Communication Modbus BCM ULP pour

Anuncio
Communication Modbus BCM ULP
pour Micrologic
Modbus BCM ULP communication
for Micrologic
FR Notice d'installation
EN Installation manual
Compact NS630b...1600, Powerpact P
FDM121
Compact NS1600...3200, Powerpact R
100
%
Masterpact NT
menu
DB126722
33106
5100512864A-02
Masterpact NW
5100512864A-02
2/60
Sommaire
1
2
3
4
5
6
Consignes de sécurité ................................................................................................. 4
Présentation générale de l’option COM
Définitions ................................................................................................................................................................................... 6
Architecture de la communication ............................................................................................................................................. 7
Schéma de principe..................................................................................................................................................................... 8
Description du module BCM ULP Modbus ................................................................................................................................ 9
Description du module CCM Modbus ...................................................................................................................................... 10
Installation des modules de communication
Précautions à prendre avant d'exécuter une tâche quelconque...........................................................................................11
Installation du module de communication "appareil" BCM ULP Modbus. ..........................................................................12
Compact NS fixe manuel.............. .............................................................................................................................................. 12
Compact NS et Masterpact NT/NW fixes à commande électrique ............................................................................................. 15
Compact NS et Masterpact NT/NW débrochables.... ................................................................................................................. 17
Installation du module de communication "châssis" CCM Modbus ................................................................................... 19
Compact NS et Masterpact NT/NW débrochables ..................................................................................................................... 19
Paramètres de communication BCM ULP
Paramètres de communication avec Micrologic A ................................................................................................................. 21
Paramètres de communication avec Micrologic E ................................................................................................................. 23
Paramètres de communication avec Micrologic P / H ............................................................................................................ 26
Paramètres de communication CCM ....................................................................... 28
Aide au dépannage..................................................................................................... 30
5100512864A-02
/60
Consignes de sécurité
Informations importantes
REMARQUE IMPORTANTE
L’installation, l’utilisation, la réparation et la
maintenance des équipements électriques doivent
être assurées par du personnel qualifié uniquement.
Schneider Electric décline toute responsabilité quant
aux conséquences de l'utilisation de cet appareil.
Une personne qualifiée est une personne disposant
de compétences et de connaissances dans le
domaine de la construction et du fonctionnement
des équipements électriques et installations et
ayant bénéficié d'une formation de sécurité afin de
reconnaître et d'éviter les risques encourus.
Documents associés
Pour des instructions supplémentaires, se reférer à :
b la documentation technique du disjoncteur approprié
b le manuel utilisateur Masterpact Modbus
COMBT2EN (en anglais uniquement)
b le manuel utilisateur du système ULP TRV99100.
Vous pouvez télécharger ces publications techniques
ainsi que d'autres informations techniques à partir de
notre site Web : www.schneider-electric.com.
Catégories de danger et symboles spéciaux
Lisez attentivement ces instructions et examinez l'appareil afin de vous familiariser
avec l'équipement avant de l'installer, de l'utiliser ou d'en assurer la maintenance. Les
messages spéciaux suivants que vous trouverez dans cette documentation ou sur
l'appareil ont pour but de vous mettre en garde contre des risques potentiels ou d’attirer
votre attention sur des informations qui clarifient ou simplifient une procédure.
L'ajout de ce symbole à une étiquette de sécurité "Danger" ou
"Avertissement" signale la présence d'un risque électrique, qui entraînera
des blessures corporelles si les consignes ne sont pas respectées.
Ceci est le symbole d’une alerte de sécurité. Il est utilisé pour vous mettre en
garde contre les risques potentiels de blessure. Respectez tous les
messages de sécurité qui accompagnent ce symbole pour éviter tout risque
de blessure ou de décès.
DANGER
L'indication DANGER signale une situation dangereuse imminente et, si elle
n'est pas résolue, entraînera la mort ou des blessures graves.
AVERTISSEMENT
L'indication AVERTISSEMENT signale une situation potentiellement dangereuse
et, si elle n'est pas résolue, risque d'entraîner la mort ou des blessures graves.
ATTENTION
L'indication ATTENTION signale une situation potentiellement dangereuse et, si elle
n'est pas résolue, risque d'entraîner des blessures d'ampleur mineure à modérée.
ATTENTION
L'indication ATTENTION, utilisée sans le symbole d'alerte de sécurité, signale
une situation potentiellement dangereuse et, si elle n'est pas résolue, risque
d'entraîner des dommages aux équipements.
5100512864A-02
4/60
1
1
Consignes de sécurité
Avant de commencer
AVERTISSEMENT
DANGER
RISQUE DE CHOC ÉLECTRIQUE, D’EXPLOSION
OU D’ARC ÉLECTRIQUE
b Utilisez des équipements de protection individuelle
(EPI) et respectez les procédures de sécurité.
Pour un marché aux normes NEMA, voir NFPA 70E.
b Seul un personnel qualifié est autorisé à installer
cet appareil ainsi qu'à en assurer l'entretien.
b Débranchez toutes les sources d'alimentation de
cet appareil avant toute opération interne ou externe
sur l'appareil.
b Utilisez toujours un dispositif de mesure de la
tension correctement calibré afin de veiller à ce que
l’unité soit hors tension.
b Remettez en place tous les équipements, les
portes et les capots avant de remettre l'appareil sous
tension.
Le non-respect de ces instructions entraînera la
mort ou des blessures graves.
5100512864A-02
PERTE DE COMMANDE
b Le concepteur d'un circuit de commande doit tenir compte des modes de
défaillance potentiels des canaux de commande et, pour certaines fonctions de
commande critiques, prévoir un moyen d'assurer la sécurité en maintenant un
état sûr pendant et après la défaillance. L’arrêt d’urgence et l’arrêt en cas de
sur-course constituent des exemples de fonctions de contrôle essentielles.
b Des chemins de contrôle séparés ou redondants doivent être fournis pour les
fonctions de contrôle essentielles.
b Les chemins de contrôle du système peuvent comprendre les liaisons de
communication. Il est nécessaire de tenir compte des conséquences des
retards de transmission inattendus ou des défaillances d’une liaison.(1)
b Chaque mise en œuvre d’un disjoncteur doté d'un BCM ULP doit être testée
individuellement et de manière approfondie afin de vérifier son fonctionnement
avant sa mise en service.
Le non-respect de ces instructions peut provoquer la mort, des blessures
graves ou des dommages matériels.
(1) Pour un marché aux normes NEMA, se reporter à la directive NEMA ICS 1.1 (dernière
édition) intitulée "Safety Guidelines for the Application, Installation, and Maintenance of Solid
State Control".
5/60
Présentation générale de l’option COM
Définitions
A propos de ce guide
Ce manuel donne les indications nécessaires pour connecter le BCM
ULP au réseau Modbus. Consultez les documentations applicables
contenant des instructions spécifiques sur l'installation du BCM ULP
dans le disjoncteur et sur l'acheminement de l'alimentation 24 V.
Définition de l’option COM
L'option COM est disponible pour tous les appareils des gammes :
b Compact NS60b à 200, Powerpact P et R
b Masterpact NT et NW
b Equipée des unités de contrôle Micrologic A, E, P et H.
L'option COM permet leur intégration dans un système de supervision
communiquant sous Modbus.
Avec toutes les unités de contrôle Micrologic, l'option COM permet :
b l'analyse des paramètres du réseau pour les besoins d'exploitation
et de maintenance
b la commande de l'appareil
b la signalisation des états
b l'identification des causes de défaut
b le paramétrage des protections
b l'identification de l'appareil.
La signalisation d'état par l'option COM est indépendante des contacts
de signalisation de l'appareil. Ces contacts restent disponibles pour une
utilisation traditionnelle.
Définition des abréviations
BCM = Breaker Communication Module (module de communication
disjoncteur).
ULP = Universal Logic Plug (Système de raccordement ULP).
CCM = Chassis Communication Module (module de communication
"châssis").
5100512864A-02
DB40159
Note: Pour s'assurer que le paramètrage des protections via le système de
communication (ou via le clavier de l'unité de contrôle) ne dépasse pas le niveau
requis par l'installation électrique, règlez les commutateurs de règlage au niveau
requis de protection avant de faire les règlages via le système de communication
(ou via le clavier de l'unité de contrôle). Reportez vous au manuel utilisateur de
l'unité de contrôle pour des informations supplémentaires concernant le
paramètrage des protections.
Système communiquant sous Modbus
raccordement
sur le bus
système communiquant
sous Modbus
3
raccordement
sur le bus
raccordement
entre modules
2
1
appareil débrochable
appareil fixe
1 unité de contrôle Micrologic
2 module de communication "appareil" BCM ULP Modbus
3 module de communication "châssis" CCM Modbus (optionnel)
Présentation générale de l’option COM.
6/60
2
2
Présentation générale de l'option COM (suite)
Architecture de la communication
Composition de l'option COM
L'option COM dépend du type de disjoncteur :
b pour un appareil fixe, l'option COM = Module de
communication "appareil" BCM ULP Modbus
b pour un appareil débrochable, l'option COM = Module
de communication "appareil" BCM ULP Modbus + module
de communication "châssis" CCM Modbus.
Appareil fixe avec
commande manuelle
2
Module BCM ULP Modbus
Un module "appareil" BCM ULP Modbus situé derrière
l'unité de contrôle est livré installé avec ses microinterrupteurs "appareil" :
b pour les appareils à commande manuelle :
v contacts OF, SDE et/ou SD
b pour les appareils à commande électrique :
v contacts OF, SDE, PF, CH
v kit de liaison aux auxiliaires de commande voltmétrique
de communication MX1 et XF.
Le module de communication est indépendant de
l'unité de contrôle. Il transmet et reçoit des
communications avec :
b le réseau Modbus,
b l'unité de contrôle informations via une liaison
infrarouge.
OF
SD
SDE
1
Remarque : une procédure de mise en route spécifique doit être
suivie (voir page 28).
5100512864A-02
CE CT
DB401540
1
2
3
4
5
6
4
CD
6
5
3
MX1
XF
3
OF
SDE
FP
CH
Remarque : les paramètres de communication BCM ULP doivent
être réglés à l'aide de l'unité de contrôle (voir pages 21 à 27).
Module CCM Modbus
Un module de communication "châssis" CCM Modbus
supplémentaire doit être monté sur un rail DIN à proximité
de l'appareil et relié :
b au module de communication "appareil" BCM ULP
Modbus dont il conserve l'adresse si l'appareil est débroché
b à des contacts auxiliaires châssis (CD, CT, CE) qui
communiquent les positions de l'appareil dans le châssis.
Appareil débrochable à
commande électrique
module de communication "appareil" BCM ULP Modbus
module de communication "châssis" CCM Modbus (optionnel)
OF, SDE ... micro-interrupteurs
contacts CE, CD et CT
auxiliaires de commande voltmétrique communicants MX et XF
bornier COM (E1 à E6)
1
: Filaire
: Modbus
Présentation de l’option COM.
7/60
Présentation générale de l'option COM (suite)
Schéma de principe
Caractéristiques
b Jusqu'à 1 appareils fixes ou 15 appareils
débrochables.
b Longueur maximum du bus y 1 200 mètres.
b Vitesse de transmission maximale = 19 200 bauds.
1
2
Alimentation des modules COM
b Modules COM : 24 V CC
b Le module d'alimentation externe (AD) est
recommandé (voir le formulaire de commande pour les
appareils Masterpact NT/NW et Compact NS).
L'alimentation de l'unité de contrôle doit être isolée.
3
Consommation des modules COM et des unités de
contrôle Micrologic
b Module de communication "appareil" BCM ULP
Modbus : 40 mA.
b Module de communication "châssis" CCM Modbus :
55 mA.
b Afficheur de tableau FDM121 : 21 mA
b Interface de communication Modbus : 21 mA
b Module d'alimentation externe (AD) jusqu'à 1 A
(24 V CC).
6
4
24 V c
5
7
12
8
9
13
14
10
11
OK
Mode
DB401541
Remarque :
pour procéder à la configuration des unités de contrôle
Micrologic lorsqu'il n'y a pas de source auxiliaire, alimenter
ces unités individuellement à l'aide de la mallette test et de la
prise test en face avant.
Logiciels RSU / RCU
Ethernet
Passerelle Ethernet (EGX100)
Module d’alimentation
externe (AD)
5 Réseau Modbus
1
2
3
4
6 Module de communication
"châssis" CCM Modbus
7 Afficheur de tableau
FDM121
8 Cordon ULP de disjoncteur
9 Bornier COM
10 Câblage préfabriqué
OK
Mode
OK
Mode
11 Module de communication
"appareil" BCM ULP
Modbus
12 Module d’interface de
communication Modbus
13 Câble ULP
14 Cordon Compact NSX
Schéma de principe d'un système de communication mettant en œuvre le protocole Modbus.
5100512864A-02
8/60
2
2
Présentation générale de l'option COM (suite)
Description du module BCM ULP Modbus
L'option COM inclut systématiquement un module de
communication "appareil" BCM ULP Modbus (voir page
7). Ce module est indépendant de l'unité de contrôle ; il
transmet et reçoit des informations avec :
b le réseau Modbus
b l'unité de contrôle via une liaison infrarouge
b l'appareil, via ses micro-interrupteurs
b les auxiliaires de commande voltmétrique de
communication MX et XF.
Ce module est composé des éléments présentés sur la
figure ci-contre qui sont livrés montés sur l'appareil et
raccordés au module.
Eléments fournis installés
sur l'appareil et connectés
au module
Compact NS
fixe manuel
réseau Modbus
connecteur COM
débrochable
E3
E1 E2
E4 E5
système de câblage fourni
avec option
MX1/XF
E6
1/2
Compact NS fixe
électrique
Masterpact NT/NW
fixe et débrochable
Auxiliaires de commande
1 Auxiliaires de commande
voltmétrique communicant
MX1 utilisés pour ouvrir
l'appareil
v
2 Auxiliaires de commande
voltmétrique communicant XF
utilisés pour fermer l'appareil
v
Contacts auxiliaires
b
4 SD (signal déclenchement)
b
5 SDE (signal déclenchement
sur défaut electrique)
b
b
3/4/5/6/7
b
b
6 PF (prêt à fermer)
7 CH (ressorts comprimés)
DB401542
OF (ON/OFF)
b
Module de communication "appareil" BCM ULP Modbus et connexions.
b standard
5100512864A-02
v optionnel
9/60
Présentation générale de l'option COM (suite)
Description du module CCM Modbus
1
s
modbu
Fault
Com
.
CE
s
2
raccordement aux
contacts châssis
+
raccordement au module
BCM ULP Modbus
DB40154
3
CD
CT
Addres
sync.
Breaker
CCM
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
+ +
Disjoncteur
Clic!
CE
CD
CT
Etapes de l'installation du module de communication "châssis" Modbus sur Compact NS et
Masterpact NT/NW débrochables.
CT
5
A’
B’
A’
B’
Network
B
B
Réseau
CD
Breaker
Address
sync.
A
Com.
6
A
7
Fault
shield
1
Disjoncteur
Description du module de communication
"châssis" CCM Modbus
1 Bornes de l’alimentation 24 V.
2 Connecteur "réseau" pour le raccordement au
réseau Modbus.
Connecteur "disjoncteur" pour le raccordement au
module de communication "appareil" BCM ULP
Modbus.
4 Bornes de sortie 24 V pour l'alimentation du
module de communication "appareil" BCM ULP
Modbus.
5 Bornes à vis pour le raccordement aux contacts
auxiliaires châssis (CE, CT, CD).
6 Bouton de synchronisation des adresses.
7 Voyants d'états de module (voir la section sur les
Modes de fonctionnement en page 29).
module de communication
"châssis" CCM Modbus
DB12671
Les appareils débrochables nécessitent deux modules
de communication :
b un module de communication "appareil" BCM ULP
Modbus monté comme indiqué en page 7
b un module de communication "châssis" CCM
Modbus livré séparément dans un emballage
spécifique qui doit être :
v monté sur rail DIN
v raccordé au module de communication "appareil"
BCM ULP Modbus, voir page 14
v raccordé aux contacts auxiliaires châssis (CE, CD,
CT), voir page 20.
Une fois les opérations ci-dessus effectuées, le module
de communication "châssis" CCM Modbus doit être
raccordé au réseau Modbus.
2
3
CE
4
Composants.
5100512864A-02
10/60
2
3
Précautions préalables à toute intervention
Appareil fixe
Avant toute intervention sur l'appareil,
mettez toujours ce dernier hors tension en
procédant comme indiqué ici. Les
appareils débrochables doivent être
placés en position débroché.
I
ON
push
O
OFF
push
I
O OFF
push
O
1
arged
disch
push
ON
OFF
d
arge
disch
O OFF
3
I
ON
push
O
OFF
push
arged
disch
discharged
O OFF
2
E47086A
E47085A
O OFF
Appareil débrochable
I
OOFF
push
ON
push
I
disch
O OFF
push
O
1
arged
push
5
ON
OFF
d
arge
disch
O OFF
I
OOFF
push
3
OOFF
ON
I ON
push
push
push
disch
dis
O OFF
2
E47084A
E4708A
O OFF
5100512864A-02
discharged
arge
d
O OFF
4
E47082A
ed
charg
11/60
3
Compact NS fixe manuel
Installation et câblage de l'option COM (module BCM ULP Modbus)
Installation du module
Fourni avec l'appareil, le module est monté derrière
l'unité de contrôle et est raccordé aux microinterrupteurs (OF, SD, SDE).
Il comporte, dans sa partie supérieure, un connecteur
de COM débrochable qui permet le raccordement
direct au réseau Modbus.
Réseau Modbus
E1
Pour le raccordement de l'appareil BCM ULP Modbus,
voir la page 14.
E3
E1 E2
E4 E5
E4
E2 E3
E5 E6
E6
Réseau Modbus
Le connecteur Modbus utilise le code couleur suivant :
Couleur
Europe
Etats-Unis
Rouge
E1
24 V
24 V
Noir
E2
0V
0V
Marron
E
A
Out-
D0
Jaune
E4
B
Out+
D1
Blanc
E5
A'
In-
D0
Blue
E6
B'
In+
D1
Connecteur COM
débrochable
E3
E1 E2
E4 E5
E6
100
%
40 %
DB401544
BCM ULP raccordé aux
micro-interrupteurs
Installation du module de communication "appareil" BCM ULP Modbus sur Compact NS fixe,
manuel.
5100512864A-02
12/60
Compact NS fixe manuel (suite)
Installation et câblage de l'option COM (module BCM ULP Modbus)
Précaution : acheminement de câbles/fils
Acheminer les fils de façon à éviter tout risque de
pincement ou d'écrasement du câble ou des fils lorsque
le couvercle avant est monté (voir l'illustration).
