line discharge class 4 construction design I Clase de descarga de linea 4 Forma constructiva I Metal oxide surge arrester Surge arresters for high voltage systems Type series SB 6/20.4-I to SB 420/20.4-I Field of application Protection of transformers, switch-gears and plants against atmospheric and switching overvoltages Selection of metal oxide surge arresters The selection of the rated and the continuous operating voltage of the arresters is depending on the neutral performance of the networks. Guidelines for selection: see DIN VDE 0675/part 5 and IEC 60099-5 Design porcelain housing: brown glazed (grey on inquiry), fittings: Al alloy connections: clamps, screws, nuts hot dip galv. or stainless steel Optional accessories Monitoring spark gap, surge counter, diagnostic appliance Operating conditions ambient temperature: rated frequency: -60°C to +55°C 48 cps to 62 cps Technical parameters Raten voltage Ur : nominal discharge current : high current impulse (4/10) : long duration current impulse: 6 kV to 420 kV 20 kA 100 kA 1200 A /2000 µs Line discharge class : rated short circuit current: specific energy withstand acc. to IEC 60099-4: double impulse 3000 µs: 4 40 to 63 kA 9,2 kJ / kVUr 16 kJ / kVUr Pararrayos de óxido de zinc Pararrayos para alta tensión Tipos SB 6/20.4-I a SB 420/20.4-I Campos de aplicación Protección de transformadores, equipos e instalaciones eléctricas contra sobretensiones atmosféricas y de maniobra Selección del pararrayos La selección de la tension asignada y la tension de operación continua del pararrayos depende de las condiciones de puesta a tierra de la red. Criterios de selección: ver DIN VDE 0675/ part 5 y IEC 60099-5. issue 01/ 05 versión 01/ 05 Diseño Envolvente de porcelana vidriada color marrón (gris bajo solicitud) Terminales : aleación de aluminio Conexiones : abrazaderas, tornillos y tuercas acero galvanizado en caliente o acero inoxidable. Accesorios opcionales Entrehierros de control, contador de descargas, unidad de diagnóstico. Temperatura ambiente: Frecuencia de la red: Prospectus no. 1377 en / sp Folleto N° 1377 en / esp Condiciones normales de operación -60°C ... +55°C 48 Hz ... 62 Hz Datos técnicos Tensión asignada Ur Corriente nominal de descarga: Impulso de corriente de alta amplitud (4/10): Impulso de corriente de larga duración 6 kV ... 240 kV 20 kA 100 kA 1200 A / 2000 µs Clase de descarga de linea: Corriente de cortocircuito asignada: Capacidad de absorción de energia según CEI 60099-4: con doble impulso de 3000 µs: 4 40 ... 63 kA 9,2 kJ / kVUr 16 kJ / kVUr Page 1/4 rated continuous temporary voltage/ operating overvoltage 1) Tensión voltage/ TOV / asignada Tensión de Sobretensión operación 1) temporal continua type / Tipo SB 6/20.4-I SB 12/20.4-I SB 18/20.4-I SB 30/20.4-I SB 48/20.4-I SB 60/20.4-I SB 72/20.4-I SB 75/20.4-I SB 78/20.4-I SB 81/20.4-I SB 84/20.4-I SB 90/20.4-I SB 96/20.4-I SB 102/20.4-I SB 108/20.4-I SB 114/20.4-I SB 120/20.4-I SB 123/20.4-I SB 132/20.4-I SB 138/20.4-I SB 144/20.4-I SB 150/20.4-I SB 168/20.4-I SB 186/20.4-I SB 192/20.4-I SB 198/20.4-I SB 210/20.4-I SB 214/20.4-I SB 228/20.4-I SB 240/20.4-I SB 264/20.4-I SB 288/20.4-I SB 336/20.4-I SB 342/20.4-I SB 360/20.4-I SB 366/20.4-I SB 372/20.4-I SB 390/20.4-I SB 396/20.4-I SB 420/20.4-I Ur Uc U1s U10s kV kV kV kV 6 12 18 30 48 60 72 75 78 81 84 90 96 102 108 114 120 123 132 138 144 150 168 186 192 198 210 214 228 240 264 288 336 342 360 366 372 390 396 420 4,8 9,6 14,4 24,0 38,4 48 58 60 62 65 67 72 77 82 86 91 96 98 106 110 115 123 134 149 154 158 168 171 182 192 211 230 269 274 288 293 298 312 317 336 6,9 13,8 20,7 34,5 55,2 69 83 86 90 93 97 104 110 117 124 131 138 141 152 159 166 173 193 214 221 228 242 246 262 276 304 331 386 393 414 421 428 449 455 483 residual voltage at steep, lightning and switching impulse current / Tensión residual con impulso de corriente de frente escarpado, impulso de maniobra e impulso tipo rayo min. housing size / Tamaño minimo de la envolvente 10 kA 5 kA 10 kA 20 kA 40 kA 250 A 500 A 1000 A 2000 A (1/2 µs) (8/20 µs) (8/20 µs) (8/20 µs) (8/20 µs) (30/70µs) (30/70µs) (30/70µs) (30/70µs) kV 6,5 15,6 12,9 31,1 19,4 46,7 32,3 77,8 51,6 124,4 65 156 77 187 81 194 84 202 87 210 90 218 97 233 103 248 110 265 116 280 123 296 129 311 132 319 142 342 148 357 155 374 161 400 181 435 200 482 206 498 213 513 226 544 230 555 245 591 258 622 284 685 310 746 361 870 368 887 387 933 393 948 400 964 419 1011 426 1026 452 1089 kV kV 13,7 