPACITY AND SUITABLE ENDS ERECTION CHECK CHECK FOR AVAILABILITY OF SUITABLE AND ADEQUATE QUANTITY OF OIL TYPES OF CHECK QUANTUM FREQUENCY OF CHECK ACCEPTANCE CRITERIA PHYSICAL ONCE BEFORE ERECTIONAT THE TIME OF STORAGE PHYSICAL VERIFICAT ION QUANTITY CHECK ONCE BEFORE ERECTION RATING AND DIAGRAM PLATE AND GA.DRAWING OPERATINN MANUAL FOR FILTERING MACHINE 2.7 CHECK THAT ALL ITEMS AND ACCESSORIES ARE INSPECTED FOR DAMAGE PHYSICAL 100% BEFORE ERECTION PACKING LIST NO DAMAGE 2.8 CHECK THAT THE PRE- PHYSICAL 100% BEFORE ERECTION FOUNDATION DRAWING, LAYOUT DRG. IN LINE WITH SPECIFICATION S ERECTION SURVEY HAS BEEN CARRIED OUT TO ENSURE THAT TRANSFORMER YARD IS READY IN ALL RESPECTS AND TO VERIFY AND ACHIEVE THE POSITION OF VARIOUS EQUIPMENTS TO BE CONNECTED, LEVEL OF FLOOR/RAILS, POSITION OF FOUNDATION BOLTS, POCKETS AND CUTOUTS, ALIGNMENT OF CABLE TRENCHES ETC. 2.9 CHECK THAT PROPER TOOLS AND TACKLES ARE USED FOR TRANSPORTING VARIOUS ITEMS TO ERECTION SITE PHYSICA L 100% BEFORE COMMENCEMENT OF ERECTION INSTRUCTION MANUAL REMARKS USE LOG SHEET ALSO OIL SPEC. -- -- This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 115 - SL. NO CHARACTERISTICS/ ITEMS 2.10 CHECK THAT TRANSFORMER IS JACKED UP USING ONLY THE JACKING LUGS PROVIDED FOR THE PURPOSE AND THAT NO OTHER PARTS ARE USED FOR THIS PURPOSE PHYSICAL VERIFICA TION 2.11 CHECK THAT ROLLERS (WHEREVER APPLICABLE) ARE GREASED PROPERLY BEFORE ASSEMBLING UNDER THE TRANSFORMER TANK. PHYSICAL 100% BEFORE ERECTION ROLLER ASSEMBLY DRAWING AND FREE MOVEMENT OF ROLLERS. 2.12 CHECK THAT ITEMS TO BE MOUNTED ARE CLEANED WITHOUT LEAVING ANY LOOSE FIBRES WITH DRY CLOTH. CHECK THAT OIL FILLING IS DONE UNDER VACUUM STRICTLY AS PER INSTRUCTION CHECK THAT BUCHHOLZ RELAY AND CONSERVATOR ARE NOT SUBJECTED TO FULL VACUUM PHYSICAL 100% BEFORE ERECTION NONFLURRY DRY CLOTH 2.13 2.14 2.15 CHECK THAT THE TRANSFORMER HAS BEEN PROPERLY DRIED BY TESTING OIL SAMPLE FROM TANK AND OLTC DIVERTER SWITCH FOR -BDV OF OIL -MOISTURE CONTENT TYPES OF CHECK QUANTUM FREQUENCY OF CHECK 100% BEFORE ERECTION ACCEPTANCE CRITERIA REMARKS NO CRACKS SHOULD APPEAR NEAR JACKING LUGS -- OPERATIO NAL ONCE DURING OIL FILLING BDV AND MOISTURE PPM AS PER OIL SPEC. USE VACUUM GAUGE OPERATIO NAL DURING PROCESS-ING REFER INSTRUCTI-ON MANUAL OPERATIO NAL AFTER COMPLETION OF OIL CIRCULATION IN TANK RELEVANT VALVES TO BE CLOSED AS PER VALVE DIAGRAM PLATE AS PER INSTRUCTIONA L MANUAL. USING OIL TESTING SET FOR BDV AND PPM KIT FOR MOISTURE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 116 - SL. NO CHARACTERISTICS/ ITEMS 2.16 ENSURE THAT THE OIL FILLING IN THE CONSERVATOR (AIRCELL TYPE)IS DONE AS PER THE OIL FILLING INSTRUCTION GIVEN AT SPECIFIED RATE AND CHECK THE WORKING OF PRESSURE RELIEF VALVES. CHECK FOR ANY DAMAGE TO CT S AND CHECK CLEANINESS CHECK THAT CT SECONDARY LEADS ARE ALL IN TACT AND KEPT SHORTED UNTIL RESPECTIVE LEADS ARE CONNECTED COMPLETE ERECTION CHECK LIST 2.17 2.18 2.19 2.20 3. 3.1 3.2 3.3 COMPLETE PRECOMMISSIONING CHECK LIST COMMISSIONING CHECKS SILICA GEL COLOUR OIL LEVEL IN CONSERVATOR BUSHING , BREATHER HOUSING, OLTC DIVERTER EACH CHECK THAT THE MARSHALLING BOXES ARE PROVIDED WITH GASKET AND BOXES ARE MADE DUST PROOF TYPES OF CHECK PHYSICAL QUANTUM FREQUENCY OF CHECK 100% BEFORE ERECTION ACCEPTANCE CRITERIA REMARKS INSTRUCTION MANUAL USE LOG SHEET PHYSICAL 100% BEFORE COMMISSI-ONING NO DAMAGE LOG SHEET PHYSICAL 100% BEFORE COMMISSIONING NO DAMAGE USE LOG SHEET AS LISTED AS LISTED INSTRUCTION MANUAL USE CHECK LIST AS LISTED AS LISTED INSTRUCTION MANUAL USE CHECK LIST PHYSICAL 100 % BLUE USE LOG SHEET PHYSICAL 100% UPTO THE MARKING ON GAUGE PHYSICAL 100 % PROPER CLOSING PHYSICAL 100% WIRING DRAWING USE LOG SHEET USE LOG SHEET 3.4 CHECK THE CORRECTNESS OF THE WIRING FOR CONNECTION TO OTI COOLERS, FANS USE LOGSHEET This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 117 - 3.5 3.6 3.7 CORRECTNESS OF WTI, OTI, MOG, BUCHHOLZ RELAY, COOLER CONTROL CONTACTS OIL SAMPLE FROM TRANSFORMER BEFORE ENERGISING SHOULD BE TESTED FOR BDV AND MOISTURE CONTENT IR VALUES 3.8 MAGNETISING