E1 E2
1
4E5
E3 E4
E5 E6
2
E6
4E5
E6
E1 E2E3E
E1 E2E3E
DANGER
RISQUE DE CHOC ÉLECTRIQUE, D’EXPLOSION
OU D’ARC ÉLECTRIQUE
Couleur
Rouge
Remettez le couvercle du disjoncteur en place avant
de mettre le disjoncteur sous tension afin d'éviter un
contact physique avec des bornes sous tension.
Le non-respect de ces instructions entraînera la
mort ou des blessures graves.
4
E1 E2
E3
E1
Noir
E2
Marron
E3
Jaune
E4
Blanc
E5
Blue
E6
E6
E4 E5
4 E5
2 E3 E
E1 E
E6
3
0,8 N.m
7 lb-in
5
4E5
E6
4E5
E1 E2E3E
E6
E1 E2E3E
DB401545
6
Raccordement de l'appareil BCM ULP Modbus.
5100512864A-02
1/60
Compact NS fixe manuel (suite)
Câblage de l'option COM (module BCM ULP Modbus) avec ou sans module ULP (FDM121...)
A RS 485 4 fils Modbus
A RS 485 2 fils Modbus
sans module ULP
sans module ULP
B RS 485 2 fils Modbus + ULP
avec module ULP
100
%
Adresse
47
Vitesse de
transmission
19.2 k
4W, 2W+ULP
+ -
+ -
- +
Modbus
Com
Alimentation externe
24 V c
A
Micrologic E
EGX100
w
Modbus
Com
Adresse
Vitesse de
transmission
19.2 k
EGX100
Rx- Rx+ Tx- Tx+
4wires
Micrologic P/H
Alimentation externe
24 V c
- +
Micrologic P/H
Alimentation externe
24 V c
- +
menu
Rx- Rx+ Tx- Tx+
+ FDM121
version > V2.0.2
+ EGX100
Rx- Rx+ Tx- Tx+
B
Micrologic E
Cordon ULP
de disjoncteur
w
4W, 2W+ULP
2W + ULP
rouge noir
4 E5
2 E3 E
E1 E
E6
E3
E1 E2
E4 E5
E6
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
B’ / Rx+ D1
BCM ULP
A’ / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
BCM ULP
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
DB401546
blanc bleu
BCM ULP
Nota : reportez vous aux instructions de service de l'EGX100 pour la mise à la terre du blindage, toutes les extrémités de blindage non raccordées doivent être proprement isolées.
5100512864A-02
14/60
3
3
Compact NS et Masterpact NT/NW fixes à commande électrique
Câblage de l'option COM (module BCM ULP Modbus)
Installation du module
Fourni avec l'appareil, le module est monté derrière
l'unité de contrôle Micrologic et est raccordé aux
micro-interrupteurs.
réseau Modbus
Raccordement au bornier client
Le module comporte un connecteur de COM
débrochable, relié au bornier client fixe (à ressorts) par
une filerie préfabriquée adaptée à l'appareil.
Le bornier client permet le raccordement au réseau
Modbus.
connecteur
préfabriqué
Le connecteur Modbus utilise le code couleur suivant :
Couleur
Europe
Etats-Unis
Rouge
E1
24 V
24 V
Noir
E2
0V
0V
Marron
E
A
Out-
réseau Modbus
bornier client
MX1 / XF
câblage
E4
B
Out+
D1
Blanc
E5
A'
In-
D0
Blue
E6
B'
In+
D1
UC1
UC3
UC2
MN MX1
SDE1
SDE1
/MX2
/M2C
UC4 /RES
XF
PF
MCH
à MX1 / XF
D0
Jaune
COM
OF1
OF2
OF3
OF4
connecteur
COM débrochable
E1 E2
E3 E4
E5 E6
E1 E2E3
E4E5
E6
I
push
100
disc
40 %
DB401547
ON
%
harg
ed
O OFF
BCM ULP raccordé aux
micro-interrupteurs
Installation du module de communication "appareil" BCM ULP Modbus sur Compact NS ou
Masterpact NT/NW fixes à commande électrique.
5100512864A-02
15/60
Compact NS et Masterpact NT/NW fixes à commande électrique
(suite)
Câblage de l'option COM (module BCM ULP Modbus) avec ou sans module ULP (FDM121...)
A RS 485 4 fils Modbus
sans module ULP
A RS 485 2 fils Modbus
sans module ULP
B RS 485 2 fils Modbus + ULP
avec module ULP
100
%
menu
+ -
+ -
- +
Adresse
47
Vitesse de
transmission
19.2 k
4W, 2W+ULP
A
Micrologic E
o
EGX100
4wires
Modbus
Com
Adresse
Vitesse de
transmission
19.2 k
EGX100
Rx- Rx+ Tx- Tx+
Micrologic P/H
Alimentation externe
24 V c
- +
Modbus
Com
Alimentation externe
24 V c
Rx- Rx+ Tx- Tx+
- +
Micrologic P/H
Alimentation externe
24 V c
+ FDM121
version > V2.0.2
+ EGX100
Rx- Rx+ Tx- Tx+
B
Micrologic E
o
Cordon ULP
de disjoncteur
4W, 2W+ULP
2w+ULP
rouge noir
E1 E2 E3 E4 E5 E6
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
DB401548
E1 E2 E3 E4 E5 E6
24 V
bornier client
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
bornier client
E1 E2 E3 E4 E5 E6
blanc bleu
bornier client
Nota : reportez vous aux instructions de service de l'EGX100 pour la mise à la terre du blindage, toutes les extrémités de blindage non raccordées doivent être proprement isolées.
5100512864A-02
16/60
3
3
Compact NS et Masterpact NT/NW débrochables
Câblage de l'option COM (modules BCM ULP et CCM Modbus)
Installation du module
Le module de communication "appareil" BCM ULP
Modbus est installé comme décrit précédemment pour
les appareils fixes.
Il est livré installé et raccordé aux micro-interrupteurs
et aux auxiliaires de commande voltmétrique de
communication.
au module de communication
"châssis" CCM Modbus
"Châssis" CCM
Raccordement au bornier client
Le module comporte en outre un connecteur de COM
débrochable, relié à une terminaison préfabriquée
clipsable sur le bandeau supérieur de l'appareil.
Lors de l'embrochage, cette terminaison assure
automatiquement le raccordement au bornier client
débrochable (à ressorts).
Le bornier client permet le raccordement au réseau
Modbus via le module de communication "châssis"
CCM Modbus.
bornier client
connecteur
préfabriqué
câblage
connecteur COM
débrochable
Raccordement des auxiliaires au module
Identique aux modèles Compact NS et Masterpact
NT/NW fixes à commande électrique
à MX1 / XF
E3
E1 E2
E4 E5
E6
E3
E1 E2
E4 E5
E6
100%
40%
Le connecteur Modbus utilise le code couleur suivant :
E1
Europe
24 V
Etats-Unis
24 V
Noir
E2
0V
0V
Marron
E
A
Out-
D0
Jaune
E4
B
Out+
D1
Blanc
E5
A'
In-
D0
Blue
E6
B'
In+
D1
MX1 / XF
DB401549
Couleur
Rouge
BCM ULP raccordé aux
micro-interrupteurs
Exemple d'installation du module de communication "appareil" BCM ULP Modbus sur
Masterpact NT débrochable.
5100512864A-02
17/60
Compact NS et Masterpact NT/NW débrochables (suite)
Câblage de l'option COM (modules BCM ULP et CCM Modbus) avec ou sans module ULP (FDM121...)
A RS 485 4 fils Modbus
sans module ULP
A RS 485 2 fils Modbus
sans module ULP
Alimentation externe
24 V c
Alimentation externe
24 V c
+ -
+ -
+ -
- +
- +
%
avec module ULP
Alimentation externe
24 V c
- +
100
B RS 485 2 fils Modbus + ULP
menu
Micrologic P/H
A
EGX100
Rx- Rx+ Tx- Tx+
Rx- Rx+ Tx- Tx+
Micrologic E
CCM comporte la marque
Schneider Electric.
4W, 2W+ULP
2w+ULP
Micrologic E
CCM
w
+ -
+ A
B
A’
B’
CCM
A
B
A’
B’
+ -
Disjoncteur Réseau
Vitesse de
transmission
19.2 k
+ -
B
Disjoncteur Réseau
Micrologic P/H
Adresse
Rx- Rx+ Tx- Tx+
lorsque la face avant du
w
4wires
Modbus
Com
EGX100
La configuration B est
possible uniquement
A
A
B
B
A’
A’
B’
+ FDM121
+ -
version > V2.0.2
CCM
B’
+ -
Disjoncteur Réseau
Modbus
Com
Adresse
47
Vitesse de
transmission
19.2 k
4W, 2W+ULP
EGX100
A
B
A’
B’
A
B
A’
B’
blanc bleu
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
bornier client
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
bornier client
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
E1 E2 E3 E4 E5 E6
A / Tx- D0
E1 E2 E3 E4 E5 E6
0V
E1 E2 E3 E4 E5 E6
24 V
DB401550
Cordon ULP
de disjoncteur
rouge noir
bornier client
Nota : reportez vous aux instructions de service de l'EGX100 pour la mise à la terre du blindage, toutes les extrémités de blindage non raccordées doivent être proprement isolées.
5100512864A-02
18/60
3
3
Compact NS et Masterpact NT/NW débrochables
Installation du module CCM Modbus
A
’
A
B
’
ak
er
ld
B
ie
’
A
sh
B
’
R
és
B
ea
A
u
N
et
w
or
k
Installation du module
Montez le module de communication "châssis" CCM
Modbus sur un rail DIN symétrique à proximité du
châssis, de telle sorte que la face avant soit accessible
pour les raccordements et le paramétrage. Dans le cas
d'un montage sur rail vertical, utilisez une butée pour
éviter le glissement.
Le rail DIN doit être commandé séparément.
nc
te
ur
B
re
Fault
D
is
jo
Com.
s
Addres
sync.
YL
CI
+
CE
–
CD
CT
33110
Modbus Cradle COM module
Module COM chassis Modbus
+ +
5100512662
CCM
modbus
Fault
Com.
RISQUE DE CHOC ÉLECTRIQUE, D’EXPLOSION
OU D’ARC ÉLECTRIQUE
DB401551
CE
CD
CT
Address
sync.
DANGER
Breaker
XXXXXXXXX
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
Made in France
Disjoncteur
P 99-44
PP-YYYY-WWW-D-T
+
étiquette signalétique
Contenu du carton d'emballage.
L'utilisation du bouton-poussoir CCM et la
consultation des indicateurs nécessitent une
alimentation 24 V CC du CCM. Le CCM doit être
placé de telle sorte que le personnel ne soit pas
exposé à des tensions ou à une énergie dangereuse
lors de l'utilisation du bouton-poussoir ou de la
consultation des indicateurs d'état.
45
1.77
DB12670
90
3.54
Le non-respect de ces instructions entraînera la
mort ou des blessures graves.
53
2.08
58
2.28
DB12672
Dimensions.
Montage sur rails DIN.
5100512864A-02
19/60
3
Compact NS et Masterpact NT/NW débrochables
Câblage des contacts auxiliaires châssis au module CCM Modbus
Raccordement aux contacts châssis (optionnel)
Il s'agit de contacts inverseurs.
b CE, indication de position "embrochée"
b CD, indication de position "débrochée"
b CT, indication de position "test"
Leur raccordement au module de communication
"châssis" CCM Modbus se fait par 6 fils (deux fils par
contact) 0,5 à 1,25 mm2 (6 x 20 à 16 AWG) à raccorder
au bornier à vis. Ces borniers sont repérés CE, CD et
CT comme indiqué sur la figure ci-contre.
Les raccordements sont à faire entre les bornes
suivantes :
b CE, bornes 11 et 14
b CD, bornes 811 et 812
b CT, bornes 911 et 914.
Pour plus d'informations sur l'installation de ces
contacts, se reporter aux manuels correspondants :
b Manuel d’installation pour les Contacts châssis
Compact NS et Masterpact NT, document numéro
51201010
b Manuel d’installation pour les Contacts châssis
Masterpact NW, document numéro 51156129.
Module de communication "châssis" CCM Modbus
Fault
.
CD
CT
s
Addre
.
s ync
s
CE
C om
Breaker
s
modbu
Disjoncteur
CCM
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
+ +
+
Contacts
châssis CD
Network
CCM
A
B
A’
B’
Breaker
Contacts châssis
CE, CT
A
B
A’
B’
CT
911
DB401552
CT
914
CD
811
CD
812
CE
311
CE
314
Masterpact
NT/NW
châssis
Connexion aux contacts châssis.
5100512864A-02
20/60
Paramètres de communication avec Micrologic A
Préalable
Les paramètres de communication BCM ULP doivent
être réglés au moyen de l'unité de contrôle Micrologic
ou du programme de téléréglage Masterpact RSU
(Remote Setting Utility).
Les paramètres de communication BCM ULP
sont : adresse, vitesse de transmission, parité et
raccordement Modbus.
La mise en service de la communication Modbus
nécessite d'avoir correctement installé les modules,
puis de les mettre sous tension.
Les unités de contrôle Micrologic doivent également
être sous tension pour procéder aux opérations de
configuration qui suivent.
afficheur numérique
boutons de navigation
appuyez simultanément
pendant 3 secondes
passe
à XX
Unités de contrôle Micrologic A
5100512864A-02
(par défaut)
1
Appuyez simultanément sur les deux boutons
et
pendant secondes. Une suite de quatre écrans
de configuration de la communication Modbus apparaît.
2
3
:
:
:
46
DB40155
Ecran 1 Adresse
L'adresse Modbus par défaut de l'appareil est 47.
L'écran affiche AdXX si l'adresse courante du module
de communication est XX.
Choisissez une adresse unique de 1 à 47 pour
l'appareil en appuyant sur le bouton
. Chaque appui
bref incrémente l'adresse de 1, l'adresse suivant 47
étant à nouveau à 1.
Une fois l'adresse choisie, appuyez sur le bouton
pendant secondes puis relâchez pour passer à
l'écran suivant.
47
Micrologic A.
Ecran 1 d'adresse.
21/60
4
4
Paramètres de communication avec Micrologic A (suite)
Ecran 3 Parité
La parité par défaut est Paire.
L'écran affiche X, où X est une des deux valeurs E
(even) et N (none).
Choisissez une parité commune à tous les appareils,
. Chaque appui bref fait
en utilisant le bouton
passer à la valeur suivante.
Une fois la parité choisie, appuyez sur le bouton
pendant trois secondes puis relâchez pour passer à
l'écran suivant.
19200
19200
19200
(par défaut)
9600
DB401554
4800
Ecran 2 : vitesse de transmission.
pE
E
E
(par défaut)
n
DB401555
Ecran 2 Vitesse de transmission
La vitesse de transmission par défaut est
19200 bauds.
L'écran affiche XXXX, où XXXX est une des trois
valeurs, 4800, 9600 ou 19200.
Choisissez une vitesse commune à tous les appareils,
. Chaque appui bref fait
en utilisant le bouton
passer à la valeur suivante.
Une fois la vitesse choisie, appuyez sur le bouton
pendant trois secondes puis relâchez pour passer à
l'écran suivant.
Ecran 3 : parité.
Raccordement de la communication Modbus
La valeur par défaut du paramètre de communication
de raccordement Modbus correspond à 4 fils.
Le paramètre de communication de raccordement
Modbus (4 fils, 2 fils + ULP) ne peut pas être réglé au
moyen de l'unité de contrôle Micrologic A. Utilisez le
logiciel Masterpact RSU (Remote Setting Utility) pour
régler ce paramètre.
5100512864A-02
22/60
Paramètres de communication avec Micrologic E
Micrologic 6.0
Activez le mode de navigation en arborescence.
Appuyez simultanément sur les deux boutons
pendant trois secondes. Une suite de quatre
et
écrans de configuration de la communication Modbus
apparaît.
5100512864A-02
afficheur
boutons de navigation
menu
appuyez simultanément
k
DB401556
Ecran 1 Adresse
L'adresse Modbus par défaut de l'appareil est 47.
L'écran affiche AdXX si l'adresse courante du module
de communication est XX.
Une icône en forme de cadenas fermé indique que la
valeur est verrouillée.
Appuyez sur le bouton
pour ouvrir le cadenas et
affichez le premier chiffre (par ex. 4) clignotant prêt à
modifier.
Chaque appui bref sur le bouton
fait passer à la
valeur suivante.
Appuyez sur le bouton
pour valider cette valeur et
afficher le second chiffre (par ex. 7) clignotant prêt
à modifier.
Chaque appui bref sur le bouton
fait passer à la
valeur suivante.
pour valider la nouvelle
Appuyez sur le bouton
adresse Modbus (les deux chiffres sélectionnés) qui
s'affiche en permanence. Le cadenas est encore
ouvert.
pour
Appuyez de nouveau sur le bouton
verrouiller cette valeur et afficher l'écran 2.
E
(voir pages 24)
2/60
4
4
Paramètres de communication avec Micrologic E (suite)
Ecran 2 Vitesse de transmission
La vitesse de transmission par défaut est 19200
bauds. L'écran affiche XXXX, où XXXX est une des
trois valeurs, 4800, 9600 ou 19200. Une icône en
forme de cadenas fermé indique que la valeur est
verrouillée.
Micrologic 6.0 E
k
5100512864A-02
k
menu
k
k
Micrologic 6.0 E
menu
DB126757
Ecran 3 Parité
La parité par défaut est E (paire). L'écran peut afficher
une valeur n (aucune) si un paramètre antérieur existe
déjà. Une icône en forme de cadenas fermé indique
que la valeur est verrouillée.
Appuyez sur le bouton
pour ouvrir le cadenas
et afficher la valeur (par ex. E) clignotante prête à
modifier.
Modifiez la parité existante en appuyant sur le
bouton
. Appuyez sur le bouton
pour valider
cette valeur, dont l'affichage devient permanent. Le
cadenas est encore ouvert. Appuyez de nouveau sur
pour verrouiller cette valeur.
le bouton
DB126756
k
Appuyez sur le bouton
pour ouvrir le cadenas
et afficher la valeur (par ex. 19,2) clignotante prête à
modifier.
Choisissez une vitesse commune à tous les appareils,
en utilisant le bouton
. Chaque appui bref fait
passer à la valeur suivante.
Une fois la vitesse sélectionnée, appuyez sur le
pour valider cette valeur dont l'affichage
bouton
devient permanent. Le cadenas est encore ouvert.
pour
Appuyez de nouveau sur le bouton
verrouiller cette valeur et afficher l'écran .
24/60
Paramètres de communication avec Micrologic E (suite)
5100512864A-02
Micrologic 6.0 E
w
w
w
w
menu
DB127872
Ecran 4 Raccordement Modbus (4 fils, 2 fils+ULP)
La valeur par défaut du paramètre de communication
de raccordement Modbus est 4 fils.
b Si le paramètre de communication "4 fils" est
sélectionné (valeur par défaut), 4 fils doivent être
connectés entre BCM ULP (bornes E, E4, E5, E6) et
le CCM (bornes A, B, A', B').
