The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. a M50 001 Tripping characteristic Manual Motor Starter MS 497 36...50A Tripping class 10 Freigegeben: 30-01-02 KlWi Geprüft: 30-01-02 GuNi Zust. Stelle: STO/CLP 1SA M50 0503 F 0006 Tripping characteristic with three pole load and two pole load based at cold state at any setting. With three pole load and two pole load and currents higher than 3 times of current setting the tolerance of the tripping time is +-20%. DIN VDE 0165, IEC 60079-14, EN 50019+A1...A5. Overload release The tripping time of the short-circuit release and the damage curve of the overload release are based on the max. rated operational current. Maximum permissable fuse if the rated short-circuit breaking capacity is exceeded three pole load two pole load Damage curve of Seconds Tripping time Tripping time Die Weitergabe und Vervielfältigung dieser Unterlage, sowie die Verwertung und Mitteilung ihres Inhaltes ist nicht gestattet, soweit nicht ausdrücklich zugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz. Alle Rechte vorbehalten, besonders für den Fall der Patenterteilung oder OEM-Eintragung. Overload release Multiples of current setting three pole load two pole load 3x 4x 5x 6x 7,2x 8x 35,0 sec. 20,0 sec. 13,0 sec. 9,5 sec. 7,0 sec. 6,0 sec. 30,0 sec. 16,5 sec. 11,0 sec. 8,0 sec. 5,9 sec. 5,0 sec. Multiples of current setting Short-circuit release