14,4 27,4 28,8 41,0 43,2 68,4 72,0 109,4 115,2 137 144 164 173 171 180 178 187 184 194 192 202 205 216 219 230 233 245 246 259 260 274 274 288 280 295 301 317 314 331 329 346 352 370 383 403 424 446 438 461 451 475 479 504 488 514 520 547 547 576 602 634 656 691 766 806 780 821 821 864 834 878 848 893 889 936 903 950 958 1008 kV kV 15,6 31,1 46,7 77,8 124,4 156 187 194 202 210 218 233 248 265 280 296 311 319 342 357 374 400 435 482 498 513 544 555 591 622 685 746 870 887 933 948 964 1011 1026 1089 17,0 34,0 51,0 85,0 135,9 170 204 212 221 229 238 255 271 289 306 323 340 348 374 391 408 437 476 526 544 561 595 607 645 680 748 815 951 969 1020 1036 1054 1104 1121 1189 kV kV kV kV 11,7 23,3 35,0 58,3 93,3 117 140 146 151 157 164 175 186 198 210 222 233 239 257 268 280 300 326 361 373 385 408 416 443 467 514 560 653 665 700 711 723 758 770 816 11,9 23,8 35,6 59,4 95,0 119 143 149 154 160 167 178 190 202 214 226 238 243 262 273 285 305 332 368 380 392 416 424 451 475 523 570 665 677 713 724 737 772 784 832 12,2 24,5 36,7 61,2 97,9 122 147 153 159 165 172 184 196 208 220 233 245 251 269 281 294 315 343 379 392 404 428 437 465 490 539 587 685 698 734 746 759 796 808 857 12,5 25,1 37,6 62,6 100,2 125 151 157 163 169 176 188 200 213 225 238 251 257 276 288 301 322 351 388 401 413 438 447 476 501 552 601 701 714 752 764 777 814 827 877 1 1 2 3 4 5 6 6 6 6 6 7 7 7 7 8 8 8 8 8 8 8 9 10 10 11 11 11 2x8 2x8 2x9 2x9 2x11 2x11 2x11 2x11 2x11 2x11 2x11 2x11 1) With a prior energy stress of two line discharges of class 4 / Con carga previa de 2 descargas de linea de clase 4 Power frequency voltage versus time characteristic (TOV) (initial temperature +60°C) Curva característica tensión a.c. - tiempo (TOV) (Temperatura inicial + 60°C) 1,4 1,3 without prestress / sin carga previo prestressed with two line discharges of class 4/ Con carga previa de 2 descargas de linea de clase 4 U/ Ur 1,2 1,1 1,0 continouos operating voltage / tensión de operación continua (Uc) 0,9 0,8 0,7 0,1 1 10 100 1000 10000 t [s] Page 2/4 housing size / Tamaño de la envolvente height / Altura creepage distance / Distancia de fuga ± 5% h mm 470 540 610 680 890 1100 1380 1520 1750 1980 2200 2200 2200 3040 3500 4400 1 2 3 4 5 6 7 8 9 10 11 12 13 2x8 2x9 2x11 weight / Peso m kg 32 38 46 54 71 90 115 132 147 168 200 210 221 256 298 415 mm 520 750 980 1210 1950 2630 3550 4000 4700 5450 6250 6800 7595 8000 9400 12500 insulation of arrester housing Figure/ Figura (applied to 1000m a.s.l) Aislamiento exterior de la envolvente a frecuencia industrial a impulso de rayo a impulso de maniobra PFWL 50 Hz kV 60 75 90 100 145 190 250 280 285 315 360 360 360 465 535 655 LIWL 1.2/50 kV 140 170 205 240 345 450 585 655 670 730 835 835 835 1085 1245 1530 SIWL 250/2500 kV 105 130 160 185 265 345 450 505 515 560 645 645 645 835 960 1175 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 4 Ø900 Ø1250 h h h h Ø700 Ø700 Figure / Figura 1 Figure / Figura 2 Figure / Figura 3 Figure / Figura 4 Mechanical withstand in acc. to IEC 60099-4, Annex N.3 / Propiedades mecánicas según IEC 60099-4, Anexo 3 Max. permissible dynamic service load Máxima carga dinámica permisible MPDSL Permissible static service load Carga estática permisible PSSL C 120 13380 Nm 5400 Nm C 130 23000 Nm 9200 Nm Page 3/4 earth terminals / Terminales de tierra line terminals / Terminales de linea type / Tipo X 100 Ø14 M12 max. Ø32mm 110 154 M12 45 60 45 45 80 type / Tipo A 25 147 Ø230 type / Tipo Y 100 50 M12 45 10 Ø14 154 110 45 25 147 Ø230 type / Tipo C 80 type / Tipo B 60 type / Tipo Z 25 88 132 80 110 60 Ø30 Ø13.5 163 Variants of installation and drilling plan / Variantes de instalación y ubicación de orificios type / Tipo L type / Tipo M type / Tipo N 20 20 8 42 M20 34 10 M16 Ø18 Ø270 Ø24 310 Ø270 120° 120° 310 Ø18 How to order / Ejemplo de pedido address / Dirección: Metal oxide surge arrester with porcelain housing / Pararrayos de ZnO con envolvente en porcelana SB 120/20.4-I Housing / Envolvente 6 line connection / Terminales de linea variant of installation / Variante de instalación earth connection / Terminales de tierra A N X TRIDELTA Überspannungsableiter GmbH Marie-Curie-Str. 3 07629 Hermsdorf e-mail: vertrieb.ableiter@tridelta-hermsdorf.de Reg.Nr. 3453 - 01 Specifications in this leaflat are subject to change without notice. / Especificaciones sujetas a modificacion sin previo aviso Teléfono: Telefax: (+49 3 66 01) 6-19 51 (+49 3 66 01) 6-40 48 www.tridelta.de Page 4/4