Le module d'affichage en face avant FDM121 ne peut
pas être raccordé.
Le raccordement au réseau 4 fils RS 485 Modbus est
possible.
b Si le paramètre de communication "ULP" est
sélectionné, 2 fils doivent être connectés entre BCM
ULP (bornes E, E4) et le CCM (bornes A, B).
Le module d'affichage en face avant FDM121 peut être
raccordé. Le raccordement au réseau 4 fils RS 485
Modbus n'est pas possible.
25/60
4
4
Paramètres de communication avec Micrologic P / H
Appuyez sur le bouton
puis dans l'écran qui
s'affiche :
b sélectionnez le menu configurer com à l'aide des
touches de navigation
et validez
b le choix par la touche
b sélectionnez ensuite, de la même manière, le menu
paramètres Com.
Adresse, vitesse de transmission, parité.
Dans le menu paramètres com, réglez les trois
paramètres Adresse, Vitesse de transmission et Parité
comme décrit précédemment. Les valeurs par défaut
et disponibles de chaque paramètre sont les mêmes
que dans le cas précédent. Voir les informations des
Ecrans 1, 2 et . La validation de chaque paramètre
se fait par la touche
.
Après la validation du paramètre parité, appuyez sur la
touche
. Le message "Voulez-vous enregistrer les
paramètres ?" s'affiche. Sélectionnez Oui et validez par
. Les paramètres sont enregistrés.
la touche
5100512864A-02
Raccordement de la communication Modbus (4W, 2W+ULP)
La valeur par défaut du paramètre de communication de raccordement Modbus est
4 fils.
b Si le paramètre de communication "4 fils" est sélectionné (valeur par défaut), 4 fils
doivent être connectés entre BCM ULP (bornes E, E4, E5, E6) et le CCM (bornes
A, B, A', B').
Le module d'affichage en face avant FDM121 ne peut pas être raccordé.
Le raccordement au réseau 4 fils RS 485 Modbus est possible.
b Si le paramètre de communication "2 fils + ULP" est sélectionné, 2 fils doivent
être connectés entre BCM ULP (E, E4) et le CCM (bornes A, B).
Le module d'affichage en face avant FDM121 peut pas être raccordé.
Le raccordement au réseau 4 fils RS 485 Modbus n'est pas possible.
Le paramètre de communication de raccordement Modbus (4 fils, 2 fils + ULP) peut
être réglé au moyen de l'unité de contrôle Micrologic P/H avec la version du
firmware > 2009AJ.
Si elle n'est pas accessible, utilisez le logiciel Masterpact RSU (Remote Setting
Utility) pour régler ce paramètre.
Tension nominale du réseau
Si un module d'affichage en face avant FDM121 est utilisé, la tension nominale du
réseau doit être réglée au moyen de l'unité de contrôle Micrologic ou du logiciel
Masterpact RSU.
, puis par le menu configurer Micrologic, puis
On y accède par la touche
"rapport des TP" et le rapport tension-transformation souhaité.
26/60
Paramètres de communication avec Micrologic P / H (suite)
Historiques
Micrologic 6.0
P
adresse
vitesse
parité
Ecran ELU - [Ecran...
0A
A
afficheur
numérique
B
Cont acts
M2C/M6C
Configurer
Micrologic
Configurer
mesures
C
Paramètre
Com.
Com
Modbus
Réglage
à dist ance
Adresse
47
Commande
à dist ance
Vitesse
19.2 k
Parit é
Paire
Configurer
Com.
100
50
0
boutons de sélection
(clé)
boutons de validation
(enter)
langue
long time
boutons de navigation
Ir
.7
.6
.5
.4
tr
8
(s) 4
.9
.95
2
1
.98
1
.5
.8
x In
@ 6 Ir
alarm
12
16
20
24
instantaneous
short time
Isd
3
2.5
2
1.5
4
x Ir
ts d
5
6
8
10
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
Ig
D
E
I t
off
4
3
6 8 10
12
15
off
2
x In
delay
Langues
Langue
Cont acts
M2C/M6C
Date / heure
Deutsch
Configurer
Micrologic
Sélection
disjoncteur
English US
Configurer
mesures
TC Neutre
Configurer
Com.
Transf o
de V
English UK
Español
Français
test
tg
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
F
G
H
C
B
A
Ii
Historiques
J
on
I t
off
ground fault
rapport
des TP
Historiques
Langues
Cont acts
M2C/M6C
Date / heure
Configurer
Micrologic
Sélection
disjoncteur
Configurer
mesures
TC Neutre
Primaire
690V
Secondaire
690V
Transf o
de V
DB401557
Configurer
Com.
Transfo
de U
Touches de navigation et exemples d'écrans.
5100512864A-02
27/60
4
5
Paramètres de communication CCM
Appareils débrochables
DANGER
Dans ce cas, le module de communication "châssis"
CCM Modbus est une interface entre l'appareil et le
réseau de communication. Une procédure existe donc
pour lui transférer les paramètres nécessaires. Ces
paramètres seront préalablement saisis comme décrit
précédemment en fonction de l'unité de contrôle (voir
page 21 pour Micrologic A, page 2 pour Micrologic E,
page 26 pour Micrologic P/H).
5100512864A-02
b Le CCM peut se trouver à proximité de tensions ou de sources d'énergie
dangereuses.
b Un équipement de protection individuelle doit être utilisé lors de l'utilisation du
bouton-poussoir CCM ou du contrôle des indicateurs d'état. Se reporter à NFPA 70E
ou à CSA Z462, ou aux codes nationaux appropriés pour plus de détails à ce sujet.
CD
A’
B’
A’
B’
Network
B
B
Breaker
Address
sync.
CT
A
Réseau
synchronisation
d’adresse
Disjoncteur
Com.
A
Fault
shield
Le non-respect de ces instructions entraînera la mort ou des blessures graves.
DB401558
Configuration du module de communication "châssis" CCM Modbus
Le module de communication "châssis" CCM Modbus
possède un bouton-poussoir et deux voyants rouge
et vert en face avant qui sont utilisés lors de la mise
en route. Une fois l'appareil paramétré comme décrit
précédemment en fonction de l'unité de contrôle,
pressez le bouton-poussoir "synchronisation des
adresses" figurant sur le module de communication
"châssis" CCM Modbus.
Au terme de cette opération, le module de
communication "châssis" CCM Modbus aura
automatiquement acquis :
b les mêmes vitesses de transmission et parités que le
module de communication "appareil" BCM ULP Modbus ;
b l'adresse affectée au module de communication
"châssis" BCM ULP Modbus est l'adresse du module de
communication "appareil" Modbus BCM ULP + 50
(@xx+50).
Le module de communication "châssis" CCM Modbus
activera automatiquement la mise en route en se
connectant à tous les autres modules "appareil" RS485
présents sur le réseau de communication.
RISQUE DE CHOC ÉLECTRIQUE, D’EXPLOSION OU D’ARC ÉLECTRIQUE
CE
appuyez sur le bouton pour
transférer les paramètres
Configuration du module de communication "châssis" CCM Modbus.
Remplacement d'un appareil débrochable équipé d'un module de communication
En cas de remplacement d'un appareil débrochable contenant un module de
communication "appareil" BCM ULP Modbus, la configuration et la mise en route
sont effectuées automatiquement par le module de communication "châssis" CCM
Modbus qui transmet automatiquement les paramètres nécessaires au module de
communication "appareil" BCM ULP Modbus avant de le reconnecter au réseau.
28/60
Paramètres de communication CCM
Modes de fonctionnement du module CCM Modbus
Voyant indiquant l'état du module CCM
Le module de communication "châssis" CCM Modbus a deux voyants de mode :
b un voyant rouge Défaut
b un voyant vert Com.
Les états sont présentés dans le tableau ci-dessous.
5100512864A-02
CD
Rouge constant
Module alimenté mais pas initialisé
Vert constant
Module alimenté, fonctionne correctement
Vert avec de courtes
interruptions
Module alimenté, fonctionne correctement, décodage des messages
de réseau en cours
Vert avec de courts
passages au rouge
Module alimenté, fonctionne correctement, mais n'est pas en mesure
de décoder les messages de réseau
Alternance de vert et de
rouge
Mode de configuration en cours (le bouton-poussoir "synchronisation
des adresses" a été enfoncé)
Rouge clignotant
Le module de communication "châssis" CCM Modbus est en cours
d'envoi de sa configuration au module de communication "appareil"
BCM ULP Modbus
Vert clignotant
Le module de communication "châssis" CCM Modbus a envoyé sa
configuration avec succès au module de communication "appareil"
BCM ULP Modbus
A’
Breaker
A’
B
B
Network
B’
DB401559
CT
CE
Mode d'exploitation
Aucune alimentation ne parvient au module
B’
Address
sync.
A
Réseau
Com.
A
voyant vert "com"
Fault
Disjoncteur
voyant rouge "défaut"
shield
Couleur des voyants
Tous les voyants sont
éteints
29/60
5
6
Aide au dépannage
L'unité de contrôle Micrologic n'affiche pas de paramètres de communication (adresse, vitesse de transmission, parité)
Cause possible
Action/solution
Alimentation 24 V cc externe absente.
Polarités inversées aux bornes E1 et E2
Contrôlez l’alimentation 24 V cc.
Contrôlez que la polarité positive (+) est sur E1 et que la polarité négative (–) est
sur E2.
L'unité de contrôle Micrologic P ou H n'affiche pas le paramètre de raccordement de la communication Modbus : 4 fils / 2 fils + ULP
Cause possible
Action/solution
La version BCM est ancienne : la version du firmware doit être > V.0.0.
Contrôler le registre Modbus 577 ou la couleur du bornier de raccordement situé
sur la partie fixe du BCM (gris et non pas vert).
La version de l'unité de contrôle Micrologic (P/H) est ancienne : la version du
firmware doit être > 2009AJ.
Remplacez le BCM existant par un BCM ULP neuf.
Utilisez le logiciel Masterpact RSU (Remote Setting Utility) pour modifier le
paramètre de raccordement de la communication Modbus.
Le module d'affichage en face avant FDM121 clignote et/ou affiche des valeurs erronées
Cause possible
Action/solution
La version du module d'affichage en face avant FDM121 est ancienne : la
version du firmware doit être > V2.0.2.
La version du firmware est inscrite dans le menu Service du module d'affichage
en face avant FDM121.
Utilisez le logiciel Compact NSX RSU (Remote Setting Utility) pour mettre à
niveau le logiciel du module d'affichage en face avant FDM121.
Réponses incohérentes suite à une requête Modbus (dépassement du temps imparti ou absence de réponse)
Cause possible
Action/solution
Raccordements incorrects
Contrôlez le câblage du BCM ULP
Configuration (paramètre 4W/2W+ULP) incompatible avec le câblage du BCM
ULP
Avec la configuration A, contrôlez que les bornes E5 et E6 ne sont pas
raccordées au système ULP.
Avec la configuration B, contrôlez que les bornes E5 et E6 ne sont pas
raccordées au réseau Modbus.
Utilisez 4 fils entre le BCM et le CCM ou remplacez le CCM existant par un CCM
nouvelle génération (CCM portant la marque Schneider Electric sur la face
avant).
Enlevez le module d'interface Modbus du système ULP ou débranchez le
réseau Modbus du BCM ULP et raccordez le réseau Modbus au port Modbus
du module d'interface Modbus (bornes D0, D1).
2 fils seulement sont utilisés entre le BCM ULP et un CCM d'ancienne
génération (CCM ne portant pas la marque Schneider Electric sur la face avant).
Le module d'interface Modbus a été raccordé au système ULP, ce qui provoque
l'inhibition du port Modbus du BCM ULP.
Les écrans LCD de l’unité de contrôle Micrologic et/ou du FDM121 clignotent
Cause possible
Action/solution
2 modules ULP de même type sont connectés sur le même système ULP.
Par exemple, 2 disjoncteurs (1 Compact NSX et 1 Masterpact).
5100512864A-02
Enlevez un des 2 modules ULP du même type. Par exemple, déconnectez le
Compact NSX du système ULP.
0/60
Contents
1
2
3
4
5
6
Safety instructions ..................................................................................................... 32
General presentation of the COM option
Definitions ................................................................................................................................................................................. 34
Communication architecture.................................................................................................................................................... 35
Simplified diagram .................................................................................................................................................................... 36
Description of the Modbus BCM ULP module ......................................................................................................................... 37
Description of the Modbus CCM module ................................................................................................................................. 38
Installation of the communication modules
Precautions before carrying out any work . ........................................................................................................................... 9
Installation of the Modbus BCM ULP "device" communication module . ........................................................................... 40
Fixed, manually operated Compact NS.............. ........................................................................................................................ 40
Fixed, electrically operated Compact NS and Masterpact NT/NW ............................................................................................. 4
Withdrawable Compact NS and drawout Masterpact NT/NW.... ................................................................................................ 45
Installation of the Modbus CCM "chassis" communication module ................................................................................... 47
Withdrawable Compact NS and drawout Masterpact NT/NW .................................................................................................... 47
BCM ULP Communication settings
Communication settings with Micrologic A ............................................................................................................................ 49
Communication settings with Micrologic E ............................................................................................................................ 51
Communication settings with Micrologic P / H ....................................................................................................................... 54
CCM communication setting .................................................................................... 57
Troubleshooting assistance ...................................................................................... 58
5100512864A-02
1/60
Safety instructions
Important information
PLEASE NOTE
Electrical equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this
material.
A qualified person is one who has skills and
knowledge related to the construction and operation
of electrical equipment and the installation, and has
received safety training to recognize and avoid the
hazards involved.
Related documents
For additional instructions, refer to:
b the appropriate Circuit Breaker technical
publications
b the COMBT2EN Masterpact Modbus User Manual
b the TRV99101 ULP system user manual.
You can download these technical publications and
other technical information from our website at:
www.schneider-electric.com.
Hazard categories and special symbols
Read these instructions carefully, and look at the equipment to become familiar
with the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Danger or Warning safety label indicates
that an electrical hazard exists, which will result in personal injury if the
instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided,
will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided,
can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided,
can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous
situation which, if not avoided, can result in equipment damage.
5100512864A-02
2/60
1
1
Safety instructions
Before you begin
WARNING
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR
ARC FLASH
LOSS OF CONTROL
b Apply appropriate personal protective equipment
(PPE) and follow safe electrical work practices.
For NEMA market, see NFPA 70E.
b This equipment must only be installed and
serviced by qualified electrical personnel.
b Turn off all power supplying this equipment before
working on or inside equipment.
b Always use a properly rated voltage sensing
device to confirm power is off.
b Replace all devices, doors and covers before
turning on power to this equipment.
b The designer of any control scheme must consider the potential failure modes
of control paths and, for certain critical control functions, provide a means to
archieve a safe state during and after a path failure. Examples of critical control
functions are emergency stop and overtravel stop.
b Separate or redundant control paths must be provided for critical control
functions.
b System control paths may include communication links. Consideration must be
given to the implications of unanticipated transmission delays or failures of the
link.(1)
b Each implementation of a circuit breaker equipped with a BCM ULP must be
individually and thoroughly tested for proper operation before being placed into
service.
Failure to follow these instructions will result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
(1) NEMA markets: For additional information refer to NEMA ICS 1.1 (latest edition), "Safety
Guidelines for the Application, Installation, and Maintenance of Solid State Control".
5100512864A-02
/60
General presentation of the COM option
Definitions
About the book
This book is the manual for connecting the BCM ULP to the Modbus
network. Consult applicable publications for specific instructions on
installing
the BCM ULP inside the circuit breaker and routing 24 V power.
Definition of the COM option
The COM option is available for all devices
of the ranges:
b Compact NS60b to 200, Powerpact P and R
b Masterpact NT and NW
b Equipped with Micrologic A, E, P and H control units.
With the COM option, the devices may be integrated in a
supervision system implementing the Modbus protocol.
In conjunction with the Micrologic control units,
the COM option is used to:
b analyse distribution-system parameters for operating and
maintenance purposes
b control the device
b indicate status conditions
b identify the causes of faults
b set protection functions
b identify the device.
Status indication by the COM option is independent of the
device indication contacts. These contacts remain available for
conventional uses.
Definition of the abbreviations
BCM = Breaker Communication Module. ULP =
Universal Logic Plug.
CCM = Chassis Communication Module.
5100512864A-02
connection
to the bus
communicating system using
the Modbus protocol
++
modb
CD
CT
CCM
us
CE
3
+
connection
to the bus
connection
between modules
Microl
∆t= I∆n=
tr=
tsd=
Isd=
Ii= Ir=
2
ogic
7.0 A
MAX
s
kA
Ig=
tg=
100
%
40 %
menu
alarm
Microl
ogic
8 12
time
tr
long
16
(s) 4
.8 .9
Ir
2
20
.7
.95
1
24
.6
.98
.5 @ 6 Ir
.5
1
.4 x In
.4 .3
time tsd
.
short
.2
(s) 4
.3
Isd 4 56
.1
3
.2
0off
2.5
8
.1 2t
I
2
on
10
delay
1.5 x Ir
setting
∆t
350
(ms)230
I∆n 5 710
(A)
3
140
800
2
20
60
1
30
.5
7.0 A
MAX
∆t= I∆n=
tr=
tsd=
Isd=
Ii= Ir=
s
kA
Ig=
tg=
earth
100
ous
Ii
4
3
instantane
6
2
8 10
12
15
off
x In
test
leakage
%
1
40 %
withdrawable device
menu
alarm
long
time
.8 .9
.95
.6
.98
.5
1
.4 x In
Ir
.7
short
time
Isd 4 56
3
2.5
8
2
10
1.5 x Ir
fixed device
DB126749
Note: To help ensure that communication network (or control unit keypad)
protection settings do not exceed required power system protection levels,
adjust the control unit switches for required protection before making
adjustments using the communication network (or control unit keypad). Refer
to control unit instructions for additional information regarding protection
settings.
Communicating system using the Modbus protocol
tr
8 12
16
20
24
.5 @ 6 Ir
(s) 4
2
1
.3
.2
.1
on
.1
2
0off
I t
4
3
instantane
6
2
8 10
12
15
off
x In
test
delay
setting
∆t
(ms)230
I∆n 5 710
(A)
3
140
2
20
60
1
30
.5
earth
ous
Ii
tsd .4 .4 .3
.2
(s)
350
800
leakage
1 Micrologic control unit
2 Modbus BCM ULP "device" communication module
3 Modbus CCM "chassis" communication module (option)
General presentation of the COM option.
4/60
2
2
General presentation of the COM option (cont.)