CURRENT AT 400 VOLTS FROM HV SIDE 3.9 CHECK THAT FOR PURPOSE OF VARIOUS PROTECTION AND ALARM ARE CARRIED OUT AS PER INSTRUCTION MANUAL AND RECORDED IN LOG SHEET COMPLETE COMMISSIONING CHECKLIST TRIAL OPERATION FOR 24 HOURS AND CHECK FOR ANY ABNORMAL NOISE / TEMPERATURE RISE 3.10 3.11 OPERATIO NAL 100% LOG SHEET OPERATIO NAL BEFORE ENERGISING AS PER INSTRUCTION MANUAL OPERATIO NAL USING MOTORISE D 2500VOLTS MEGGAR OPERATIO NAL 100% TEST CERTIFICATE VALUE FOR GENERAL COMPARISON 100% OIL TEST SET FOR BDV, PPM KIT FOR MOISTURE USE MILLI AMMETER OPERATIO NAL 100% INSTRUCTION MAUAL CONTACTS SHOULD CLOSE USE LOG SHEET AS LISTED AS LISTED INSTRUCTION MANUAL USE CHECKLIST OPERATIO NAL 100% SATISFACTORY OPERATION FOR 24 HOURS USE LOG SHEET This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 118 - PART 14 TROUBLE SHOOTING This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 119 - 14 TROUBLE SHOOTING 14.1 MAINTENANCE AND REVISION 14.1.1 GENERAL 14.1.2 CHECK LIST - MAINTENANCE 14.1.3 TROUBLE SHOOTING 14.2 STORAGE 14.2.1 TRANSFORMER DISASSEMBLED TRANSFORMER WITH LOWERED OIL LEVEL TRANSFORMER WITH DRY-GAS FILLING 14.2.2 TRANSFORMER READY FOR OPERATING 14.2.3 ACCESSORIES 14.2.4 CHECKING LIST STORAGE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 120 - 14 TROUBLE SHOOTING 14.1 MAINTENANCE AND REVISION 14.1.1 GENERAL ABB transformers are designed to reduce maintenance to a minimum. In order to ensure trouble-free operation, maintenance works must be carried out in regular intervals. Checking list "Maintenance" shows the recommended time intervals for maintenance. Detailed instructions concerning maintenance works of various accessories can be found in the catalogues of the respective manufacturers, which are included in this manual. ( PART 4) This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 121 - CHECKING LIST - MAINTENANCE SUBJECT CHECK TIME PERIOD YEAR Insulating oil Oil tightness Oil level Venting devices Earthing devices Shut-off devices Buchholz relay Dielectric strength Moisture content Neutralisation value Interfacial surface tension Water content Sludge content Gas analysis Tank Conservator Cooling equipment Piping Bushings Cable sealing ends Cable boxes Buchholz relay Gate valves Valves Tank Conservator Bushings Cable sealing ends Cable boxes Thermometer pockets Tank Cooling equipment Intermediate piping Bushings Piping Buchholz relay cable sealing ends All metal parts Tank Motors Star points Surge arresters Control cabinet Steel armoured cabling In position "service" Direction of oil flow Float Contacts gas sampling device Functional test MONTH S 3 3 3 3 3 3 3 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 6 6 6 6 6 6 REMARKS if applicable if applicable if applicable if applicable Release vent screws until oil emerges. Afterwards screw plugs tight if applicable 1 6 6 6 6 6 6 6 as required if applicable if applicable see plan "Position of shut-off devices" (if provided) 1 1 1 1 1 if applicable This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 122 - 14.1.2 CHECKING LIST MAINTENANCE CONTD… SUBJECT CHECK TIME PERIOD REMARKS year Dial-type Thermometers transformers Oil level indicators Breathers Internal wiring Corrosion Protection Cleanliness Terminal box On-load tap Changer Protective relay for OLTC Thermostat Resistance thermometer Pressure relief device months Contact setting Position of maximum pointer Functional test 1 1 1 Polarity Ratio Short-circuit connection Contact setting Float Functional test Silicagel Oil level Venting pipes Insulation resistance Correct wiring connections Paint Blank steel parts 3 3 3 1 1 1 Bushings Fittings Indicating devices Tank cover Fans Connections [as per EASUN-MR CATALOGUES] Setting see Technical data 1 1 1 3 3 1 1 With 1000 V Megger Tester, Touch-up Grease 1 1 1 1 Remove loose parts, if applicable 1 See instructions of the manufacturer Functional test Functional test 1 1 Functional test 1 See instructions of manufacturer NOT PROVIDED SEE MANUFACTURERS CATALOGUE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 123 - 14.1.3 TROUBLE SHOOTING CONTINUED Protective& FAULT Possible cause supervisory instruments, components Buchholz relay Buchholz Oil loss relay Violent oil surge tripping due to inside flashover. Violent gas generation due to inside failure. Violent vibration Fault tripping Protective Tripping EASUN-MR device for due to CATALOGUE OLTC strong oil surge Resistance thermo meter Oil temperat-ure too high Thermostat Dial type thermometer for oil or winding temp. Winding or oil temp. too high Transformer overloaded or inadequate cooling. Incorrect temperature adjustment Remedial measure Detailed description Maintain the shutdown status. Carry out tests and measurements as described above. Vent the transformer and put it back into operation when faults cannot be found or faults have been eliminated Maintain the shutdown status. Check the tripping mechanism. Remove and check the diverter switch.Reset the tripping mechanism and put the transformer into operation Reduce load of the transformer Put fans or cooling equipment in service Clean the cooling equipment Check the position of butterfly valves Adjust incorrect temperature setting. Check the thermometer by comparative measurements Check the electrical connections and the tripping mechanism Check control devices for cooling equipment Check current transformers and thermometers Operating Instructions of OLTC Operating. instructions of thermometer manufacturer This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 124 - 14.1.3 TROUBLE SHOOTING (CONTINUED) Protective and supervisory instruments Various components Oil level indicator FAULT Possible cause Remedial measure Detailed description Oil level too low Not enough oil (low temperature or oil loss) Gate valve closed , pipe clogged,, pipe leaky,oil circulation pump faulted(no voltage or voltage too low, defective winding,incorrec t direction of rotation, bearing damage) Conservator pipe shut-off or clogged. Electric flashover inside the tank Check for tightness Top-up oil Operating instructions of manufacturer. Operating instructions. Oil flow monitor No Oil flow Pressure relief device Internal tank pressure too high Top-up cooling water to the required level Check the electrical connections Check the pipes and shut-off devices Check the transformer as described in "Buchholz relay Above. Operating instructions. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 125 - 14.1.3 TROUBLE SHOOTING (CONTINUED) Protective & supervisory instruments, components Motor drive for OLTC Fault Possible cause Remedial measure Drive cannot be operated electrically No voltage supply at motorprotective switch Motor protective switch not in operating position. Open circuit on one or more motor phases Brake contactor stuck Check supply feeders. See operating instructions of OLTC Close motor protective switch Correct it. Emergency stop button is on or stuck. Motor current excessive due to overload or phase failure Repair or replace emergency stop button Check drive for stiffness with crank handle. Request a factory engineer, if a mechanical fault in the tapchanger is suspected Adjusting device defective Repair adjusting device; operate multiple the tap changer once a year over all positions (extraction points).Check the transformer as described for the Buchholz relay Replace dehydrating agent. Replace glass cylinder or seal properly. seal pipe leaks, check the oil for moisture content. Flush the conservator with dry air Drive keeps on running Motor protective switch trips during operation of motor drive Off-circuit tap changer Operation not possible Gas in Buchholz relay Carbon formation on contacts Dehydrating breather The drying crystals turn from blue to pink and then to white from below from the top in general High atmospheric humidity, glass cylinder leaky. Moisture in conservator, pipe leaky, glass cylinder leaky.Moisture in conservator, pipe leaky, glass cylinder leaky. Glass cylinder burst, maintenance interval Clean or replace This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 126 - 14.1.3 