Communication architecture
COM option composition
The COM option depends on the type of circuit breaker:
b for fixed device, COM option = Modbus BCM ULP
communication module
b for withdrawable device, COM option = Modbus BCM
ULP communication module + Modbus CCM "chassis"
communication module.
Manually operated,
fixed device
Electrically operated,
withdrawable device
2
Modbus BCM ULP module
A Modbus BCM ULP "device" module, located behind
the control unit, is supplied installed with its "device"
micro-switches:
b for manually operated devices:
v OF, SDE and/or SD contacts
b for electrically operated devices:
v OF, SDE, PF, CH contacts
v connection kit to the MX1 and XF communicating
voltage releases.
The communication module is independent of the
control unit. It communicates two-way with:
b the Modbus network
b the control unit via an infra-red link.
OF
SD
SDE
1
CE CT
CD
3
6
MX1
XF
3
OF
SDE
PF
CH
4
5
1
Modbus CCM module
Additional Modbus CCM "chassis" communication
module that must be installed on a DIN rail near the
device and connected:
b to the Modbus BCM ULP "device" communication
module for which it stores the address if the device is
disconnected
b to the carriage switch contacts (CD, CT, CE) that
transmit the position of the device in the chassis.
DB126750
Note: the BCM ULP communication parameters must be set
using the control unit (see pages 49 to 55).
1
2
3
4
5
6
Modbus BCM ULP "device" communication module
Modbus CCM "chassis" communication module (option)
OF, SDE ... micro-switches
CE, CD and CT contacts
MX1 and XF communicating voltage releases
COM terminal block (E1 to E6)
: Hard wire
: Modbus
Presentation of the COM option.
Note: specific start-up procedure must be followed (see page 56).
5100512864A-02
5/60
General presentation of the COM option (cont.)
Simplified diagram
Characteristics
b Up to 1 fixed or 15 withdrawable (or drawout)
devices.
b Maximum length of bus y 1200 meters.
b Maximum baud rate = 19200 bauds.
1
2
24 V c
5
6
Consumption of the COM modules and
the Micrologic control units
b Modbus BCM ULP "device" communication module:
40 mA.
b Modbus CCM "chassis" communication module:
55 mA.
b FDM121 display: 21 mA.
b Modbus Communication Interface Module: 21 mA.
b External power supply module (AD) up to 1 A
(24 V DC).
7
12
8
9
13
14
10
11
OK
Mode
DB12672
Note:
to configure the Micrologic control units, if there is no power
supply module, they may be individually supplied via the test
kit and the test connector on the front panel.
4
3
Power supply for COM modules
b COM modules: 24 V DC.
b The external power supply module (AD) is
recommended (see the order form for Masterpact NT/
NW and Compact NS devices).
The control unit power supply must be un-earthed
(isolated).
PC consultation RSU / RCU 6
Ethernet
Ethernet gateway (EGX100) 7
8
External power supply
9
module (AD)
10
5 Modbus network
1
2
3
4
Modbus CCM "chassis"
communication module
FDM121 display
Breaker ULP cord
COM terminal block
Prefabricated wiring
OK
Mode
OK
Mode
11 Modbus BCM ULP
"device" communication
module
12 Modbus Communication
Interface Module
13 ULP cable
14 Compact NSX cord
Simplified diagram of a communicating system implementing the Modbus protocol.
5100512864A-02
6/60
2
2
General presentation of the COM option (cont.)
Description of the Modbus BCM ULP module
The COM option systematically includes a Modbus BCM
ULP "device" communication module (see page 5).
This module is independent of the control unit; it sends
to and receives information from:
b the Modbus network
b the control unit via an infra-red link
b the device, via its micro-switches
b MX1 and XF communicating voltage releases.
The module is made up of the parts shown in
figure opposite, which are supplied installed on the
device and connected to the module.
Parts supplied installed on
the device and connected to
the module
Fixed,
manually
operated
Compact NS
Modbus network
plug-in COM
connector
E3
E1 E2
E4 E5
wiring system
supplied with
MX1/XF option
E6
1/2
Fixed, electrically
operated Compact NS
Fixed and drawout
Masterpact NT/NW
Voltage releases
1 MX1 communicating voltage
releases used to open the
device
2 XF communicating voltage
releases used to close the
device
v
v
Auxiliary contacts
b
4 SD (trip indication)
b
5 SDE (fault-trip indication)
b
b
b
6 PF (ready-to-close)
b
7 CH (springs charged)
b
b standard
v optional
3/4/5/6/7
DB126724
OF (ON/OFF)
Modbus BCM ULP "device" communication module with connections.
5100512864A-02
7/60
General presentation of the COM option (cont.)
Description of the Modbus CCM module
Modbus CCM "chassis"
communication module
1
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
s
modbu
Fault
Com
.
3
CE
CD
CT
s
Addres
sync.
Breaker
CCM
Disjoncteur
Click!
+ +
2
connection to carriage
switch contacts
+
connection to
BCM ULP module
DB126729
Withdrawable (or drawout) devices require two
communication modules :
b a Modbus BCM ULP "device" communication module
installed as indicated on page 5
b a Modbus CCM "chassis" communication module,
supplied separately in a specific package, that must be:
v installed on a DIN rail
v connected to the Modbus BCM ULP "device"
communication module, see page 42.
v connected to the carriage switch contacts (CE, CD,
CT), see page 48.
Once the above operations have been carried out, the
Modbus CCM "chassis" communication module must
be connected to the Modbus network.
CE
CD
CT
Steps for installation of the Modbus CCM "chassis" communication module on withdrawable
Compact NS and drawout Masterpact NT/NW.
Modbus CCM "chassis" communication module
components
1 24 V power supply terminals.
2 "Network" connector for connection to the Modbus
network.
"Breaker" connector for connection to the Modbus
BCM ULP "device" communication module.
4 24 V output terminals for the Modbus BCM ULP
"device" communication module power supply.
5 screw terminals for connection to carriage switch
contacts (CE, CT, CD).
6 address-synchronisation button.
7 module status-conditions LEDs (see the Operating
modes section on page 57).
DB12671
CT
5
B
A’
B’
B
A’
B’
Network
A
Réseau
CD
Breaker
Address
sync.
A
Com.
6
Disjoncteur
7
Fault
shield
1
2
3
CE
4
Components.
5100512864A-02
8/60
2
3
Precautions before carrying out any work
Fixed device
Before carrying out any work, always
de-energize the device as indicated here.
Withdrawable devices should
be moved to disconnected position.
I
ON
push
O
OFF
push
I
O OFF
push
O
1
arged
disch
push
ON
OFF
d
arge
disch
O OFF
3
I
ON
push
O
OFF
push
arged
disch
discharged
O OFF
2
E47086A
E47085A
O OFF
Withdrawable device
I
OOFF
push
ON
push
I
disch
O OFF
push
O
1
arged
push
5
ON
OFF
d
arge
disch
O OFF
I
OOFF
push
3
OOFF
ON
I ON
push
push
push
disch
dis
O OFF
2
E47084A
E4708A
O OFF
5100512864A-02
discharged
arge
d
O OFF
4
E47082A
ed
charg
9/60
3
Fixed, manually operated Compact NS
Installation and wiring of the COM option (Modbus BCM ULP module)
Module installation
Supplied with the device, the module is mounted
behind the control unit and is wired to the
micro-switches (OF, SD, SDE).
On the top of the module is a plug-in COM connector
for direct connection to the Modbus network.
Modbus network
For the connection of the Modbus BCM ULP device,
see page 42.
E1
E3
E1 E2
E4 E5
E4
E2 E3
E5 E6
E6
Modbus network
Modbus connector uses the following colour code:
Colour
plug-in COM
connector
Europe
USA
Red
E1
24 V
24 V
Black
E2
0V
0V
Brown
E
A
Out-
D0
Yellow
E4
B
Out+
D1
White
E5
A'
In-
D0
Blue
E6
B'
In+
D1
E3
E1 E2
E4 E5
E6
100
%
DB126725
40 %
BCM ULP connected to the
micro-switches
Installation of the Modbus BCM ULP "device" communication module on a fixed, manually
operated Compact NS.
5100512864A-02
40/60
Fixed, manually operated Compact NS (cont.)
Installation and wiring of the COM option (Modbus BCM ULP module)
Precaution: wire routing
Run the wires in such a way as to avoid all risk
of pinching or crushing the cable or the wires when
the front cover is fitted (see illustration).
E1 E2
1
4E5
E3 E4
E5 E6
2
E6
4E5
E6
E1 E2E3E
E1 E2E3E
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION
OR ARC FLASH
Replace circuit breaker accessory cover before
energizing circuit breaker to prevent access to live
terminals.
Failure to follow these instructions will result
in death or serious injury.
4
E1 E2
E5
E3 E4
Colour
Red
E1
Black
E2
Brown
E3
Yellow
E4
White
E5
Blue
E6
E6
E1 E2
E3 E4
E5 E6
3
0.8 N.m
7 lb-in
5
4E5
E6
4E5
E1 E2E3E
E6
E1 E2E3E
DB127871
6
Connection of the Modbus BCM ULP "device".
5100512864A-02
41/60
Fixed, manually operated Compact NS (cont.)
Wiring of the COM option (Modbus BCM ULP Module) with or without ULP module (FDM121...)
A Modbus RS 485 4-wire
A Modbus RS 485 2-wire
without ULP module
without ULP module
B Modbus RS 485 2-wire + ULP
with ULP module
100
%
Address
47
- +
Modbus
Com
A
Micrologic E
Baud-rate
19.2 k
+ -
4W, 2W+ULP
4wires
Modbus
Com
Address
+ -
EGX100
Rx- Rx+ Tx- Tx+
w
Micrologic P/H
External power supply
24 V c
- +
Micrologic P/H
External power supply
24 V c
- +
External power supply
24 V c
menu
EGX100
Rx- Rx+ Tx- Tx+
+ FDM121
+ EGX100
Rx- Rx+ Tx- Tx+
version > V2.0.2
B
Micrologic E
Baud-rate
19.2 k
Breaker ULP
cord
w
4W, 2W+ULP
2w+ULP
red black
4 E5
2 E3 E
E1 E
E6
E3
E1 E2
E4 E5
E6
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
E1 E2 E3 E4 E5 E6
B’ / Rx+ D1
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
B’ / Rx+ D1
BCM ULP
A’ / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
B’ / Rx+ D1
BCM ULP
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
DB126744
white blue
BCM ULP
Note: please refer to gateway (EGX100) instructions for grounding shield terminations, all unconnected ends of shields shall be properly insulated.
5100512864A-02
42/60
3
3
Fixed, electrically operated Compact NS and Masterpact NT/NW
Wiring of the COM option (Modbus BCM ULP module)
Module installation
Supplied with the device, the module is mounted
behind the Micrologic control unit and is wired to the
micro-switches.
Modbus network
Connection to the customer terminal block
The module is equipped with a plug-in COM connector
that connects to the fixed customer terminal block
(spring terminals) via prefabricated wiring.
The customer terminal block is used for connection to
the Modbus network.
customer terminal
block
prefabricated
connector
Modbus connector uses the following colour code:
Colour
Europe
USA
Red
E1
24 V
24 V
Black
E2
0V
0V
Brown
E
A
Out-
Modbus network
MX1 / XF
wires
COM
E4
B
Out+
D1
White
E5
A'
In-
D0
Blue
E6
B'
In+
D1
UC3
UC2
MN MX1
SDE1
SDE1
/MX2
/M2C
UC4 /RES
XF
PF
MCH
to MX1 / XF
D0
Yellow
UC1
OF1
OF2
OF3
OF4
plug-in COM
connector
E3
E1 E2
E4 E5
E6
E3
E1 E2
E4 E5
E6
I
push
100
40 %
DB126726
ON
%
ed
harg
disc
O OFF
BCM ULP connected to the
micro-switches
Modbus BCM ULP "device" communication module installation on a fixed, electrically operated
Compact NS or Masterpact NT/NW.
5100512864A-02
4/60
Fixed, electrically operated Compact NS and Masterpact NT/NW (cont.)
Wiring of the COM option (Modbus BCM ULP module) with or without ULP module (FDM121...)
A Modbus RS 485 4-wire
without ULP module
A Modbus RS 485 2-wire
without ULP module
B Modbus RS 485 2-wire + ULP
with ULP module
100
%
menu
Address
47
- +
Modbus
Com
A
Micrologic E
Baud-rate
19.2 k
+ -
w
4wires
Micrologic P/H
Modbus
Com
Address
Baud-rate
19.2 k
+ -
EGX100
Rx- Rx+ Tx- Tx+
4W, 2W+ULP
External power supply
24 V c
- +
Micrologic P/H
External power supply
24 V c
EGX100
Rx- Rx+ Tx- Tx+
- +
External power supply
24 V c
+ FDM121
+ EGX100
Rx- Rx+ Tx- Tx+
version > V2.0.2
B
Micrologic E
w
Breaker ULP
cord
4W, 2W+ULP
2w+ULP
red black
E1 E2 E3 E4 E5 E6
DB126745
B’ / Rx+ D1
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
customer terminal block
E1 E2 E3 E4 E5 E6
24 V
B’ / Rx+ D1
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
0V
A / Tx- D0
24 V
customer terminal block
E1 E2 E3 E4 E5 E6
white blue
customer terminal block
Note: please refer to gateway (EGX100) instructions for grounding shield terminations, all unconnected ends of shields shall be properly insulated.
5100512864A-02
44/60
3
3
Withdrawable Compact NS and drawout Masterpact NT/NW
Wiring of the COM option (Modbus BCM ULP and CCM modules)
Module installation
The Modbus BCM ULP "device" communication
module is installed as previously described for the fixed
devices.
It is supplied already installed and connected to the
micro-switches and the communicating voltage releases.
to Modbus CCM "chassis"
communication module (option)
Connection to the customer terminal block
The module is equipped with a plug-in COM connector,
wired to the prefabricated connector that clips to the
top part of the device.
When the device is racked in, the prefabricated
connector automatically establishes contact with the
customer terminal block (spring terminals).
The customer terminal block is used for connection to
the Modbus network via the Modbus CCM "chassis"
communication module.
CCM "Chassis"
customer terminal
block
prefabricated
connector
wires
to MX1 / XF
Connection of auxiliaries to the module
Same as fixed, electrically operated Compact NS and
Masterpact NT/NW.
plug-in COM
connector
E3
E1 E2
E4 E5
E6
E3
E1 E2
E4 E5
E6
100%
40%
Modbus connector uses the following colour code:
E1
Europe
24 V
USA
24 V
Black
E2
0V
0V
Brown
E
A
Out-
D0
Yellow
E4
B
Out+
D1
White
E5
A'
In-
D0
Blue
E6
B'
In+
D1
MX1 / XF
DB126727
Colour
Red
BCM ULP connected to the
micro-switches
Example of Modbus BCM ULP "device" communication module installation on a drawout
Masterpact NT.
5100512864A-02
45/60
Withdrawable Compact NS and drawout Masterpact NT/NW (cont.)
Wiring of the COM option (Modbus BCM ULP and CCM modules) with or without ULP module (FDM121...)
A Modbus RS 485 4-wire
A Modbus RS 485 2-wire
without ULP module
without ULP module
- +
%
External power supply
24 V c
- +
100
with ULP module
External power supply
24 V c
- +
External power supply
24 V c
B Modbus RS 485 2-wire + ULP
menu
+ -
Micrologic P/H
A
+ -
EGX100
Rx- Rx+ Tx- Tx+
Micrologic E
Baud-rate
19.2 k
w
+ -
A
B
A’
B’
CCM
B
A’
B’
+ -
Network
CCM
A
A
Breaker
2w+ULP
Micrologic E
+ -
Network
Baud-rate
19.2 k
4W, 2W+ULP
+ -
B
Breaker
Micrologic P/H
A
B
B
A’
A’
B’
+ FDM121
+ -
version > V2.0.2
CCM
B’
+ -
Network
on the front face.
4wires
Address
The B configuration is
only possible with CCM
marked Schneider Electric
w
4W, 2W+ULP
Modbus
Com
EGX100
Rx- Rx+ Tx- Tx+
A
B
A’
B’
Breaker
Modbus
Com
Address
47
+ -
EGX100
Rx- Rx+ Tx- Tx+
A
B
A’
B’
Breaker ULP
cord
red black
E1 E2 E3 E4 E5 E6
DB126746
B’ / Rx+ D1
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
customer terminal block
E1 E2 E3 E4 E5 E6
24 V
B’ / Rx+ D1
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
B’ / Rx+ D1
A’ / Rx- D0
A / Tx- D0
B / Tx+ D1
0V
24 V
customer terminal block
E1 E2 E3 E4 E5 E6
white blue
customer terminal block
Note: please refer to gateway (EGX100) instructions for grounding shield terminations, all unconnected ends of shields shall be properly insulated.
5100512864A-02
46/60
3
3
Withdrawable Compact NS and drawout Masterpact NT/NW
Installation of the Modbus CCM module
A
’
A
B
’
ak
er
ld
B
ie
’
A
sh
B
’
R
és
B
ea
A
u
N
et
w
or
k
Module installation
Mount the Modbus CCM "chassis" communication
module on a symmetrical DIN rail near the chassis in a
position where the front can be easily accessed for
connections and settings. If mounting is on a vertical
rail, install a stop to secure the module.
DIN rail must be ordered separately.
nc
te
ur
B
re
Fault
D
is
jo
Com.
s
Addres
sync.
YL
CI
+
CE
–
CD
CT
33110
Modbus Cradle COM module
Module COM chassis Modbus
+ +
5100512662
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR
ARC FLASH
modbus
Fault
CE
CD
CT
Address
sync.
Breaker
CCM
Disjoncteur
XXXXXXXXX
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
Made in France
Com.
DB126728
DANGER
P 99-44
PP-YYYY-WWW-D-T
+
identification label
Package contents.
Use of CCM pushbutton and viewing of indicators
requires 24 V DC power to CCM. The CCM must be
located so personnel are not exposed to hazardous
voltages or energy when operating the CCM
pushbutton or viewing its status indicators.
45
1.77
90
3.54
DB12670
Failure to follow these instructions will result in
death or serious injury.
53
2.08
58
2.28
DB12672
Dimensions.
DIN rail mounting.
5100512864A-02
47/60
3
Withdrawable Compact NS and drawout Masterpact NT/NW
Wiring of the carriage switch contacts to the Modbus CCM module
Connection to the carriage switch contacts (optional)
These are changeover contacts.
b CE, indicating the connected position
b CD, indicating the disconnected position
b CT, indicating the test position.
They connect to the screw terminals on the Modbus
CCM "chassis" communication module via 6 x 0.5 to
1.25 mm2 (6 x 20 to 16 AWG) wires, i.e. two wires per
contact. The terminals are marked CE, CD and CT, as
indicated in figure opposite.
Connections are made to the following terminals:
b CE, terminals 11 and 14
b CD, terminals 811 and 812
b CT, terminals 911 and 914.
For further information on installing the carriage
switches, see the corresponding manuals:
b Manual for Compact NS and Masterpact NT carriage
switches, document no. 51201010
b Manual for Masterpact NW carriage switches,
document no. 51156129.
Modbus CCM "chassis" communication module
s
Fault
Com.
ss
CE
CD
CT
Addre
sync.
Breaker
modbu
Disjoncteur
CCM
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
+ +
+
Network
A
B
A’
B’
Breaker
CE, CT
carriage
contacts
A
B
A’
B’
CCM
CD
carriage
contacts
DB1267
CT
CD
CE
911 914
811 812 311
314
CT
CD
CE
Chassis
Masterpact
NT/NW
Connection to the carriage switches.
5100512864A-02
48/60
Communication settings with Micrologic A
Preliminary remarks
Micrologic 6.0 A
The BCM ULP communication parameters must be
set using the Micrologic control unit or the Masterpact
Remote Setting Utility (RSU) software.
The BCM ULP communication parameters are:
address, baud rate, parity and Modbus connection.
To start Modbus communication, the modules must
have been correctly installed and energized.
The Micrologic control units must also be energized
in order to carry out the following configuration
procedures.
∆t= I∆n=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
s
kA
navigation buttons
40 %
menu
long time
Ir
.7
.6
.5
.4
Simultaneously press the
and the
buttons for
three seconds. A series of four screens are displayed
for configuration of the Modbus communication.
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
D
C
B
A
E
press simultaneously
for 3 seconds
alarm
@ 6 Ir
short time
Ig
I t
off
delay
Ii
instantaneous
4
3
6 8 10
12
15
off
2
x In
Ad47
change
to XX
.4 .4 .3
.2
.3
.1
.2
.1 2 0
I t
(by default)
1
(s)
on
47
test
tg
F
G
H
J
off
ground fault
2
3
DB12674
:
:
:
46
Micrologic A.
5100512864A-02
digital display
100 %
Micrologic A control units
Screen 1 Address
The default Modbus address for the device is 47.
The screen displays AdXX when the existing address
for the communication module is XX.
Select an address from 1 to 47 (unique for the given
device) by pressing the
button. Briefly press the
button to increment the address by one, where the
address displayed after 47 is 1.
Once the address has been selected, press the
button for three seconds, then release it to go on to
the next screen.
MAX
Screen 1 for address.
49/60
4
4
Communication settings with Micrologic A (cont.)
19200
19200 19200
(by default)
9600
4800
DB12675
Screen 2 Baud rate
The default rate is 19200 bauds.
The screen displays XXXX which may be one of three
values, 4800, 9600 or 19200.
Select a rate that is the same for all devices using the
button. Briefly press the button to go on to the
next value in the loop.
button
Once the rate has been selected, press the
for three seconds, then release it to go on to the next
screen.
Screen 2 for baud rate.
pE
E
E
(by default)
n
DB12676
Screen 3 Parity
The default parity is even.
The screen displays X which may be one of two values,
E (even) or n (none).
Select a value that is the same for all devices using the
button. Briefly press the button to go on to the next
value in the loop.
Once the parity has been selected, press the
button for three seconds, then release it to go on
to the next screen.
Screen 3 for parity.
Modbus connection
The default value of the Modbus connection
communication parameter is 4 wires.
The Modbus connection communication parameter
(4 wires, 2 wires + ULP) cannot be set using
Micrologic A control unit. In order to set this parameter,
use the Masterpact Remote Setting Utility (RSU)
software.
5100512864A-02
50/60
Communication settings with Micrologic E
Micrologic 6.0 E
Activate tree navigation mode.
and the
buttons for
Simultaneously press the
three seconds. A series of four screens are displayed
for configuration of the Modbus communication.
digital display
navigation buttons
Screen 1 Address
The default Modbus address for the device is 47. The
screen displays AdXX when the existing address for the
communication module is XX.
A closed padlock icon displayed indicates that the value
is locked.
Press on the
button to open the padlock and
display the first digit (e.g. 4) flashing, ready to be
modified.
Briefly press on the
button to increment in a loop
the value up to the new setting.
Briefly press on the
button to validate this value
and display the second digit (e.g. 7) flashing, ready
to be modified.
Briefly press on the
button to increment in a loop
the value up to the new setting.
button to validate the new
Briefly press on the
Modbus address (the two choosen digits) whose
display becomes permanent. The padlock is still open.
button to padlock this
Briefly press again on the
value and display screen 2.
menu
press simultaneously
DB12675
k
5100512864A-02
(see pages 47)
51/60
4
4
Communication settings with Micrologic E (cont.)
Screen 2 Baud rate
The default rate is 19200 bauds. The screen displays
XXXX which may be one of the three values 4800,
9600 or 19200. A closed padlock icon displayed
indicates that the value is locked.
Screen 3 Parity
The default parity is E (Even). The screen may display
n (none) if a previous setting is existing. A closed
padlock icon displayed indicates that the value is
locked.
Press on the
button to open the padlock and
display the value (e.g. E) flashing, ready to be modified.
Change the existing parity to the other value by
pressing the
button. Press the
button to
validate this value whose display becomes permanent.
The padlock is still open. Briefly press again on the
button to padlock this value.
5100512864A-02
k
DB126756
k
k
menu
k
k
Micrologic 6.0 E
menu
DB126757
Press on the
button to open the padlock and
display the value (e.g. 19.2) flashing, ready to be
modified.
Select a rate that is the same for all devices using the
button. Briefly press the button to go on to the next
value of the loop.
Once the rate has been selected press the
button to validate this value whose display becomes
permanent. The padlock is still open. Briefly press
button to padlock this value and
again on the
display screen .
Micrologic 6.0 E
52/60
Communication settings with Micrologic E (cont.)
5100512864A-02
Micrologic 6.0 E
w
w
w
w
menu
DB127872
Screen 4 Modbus connection (4W, 2W+ULP)
The default value of the Modbus connection
communication parameter is 4 wires.
b If "4W" communication parameter is selected
(default value), 4 wires must be connected between the
BCM ULP (E, E4, E5, E6 terminals) and the CCM (A,
B, A’, B’ terminals).
The front display module FDM121 cannot be
connected.
Connection to Modbus RS 485 4-wire network is
possible.
b If "ULP" communication parameter is selected, 2
wires must be connected between the BCM ULP
(E, E4 terminals) and the CCM (A, B terminals).
The front display module FDM121 can be connected.
Connection to Modbus RS 485 4-wire network is not
possible.
5/60
4
4
Communication settings with Micrologic P / H
Press the
button and in the displayed screen:
b select the Com. setup menu using the
and
navigation keys, then confirm
b the selection by pressing the
key
b then select the Com parameter menu in the same
manner.
Address, baud rate, parity
In the Com parameter menu, set the Address, Baud
rate and Parity values as indicated on the previous
pages. The default and selectable values for each
parameter are the same as indicated previously. See
the information on Screen 1, Screen 2 and Screen .
Press the
key to confirm the selection for each
parameter.
After confirming the Parity parameter, press the
key. A message is displayed asking you if you want to
save the settings. Select Yes and confirm by pressing
key. The three parameters are saved.
the
5100512864A-02
Modbus connection (4W, 2W+ULP)
The default value of the Modbus connection communication parameter is 4 wires.
b If "4 wires" communication parameter is selected (default value), 4 wires must
be connected between BCM ULP (E, E4, E5, E6 terminals) and the CCM
(A, B, A', B' terminals).
The front display module FDM121 cannot be connected.
Connection to Modbus RS 485 4-wire network is possible.
b If "2 wires + ULP" communication parameter is selected, 2 wires must be
connected between BCM ULP (E, E4) and the CCM (A, B terminals).
The front display module FDM121 can be connected.
Connection to Modbus RS 485 4-wire network is not possible.
The Modbus connection communication parameter (4 wires, 2 wires + ULP) can be
set using Micrologic P/H control unit with firmware version > 2009AJ.
If not accessible, use the Masterpact Remote Setting Utility (RSU) software in order
to set this parameter.
Rated system voltage
If a front display module FDM121 is used, it is necessary to set the rated distributionsystem voltage using the Micrologic control unit or the Masterpact RSU software.
button, select the Micrologic setup menu, then the VT ratio command
Press the
and the desired voltage-transformation ratio.
54/60
Communication settings with Micrologic P / H (cont.)
Event
history
Micrologic 6.0 P
address
baud rate,
parity
Ecran ELU - [Ecran...
0A
A
digital display
B
Contacts
M2C/M6C
Micrologic
setup
Metering
setup
C
100
Com.
parameter
Modbus
Com
Remote
settings
Address
47
Remote
control
Baud-rate
19.2 k
4W, 2W+ULP
4wires
Com.
setup
50
0
selection button (key)
confirm button (CR)
language
navigation buttons
long time
Ir
.7
.6
.5
.4
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
setting
D
C
B
A
E
I t
off
Ii
instantaneous
4
3
6 8 10
12
15
off
2
x In
delay
tg
F
G
H
J
(s)
Language
Language
Contacts
M2C/M6C
Date / hour
Deutsch
Breaker
selection
English US
Micrologic
setup
Metering
setup
@ 6 Ir
short time
Isd
4
5
3
2.5
6
8
2
1.5
10
x Ir
Ig
alarm
Event
history
Com.
setup
Neutral TC
VT ratio
English UK
Español
Français
test
.4 .4 .3
.3
.2
.1
on
2
I t
.2
.1
0
off
ground fault
VT ratio
Event
history
Language
Contacts
M2C/M6C
Date / hour
Micrologic
setup
Metering
setup
Neutral TC
Primary
690V
Secondary
690V
VT ratio
DB12677
Com.
setup
Breaker
selection
VT ratio
Navigation buttons and examples of screens.
5100512864A-02
55/60
4
5
CCM communication setting
Withdrawable (or drawout) devices
DANGER
For withdrawable (or drawout) devices, the Modbus
CCM "chassis" communication module is an interface
between the device and the communication network
and there is consequently a procedure for transmitting
the necessary parameters to the module. The
parameters must first be set as indicated previously
and depending on the respective control units (for
Micrologic A, see page 49, for Micrologic E, see page
51, for Micrologic P/H, see page 54).
5100512864A-02
b The CCM may be in proximity to hazardous voltages or energy sources.
b Appropriate Personal Protective Equipment must be used when operating the
CCM pushbutton or monitoring the status indicators. Refer to NFPA 70E or CSA
Z462 or appropriate national codes for additional detail.
CT
CD
A’
B’
A’
B’
Network
B
B
Breaker
Address
sync.
A
Réseau
Address synchronisation
A
Com.
Disjoncteur
Fault
shield
Failure to follow these instructions will result in death or serious injury.
DB12678
Modbus CCM "chassis" communication module
configuration
The Modbus CCM "chassis" communication module
has a pushbutton and two LEDs (red and green) on
the front panel that are used during start-up. Once all
the parameters have been set as indicated previously
and depending on the respective control units, press
the "Address synchronisation" pushbutton on the
Modbus CCM "chassis" communication module.
The Modbus CCM "chassis" communication module
will automatically set up with:
b the same baud-rate and parity values as the Modbus
BCM ULP "device" communication module.
b the address of the Modbus CCM "chassis"
communication module is the address of the Modbus
BCM ULP "device" communication module incremented
by 50 (@xx+50).
The Modbus CCM "chassis" communication module
then automatically launches start-up by connecting
to all the other RS485 devices on the communication
network.
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
CE
press the button to
transfer the parameters
Modbus CCM "chassis" communication module configuration.
Replacement of a withdrawable device equipped with a communication
module
If a withdrawable device equipped with a Modbus BCM ULP "device"
communication module is replaced, configuration and start-up are automatically
carried out by the Modbus CCM "chassis" communication module which sends
the necessary parameters to the Modbus BCM ULP "device" communication
module and then connects it to the communication network.
56/60
CCM communication setting
Modbus CCM module operating modes
CCM module status-conditions LEDs
The Modbus CCM "chassis" communication module has two operating-mode LEDs:
b a red LED Fault
b a green LED Com.
Their states are presented in the table below.
DB400260
CT
5100512864A-02
CD
Network
Module supplied with power, operation OK, currently unable to decode
network messages
Alternating green
and red
Configuration in progress (the Address synchronisation button was
pushed)
Flashing red
Modbus CCM "chassis" communication module currently sending
configuration to the Modbus BCM ULP "device" communication module
Flashing green
Modbus CCM "chassis" communication module successfully sent
configuration to the Modbus BCM ULP "device" communication module
B’
Green interrupted
by short red flashes
A’
Module supplied with power, operation OK, currently decoding network
messages
B
Module supplied with power, operation OK
B’
Module supplied with power, but not initialised
A’
Steady red
Steady green
Green with short
interruptions
Breaker
CE
Operating mode
Module not supplied with power
B
Address
sync.
A
Réseau
Com.
A
green LED Com.
Fault
Disjoncteur
red LED Fault
shield
Colour of LED(s)
All LEDs off
57/60
5
6
Troubleshooting assistance
Micrologic control unit does not display the communication parameters (address, baud rate, parity)
Possible cause
Action/remedy
External 24 V DC power supply absent.
Polarities reversed on terminals E1, E2.
Check the 24 V DC power supply.
Check the + is on E1, the – on E2.
Micrologic control unit P or H does not display the Modbus connection parameter : 4wires / 2w+ULP
Possible cause
Action/remedy
The BCM is an old version: firmware version must be > V.0.0
Check the Modbus register 577 or check the color of the terminal block located
on the fixed part of the BCM (should be grey instead of green).
Micrologic control unit (P/H) is an old version: firmware version must be >
2009AJ.
Replace the existing BCM with a new BCM ULP.
Use the Masterpact Remote Settings Utility (RSU) software in order to modify
the Modbus connection parameter.
The front display module FDM121 is flashing and/or display wrong values
Possible cause
Action/remedy
The front display module FDM121 is an old version: firmware version must be
> V2.0.2.
Firmware version is readable on the Service menu of the front display module
FDM121.
Use the Compact NSX Remote Settings Utility (RSU) software in order to
upgrade the firmware of the front display module FDM121.
Erratic responses on Modbus request (time-out or no response)
Possible cause
Action/remedy
Wrong connections
Configuration (4Wire/2wire+ULP parameter) not consistent with the wiring of the
BCM ULP
Only 2 wires are used between the BCM and an old version of CCM (CCM not
marked Schneider Electric on the front face).
The Modbus communication interface module has been connected to the ULP
system and therefore the Modbus port of the BCM ULP is disabled.
Micrologic control unit and/or FDM121 LCD’s are flashing
Possible cause
2 ULP modules of the same type are connected on the same ULP system. For
example, 2 circuit breakers (1 Compact NSX and 1 Masterpact)
5100512864A-02
Check the wiring of the BCM ULP.
Within configuration A, make sure the terminal blocks E5 and E6 are not
connected to the ULP system.
Within configuration B, make sure the terminal blocks E5 and E6 are not
connected to the Modbus network.
Use 4 wires between the BCM and the CCM or replace the existing CCM with a
new version of CCM (CCM marked Schneider Electric on the front face).
Either disconnect the Modbus communication interface module from the ULP
system, or disconnect the Modbus network from the BCM ULP and connect the
Modbus network to the Modbus port of the Modbus communication interface
module (terminals D0,D1).
Action/remedy
Remove one of the duplicated ULP module. For example, disconnect the
Compact NSX from the ULP system.
58/60
Notes
5100512864A-02
59/60
088 © 2010 Schneider Electric. All rights reserved.
Schneider Electric Industries SAS
5 rue Joseph Monier
CS 02
F - 92506 Rueil Malmaison Cedex
RCS Nanterre 954 50 49
Capital social 896 313 776 €
www.schneider-electric.com
5100512864A-02
En raison de l'évolution des normes et du matériel, les caractéristiques indiquées par le texte
et les images de ce document ne nous engagent qu'après confirmation par nos services.
As standards and equipment change from time to time, please ask for confirmation of the
information given in this document.
Ce document a été imprimé sur du papier écologique.
This document has been printed on ecological paper.
Conception et réalisation : AMEG
Impression :
12/2010
Communicación Modbus (módulo BCM con
conector ULP) para Micrologic
ESPAÑOL
Boletín de instrucciones
5100512864A-02
12/2010
Conservar para uso futuro.
™
ESPAÑOL
ESPAÑOL
5100512864A
12/2010
Contenido
Contenido
Instrucciones de seguridad ...................................................................... 5
Información importante ............................................................................... 5
OBSERVE QUE .................................................................................... 5
Documentos relacionados ..................................................................... 5
Categorías de riesgos y símbolos especiales ....................................... 6
Antes de comenzar ..................................................................................... 7
Acerca de este manual ............................................................................... 8
Definiciones ........................................................................................... 8
Definición de las abreviaturas ............................................................... 9
Arquitectura con comunicación ................................................................... 9
Composición de la opción COM ............................................................ 9
Módulo BCM con conector ULP Modbus .............................................. 9
Módulo CCM Modbus .......................................................................... 10
Diagrama simplificado ............................................................................... 11
Características .................................................................................... 11
Fuente de alimentación para los módulos COM ................................. 11
Consumo de los módulos COM y las unidades de disparo Micrologic 11
Descripción del módulo de conexión ULP con BCM Modbus ................... 12
Descripción del módulo CCM Modbus ...................................................... 13
Componentes del módulo de comunicación “cuna” (CCM) Modbus ... 13
Precauciones antes de efectuar cualquier trabajo ............................... 14
Dispositivo fijo ..................................................................................... 14
Dispositivo extraíble ............................................................................ 14
Fijo de funcionamiento manual, Compact NS....................................... 15
Instalación y alambrado de la opción COM
(módulo BCM con conector ULP Modbus) ............................................... 15
Instalación del módulo ......................................................................... 15
Precaución: enrutamiento de cables ................................................... 16
Alambrado de la opción COM (módulo BCM con conector
ULP Modbus) con o sin módulo ULP (FDM121) ................................. 17
Fijo de funcionamiento eléctrico, Compact NS y Masterpact NT/NW. 18
Alambrado de la opción COM
(módulo BCM con conector ULP Modbus) ............................................... 18
Instalación del módulo ......................................................................... 18
Conexión al bloque de terminales del cliente ...................................... 18
Alambrado de la opción COM (módulo BCM con conector
ULP Modbus) con o sin módulo ULP (FDM121) ....................................... 19
Compact NS extraíble y Masterpact NT/NW extraíble .......................... 20
Alambrado de la opción COM
(módulos CCM y BCM con conector ULP Modbus) .................................. 20
Instalación del módulo ......................................................................... 20
Conexión al bloque de terminales del cliente ...................................... 20
Conexión de accesorios auxiliares al módulo ..................................... 20
Alambrado de la opción COM (módulo BCM con conector
ULP Modbus y módulos CCM) con o sin módulos ULP (FDM121) .......... 21
Instalación del módulo CCM Modbus ....................................................... 22
Instalación del módulo ......................................................................... 22
Alambrado de los contactos de carro en el módulo CCM Modbus ........... 23
Conexión a los contactos de carro (opcional) ..................................... 23
© 2010 Schneider Electric Reservados todos los derechos
3
ESPAÑOL
Presentación general de la opción COM ................................................. 8
Contenido
5100512864A
12/2010
Configuraciones de comunicación con Micrologic A........................... 24
Comentarios preliminares .................................................................... 24
Unidades de disparo Micrologic A ....................................................... 24
Pantalla 1 – Dirección .................................................................... 24
Pantalla 2 – Velocidad en baudios................................................. 25
Pantalla 3 – Paridad....................................................................... 25
Conexión Modbus .......................................................................... 25
Configuraciones de comunicación con Micrologic E........................... 26
ESPAÑOL
Pantalla 1 – Dirección ....................................................................