TROUBLE SHOOTING (CONTINUED) Protective and Fault Possible cause supervisory instruments Various components Electrical Breakdown voltage too low. Breather inoperable or breakdown voltage Water content too high transformer in service of the oil very low. Leaks in water cooling system. Water pressure reducer inoperable. Protective spark gap on bushings Frequent operation Electrical arcing distance no longer correct Terminal lugs on bushing control Control cabinet Discoloration of connecting parts Electrical apparatus does not operate properly.Contacts corroded contaminated.Appa -ratus housing bent Poor contact making Earthing connection Earthing line interrupted Excessive humidity in control cabinet. Water or dust inside the cabinet. Excessive high temperature in the cabinet Excessive currents due to external flashovers. Impermissible current loops through multiple earthing. Remedial measure Put breather into operation. Seal or repair coolers. Contact manufacturer; dry the oil, if necessary Adjust the clearance between the arcing horns and screw them tight Clear the contact faces. Tighten the screws Set the cabinet heater to a higher temperature Seal the cabinet door, fit a dust filter if necessary.Protect the cabinet against solar irradiation; provide for better ventilation Clean the contacts, tighten the screws and check the electrical distances. Open up current loops. Only one earthing with a sufficient cross section This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 127 - 14.1.3 Protective and supervisory instruments Various comp . Presssure gauge for HV-bushing Pressure monitor for HV-bushing Air flow monitoring TROUBLE SHOOTING( CONTINUED) Fault Possible cause Remedial measure Oil pressure in HVbushing too high Incorrect contact adjustment. Bushing overloaded, oil temperature too high due to solar irradiation Correct the contact adjustment Incorrect contact adjustment Bushing overloaded, oil temperature too high due to solar irradiation. Violent vibration on transformer Correct the contact adjustment Oil pressure of the HV-bushing too high No air flow or reduced air flow Protective screen iced up or clogged. Cooler clogged or very dirty. Fan motor faulty (winding defective or overheated, bearing damage).Incorrect direction of rotation Check the reading. Check the bushing; reduce the transformer load, increase the cooling effect Check the pressure monitor and reset the auxiliary switch. Check the bushings; reduce the transformer load; increase the cooling Clean protective screen, open the frost flaps Clean coolers Check the supply leads Repair fans Oil sightpot Traces of oil on the water surface Leakages in the oil circuit or the water cooling system Seal and repair coolers This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 128- PART 15 STORAGE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 129 - 15. STORAGE 15.1 TRANSFORMER DISASSEMBLED : WITH LOWERED OIL LEVEL 15.2 TRANSFORMER WITH DRY-GAS FILLING 15.3 TRANSFORMER READY FOR OPERATION ACCESSORIES 15.5 CHECK LIST FOR STORAGE This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 130 - 15 STORAGE 15.1 TRANSFORMER DISASSEMBLED : WITH LOWERED OIL LEVEL A transformer with lowered oil level (i.e. the entire insulation of the core and coil assembly has to be completely covered with oil) must be provided with a dehydrating breather during storage, in order to avoid the ingress of humid air in the transformer tank. In case heating elements are installed in the motor drive cabinet, and control cabinet, they must be connected to a power supply system to prevent the formation of condensation water. The heating elements shall be checked at regular intervals. The silica-gel content of the dehydrating breathers is to be checked every 2 weeks . When more than 2/3 of the blue silica-gel filling have turned light, the filling has to be exchanged. However, it can be reused after having been dried at 120 °C (24 hrs.). At the same time the tank has to be examined for oil traces. Should any leakage be detected, they have to be sealed