Pantalla 2 – Velocidad en baudios.................................................
Pantalla 3 – Paridad.......................................................................
Pantalla 4 – Conexión Modbus (4W, 2W+ULP).............................
26
27
27
28
Configuraciones de comunicación con Micrologic P / H ..................... 29
Dirección, velocidad en baudios, paridad ...................................... 29
Conexión Modbus (4W, 2W+ULP)................................................. 29
Tensión nominal del sistema ......................................................... 29
Configuración de comunicación del CCM ............................................. 31
Dispositivos extraíbles ................................................................... 31
Configuración del módulo de comunicación “cuna” (CCM)
Modbus .......................................................................................... 31
Sustitución de un dispositivo extraíble equipado con
un módulo de comunicación .......................................................... 31
Modos de funcionamiento del módulo CCM Modbus ............................... 32
LED de estado del módulo CCM ................................................... 32
Asistencia de diagnóstico de problemas .............................................. 33
4
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Instrucciones de seguridad
Información importante
Instrucciones de seguridad
Información importante
OBSERVE QUE
Solamente el personal especializado deberá instalar, hacer funcionar y
prestar servicios de mantenimiento al equipo eléctrico.
Schneider Electric no asume responsabilidad alguna por las consecuencias
emergentes de la utilización de este material.
Documentos relacionados
ESPAÑOL
Una persona calificada es aquella que tiene destreza y conocimiento
técnico relacionado con la construcción y funcionamiento del equipo
eléctrico y la instalación; asimismo, esta persona ha recibido capacitación
sobre seguridad con la cual puede reconocer y evitar los riesgos
involucrados.
Para obtener instrucciones adicionales, consulte:
• las publicaciones técnicas apropiadas del interruptor automático
• el manual de usuario de Modbus Masterpact COMBT32EN
• el manual de usuario del sistema de conexión ULP TRV99101.
Es posible obtener estas publicaciones técnicas y otra información técnica
de nuestro sitio web:
www.schneider-electric.com.
© 2010 Schneider Electric Reservados todos los derechos
5
Instrucciones de seguridad
Información importante
Categorías de riesgos y símbolos
especiales
5100512864A
12/2010
Asegúrese de leer detenidamente estas instrucciones y realice una
inspección visual del equipo para familiarizarse con él antes de instalarlo,
hacerlo funcionar o prestarle servicio de mantenimiento. Los siguientes
mensajes especiales pueden aparecer en este boletín o en el equipo para
advertirle sobre peligros potenciales o llamar su atención sobre cierta
información que clarifica o simplifica un procedimiento.
La adición de este símbolo a una etiqueta de seguridad de “Peligro” o
“Advertencia” indica la existencia de un peligro eléctrico que podrá causar
lesiones personales si no se observan las instrucciones.
ESPAÑOL
Este es el símbolo de alerta de seguridad. Se usa para avisar sobre
peligros potenciales de lesiones personales. Respete todos los mensajes
de seguridad con este símbolo para evitar posibles lesiones o la muerte.
PELIGRO
PELIGRO indica una situación de peligro inminente que, si no se evita,
causará la muerte o lesiones serias.
ADVERTENCIA
ADVERTENCIA indica una situación potencialmente peligrosa que, si no
se evita, puede causar la muerte o lesiones serias.
PRECAUCIÓN
PRECAUCIÓN indica una situación potencialmente peligrosa que, si no se
evita, puede causar lesiones menores o moderadas.
PRECAUCIÓN
PRECAUCIÓN, cuando se usa sin el símbolo de alerta de seguridad,
indica una situación potencialmente peligrosa que, si no se evita, puede
causar daños a la propiedad.
NOTA: Proporciona información adicional para clarificar o simplificar un
procedimiento.
6
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Instrucciones de seguridad
Antes de comenzar
Antes de comenzar
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO
POR ARQUEO
• Utilice equipo de protección personal (EPP) apropiado y siga las
prácticas de seguridad en trabajos eléctricos establecidas por su
Compañía, consulte la norma 70E de NFPA y NOM-029-STPS.
• Desenergice el equipo antes de realizar cualquier trabajo en él.
• Siempre utilice un dispositivo detector de tensión nominal adecuado
para confirmar la desenergización del equipo.
• Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes
de volver a energizar el equipo.
El incumplimiento de estas instrucciones podrá causar la muerte o
lesiones serias.
ADVERTENCIA
PÉRDIDA DE CONTROL
• El diseñador de un plan de control deberá tener en cuenta los modos
potenciales de fallas en las trayectorias de control y, para ciertas
funciones de control críticas, deberá proporcionar un medio para
alcanzar un estado seguro durante y después de una falla en la
trayectoria. Un paro de emergencia y un paro por sobre recorrido son
ejemplos de funciones de control críticas.
• Deberán proporcionarse trayectorias de control independientes o
redundantes para las funciones de control críticas.
• Las trayectorias de control del sistema pueden incluir enlaces de
comunicación. Deberán tenerse en cuenta las implicaciones de fallas o
retardos de transmisión no anticipados del enlace. (1)
• Cada interruptor automático equipado con un módulo BCM con
conector ULP deberá ser probado individualmente y asegurarse de que
funciona correctamente antes de ponerlo en funcionamiento.
El incumplimiento de estas instrucciones puede causar la muerte,
lesiones serias o daño al equipo.
1
© 2010 Schneider Electric Reservados todos los derechos
Mercados NEMA: Para obtener información adicional, consulte la publicación NEMA ICS 1.1
(última edición), “Procedimientos de seguridad sobre la aplicación, instalación y
mantenimiento de control de estado sólido”.
7
ESPAÑOL
• Solamente el personal eléctrico especializado deberá instalar y prestar
servicio de mantenimiento a este equipo.
Presentación general de la opción COM
Acerca de este manual
5100512864A
12/2010
Presentación general de la
opción COM
ESPAÑOL
Acerca de este manual
Este manual contiene las instrucciones de conexión del módulo BCM
(módulo de comunicación del interruptor) con conector ULP (conector
lógico universal) a la red Modbus. Consulte las publicaciones
correspondientes para obtener instrucciones específicas sobre cómo
instalar el módulo BCM con conector ULP dentro del interruptor automático
y dirigir la alimentación de 24 V.
Definiciones
Definición de la opción COM
La opción COM está disponible para todos los dispositivos de las gamas:
• Compact NS630b a 3200, Powerpact P y R
• Masterpact NT y NW
• Equipados con unidades de disparo Micrologic A, E, P y H.
Con la opción COM, los dispositivos pueden ser integrados a un sistema de
supervisión implementando el protocolo Modbus. Junto con las unidades de
disparo Micrologic, la opción COM se usa para:
• analizar parámetros del sistema de distribución con fines de
funcionamiento y mantenimiento
•
•
•
•
•
controlar el dispositivo
indicar las condiciones de estado
identificar las causas de las fallas
configurar las funciones de protección
identificar el dispositivo.
La indicación de estado a través de la opción COM es independiente de los
contactos de indicación del dispositivo. Estos contactos permanecen
disponibles para usos comunes.
NOTA: Para garantizar que los ajustes de protección de la red de
comunicación (o terminal de programación y ajustes de la unidad de
disparo) no excedan los niveles necesarios de protección del sistema de
alimentación, ajuste los conmutadores de la unidad de disparo en la
protección necesaria antes de realizar ajustes empleando la red de
comunicación (o la terminal de programación y ajustes de la unidad de
disparo). Consulte el boletín de instrucciones de la unidad de disparo para
obtener más información con respecto a los ajustes de protección.
8
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Definición de las abreviaturas
Presentación general de la opción COM
Arquitectura con comunicación
BCM = Módulo de comunicaciones del interruptor
ULP = Conector lógico universal
CCM = Módulo de comunicación de la cuna
conexión al
bus
sistema de comunicación usando
el protocolo Modbus
++
us
modb
CD
CT
CCM
CE
3
+
ESPAÑOL
conexión al
bus
conexión entre
módulos
ogic
Microl
Δt= IΔn=
tr=
tsd=
Isd=
Ii= Ir=
Ig=
tg=
2
100
7.0 A
MAX
s
kA
%
40 %
menu
alarm
ogic
Microl
7.0 A
MAX
Δt= IΔn=
tr=
tsd=
Isd=
Ii= Ir=
s
kA
dispositivo extraíble
Ig=
tg=
100
8 12
time
tr
long
(s) 4
16
.8 .9.95 2
Ir
20
.7
1
24
.6
.98
.5 @ 6 Ir
.5
1
.4 x In
.4 .3
time tsd
.
short
.2
(s) 4
.3
Isd 4 56
.1
3
.2
0off
2.5
8
.1 2t
I
2
on
10
delay
1.5 x Ir
setting
Δt
350
(ms)230
IΔn 5 710
(A)
3
140
800
2
20
60
1
30
.5
earth
us
instantaneo
Ii
6
4
3
2
8 10
12
15
off
x In
test
leakage
%
40 %
1
menu
alarm
long
dispositivo fijo
time
.8 .9
.7
.95
.6
.98
.5
1
.4 x In
Ir
short
time
Isd 4 56
3
2.5
8
2
10
1.5 x Ir
tr
8 12
16
20
24
.5 @ 6 Ir
(s) 4
2
1
.3
.2
.1
on
2
.1
0off
I t
6
4
3
2
8 10
12
15
off
x In
test
delay
setting
Δt
(ms)230
IΔn 5 710
(A)
3
140
2
20
60
1
30
.5
earth
ous
instantane
Ii
tsd .4 .4 .3
.2
(s)
350
800
leakage
1. Unidad de disparo Micrologic
2. Módulo de comunicación BCM con conector ULP Modbus
3. Módulo de comunicación “cuna” (CCM) Modbus (opción)
Descripción general de la opción COM.
Arquitectura con comunicación
Composición de la opción COM
La opción COM depende del tipo de interruptor automático:
• para el dispositivo fijo, la opción COM = Módulo de comunicación BCM
con conector ULP Modbus
• para el dispositivo extraíble, la opción COM = Módulo de comunicación
BCM con conector ULP + módulo de comunicación “cuna” (CCM)
Modbus.
Módulo BCM con conector ULP Modbus
Un módulo de comunicación BCM con conector ULP Modbus, situado
detrás de la unidad de disparo, incluye microconmutadores:
• para los dispositivos de funcionamiento manual:
— contactos OF, SDE y/o SD
• para los dispositivos de funcionamiento eléctrico:
— contactos OF, SDE, PF, CH
— kit de conexión a los disparadores voltimétricos de comunicación
MX1 y XF
© 2010 Schneider Electric Reservados todos los derechos
9
Presentación general de la opción COM
Arquitectura con comunicación
5100512864A
12/2010
El módulo de comunicación es independiente de la unidad de disparo.
Tiene comunicación bidireccional con:
• la red Modbus
• la unidad de disparo a través de un enlace infrarojo.
NOTA: Los parámetros de comunicación del módulo BCM con conector
ULP deben configurarse empleando la unidad de disparo (consulte las
páginas 24 a 29).
Módulo CCM Modbus
Módulo de comunicación “cuna” (CCM) Modbus adicional que debe ser
instalado en un riel DIN junto al dispositivo y conectado:
ESPAÑOL
• al módulo de comunicación BCM con conector ULP Modbus en el que
se almacena la dirección si el dispositivo es desconectado
• a los contactos de carro (CD, CT, CE) que transmiten la posición del
dispositivo en la cuna.
NOTA: el procedimiento de arranque específico debe seguirse (consulte la
página 31).
Funcionamiento manual,
dispositivo fijo
Funcionamiento eléctrico,
dispositivo extraíble
2
CE CT
OF
SD
SDE
6
5
3
1
MX1
XF
3
OF
SDE
PF
CH
1.
2.
3.
4.
5.
6.
4
CD
Módulo de comunicación BCM con conector ULP Modbus
Módulo de comunicación “cuna” (CCM) Modbus (opción)
Microconmutadores OF, SDE
Contactos CE, CD y CT
Disparadores voltimétricos de comunicación MX1 y XF
Bloque de terminales COM (E1 a E6)
1
Conexión
con cables
Modbus
Descripción de la opción COM.
10
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Presentación general de la opción COM
Diagrama simplificado
Diagrama simplificado
Características
• Hasta un máximo de 31 dispositivos fijos o 15 extraíbles.
• Longitud máxima del bus = 1 200 metros
• Velocidad máxima en baudios = 19 200.
Fuente de alimentación para los módulos
COM
• Módulos COM: 24 Vcd
• Se recomienda el módulo de la fuente de alimentación externa (AD),
La fuente de alimentación de la unidad de disparo no debe estar puesta a
tierra (aislada).
Consumo de los módulos COM y las
unidades de disparo Micrologic
•
•
•
•
•
Módulo de comunicación BCM con conector ULP Modbus : 40 mA.
Módulo de comunicación “cuna” (CCM) Modbus: 55 mA.
Módulo de visualización FDM121: 21 mA.
Módulo de interfaz de comunicación Modbus: 21 mA.
Módulo de la fuente de alimentación externa (AD) hasta un máximo
de 1 A (24 Vcd).
NOTA: para configurar las unidades de disparo Micrologic, si no hay un
módulo de fuente de alimentación, estos pueden ser provistos
individualmente a través del kit de prueba y el conector de prueba en el
panel frontal.
1
2
4
3
24 V c
5
6
7
12
8
13
9
14
10
11
OK
Mode
1. Consulte a través de una
PC – RSU/RCU
2. Ethernet
3. Pasarela Ethernet
(EGX100)
4. Módulo de alimentación
externa (AD)
5. Red Modbus
6. Módulo de comunicación
“cuna” (CCM) Modbus
7. Módulo de visualización
FDM121
8. Cordón ULP
9. Bloque de terminales
COM
10. Alambrado prefabricado
OK
OK
Mode
Mode
11. Módulo de comunicación
BCM con conector ULP
Modbus
12. Módulo de interfaz de
comunicación Modbus
13. Cable ULP
14. Cordón Compact NSX
Diagrama simplificado de un sistema de comunicación con implementación del protocolo
Modbus.
© 2010 Schneider Electric Reservados todos los derechos
11
ESPAÑOL
consulte la solicitud de pedido para los dispositivos Masterpact NT/NW
y Compact NS.
Presentación general de la opción COM
Descripción del módulo de conexión ULP con BCM Modbus
Descripción del módulo de
conexión ULP con BCM Modbus
5100512864A
12/2010
La opción COM sistemáticamente incluye un módulo de comunicación BCM
con conector ULP Modbus (consulte la página 9). Este módulo es
independiente de la unidad de disparo, envía información a y recibe de:
•
•
•
•
la red Modbus
la unidad de disparo a través de un enlace infrarojo
el dispositivo, a través de los microconmutadores
los disparadores voltimétricos de comunicación MX1 y XF.
El módulo está compuesto de las partes mostradas en la figura, las cuales
son provistas y vienen instaladas en el dispositivo y conectadas en el
módulo.
ESPAÑOL
Fijo de
funcionamiento
manual, Compact
NS
Partes provistas e instaladas en el
dispositivo y conectadas al módulo
Fijo de funcionamiento
eléctrico, Compact NS –
Fijo y extraíble, Masterpact
NT/NW
Disparador voltimétrico
1. Disparadores voltimétricos para
comunicación MX1 que se usan para
abrir el dispositivo
2. Disparador voltimétrico para
comunicación XF que se usa para
cerrar el dispositivo
Contactos auxiliares
3. OF (ON/OFF)
4. SD (indicación de disparo)
5. SDE (indicación de disparo por falla)
6. PF (cierre)
7. CH (resorte cargado)
estándar
opcional
red Modbus
E3
E1 E2
E4 E5
sistema de
alambrado
provisto con
opción
MX1/XF
E6
1/2
conector COM
enchufable
3/4/5/6/7
Módulo de comunicación BCM con conector ULP Modbus y conexiones
12
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Presentación general de la opción COM
Descripción del módulo CCM Modbus
Descripción del módulo CCM
Modbus
Los dispositivos extraíbles necesitan dos módulos de comunicación:
• un módulo de comunicación BCM con conector ULP Modbus instalado
como se indicó en la página 9
• un módulo de comunicación “cuna” (CCM) Modbus, provisto por
separado en un paquete específico, que debe estar:
— instalado en un riel DIN
— conectado al módulo de comunicación BCM con conector ULP
Modbus, consulte la página 17.
Una vez que se hayan realizado las operaciones anteriores, el módulo de
comunicación “cuna” (CCM) Modbus debe ser conectado a la red Modbus
módulo de comunicación
“cuna” (CCM) Modbus
modbu
s
Fault
Com.
CE
CD
CT
s
Addres
sync.
Breaker
CCM
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
+ +
1
Disjoncteur
¡Clic!
conexión a los contactos
2 de carro
+
3 conexión al módulo BCM
con conector ULP
CE
CD
CT
Pasos para instalar el módulo de comunicación “cuna” (CCM) Modbus en los Compact NS
extraíbles y Masterpact NT/NW extraíbles
Componentes del módulo de
comunicación “cuna” (CCM) Modbus
1
1. Terminales de la fuente de alimentación de 24 V.
2. Conector “red” para conexión a la red Modbus.
5
CD
A’
B’
A’
B’
Network
B
B
Breaker
Address
sync.
CT
A
Réseau
6
Disjoncteur
Com.
A
Fault
7
shield
3. Conector “interruptor” para conexión al módulo de comunicación BCM
con conector ULP Modbus.
2
3
4. Terminales de salida de 24 V para la fuente de alimentación del módulo
de comunicación BCM con conector ULP Modbus.
5. Terminales de tornillo para conexión a los contactos de carro
(CE, CD, CT).
6. Botón de sincronización de direcciones.
7. LED de estado del módulo (consulte la sección de modos de
funcionamiento en la página 32).
CE
4
Componentes
© 2010 Schneider Electric Reservados todos los derechos
13
ESPAÑOL
— conectado a los contactos de carro (CE, CD, CT), consulte la
página 23.
Precauciones antes de efectuar cualquier trabajo
5100512864A
12/2010
Precauciones antes de
efectuar cualquier trabajo
Antes de efectuar cualquier trabajo, siempre desenergice el dispositivo
como se indica aquí. Los dispositivos extraíbles deberán moverse a la
posición de desconectado.
Dispositivo fijo
I
OF
ON
push
ESPAÑOL
OF
push
I
ON
push
OOFF
1
arged
disch
push
O OFF
arged
disch
O OFF
I
O
push
3
ON
OFF
push
arged
disch
O OFF
discharged
O OFF
2
Dispositivo extraíble
I
OOFF
ON
push
push
5
I
1
arged
disch
O
ON
push
O
push
OFF
OFF
d
arge
disch
O OFF
3
I
OOFF
I
O
ON
push
push
push
ON
OFF
push
arge
disch
arged
disch
O OFF
14
2
O OFF
discharged
O
d
OFF
4
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Fijo de funcionamiento manual, Compact NS
Instalación y alambrado de la opción COM (módulo BCM con conector ULP Modbus)
Fijo de funcionamiento
manual, Compact NS
Instalación y alambrado de la
opción COM (módulo BCM con
conector ULP Modbus)
Instalación del módulo
ESPAÑOL
Provisto con el dispositivo, el módulo viene montado detrás de la unidad de
disparo y está conectado a los microconmutadores (OF, SD, SDE).
En la parte superior del módulo hay un conector COM enchufable para
conexión directa a la red Modbus.
Para la conexión módulo BCM con conector ULP Modbus, consulte la
página 17.
red Modbus
E1
E3
E1 E2
E4 E5
E4
E2 E3
E5 E6
E6
red Modbus
El conector Modbus utiliza el siguiente código de colores:
Color
Europa
EUA
Rojo
conector COM
enchufable
Negro
Café
Amarillo
Blanco
E3
E1 E2
E4 E5
E6
Azul
100
%
40 %
Módulo BCM con conector
ULP conectado a los
microconmutadores
Instalación del módulo BCM con conector ULP Modbus en un Compact NS fijo de funcionamiento
manual.
© 2010 Schneider Electric Reservados todos los derechos
15
Fijo de funcionamiento manual, Compact NS
Instalación y alambrado de la opción COM (módulo BCM con conector ULP Modbus)
Precaución: enrutamiento de cables
5100512864A
12/2010
Coloque los cables de manera tal para evitar todo riesgo de prensar o
aplastar el cable o los conductores cuando la cubierta frontal es colocada
(vea la ilustración).
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO
POR ARQUEO
Vuelva a colocar la cubierta de accesorios del interruptor antes de
energizarlo para evitar el acceso a las terminales vivas.
ESPAÑOL
El incumplimiento de estas instrucciones podrá causar la muerte o
lesiones serias.
E1 E2
1
E1 E2E3E
4E5
4E5
E6
E1 E2E3E
Color
Rojo
Negro
Café
4
E1 E2
E5 E6
2
E6
E5
E3 E4
E3 E4
E1
2
E3
Amarillo
E4
Blanco
E5
Azul
E6
E1 E2
E3 E4
E5 E6
3
E6
0,8 N•m
7 lbs-pulg
5
4E5
E6
E1 E2E3E
E1 E2E3
E4E5
E6
6
Conexión del módulo BCM con conector ULP Modbus.
16
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Fijo de funcionamiento manual, Compact NS
Instalación y alambrado de la opción COM (módulo BCM con conector ULP Modbus)
Alambrado de la opción COM (módulo
BCM con conector ULP Modbus) con o
sin módulo ULP (FDM121)
A
Modbus RS 485 de 4
hilos sin módulo ULP
A
Modbus RS 485 de 2
hilos sin módulo ULP
B
Modbus RS 485 de 2 hilos con
módulo ULP
100
%
Fuente de alim. externa
24 V c
Fuente de alim. externa
24 V c
- +
Address
47
A
Micrologic E
Baud-rat
e
19.2 k
+ -
4W, 2W+ULP
4wires
Micrologic P/H
+ -
EGX100
Rx- Rx+ Tx- Tx+
w
EGX100
Rx- Rx+ Tx- Tx+
+ FDM121
ESPAÑOL
Modbus
Com
- +
Micrologic P/H
Fuente de alim. externa
24 V c
- +
menu
+ EGX100
Rx- Rx+ Tx- Tx+
version > V2.0.2
B
Modbus
Com
Address
Micrologic E
Baud-rate
19.2 k
Cordón ULP
w
4W, 2W+UL
P
E6
4 E5
2 E3 E
E1 E
E3
E1 E2
E4 E5
E6
E1 E2 E3 E4 E5 E6
Azul
Blanco
E1 E2 E3 E4 E5 E6
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
A’ / Rx- D0
BCM ULP
B’ / Rx+ D1
B / Tx+ D1
A / Tx- D0
0V
24 V
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
BCM ULP
E1 E2 E3 E4 E5 E6
Negro
Rojo
2w+ULP
BCM ULP
NOTA: consulte las instrucciones de la pasarela (EGX100) para conectar a tierra las terminaciones de blindaje, todos los extremos de blindajes no conectados
deben estar correctamente aislados.
© 2010 Schneider Electric Reservados todos los derechos
17
Fijo de funcionamiento eléctrico, Compact NS y Masterpact NT/NW
Alambrado de la opción COM (módulo BCM con conector ULP Modbus)
5100512864A
12/2010
Fijo de funcionamiento
eléctrico, Compact NS y
Masterpact NT/NW
Alambrado de la opción COM
(módulo BCM con conector ULP
Modbus)
ESPAÑOL
Instalación del módulo
Provisto con el dispositivo, el módulo viene montado detrás de la unidad de
disparo Micrologic y está conectado a los microconmutadores.
Conexión al bloque de terminales del
cliente
El módulo está equipado con un conector COM enchufable que se conecta
al bloque de terminales fijas del cliente (terminales de resorte) a través del
alambrado prefabricado. El bloque de terminales del cliente se usa para
conexión a la red Modbus.
red Modbus
bloque de
terminales del
cliente
El conector Modbus utiliza el siguiente código de colores:
Color
Rojo
Negro
Café
Amarillo
Europa
EUA
red Modbus
MX1 / XF
conector
prefabricado
conductores
UC2
UC1
COM
UC3
MN MX1
SDE1
SDE1
/MX2
/M2C
UC4 /RES
XF
PF
MCH
OF1
OF2
OF3
OF4
a MX1 / XF
conector COM
enchufable
E1
E4
E2 E3
E5 E6
E3
E1 E2
E4 E5
E6
Blanco
I
push
Azul
100
ON
%
disc
40 %
harg
ed
O OFF
BCM con conector ULP conectado
a los microconmutadores
Instalación del módulo de comunicación BCM con conector ULP Modbus en un Compact NS o
Masterpact NT/NW fijo de funcionamiento eléctrico.
18
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Fijo de funcionamiento eléctrico, Compact NS y Masterpact NT/NW
Alambrado de la opción COM (módulo BCM con conector ULP Modbus) con o sin módulo ULP (FDM121)
Alambrado de la opción COM
(módulo BCM con conector ULP
Modbus) con o sin módulo ULP
(FDM121)
A
Modbus RS 485 de 4
hilos sin módulo ULP
A
Modbus RS 485 de 2
hilos sin módulo ULP
B
Modbus RS 485 de 2 hilos con
módulo ULP
100
%
menu
A
Micrologic E
Baud-rate
19.2 k
+ -
w
+ -
EGX100
Rx- Rx+ Tx- Tx+
4W, 2W+ULP
4wires
Micrologic P/H
ESPAÑOL
Address
47
- +
Modbus
Com
Fuente de alim. externa
24 V c
- +
Micrologic P/H
Fuente de alim. externa
24 V c
- +
Fuente de alim.externa
24 V c
EGX100
Rx- Rx+ Tx- Tx+
+ FDM121
+ EGX100
version > V2.0.2
Rx- Rx+ Tx- Tx+
B
Modbus
Com
Address
Baud-rate
19.2 k
Micrologic E
w
Cordón ULP
4W, 2W+ULP
E1 E2 E3 E4 E5 E6
Blanco
Azul
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
0V
A / Tx- D0
bloque de terminales del
cliente
E1 E2 E3 E4 E5 E6
24 V
B’ / Rx+ D1
A’ / Rx- D0
B / Tx+ D1
A / Tx- D0
0V
24 V
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
0V
A / Tx- D0
24 V
bloque de terminales del
cliente
E1 E2 E3 E4 E5 E6
Negro
Rojo
2w+ULP
bloque de terminales del
cliente
NOTA: consulte las instrucciones de la pasarela (EGX100) para conectar a tierra las terminaciones de blindaje, todos los extremos de blindajes no conectados
deben estar correctamente aislados.
© 2010 Schneider Electric Reservados todos los derechos
19
Compact NS extraíble y Masterpact NT/NW extraíble
Alambrado de la opción COM (módulos CCM y BCM con conector ULP Modbus)
5100512864A
12/2010
Compact NS extraíble y
Masterpact NT/NW extraíble
Alambrado de la opción COM
(módulos CCM y BCM con
conector ULP Modbus)
Instalación del módulo
El módulo de comunicación BCM con conector ULP Modbus se instala
como se describió anteriormente para los dispositivos fijos.
ESPAÑOL
Es incluido y está instalado y conectado a
microconmutadores y disparadores voltimétricos de comunicación.
Conexión al bloque de terminales del
cliente
El módulo está equipado con un conector COM enchufable alambrado al
conector prefabricado y se sujeta a la parte superior del dispositivo.
Cuando el dispositivo es insertado, el conector prefabricado
automáticamente establece contacto con el bloque de terminales del cliente
(terminales de resorte).
El bloque de terminales del cliente se usa para conexión a la red Modbus a
través del módulo de comunicación “cuna” (CCM) Modbus.
Conexión de accesorios auxiliares al
módulo
Mismo que el Compact NS y Masterpact NT/NW fijo de funcionamiento
eléctrico.
al módulo de comunicación
“cuna” (CCM) Modbus (opción)
CCM “cuna”
bloque de
terminales del
cliente
conector
prefabricado
conductores
a MX1 / XF
conector
COM
enchufable
E1 E2
E5
E3 E4
E6
E3
E1 E2
E4 E5
E6
100%
40%
El conector Modbus utiliza el siguiente código de colores:
Europa
EUA
Color
Rojo
Negro
Café
MX1 / XF
Amarillo
Blanco
Azul
BCM con conector ULP conectado
a los microconmutadores
Ejemplo de una instalación del módulo de comunicación BCM con conector ULP Modbus en un
Masterpact NT extraíble.
20
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
Compact NS extraíble y Masterpact NT/NW extraíble
12/2010
Alambrado de la opción COM (módulo BCM con conector ULP Modbus y módulos CCM) con o sin módulos ULP (FDM121)
Alambrado de la opción COM
(módulo BCM con conector ULP
Modbus y módulos CCM) con o
sin módulos ULP (FDM121)
hilos sin módulo ULP
A Modbus RS 485 de 2
hilos sin módulo ULP
Fuente de alim. externa
módulo ULP
Fuente de alime. externa
24 V c
Fuente de alim. externa
24 V c
- +
- +
100
B Modbus RS 485 de 2 hilos con
24 V c
- +
A Modbus RS 485 de 4
%
menu
A’
B’
w
A
B
A’
B’
+ FDM121
+ -
version > V2.0.2
CCM
CCM
4W, 2W+UL
P
2w+ULP
B
A
B
A’
B’
+ -
A
B
A’
B’
A’
B’
A
B
A’
B’
ESPAÑOL
+ -
Cordón
ULP
E1 E2 E3 E4 E5 E6
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
0V
A / Tx- D0
bloque de terminales del
cliente
E1 E2 E3 E4 E5 E6
24 V
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
0V
A / Tx- D0
24 V
B’ / Rx+ D1
B / Tx+ D1
A’ / Rx- D0
0V
A / Tx- D0
24 V
bloque de terminales del
cliente
B
CCM
+ -
E1 E2 E3 E4 E5 E6
A
Azul
Baud-rate
19.2 k
Micrologic E
Breaker
Address
+ A
Network
+ -
B
Modbus
Com
Breaker
Micrologic P/H
Network
4wires
Blanco
w
4W, 2W+ULP
Rx- Rx+ Tx- Tx+
Network
Micrologic E
Baud-rat
e
19.2 k
EGX100
La configuración B
es posible únicamente
con el CCM que tenga
la marca de Schneier
Electric en la parte
frontal.
Breaker
Modbus
Com
Address
47
A
+ -
EGX100
Rx- Rx+ Tx- Tx+
Rojo
Micrologic P/H
+ -
EGX100
Rx- Rx+ Tx- Tx+
Negro
+ -
bloque de terminales del
cliente
NOTA: consulte las instrucciones de la pasarela (EGX100) para conectar a tierra las terminaciones de blindaje, todos los extremos de blindajes no conectados
deben estar correctamente aislados.
© 2010 Schneider Electric Reservados todos los derechos
21
Compact NS extraíble y Masterpact NT/NW extraíble
Instalación del módulo CCM Modbus
5100512864A
12/2010
Instalación del módulo CCM
Modbus
Instalación del módulo
Monte el módulo de comunicación “cuna” (CCM) Modbus en un riel DIN
simétrico junto a la cuna en una posición en la que el frente esté fácilmente
accesible para realizar las conexiones y configuraciones. Si se va a montar
en un riel vertical, instale un tope para asegurar el módulo.
El riel DIN debe ser solicitado por separado.
PELIGRO
ESPAÑOL
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO
POR ARQUEO
Para poder usar el botón pulsador del CCM y ver los indicadores se
necesita una fuente de alimentación de 24 Vcd para el CCM. El CCM
debe situarse en un lugar en el que el personal no esté expuesto a
tensiones o energía peligrosa al hacer funcionar el CCM (oprimir el botón
o visualizar sus indicadores de estado).
A
’
A
’
B
B
er
ak
re
A’
sh
’
B
ld
ie
B
A
au
ése
R
N
et
ork
w
El incumplimiento de estas instrucciones podrá causar la muerte o
lesiones serias.
nc
te
ur
B
Fault
D
is
jo
Com.
s
Addres
sync.
YL
CI
+
–
CE
CD
CT
33110
Modbus Cradle COM module
Module COM chassis Modbus
+ +
5100512662
CCM
modbus
Fault
Com.
CE
CD
CT
Address
sync.
Breaker
XXXXXXXXX
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
Made in France
Disjoncteur
P 99-44
PP-YYYY-WWW-D-T
+
etiqueta de identificación
Contenido de la caja
45
1.77
90
3.54
53
2.08
58
2.28
Dimensiones
Montaje en riel DIN
22
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Compact NS extraíble y Masterpact NT/NW extraíble
Alambrado de los contactos de carro en el módulo CCM Modbus
Alambrado de los contactos de
carro en el módulo CCM Modbus
Estos son contactos de cambio.
• CE indica la posición de conectado
• CD indica la posición de desconectado
• CT indica la posición de prueba.
Estos se conectan a las terminales de tornillo en el módulo de
comunicación “cuna” (CCM) Modbus a través de 6 conductores de 0,5 a
1,25 mm2 (6 x 20 a 16 AWG); esto es, dos conductores por contacto. Las
terminales están marcadas CE, CD y CT como se ilustra en la figura.
Las conexiones se realizan a las siguientes terminales.
• CE, terminales 311 y 314
• CD, terminales 811 y 812
• CT, terminales 911 y 914.
Para obtener más información sobre cómo instalar los contactos de carro,
consulte los manuales correspondientes:
• Manual de los contactos de carro Compact NS y Masterpact NT,
documento no. 51201010
• Manual de los contactos de carro Masterpact NW, documento no.
51156129
Módulo de comunicación “cuna” (CCM) Modbus
Fault
Com.
CE
CD
CT
s
Addres
sync.
Breaker
dbus
mo
CCM
Disjoncteur
Réseau
shield
B’ B’
A’ A’
B B
A A
Network
+ +
+
Network
A
B
A’
B’
Breaker
Contactos
de carro
CE, CT
A
B
A’
B’
CCM
Contactos
de carro
CD
CT
CD
CE
911 914
811 812 311
314
CT
CD
CE
Cuna
Masterpact
NT/NW
Conexión a los contactos de carro.
© 2010 Schneider Electric Reservados todos los derechos
23
ESPAÑOL
Conexión a los contactos de carro
(opcional)
Configuraciones de comunicación con Micrologic A
5100512864A
12/2010
Configuraciones de
comunicación con
Micrologic A
Comentarios preliminares
Los parámetros de comunicación del módulo BCM con conector ULP deben
configurarse empleando la unidad de disparo Micrologic o el software de
ajustes y configuraciones RSU Masterpact.
ESPAÑOL
Los parámetros de comunicación del módulo BCM con conector ULP son:
dirección, velocidad en baudios, paridad y conexión Modbus. Para iniciar la
comunicación Modbus, los módulos deben estar correctamente instalados y
energizados.
Las unidades de disparo Micrologic deben también estar energizadas para
efectuar los siguientes procedimientos de configuración.
Unidades de disparo Micrologic A
Simultáneamente presione los botones
y
durante tres segundos.
Se muestra una serie de cuatro pantallas para configurar la comunicación
de Modbus.
Pantalla 1 – Dirección
La dirección Modbus por omisión para el dispositivo es 47.
menu
La pantalla muestra AdXX cuando la dirección existente para el módulo de
comunicación es XX. Seleccione una dirección del 1 al 47 (única para el
dispositivo dado) presionando el botón
. Brevemente, presione el botón
para aumentar la dirección en uno, donde la dirección mostrada después
de 47 es 1.
Una vez que la dirección ha sido seleccionada, presione el botón
durante tres segundos, luego suéltelo para pasar a la siguiente pantalla.
Micrologic 6.0 A
Δt= IΔn=
tsd= tr=
Isd=
Ii= Ir=
Ig=
tg=
MAX
s
kA
pantalla digital
100 %
botones de navegación
40 %
presione
simultáneamente durante
3 segundos
menu
long time
Ir
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
@ 6 Ir
instantaneous
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
tsd
.4 .4 .3
.2
.3
.1
.2
.1 2 0
on
setting
Ig
D
C
B
A
E
Ii
(s)
I t
off
delay
4
3
6 8 10
12
15
off
2
x In
Ad47
cambie a
XX
47
(por
omisión)
test
tg
F
G
H
J
.4 .4 .3
.2
.3
.1
.2
.1 2 0
(s)
on
I t
1
off
ground fault
2
3
:
:
:
46
Micrologic A
24
Pantalla 1 para la dirección
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Pantalla 2 – Velocidad en baudios
Configuraciones de comunicación con Micrologic A
La velocidad por omisión es 19 200 baudios.