immediately. Before commissioning and after a long storage the oil is to be checked for moisture content. Motor drive cabinet and control cabinet have be checked for Condensation of water 15.2 TRANSFORMER WITH DRY-GAS FILLING In case it is not possible to store the transformer completely mounted or with oil filling, the transformer is to be filled with dry gas in order to prevent the ingress of moisture during storage. After the transformer has been filled with dry gas/ air, one or several gas cylinder attached to the tank has to be connected. In order to provide a constant positive pressure in the transformer tank, the gas cylinders are connected via pressure-reducing and pressure relief valve (see also chapter on transport( PART 5 ) in this instruction manual). The valves have been adjusted to maintain a positive pressure in the tank ie approx. 0.25 bar. The pressure is to be checked every two weeks. Caution: The pressure must not fall below 0.05 bar. In case of leakages in the transformer tank have been detected or in the case of high pressure loss in the gas cylinders, the leakage has to be sealed. If there are heating elements provided in the motor drive cabinet and control cabinets, they have to be connected to a power supply system, in order to avoid the formation of condensation water. The storage with dry-gas filling should be not be longer than 6 months. If the storage exceeds 6 months, the ABB must be contacted. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 131 - 15.3 TRANSFORMER READY FOR OPERATION This type of storage is to be preferred over all other alternatives. After arriving at the place of installation the transformer should be assembled completely and filled with oil. The heating elements installed in the motor drive cabinet and control cabinet have to be connected to a power supply system, in order to prevent the formation of condensation water. The heating elements have to be checked at regular intervals. The condition of the silica-gel content in the dehydrating breathers has to be checked every 2 weeks. Should more than 2/3 of the blue silica-gel filling have turned light, the filling must be exchanged. However, it can be reused after drying at 120 °C (24 hrs.). At the same time it is necessary to check the oil level in the conservator, and to examine the tank for oil traces. Should any leakage be detected, they have to be taken care of immediately. Before commissioning and after long storage the oil is to be checked for humidity. 15.4 ACCESSORIES The accessories shall be stored in compliance with the printed-on storage instructions and the hints given in the brochures for the individual accessory parts. In principle the accessories should be stored in their respective transport packing in dry rooms. Possibly, dessicant bags have to be enclosed in the crates. All accessories shall be protected against damages. This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 132 - 15.5 CHECK LIST FOR STORAGE SUBJECT Insulating oil Oil level Oil tightness Earthing Fans Control cabinet Oil circulation pumps Silica gel breathers Cleanness Corrosion protection Bushings CHECK Dielectric strength Moisture content Conservator Tank Conservator Piping Buchholz relay Bushings Tank Test run Heating Time periods YEAR MONTH 1 1 1 1 1 1 1 6 3 1 Trial run 3 Silicagel 1 Cooler Bushings Tank Final coat 1 1 1 1 During storage or at time 1 of handling the bushing can be placed: - either in horizontal position - on inclined, but with the head at the highest point Please take care that the oil level indicator always directs to the bottom. A respective label is fixed on every bushing or shipping crate. REMARKS 1 hour 1 hour Touch up Before the bushing is assembled on the tank, the whole surface should be dried and cleaned thoroughly. Observe standing times This document must not be copied without our written permission, and the contents thereof must not be imparted to a third party nor be used for any unauthorized purpose. ABB LIMITED, MANEJA , VADODARA, GUJARAT, INDIA Page - 133 -