La pantalla muestra XXXX que puede ser uno de tres valores, 4800, 9600 ó
19200.
Seleccione una velocidad que sea la misma para todos los dispositivos
empleando el botón
. Brevemente, presione el botón para pasar al
siguiente valor.
Una vez que la velocidad ha sido seleccionada, presione el botón
durante tres segundos, luego suéltelo para pasar a la siguiente pantalla.
Pantalla 3 – Paridad
La paridad por omisión es par.
ESPAÑOL
La pantalla muestra X que puede ser uno de dos valores, E (par) o n
(ninguna).
Seleccione un valor que sea el mismo para todos los dispositivos
empleando el botón
. Brevemente, presione el botón para pasar al
siguiente valor.
Una vez que la paridad ha sido seleccionada, presione el botón
durante tres segundos, luego suéltelo para pasar a la siguiente pantalla.
Conexión Modbus
El valor por omisión del parámetro de comunicación para la conexión
Modbus es 4 hilos.
El parámetro de comunicación para la conexión Modbus (4 hilos, 2 hilos +
ULP) no se puede configurar empleando la unidad de disparo Micrologic A.
Para configurar este parámetro, utilice el software de ajustes y
configuraciones RSU Masterpact.
19200
19200 19200
(por
omisión)
9600
4800
Pantalla 2 para la velocidad en baudios
pE
E
E
(por
omisión)
n
Pantalla 3 para la paridad
© 2010 Schneider Electric Reservados todos los derechos
25
Configuraciones de comunicación con Micrologic E
Configuraciones de
comunicación con
Micrologic E
Pantalla 1 – Dirección
5100512864A
12/2010
Activa el modo de navegación.
Simultáneamente, presione los botones
y
durante tres segundos.
Se muestra una serie de cuatro pantallas para configurar la comunicación
de Modbus.
menu
La dirección por omisión de Modbus para el dispositivo es 47. La pantalla
muestra AdXX cuando la dirección existente para el módulo de
comunicación es XX. Un icono de candado cerrado indica que el valor está
bloqueado.
Presione el botón
para abrir el candado y visualizar el primer dígito (por
ej., 4) parpadeando, listo para ser modificado.
ESPAÑOL
Brevemente, presione el botón
configuración.
para aumentar el valor hasta la nueva
Brevemente, presione el botón
para validar este valor y visualizar el
segundo dígito (por ej., 7) parpadeando, listo para ser modificado.
Brevemente, presione el botón
configuración.
para aumentar el valor hasta la nueva
Brevemente, presione el botón
para validar la nueva dirección de
Modbus (los dos dígitos seleccionados) que será mostrada
permanentemente. El candado está todavía abierto.
Brevemente, presione el botón
visualizar la pantalla 2.
nuevamente para bloquear este valor y
Micrologic 6.0 E
pantalla digital
botones de navegación
menu
presionar simultáneamente
k
consulte la página 22.
26
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Pantalla 2 – Velocidad en baudios
Configuraciones de comunicación con Micrologic E
La velocidad por omisión es 19 200 baudios. La pantalla muestra XXXX que
puede ser uno de tres valores, 4800, 9600 ó 19200. Un icono de candado
cerrado indica que el valor está bloqueado.
Presione el botón
para abrir el candado y visualizar el valor (por ej.,
19.2) parpadeando, listo para ser modificado.
Una vez que la velocidad ha sido seleccionada, presione el botón
para
validar este valor que se visualizará permanentemente. El candado está
todavía abierto. Brevemente, presione el botón
nuevamente para
bloquear este valor y visualizar la pantalla 3.
Pantalla 3 – Paridad
La paridad por omisión es E (par). La pantalla puede visualizar n (ninguna)
si existe una configuración previa. Un icono de candado cerrado indica que
el valor está bloqueado.
Presione el botón
para abrir el candado y visualizar el valor (por ej., E)
parpadeando, listo para ser modificado.
Cambie la paridad existente en el otro valor presionando el botón
.
Presione el botón
para validar este valor que se visualizará
permanentemente. El candado está todavía abierto. Brevemente, presione
el botón
nuevamente para bloquear este valor.
Micrologic 6.0 E
menu
© 2010 Schneider Electric Reservados todos los derechos
27
ESPAÑOL
Seleccione una velocidad que sea la misma para todos los dispositivos
empleando el botón
. Brevemente, presione el botón para pasar al
siguiente valor.
Configuraciones de comunicación con Micrologic E
Pantalla 4 – Conexión Modbus (4W, 2W+ULP)
5100512864A
12/2010
El valor por omisión del parámetro de comunicación para la conexión
Modbus es 4 hilos.
• Si el parámetro de comunicación “4W” es seleccionado (valor por
omisión), 4 hilos debe ser conectado entre el módulo BCM con conector
ULP (terminales E3, E4, E5, E6) y el módulo CCM (terminales A, B, A’,
B’).
— El módulo de visualización frontal FDM121 no puede conectarse.
— La conexión a la red Modbus RS 485 de 4 hilos es posible.
• Si el parámetro de comunicación “ULP” es seleccionado, 2 hilos debe
ESPAÑOL
ser conectado entre el módulo BCM con conector ULP (terminales E3,
E4) y el módulo CCM (terminales A, B).
— El módulo de visualización frontal FDM121 puede conectarse.
— La conexión a la red Modbus RS 485 de 4 hilos no es posible.
28
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Configuraciones de
comunicación con
Micrologic P / H
Configuraciones de comunicación con Micrologic P / H
Presione el botón
, se mostrará una pantalla, luego:
• seleccione el menú “Com. Setup” (configuración de comunicación)
empleando las teclas de navegación
— la selección presionando la tecla
y
, luego confirme
.
Dirección, velocidad en baudios, paridad
En el menú “Com parameter”, configure los valores de dirección, velocidad
en baudios y paridad como se indicó en las páginas anteriores. Los valores
por omisión y de selección para cada parámetro son los mismos como se
indicó anteriormente. Consulte la información en las pantallas 1, 2 y 3.
Presione la tecla
para confirmar la selección de cada parámetro.
Después de confirmar el parámetro de paridad, presione la tecla
.
Aparece un mensaje solicitándole si desea guardar las configuraciones.
Seleccione “Yes" y confirme presionando la tecla
. Los tres parámetros
son guardados:
Conexión Modbus (4W, 2W+ULP)
El valor por omisión del parámetro de comunicación para la conexión
Modbus es 4 hilos.
• Si el parámetro de comunicación “4 wires” es seleccionado (valor por
omisión), 4 hilos debe ser conectado entre el módulo BCM con conector
ULP (terminales E3, E4, E5, E6) y el módulo CCM (terminales A, B, A’,
B’).
— El módulo de visualización frontal FDM121 no puede conectarse.
— La conexión a la red Modbus RS 485 de 4 hilos es posible.
• Si el parámetro de comunicación “2 wires + ULP” es seleccionado, 2
hilos debe ser conectado entre el módulo BCM con conector ULP
(terminales E3, E4) y el módulo CCM (terminales A, B).
— El módulo de visualización frontal FDM121 puede conectarse.
— La conexión a la red Modbus RS 485 de 4 hilos no es posible.
El parámetro de comunicación para la conexión Modbus (4 hilos, 2 hilos +
ULP) puede ser configurado empleando la unidad de disparo Micrologic
P/H con la versión de firmware posterior al 2009AJ. Si este parámetro no
está accesible, utilice el software de ajustes y configuraciones RSU
Masterpact para configurarlo.
Tensión nominal del sistema
Si se usa un módulo de visualización frontal, será necesario configurar la
tensión nominal del sistema de distribución empleando la unidad de disparo
Micrologic o el software de ajustes y configuraciones RSU Masterpact.
Presione el botón
, seleccione el menú de configuración Micrologic,
luego el comando de razón VT y la razón de tensión-transformación
deseada.
© 2010 Schneider Electric Reservados todos los derechos
29
ESPAÑOL
— luego, seleccione el menú “Com parameter” (parámetro de
comunicación) de la misma manera.
Configuraciones de comunicación con Micrologic P / H
dirección,
velocidad
en
baudios,
paridad
Micrologic 6.0 P
Ecran ELU - [Ecran...
0A
A
pantalla
digital
B
5100512864A
12/2010
Event
history
Contacts
M2C/M6C
Micrologic
setup
Com.
parameter
Remote
settings
Address
47
Remote
control
Baud-rate
19.2 k
Metering
setup
C
100
Modbus
Com
4W, 2W+ULP
4wires
Com.
setup
50
0
tecla del botón de
selección
ESPAÑOL
botón de
confirmación (CR)
idioma
.7
.6
.5
.4
alarm
tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
.8
x In
instantaneous
tsd
(s)
.4 .4 .3
.3
.2
.1
on
setting
Ig
D
C
B
A
E
delay
tg
F
G
H
J
.2
.1
0
2
I t off
(s)
Language
Date / hour
Deutsch
Breaker
selection
English US
Metering
setup
@ 6 Ir
short time
Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Language
Contacts
M2C/M6C
Micrologic
setup
long time
Ir
botones de
navegación
Event
history
Ii
6 8 10
4
12
3
15
off
2
x In
Com.
setup
English UK
Neutral TC
Español
VT ratio
Français
test
.4 .4 .3
.3
.2
.1
on
2
I t
.2
.1
0
off
ground fault
Razón VT
Event
history
Language
Contacts
M2C/M6C
Date / hour
Micrologic
setup
Metering
setup
Com.
setup
Breaker
selection
Neutral TC
VT ratio
Primary
690V
Secondary
690V
VT ratio
Botones de navegación y ejemplos de pantallas
30
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Configuración de comunicación del CCM
Configuración de
comunicación del CCM
Para los dispositivos extraíbles, el módulo de comunicación “cuna” (CCM)
Modbus es una interfaz entre el dispositivo y la red de comunicación y
existe, por siguiente, un procedimiento para transmitir los parámetros
necesarios al módulo. Los parámetros, primero, deben ser configurados
como se indicó anteriormente y depende de las unidades de disparo
respectivas (consulte la página 24 para Micrologic A, consulte la página 26
para Micrologic E, consulte la página 29 para Micrologic P/H).
ESPAÑOL
Dispositivos extraíbles
PELIGRO
PELIGRO DE DESCARGA ELÉCTRICA, EXPLOSIÓN O DESTELLO
POR ARQUEO
• El CCM puede estar en proximidad a tensiones peligrosas o fuentes de
energía.
• Se debe usar equipo de protección personal apropiado al hacer
funcionar el botón pulsador del CCM o visualizar los indicadores de
estado. Consulte la norma NFPA 70E o CSA Z462 o los códigos
nacionales apropiados para obtener detalles adicionales.
El incumplimiento de estas instrucciones podrá causar la muerte o
lesiones serias.
Configuración del módulo de comunicación
“cuna” (CCM) Modbus
El módulo de comunicación “cuna” (CCM) Modbus tiene un botón pulsador
y dos LED (rojo y verde) en el panel frontal que se usan durante el
arranque. Una vez que todos los parámetros han sido configurados, como
se indicó anteriormente y según las unidades de disparo respectivas,
presione el botón de sincronización de direcciones en el módulo de
comunicación “cuna” (CCM) Modbus.
El módulo de comunicación “cuna” (CCM)
Modbus automáticamente se configurará con:
El módulo de comunicación “cuna” (CCM)
Modbus entonces automáticamente inicia el
arranque al conectarse con todos los demás
dispositivos RS 485 en la red de comunicación.
Sustitución de un dispositivo extraíble equipado
con un módulo de comunicación
© 2010 Schneider Electric Reservados todos los derechos
CD
A’
B’
B’
Network
B
A’
Breaker
Address
sync.
CT
B
Réseau
Com.
Sincronización de
direcciones
Disjoncteur
“cuna” (CCM) Modbus es la dirección del
módulo BCM con conector ULP Modbus
incrementado por 50 (@xx+50).
A
Fault
• La dirección del módulo de comunicación
A
y paridad que el módulo BCM con conector
ULP Modbus.
shield
• los mismos valores de velocidad en baudios
CE
presione el botón para
transferir los parámetros
Configuración del módulo de comunicación “cuna” (CCM) Modbus.
Si un dispositivo extraíble equipado con un módulo BCM con conector ULP
Modbus es sustituido, la configuración y arranque se realizan
automáticamente a través del módulo de comunicación “cuna” (CCM)
Modbus que envía los parámetros necesarios al módulo BCM con conector
ULP Modbus y luego lo conecta a la red de comunicación.
31
Configuración de comunicación del CCM
Modos de funcionamiento del módulo CCM Modbus
5100512864A
12/2010
Modos de funcionamiento del
módulo CCM Modbus
LED de estado del módulo CCM
El módulo de comunicación “cuna” (CCM) Modbus tiene dos LED de modo
de funcionamiento:
• un LED rojo de falla (Fault)
• un LED verde de comunicación (Com)
Sus estados se presentan en la tabla a continuación
Color de los LED
32
CD
Network
El módulo no tiene alimentación
Rojo continuo
El módulo tiene alimentación pero no ha sido inicializado
Verde continuo
El módulo tiene alimentación, funcionando
correctamente
Verde con interrupciones cortas
El módulo tiene alimentación, funcionando
correctamente, actualmente descifrando mensajes de la
red
Verde interrumpido por destellos
rojos cortos
El módulo tiene alimentación, funcionando
correctamente, actualmente no puede descifrar
mensajes de la red
Alternando entre verde y rojo
Configuración en curso (el botón de sincronización de
direcciones fue presionado)
Parpadeando en rojo
El módulo de comunicación “cuna” (CCM) Modbus está
actualmente enviando la configuración al módulo BCM
con conector ULP Modbus
Parpadeando en verde
El módulo de comunicación “cuna” (CCM) Modbus envió
exitosamente la configuración al módulo BCM con
conector ULP Modbus
B’
A’
B
Todos los LED apagados
Breaker
B’
A’
B
Réseau
Address
sync.
CT
A
A
Com.
Disjoncteur
LED verde de
comunicación
Fault
shield
ESPAÑOL
LED rojo de falla
Modo de funcionamiento
CE
© 2010 Schneider Electric Reservados todos los derechos
5100512864A
12/2010
Asistencia de diagnóstico de problemas
Asistencia de diagnóstico de
problemas
Causa posible
Acción/solución
Fuente de alimentación de 24 Vcd externa no presente.
Revise la fuente de alimentación de 24 Vcd.
Polaridades inversas en las terminales E1, E2.
Asegúrese de que la polaridad + esté en E1, y la – en E2.
ESPAÑOL
La unidad de disparo Micrologic no muestra los parámetros de comunicación (dirección, velocidad en baudios, paridad)
La unidad de disparo Micrologic P o H no muestra el parámetro de conexión Modbus: 4wires / 2w+ULP
Causa posible
El módulo BCM es de una versión antigua: la versión de firmware debe ser
posterior a la V3.0.0
Verifique el registro 577 de Modbus o compruebe el color del bloque de
terminales situado en la parte fija del módulo BCM (deberá ser gris en lugar de
verde).
La unidad de disparo Micrologic (P/H) es una versión antigua: la versión de
firmware debe ser posterior al 2009AJ.
Acción/solución
Sustituya el módulo BCM existente con un nuevo módulo BCM con conector
ULP.
Utilice el software de ajustes y configuraciones RSU Masterpact para modificar el
parámetro de conexión Modbus.
El módulo de visualización frontal FDM121 está parpadeando y/o muestra valores incorrectos
Causa posible
Acción/solución
El módulo de visualización frontal FDM121 es una versión antigua: la versión de
firmware debe ser
Posterior a V2.0.2.
Utilice el software de ajustes y configuraciones RSU Compact NSX para
actualizar el firmware del módulo de visualización frontal FDM121.
La versión de firmware se puede leer en el menú “Service” del módulo de
visualización frontal FDM121.
Respuestas erráticas en la solicitud de Modbus (tiempo vencido o sin respuesta)
Causa posible
Conexiones incorrectas
La configuración (parámetro 4Wire/2wire+ULP ) no concuerda con el alambrado
del módulo BCM con conector ULP
Acción/solución
Revise el alambrado del módulo BCM con conector ULP.
Dentro de la configuración A, asegúrese de que los bloques de terminales E5 y
E6 no estén conectados al conector ULP.
Dentro de la configuración B, asegúrese de que los bloques de terminales E5 y
E6 no estén conectados a la red Modbus.
Únicamente 2 hilos son usados entre el módulo BCM y una versión antigua del
CCM (el CCM no tiene la marca de Schneider Electric en la parte frontal).
Utilice 4 hilos entre el módulo BCM y el CCM o sustituya el CCM existente con
una versión nueva de CCM (el CCM tiene la marca de Schneider Electric en la
parte frontal).
El módulo de interfaz de comunicación Modbus ha sido conectado al conector
ULP y, por consiguiente, el puerto Modbus del módulo BCM con conector ULP
está desactivado.
Desconecte el módulo de interfaz de comunicación Modbus del conector ULP, o
desconecte la red Modbus del módulo BCM con conector ULP y conecte la red
Modbus al puerto Modbus del módulo de interfaz de comunicación Modbus
(terminales D0, D1).
La pantalla de cristal líquido de la unidad de disparo Micrologic y/o del FDM121 está parpadeando
Causa posible
Acción/solución
2 módulos ULP del mismo tipo están conectados en el mismo sistema de
conexión ULP . Por ejemplo, 2 interruptores automáticos (1 Compact NSX y 1
Masterpact)
Retire uno de los módulos ULP duplicados. Por ejemplo, desconecte el Compact
NSX del sistema de conexión ULP.
© 2010 Schneider Electric Reservados todos los derechos
33
Asistencia de diagnóstico de problemas
5100512864A
12/2010
ESPAÑOL
34
© 2010 Schneider Electric Reservados todos los derechos
ESPAÑOL
Communicación Modbus (módulo BCM con conector ULP) para Micrologic
Boletín de instrucciones
ESPAÑOL
Solamente el personal especializado deberá instalar, hacer funcionar y prestar servicios de
mantenimiento al equipo eléctrico. Schneider Electric no asume responsabilidad alguna por las
consecuencias emergentes de la utilización de este material.
Importado en México por:
Schneider Electric México, S.A. de C.V.
Calz. J. Rojo Gómez 1121-A
Col. Gpe. del Moral 09300 México, D.F.
Tel. 55-5804-5000
www.schneider-electric.com.mx
Square D™ y Schneider Electric™ son marcas comerciales o marcas registradas de Schneider
Electric. Cualquier otra marca comercial utilizada en este documento pertenece a sus respectivos
propietarios.
5100512864A-02 12/2010
© 2010 Schneider Electric Reservados todos los derechos